RTNY3 - RTAY3 RTNY3

RTNY3 - RTAY3
Industrial temperature switch, direct mounting
with intrinsic safety
Main Features
„„
Excellent repeatability
„„
Dead band adjustment for regulation
„„
Fix dead band for control and alarm
„„
Intrinsic safety Hazardous area 0, 1, 2
Applications
„„Power generation safety equipment
Technical Data
-46 ... 0°C to 40 ... 120°C
Temperature
Process : Ambient : Storage : Repeatability
± 1% F.S. @ constant temperature cycle
CE conformity
Low Voltage Directive LVD 2006/95/EC
ATEX Directive 94/9/EC
IP 66 (EN 60529)
Protection rating
Process connection
Bulb
Scale
Cover
-46 ... +120°C
-30 ... +55°C
-40 ... +55°C
RTA :
Copper alloy
RTN :
Stainless steel 1.4404 (316L)
RTA :
Copper alloy
RTN :
Stainless steel 1.4404 (316L)
Internal. Accuracy on reading ± 5% FS
Case
Zamak blue painted
Captive stainless steel screws
Black Zamak
Mounting
Direct mounting or with wall mounting braket
Ground connection
Via internal terminal block
Electrical
connection
Terminal block with plastic cable gland for
Ø 7 to 10.5 mm
Electrical
function
See ordering code details on page 5
Adjustment
2 external adjustment screws on top of the case
for set point and dead band
Type examination certificate
LCIE 03 ATEX 6123X
EN 60079-0: 2012 (internal conformity analysis)
EN 60079-11: 2012
Marking
0081
IM1
Ex ia I Ma
II 1 G
Ex ia IIC T6 or T5 Ga
Electrical data
Umax = 28 Vdc
Imax = 120 mA
Pmax = 0.84 W
ATEX
Ci = Negligible ; Li = Negligible
Design and specifications subject to change without notice
Temperature range
Options
Customer specific set point adjustment
Code SETP
Stainless steel tag plate and wire
Code 9941
Lead seal of the adjustment screws
Code 8990
Nuclear cleanliness (RTN only)
Code 0838
Electrical connection : stainless steel connector (Souriau) Code 2298
Code 2249
2015-04-14
Mobile plug for stainless steel connector (Souriau)
www.baumer.com
Data sheet B31.11
Page 1 / 5
RTNY3 - RTAY3
Industrial temperature switch, direct mounting
with intrinsic safety
Principle
A vapour filled flexible sensing element actuates a microswitch by
means of a lever. The set point is adjusted by means of a compressible spring installed in opposition.
NC
NC
NC
C
C
C
NO
NO
NO
Set point and reset point must be between 10% and 90% of the
selected scale.
Standard factory adjustment
Setpoint at 50% of the scale on falling temperature
NC
C
NC
NC
C
C
NO
NO
NO
Customer specific factory adjustment (option SETP)
The following specifications have to be given with the order:
• Setpoint value
• Adjustment on falling or raising temperature
• Dead band value when using an adjustable dead band switch
Electrical connections
2 SPDT
1 SPDT
NC
Blue
COM
Red
NO
White
NC
Blue
COM
Red
NO
White
NC
Blue
COM
Red
Yellow / green
NO
White
NO
C
Non hazardous
area
NO
or NC
NC
+
Rc 1
Supply
–
Screen
For max. ambient temperature refer to technical data on page 1.
The installation must be made in an intrinsically safe circuit whose certified electrical safety parameters do not exceed any of the values Umax,
Imax and Pmax given in the electrical data on page 1.
All necessary measures must be taken by the user, to avoid the calorific transfer from the fluid to the apparatus head increasing the head's
temperature to such that it reaches the self-ignition temperature of the gas in which it is used.
www.baumer.com
Data sheet B31.11
Page 2 / 5
2015-04-14
Certified safety
barrier
Hazardous area
Zone 0, 1, 2
Design and specifications subject to change without notice
Yellow / green
RTNY3 - RTAY3
Industrial temperature switch, direct mounting
with intrinsic safety
Micro switches characteristics
Switch code
N (T)
M (K)
C (W)
S
Type
Tropicalized
Gold contact
Hermetic
Ultrasensitive
Gold contact
6 Vdc
0.1 ... 0.12 A
10 ... 50 mA
5 ... 120 mA
10 ... 50 mA
12 Vdc
N/A
10 ... 50 mA
5 ... 66 mA
10 ... 50 mA
24 Vdc
N/A
10 ... 33 mA
5 ... 33 mA
10 ... 33 mA
30 Vdc
N/A
N/A
N/A
N/A
48 Vdc
N/A
N/A
N/A
N/A
110 Vdc
N/A
N/A
N/A
N/A
220 Vdc
N/A
N/A
N/A
N/A
115 Vac
N/A
N/A
N/A
N/A
250 Vac
Dielectric rigidity between contacts and ground
N/A
N/A
N/A
N/A
2000 V
2000 V
1500 V
2000 V
Adjustable ranges
Micro-switch dead band 1)
TMax
Scale
accidential
°C
Adjustable dead band
Code
°C
N (T*)
M (K*)
10%
90%
Fixed dead band
C (W*)
10%
S
90%
10%
90%
°C
0
40
300
4-9
2-9
8 - 12
4 - 12
3
2.5
-20 ... 20
60
301
3-8
1.5 - 8
6 - 12
4 - 12
2.5
1.5
0
... 45
60
302
4-9
2-9
7 - 12
4 - 12
3
2
40 ... 120
145
303
5 - 16
3 - 16
10 - 20
6 - 20
4
3.5
20 ... 80
100
315
5 - 12
3 - 12
9 - 15
5 - 15
4
3
-46 ... (*) For version with 2 microswitches lower values of the dead band must be multiplied x 1.5
The value of the dead band is depending on the value of the set point.
This table contains the dead band values for set point adjustment at 10% and 90% of the selected scale. For adjustable dead band the lower value corresponds to
the dead band spring totally released and the higher corresponds to the dead band spring fully tensed. For other set points the dead band value can be calculated
by linear interpolation between the values at 10% and 90%.
2015-04-14
Design and specifications subject to change without notice
1)
www.baumer.com
Data sheet B31.11
Page 3 / 5
RTNY3 - RTAY3
Industrial temperature switch, direct mounting
with intrinsic safety
Dimensions (mm)
76.5
=
125
=
58
130
100
28.5
64
144
139
5
45°
130
Thermowell
144
Thermowell for RTxx3
Stainless steel
Ordering code : 10271317
20
Hex 29
22
G 3/8
70
103
P= 135
3/4 BSP.TR
Ø 18X16
2015-04-14
Design and specifications subject to change without notice
Ø 14
www.baumer.com
Data sheet B31.11
Page 4 / 5
RTNY3 - RTAY3
Industrial temperature switch, direct mounting
with intrinsic safety
Ordering details RTNY3-RTAY3
RT
Model
Industrial temperature switch
RT
Type of the bulb
Copper alloy bulb
Stainless steel bulb
Approval
ATEX intrinsic safety
Type of micro switches
1 SPDT hermetically changeover switch
2 SPDT hermetically changeover switch
1 SPDT gold contact changeover switch
2 SPDT gold contact changeover switch
1 SPDT tropicalized changeover switch
2 SPDT tropicalized changeover switch
1 SPDT ultrasensitive gold contact changeover switch
Y
–
.
3xx
.
E
0
0
E
J
/
–
A
N
Y
Deadband
Adjustable
Adjustable
Adjustable
Adjustable
Adjustable
Adjustable
Fix
C
W
M
K
N
T
S
Temperature range (°C)
-46... 0
-20 ... 20
0 ... 45
40 ... 120
20 ... 80
.
300
301
302
303
315
.
Type of design
Direct mounting (TRD)
Capillary length
Without capillary
Stem length P
P=135 mm
Bulb diameter
Ø 14 mm
Process connection
G3/8
Options to be added behind the / (see example below)
E
0
0
E
J
/
Ordering example with options
RT
–
A
Y
C
.
300
.
E
0
0
E
J
/
SETP
_
9941
Industrial temperature switch
Copper alloy bulb
ATEX intrinsic safety
1 SPDT standard changeover switch
Design and specifications subject to change without notice
Temperature range -46 ... 0 °C
TRD direct mounting
Without capillary
Immersion length P=135 mm
Bulb diameter Ø 14mm
Process connection G3/8
Option : Customer specific set point adjustment
2015-04-14
Option : Stainless steel tag plate and wire
www.baumer.com
Data sheet B31.11