UFEC15W SERIES

UFEC15W SERIES
DC-DC CONVERTER
4:1 ULTRA WIDE INPUT RANGE
UP TO 15 Watts
FEATURES
APPLICATIONS
• NO MINIMUM LOAD REQUIRED
• 1600VDC INPUT TO OUTPUT ISOLATION
• APPLICATION OF CHASSIS-MOUNT DC/DC CONVERTERS
• SCREW TERMINALS FOR INPUT AND OUTPUT CONNECTIONS
• INTERNAL INPUT FUSE PROTECTION
• INTERNAL OUTPUT LED INDICATOR
• MEET EN55022 CLASS B
• SAFETY MEETS UL60950-1, EN60950-1, & IEC60950-1
• CE MARKED
• COMPLIANT TO RoHS II & REACH
1600VDC
ISOLATION
REMOTE
CONTROL
UVP
OCP
• WIRELESS NETWORK
• TELECOM/DATACOM
• INDUSTRY CONTROL SYSTEM
• MEASUREMENT EQUIPMENT
• SEMICONDUCTOR EQUIPMENT
SCP
FUSE
INCLUDED
OVP
TECHNICAL SPECIFICATION All specifications are typical at nominal input, full load and 25℃
Model
Number
UFEC15-24S3P3W
UFEC15-24S05W
UFEC15-24S5P1W
UFEC15-24S12W
UFEC15-24S15W
UFEC15-24D05W
UFEC15-24D12W
UFEC15-24D15W
UFEC15-48S3P3W
UFEC15-48S05W
UFEC15-48S5P1W
UFEC15-48S12W
UFEC15-48S15W
UFEC15-48D05W
UFEC15-48D12W
UFEC15-48D15W
REVERSE
POLARITY
PROTECTION
INRUSH
LIMIT
otherwise noted
Input Range
Output Voltage
Output Current
@Full Load
Input Current
@ No Load
Efficiency
Maximum
Capacitor Load (1)
VDC
9.5 ~ 36
9.5 ~ 36
9.5 ~ 36
9.5 ~ 36
9.5 ~ 36
9.5 ~ 36
9.5 ~ 36
9.5 ~ 36
18 ~ 75
18 ~ 75
18 ~ 75
18 ~ 75
18 ~ 75
18 ~ 75
18 ~ 75
18 ~ 75
VDC
3.3
5
5.1
12
15
±5
±12
±15
3.3
5
5.1
12
15
±5
±12
±15
mA
4500
3000
3000
1250
1000
±1500
±625
±500
4500
3000
3000
1250
1000
±1500
±625
±500
mA
51
66
66
25
26
56
33
34
36
36
36
17
17
36
19
19
%
85
86
86
86
86
86
87
87
85
87
87
86
86
87
87
87
µF
14700
7200
7200
1250
800
±3600
±625
±400
14700
7200
7200
1250
800
±3600
±625
±400
PART NUMBER STRUCTURE
UFEC15 Series Name
48
S
Input
Voltage
(VDC)
24: 9.5~36
48: 18~75
Output
Quantity
S: Single
D: Dual
1
05
W -
Output
Voltage
(VDC)
3P3: 3.3
05: 5
5P1 5.1
12: 12
15: 15
05: ±5
12: ±12
15: ±15
Input
Range
4:1
P
EC
Remote Control
Option
Assembly Option
P: Positive logic
N: Negative logic
www.PDUKE.com
:
EC:
DR:
ED:
No Assembly Option
Enclosed Mounting Type
Din Rail Mounting Type
Enclosed & Din Rail Mounting Type
2014/6/5
INPUT SPECIFICATIONS
Parameter
Conditions
Operating input voltage range
24Vin(nom)
48Vin(nom)
24Vin(nom)
48Vin(nom)
Input fuse (slow blow)
In-rush current
Input reflected ripple current
Start up voltage
Start up time
Constant resistive load
Input surge voltage
100ms, max.
Remote ON/OFF (Option)
Referred to –Vin pin
OUTPUT SPECIFICATIONS
Parameter
24Vin(nom)
48Vin(nom)
Positive logic
DC-DC ON
DC-DC OFF
Negative logic
DC-DC ON
DC-DC OFF
Input current of Ctrl pin
Remote off input current
Conditions
Line regulation
Low Line to High Line at Full Load
Load regulation
No Load to Full Load
Cross regulation
Ripple and noise
Asymmetrical load 25%/100% FL
Measured by 20MHz bandwidth
Single
Dual
VDC
A
A
mAp-p
9.5
18
7.5
15
100
Typ.
-1.5
-1.0
-0.2
-0.5
-1.5
-1.0
-5.0
VDC
VDC
ms
50
100
Open or 3 ~ 12VDC
Short or 0 ~ 1.2VDC
Short or 0 ~ 1.2VDC
Open or 3 ~ 12VDC
-0.5
0.5
2.5
Min.
3.3Vout
Others
Single
Dual
3.3Vout
Others
Dual
3.3Vout, 5Vout, 5.1Vout
12Vout, 15Vout
All
3.3Vout
5Vout, 5.1Vout
12Vout
15Vout
% of Iout rated
Conditions
Isolation voltage
1 minute
Isolation resistance
Isolation capacitance
Switching frequency
Safety meets
500VDC
2
Unit
36
75
VDC
mA
mA
Max.
Unit
+1.5
+1.0
+0.2
+0.5
+1.5
+1.0
+5.0
%
50
75
75
%
%
%
mVp-p
-0.02
25% load step change
Zener diode clamp
GENERAL SPECIFICATIONS
Parameter
Chassis material
Weight
MTBF
Max.
24
48
6
4
15
10
24Vin(nom)
48Vin(nom)
24Vin(nom)
48Vin(nom)
Power up
Voltage accuracy
Output indicator
Over load protection
Short circuit protection
Typ.
9.5
18
Nominal input and Full load
Shutdown voltage
Temperature coefficient
Transient response recovery time
Over voltage protection
Min.
Input to Output
Input (Output) to Chassis
+0.02
%/℃
250
µs
3.9
6.2
VDC
15
18
Green LED
150
%
Continuous, automatics recovery
Min.
360
MIL-HDBK-217F, Full load
www.PDUKE.com
Typ.
1600
1600
1
Max.
Unit
VDC
400
GΩ
pF
kHz
UL60950-1
EN60950-1
IEC60950-1
Aluminum
89g (3.13oz)
2.544 x 106 hrs
4000
440
2014/6/5
ENVIRONMENTAL SPECIFICATIONS
Parameter
Conditions
Operating ambient temperature
Min.
Without derating
With derating
Storage temperature range
Thermal shock
Vibration
Relative humidity
EMC SPECIFICATIONS
Parameter
EMI
ESD
Radiated immunity
Fast transient
Surge
Conducted immunity
Conditions
EN55022
EN61000-4-2
EN61000-4-3
EN61000-4-4
EN61000-4-5
EN61000-4-6
-40
+83
-40
Typ.
Max.
Unit
℃
℃
+83
+93
+105
MIL-STD-810F
MIL-STD-810F
5% to 95% RH
Level
Air ± 8kV and Contact ± 6kV
10V/m
± 2kV
± 0.5kV
10Vr.m.s
Class B
Perf. Criteria A
Perf. Criteria A
Perf. Criteria A
Perf. Criteria A
Perf. Criteria A
Note:
1.
Test by minimum input and constant resistive load.
CHARACTERISTIC CURVE
UFEC15-48S05W Derating Curve
3
UFEC15-48S05W Efficiency vs. Input Voltage
www.PDUKE.com
UFEC15-48S05W Efficiency vs. Output Load
2014/6/5
MECHANICAL DRAWING
CHASSIS MOUNTING TYPE
PIN CONNECTION
PIN
SINGLE
1
+Vin
2
-Vin
3
Ctrl(Option)
4
NC
5
-Vout
6
+Vout
7
NC
DUAL
+Vin
-Vin
Ctrl(Option)
NC
-Vout
Common
+Vout
* NC:No Connection
* Screw terminals –
wire range from 14 to 18 AWG
ENCLOSED MOUNTING TYPE
DIN RAIL MOUNTING TYPE
1. All dimensions in Inch (mm)
2. Tolerance : X.XX±0.02 (X.X±0.5)
4. Tolerance : X.XXX±0.01 (X.XX±0.25)
3. Hole screw locked torque :
MAX 5.0kgf-cm (0.49N-m)
4. Terminal screw locked torque :
MAX 2.5kgf-cm (0.25N-m)
4
www.PDUKE.com
2014/6/5