1305 Connection Guide

1305 Connection/Installation Guide
Power Wiring
Input and output power connections are performed through a ten position terminal block, TB1.
(1) Connection for Dynamic Brake Resistors for all models except the 200-230 Volt, 0.37 to 75kW (1/2 to 1 HP) drive.
NOTE: The[DB Enable] parameter must be enabled for proper operation.
(2) For single phase applications, the AC input line can be connected to any two of the three input terminals
R, S, T (L1, L2, L3).
(3) Bulletin 1305 drives are UL listed and CSA certified as a motor overload protective device. An external overload
relay is not required for single motor applications.
NOTE: This drive is not intended for use with single phase motors.
Terminals
GND
R, S, T (L1, L2, L3)
+DC, BRK (or -DC)
U, V, W (T1, T2, T3)
Terminal
TB1 (230V)
TB1 (460V)
TB2 (All)
Terminal No(s)
1,2,3
2,3
4,3
5,3
6,7
8,7
9,10
11,12
13,12
14,12
16,15
17,15
18,15
19,20
(3) Internal 5V supply.
Power Block Terminal (TB1)
Description
Earth Ground
AC Input Line Terminals
Dynamic Brake Option - Refer to instructions included with
option
Motor Connection
Screw Size, Wire Size and Torque Specifications
Screw Size
Maximum Torque
Max. /Min. Wire Size
M4
M4
M3.5
3.5/0.75 (12/18)
4/0.75 (10/18)
1.5/0.20 (14/24)
0.90 (8)
1.81(16)
0.90 (8)
Control Terminal Block (TB2) Descriptions
Signal
Specification
External Speed Pot
10k Ohm Potentiometer
0-10V Analog Input
Drive Input Impedance = 100k Ohm
4-20mA Analog Input
Drive Input Impedance = 250 Ohm
0-10V Analog Output
Meter Impedance > 4k Ohm
Start Contact
Closure Input (3)
Stop Contact
Closure Input (3)
Programmable Output 1
Resistive Rating = 115 V AC/30 V DC, 5A
Inductive Rating = 115 V AC/30 V DC, 2A
Drive Enable
Contact Closure Input (3)
Reverse
Contact Closure Input (3)
Jog
Contact Closure Input (3)
SW1
Contact Closure Input (3)
SW2
Contact Closure Input (3)
SW3
Contact Closure Input (3)
Programmable Output 2
24V DC +/- 20%, 50 m Amps Max.
The recommended control signal wire is:
•
•
•
Belden 8760 (or equiv.) - 18 AWG (0.750 mm2), twisted pair, shielded.
Belden 8770 (or equiv.) - 18 AWG (0.750 mm2), 3 conductor, shielded.
Belden 9460 (or equiv.) - 18 AWG (0.750 mm2), twisted pair, shielded.
Note: This drive is not intended for use with single phase motors.
Conduit
If metal conduit is preferred for cable distribution, the following guidelines must be followed.
1. Drives are normally mounted in cabinets and ground connections are made at a common ground point in the cabinet.
If the conduit is connected to the motor junction box and at the drive end, no further conduit connections are
necessary.
2. No more than three sets of motor leads can be routed through a single conduit. This will minimize “cross talk” that
could reduce the effectiveness of the noise reduction methods described. If more than three drive/motor connections
per conduit are required, shielded cable as described above must be used. If practical, each conduit should contain
only one set of motor leads.
ATTENTION: To avoid a possible shock hazard
caused by induced voltages, unused wires in the
conduit must be grounded at both ends. For the
same reason, if a drive sharing a conduit is being
serviced or installed, all drives using this conduit
should be disabled. This will eliminate the
possible shock hazard from “cross coupled” drive
motor leads.
Motor Lead Lengths
Installations with long cable lengths between the 1305 drive and motor may require the use of an output reactor or
Terminator. The following guidelines allow for selection of the appropriate drive HP rating (and output reactor or
Terminator, if required) to work with an existing motor, and provide motor–lead length solutions for new installations.
Voltage doubling at motor terminals, known as reflected wave phenomenon, standing wave or transmission line effect,
can occur when using long motor cables with drives. Long motor cables can cause capacitive charging current in excess
of the rating of a smaller drive. To ensure proper installation, follow the guidelines provided. All cabling and distances are
based on using 14 AWG, 4-conductor type cabling. In general, motors designed and built without phase separating
insulation paper between motor windings should be classified as 1000VP–P insulation design.
Section A: No Output Reactor or Terminator
The following Table 4 lists the maximum cable lengths permitted when applying a 460V, 1305 drive to a 460V motor for
motor insulation ratings of 1000V, 1200V, and 1600V without an output reactor or Terminator. Shielded and unshielded
maximum cable lengths also are listed. Tables are based on operation at nominal line condition (480V).
1000V and 1200V Motor Insulation Ratings:
Cable lengths listed in Table 4 are for operating the 1305 drive at a maximum carrier frequency of 4 kHz on motor
insulation ratings of 1000V and 1200V. Consult the factory regarding operation above 4 kHz carrier frequency. Multiply
listed distances by 0.85 for operation at high line conditions (above 480V). If the maximum cable length used exceeds
the distances indicated, refer to Section B.
1600V Motor Insulation Ratings:
Cable lengths listed in Table 4 are based on operating the 1305 drive at a maximum carrier frequency of 2 kHz on motor
insulation ratings of 1600V. Consult the factory regarding operation above 2 kHz carrier frequency. Multiply listed
distances by 0.55 for operation at high line conditions (above 480V). If the maximum cable length used exceeds the
distances indicated, refer to Section B. The Allen-Bradley 1329-HR is representative of 1600VP-P insulation rating designs
and is recommended in applications where long cable lengths are required.
Table 4 Maximum Motor Cable Length Restrictions
Drive HP (460V)
Motor HP(460V)
Maximum Carrier Frequency
High–Line Derate Multiplier
5
3
2
1
0.5
5
3
2
1
0.5
3
2
1
0.5
2
1
0.5
1
0.5
0.5
No External Devices or Reactor at the Motor
Using a Motor with Insulation VP-P
1000 Volt
1200 Volt
1600 Volt 1329 HR
Any Cable Any Cable
Shielded Cable
Unshielded Cable
4 kHz
4 kHz
2 kHz
2 kHz
0.85
0.85
0.55
0.55
9m (30ft)
30m (100ft) 121m (400ft)
121m (400ft)
9m (30ft)
30m (100ft) 121m (400ft)
121m (400ft)
9m (30ft)
30m (100ft) 121m (400ft)
121m (400ft)
9m (30ft)
30m (100ft) 121m (400ft)
121m (400ft)
9m (30ft)
30m (100ft) 121m (400ft)
121m (400ft)
9m (30ft)
9m (30ft)
9m (30ft)
9m (30ft)
30m (100ft)
30m (100ft)
30m (100ft)
30m (100ft)
91m (300ft)
121m (400ft)
121m (400ft)
121m (400ft)
121m (400ft)
121m (400ft)
121m (400ft)
121m (400ft)
9m (30ft)
9m (30ft)
9m (30ft)
30m (100ft) 76m (250ft)
30m (100ft) 121m (400ft)
30m (100ft) 121m (400ft)
121m (400ft)
121m (400ft)
121m (400ft)
9m (30ft)
9m (30ft)
30m (100ft) 68m (225ft)
30m (100ft) 121m (400ft)
121m (400ft)
121m (400ft)
9m (30ft)
30m (100ft) 45m (150ft)
106m (350ft)
Section B: Use of Output Reactor or Terminator
For longer motor-lead length applications, an output reactor or Terminator is required to ensure proper drive operation,
and for the motor to operate within its specified insulation rating. The guidelines in Table 5 are required for proper drive
and motor operation, or motor designs without phase–separating insulation paper between motor windings. Applications
with non-inverter duty rated motors, with long lead lengths, require an output reactor or Terminator. An output reactor or
Terminator helps reduce voltage reflection to the motor to levels which are less than the motor insulation rating. Table 5
lists maximum cable lengths that can be run when using an output reactor, or one of two available Terminators, for motor
insulation ratings of 1000V, 1200V, and 1600V. Shielded and unshielded maximum cable lengths also are listed. When
an output reactor is required, locate the reactor at the drive if possible. Consult the factory for applications which require
mounting the reactor at the motor.
1000V and 1200V Motor Insulation Ratings:
Cable lengths listed in Table 5 are for operating the 1305 drive at a maximum carrier frequency of 2 kHz on motor
insulation ratings of 1000V and 1200V when used with an output reactor or Terminator. Consult the factory regarding
operation above 2 kHz carrier frequency. Multiply listed distances by 0.85 for operation at high line conditions (above
480V).
1600V Motor Insulation Ratings:
Cable lengths listed in Table 5 are based on operating the 1305 drive at a maximum carrier frequency of 2 kHz on motor
insulation ratings of 1600V. Consult the factory regarding operation above 2 kHz carrier frequency. The Allen-Bradley
1329-HR is representative of 1600VP-P insulation rating designs and is recommended in applications where long cable
lengths are required. Example: An existing installation includes a 2 HP, 1200V motor with a 84-meter (275-foot) cablelength requirement between the 1305 drive and the motor. What are the possible solutions to this installation?
1. Table 4 indicates that either an output reactor or a Terminator is required for this installation example. Consult Table 5
for output reactor, Terminator, and cable types.
2. Table 5 suggests these possible solutions:
• Install a 1305 2-HP drive with an output reactor installed at the drive, and use unshielded cable.
• Install a 1305 3-HP drive with an output reactor installed at the drive, and use shielded or unshielded cable.
• Install a 1305 2-HP drive with a 1204-TFA1 Terminator, and use shielded or unshielded cable.
Contact Allen-Bradley for further assistance if required.
Table 5 Maximum Motor Cable Length
Drive
HP
(460V)
Motor
HP
(460V)
1
Reactor at the Drive
Using a Motor with
Insulation VP-P
1000
Volt
Any
Cable
2 kHz
Maximum Carrier
Frequency
High-Line Derating 0.85
Multiplier
5
5
15m
(50ft)
3
15m
(50ft)
2
15m
(50ft)
1
15m
(50ft)
15m
0.5
(50ft)
3
3
15m
(50ft)
2
15m
(50ft)
1
15m
(50ft)
15m
0.5
(50ft)
2
2
15m
(50ft)
1
15m
(50ft)
15m
0.5
(50ft)
1
1
15m
(50ft)
15m
0.5
(50ft)
15m
0.5
0.5
(50ft)
1200 Volt or
1600 Volt
Shielded Unshielded
With 1204-TFB2
Terminator
With 1204-TFA1 Terminator
Using a Motor with
Using a Motor with Insulation VP-P
Insulation VP-P
1000 Volt or 1200 Volt
1000 Volt
1200 Volt
Shielded Unshielded Shielded
Unshielded
Shielded
Unshielded
2 kHz
2 kHz
2 kHz
2 kHz
2 kHz
2 kHz
2 kHz
2 kHz
0.85
0.85
0.85
0.85
0.85
0.85
0.85
0.85
182m
(600ft)
182m
(600ft)
182m
(600ft)
182m
(600ft)
182m
(600ft)
91m
(300ft)
182m
(600ft)
182m
(600ft)
182m
(600ft)
76m
(250ft)
182m
(600ft)
182m
(600ft)
68m
(225ft)
121m
(400ft)
45m
(150ft)
182m
(600ft)
182m
(600ft)
182m
(600ft)
182m
(600ft)
182m
(600ft)
182m
(600ft)
182m
(600ft)
182m
(600ft)
182m
(600ft)
167m
(550ft)
182m
(600ft)
182m
(600ft)
152m
(500ft)
182m
(600ft)
106m
(350ft)
NR
NR
91m
(300ft)
121m
(400ft)
121m
(400ft)
182m
(600ft)
NR
91m
(300ft)
91m
(300ft)
121m
(400ft)
NR
61m
(200ft)
91m
(300ft)
NR
NR
NR
91m
(300ft)
121m
99m
(400ft)
(325ft)
182m
99m
(600ft)
(325ft)
182m
99m
(600ft)
(325ft)
182m
99m
(600ft)
(325ft)
NR
91m
(300ft)
121m
99m
(400ft)
(325ft)
182m
99m
(600ft)
(325ft)
182m
99m
(600ft)
(325ft)
NR
91m
(300ft)
61m (200ft) 99m
(325ft)
121m
99m
(400ft)
(325ft)
NR
45m
(150ft)
NR
76m
(250ft)
NR
NR
61m (200ft) 91m
(300ft)
61m (200ft) 152m
(500ft)
61m (200ft) 182m
(600ft)
61m (200ft) 182m
(600ft)
61m (200ft) 182m
(600ft)
61m (200ft) 91m
(300ft)
61m (200ft) 152m
(500ft)
61m (200ft) 182m
(600ft)
61m (200ft) 182m
(600ft)
61m (200ft) 91m
(300ft)
61m (200ft) 121m
(400ft)
61m (200ft) 152m
(500ft)
61m (200ft) 45m
(150ft)
61m (200ft) 76m
(250ft)
NR
NR
121m
(400ft)
121m
(400ft)
121m
(400ft)
121m
(400ft)
121m
(400ft)
121m
(400ft)
121m
(400ft)
121m
(400ft)
121m
(400ft)
121m
(400ft)
121m
(400ft)
121m
(400ft)
76m (250ft)
121m
(400ft)
NR
NR = Not Recommended.
1
IMPORTANT: A 3% reactor reduces motor stress but may cause a degradation of motor waveform quality.
Reactors must have a turn-to-turn insulating rating of 2100 volts or higher. Reactors are not recommended for lightly
loaded applications because over-voltage trips may result at low output frequencies.