Drive Application Software Application Set Application Set Title Drive Product File Name for (AS) Date – Firmware Rev Adjustable Voltage PowerFlex 700VC AC Drive AS_PF700VC_Adj_Voltage_PwrSupply.dno 02/27/06 4.01 Attention: This document and related file(s) are designed to supplement configuration of the listed drive product. The information provided does not replace the drive products user manual and is intended for qualified personnel only. Description: Basic configuration of the Adjustable Voltage mode for use as a universal power supply. Limitations: Additional hardware, such as an output sine wave filter, may be required to protect the load from direct PWM voltages. Options & Notes: Drive Input & Output Connections: Inputs Function DI 1 4 - Stop / CF DI 2 5 - Start DI 3 15 – Speed Sel 1 DI 4 0 – Unused DI 5 0 – Unused DI 6 0 – Unused AI 1 AI 2 AI 3 NA Outputs Function DO 1 DO 2 DO 3 AO 1 AO 2 AO 3 NA AS_PF700VC_Adj_Voltage_PwrSupply.doc Form Revision – A Page 1 of 2 Description 3 wire Stop with Clear Fault function 3 wire Start Speed Reference Selection (toggle between Ref A and Ref B) Description Drive Application Software Application Set Parameter Configurations Changes from Default Parameter Settings Par Name Value 42 Motor NP FLA x.x A 5 – Adj 53 Motor Cntl Sel Voltage 54 Maximum Voltage Default 55 Maximum Freq 60.0 hz 81 Minimum Speed 0.0 hz 82 Maximum Speed 60.0 hz 83 Overspeed Limit 10 hz 90 Speed Ref A Sel 93 Speed Ref B Sel 101 102 Preset Speed 1 Preset Speed 2 140 Accel Time 1 xx.xx sec 142 Decel Time 1 xx.xx sec 155 650 Stop/Brk Mode a Adj Volt Phase 651 Adj Volt Select 654 Adj Volt Preset 1 208 655 Adj Volt Preset 2 230 656 Adj Volt Preset 3 380 657 Adj Volt Preset 4 415 658 Adj Volt Preset 5 460 661 Min Adj Voltage 0.00 672 Adj Volt Trim % 0.0% 675 676 Adj Volt AccTime Adj Volt DecTime 11 – Preset Spd1 12 – Preset Spd2 50 hz 60 hz 0 - Coast 1 – 3 Phase 11 – Preset Volt1 xx.xx sec xx.xx sec AS_PF700VC_Adj_Voltage_PwrSupply.doc Form Revision – A Page 2 of 2 Link Description Set to drive rating. Selects adjustable voltage control mode. The default value is Drive Rated Voltage. Sets the upper limit for output frequency. Sets the lower limit for speed reference after scaling is applied. Sets the upper limit for speed reference after scaling is applied. Setting should correspond to work with P82 and P55 settings (10Hz is default). Selects the speed reference source. Selects the speed reference source. Speed reference when Ref source A selected. Speed reference when Ref source B selected. The frequency ramp is typically set to 1 second or less for a power supply application. The frequency ramp is typically set to 1 second or less for a power supply application. Since the load is not rotating a coast stop is used. Select when 3 phase loads are connected. Selects the voltage reference source. Internal fixed voltage command available as a selection for P651. Internal fixed voltage command available as a selection for P651. Internal fixed voltage command available as a selection for P651. Internal fixed voltage command available as a selection for P651. Internal fixed voltage command available as a selection for P651. Sets the low limit for the voltage reference Scales the voltage trim value. The sign determines if it is added or subtracted from the reference The voltage ramp should be fast. 1 second is typical. The voltage ramp should be fast. 1 second is typical.