User Data Sheet

Drive Application Software
Application Set
Application Set Title
Drive Product
File Name for (AS)
Date / Revision
TorqProve™ - Vertical Conveyor with Encoder
PowerFlex® 700 Vector Control (Series B)
AS PF700 Vert Conveyor w-enc TorqProve.doc
12/13/04
-
01
Attention:
This document and related file(s) are designed to
supplement configuration of the listed drive product. The
information provided does not replace the drive products
user manual and is intended for qualified personnel only.
Description:
TorqProve for a counterbalanced vertical conveyor with an encoder. PLC was used to send
digital signals to drive for starting and stopping only. Decel and End Limit Inputs were used to
position conveyor in upper and lower conveyor locations.
Reference Application Brief Publication:
PowerFlex 700 App Brief-Vertical Conveyor 20B-AP005A-EN-P – April 2005
Limitations:
Options &
Notes:
ATTENTION: To guard against personal injury and/or equipment damage caused by
unexpected brake release, verify the Digital Out 1 brake connections and/or programming.
The default drive configuration energizes the Digital Out 1 relay when power is applied to the
drive. The PowerFlex 700 drive will not control the mechanical brake until TorqProve is
enabled. If the brake is connected to this relay, it could be released. If necessary,
disconnect the relay output until wiring/programming can be completed and verified.
Drive Input & Output Connections:
Inputs
Function
DI 1
8 - Run Forward
DI 2
9 - Run Reverse
DI 3
38 - Fast Stop
DI 4
39 - Decel Limit
DI 5
40 - End Limit
DI 6
1 - Enable
AI 1
AI 2
Outputs
Function
DO 1
4 - Run
DO
DO
AO
AO
2 - Alarm
1 - Fault
2
3
1
2
AS_PF700_Vert_Conveyor_w-enc_TorqProve.doc
Form Revision – A
Page 1 of 2
Description
P361
P362
P363
P364
P365
P366
Not Used
Not Used
Description
P380 - Brake relay output. Only terminals 12 & 13 should be used.
When TorqProve is “enabled” in P600, Relay 1 is dedicated for brake
control only. (All other programmed selections are ignored.)
P381
P382
Not Used
Not Used
Drive Application Software
Application Set
Parameter Configurations
Changes from Default Parameter Settings (Any listed defaults are in gray.)
Par
Name
Value
Link
Description
per
41(Data entered per motor nameplate)
Motor NP . . .
nameplate
45
4 - “FVC
53
Motor Cntl Sel
Vector”
80
Feedback Select
3 - “Encoder”
Must use quadrature and differential encoder
12 - “Preset
90
Speed Ref A Sel
Spd2”
101
Preset Speed 1
55 Hz
Normal operating speed
102
Preset Speed 2
10 Hz
Decel Limit speed (Creep Speed)
140
Accel Time 1
2.0 Sec.
Affected by desired cycle time and system Inertia
142
Decel Time 1
2.0 Sec.
Affected by desired cycle time and system Inertia
146
S Curve %
25%
Used to smooth accel / decel profile
436
Pos Torque Limit
140%
Limit was used to protect machine in event of a jam.
Typical range will be 20-40 rad/sec. Adjusting this will
449
Speed Desired BW
40 Rad/Sec.
automatically change Parameters 445 and 446
For Reference Only. Automatically adjusted when
445
Ki Speed Loop
(69.3)
Parameters 449 is changed.
For Reference Only. Automatically adjusted when
446
Kp Speed Loop
(23.2)
Parameters 449 is changed.
For Reference Only. Automatically determined during
450
Total Inertia
(0.58 Sec)
inertia autotune. (Note: Kp = BW x Inertia)
***
TorqProve Settings
600
TorqProve Cnfg
601
TorqProve SetUp
602
Spd Dev Band
603
604
605
606
607
608
609
610
611
Spd Band Integrator
Brake Release Time
ZeroSpdFloatTime
Float Tolerance
Brk Set Time
TorqLim SlewRate
BrkSlip Count
Brk Alarm Travel
MicroPos Scale%
Bit 0 = 1
0
5.0 Hz
80 mSec.
0.1 Sec
0.1 Sec
0.2 Hz
0.10 Sec
10.0 Sec
250 Revs
1.0 Rev
10 %
AS_PF700_Vert_Conveyor_w-enc_TorqProve.doc
Form Revision – A
Page 2 of 2
This “enables” TorqProve and Digital Output 1 will
now control the mechanical brake (Note: this is not
changed when “Reset to Defaults”)
Default – used only if using communications to control
TorqProve parameters.
This was used to protect machine in event of a jam. It
may need to increase depending on application.
May need to increase depending on application.
Set to minimum since these lifts rarely need float.
Default
Default
Default
Default
Default
Default – not used in this application