ADA600F

Ordering information
AC-DC Power Supplies Enclosed type
ADA600F
ADA 600
1
2
F
3
-24
4
Recommended EMI/EMC Filter
NAC-20-472
R
ADA
High voltage pulse noise type : NAP series
Low leakage current type : NAM series
*The EMI/EMC Filter is recommended
*to connect with several devices.
-O
5
1Series name
2Output wattage
3Universal input
4Output voltage
5Optional *7
G :Low leakage current
E :Low leakage current
and EMI class A
F :with Fan unit
T :Vertical terminal block
J :Connector type
C :with Coating
R :Remote ON/OFF
N1:DIN rail
W:Alarms and Redundant
operation
Specification is changed at
option,refer to Instruction
Manual.
Please refer to derating curve, because the rated load current depends on cooling method that is convection cooling or forced air.
SPECIFICATIONS
MODEL
VOLTAGE[V]
FREQUENCY[Hz]
ACIN 100V
ACIN 200V
ACIN 100V
POWER FACTOR
ACIN 200V
ACIN 100V *1
INRUSH CURRENT[A]
ACIN 200V *1
LEAKAGE CURRENT[mA]
VOLTAGE[V]
ACIN 100V *2
ACIN 100V *2
CURRENT[A]
ACIN 200V *2
ACIN 200V *2
LINE REGULATION[mV]
LOAD REGULATION[mV]
0 to +50C *3
RIPPLE[mVp-p]
-10 - 0C *3
0 to +50C *3
RIPPLE NOISE[mVp-p]
-10 - 0C *3
TEMPERATURE REGULATION[mV] 0 to +50C
*4
DRIFT[mV]
START-UP TIME[ms]
HOLD-UP TIME[ms]
OUTPUT VOLTAGE ADJUSTMENT RANGE[V]
OUTPUT VOLTAGE SETTING[V]
OVERCURRENT PROTECTION
OVERVOLTAGE PROTECTION[V]
OPERATING INDICATION
ALARM OUTPUT
REMOTE ON/OFF(RC)
*5
INPUT-OUTPUT -RC
INPUT-FG
*5
OUTPUT-RC-FG
OPERATING TEMP.,HUMID.AND ALTITUDE
STORAGE TEMP.,HUMID.AND ALTITUDE
VIBRATION
IMPACT
AGENCY APPROVALS
CONDUCTED NOISE
HARMONIC ATTENUATOR
CASE SIZE/WEIGHT
COOLING METHOD
EFFICIENCY[%]
INPUT
OUTPUT
PROTECTION
CIRCUIT AND
OTHERS
ISOLATION
ENVIRONMENT
SAFETY AND
NOISE
REGULATIONS
OTHERS
ADA600F-24
ADA600F-30
ADA600F-36
ADA600F-48
AC85 - 264 1f or DC 120 - 350 (AC64 or DC90 optionally available *6)
50/60 (47 - 63) or DC
84typ (Io=100%)
86typ (Io=100%)
86typ (Io=100%)
86typ (Io=100%)
86typ (Io=100%)
87typ (Io=100%)
87typ (Io=100%)
89typ (Io=100%)
0.99typ (Io=100%)
0.98typ (Io=100%)
20typ (Io=100%) (More than 3sec.to re-start)
40typ (Io=100%) (More than 3sec.to re-start)
0.75max (60Hz, According to IEC60950 and DEN-AN) (Io=100%)
24
30
36
48
14 (Peak 25) convection
11 (Peak 20) convection
9 (Peak 16.5) convection
6.5 (Peak 12.5) convection
21 (Peak 25) forced air
16.5 (Peak 20) forced air
14 (Peak 16.5) forced air
10.5 (Peak 12.5) forced air
15 (Peak 31) convection
12 (Peak 24.5) convection 10 (Peak 20.5) convection 7 (Peak 15.5) convection
25 (Peak 31) forced air
20 (Peak 24.5) forced air
16.5 (Peak 20.5) forced air 12.5 (Peak 15.5) forced air
96max
120max
144max
192max
150max
180max
240max
300max
120max
160max
200max
200max
160max
230max
260max
300max
150max
190max
230max
250max
180max
250max
280max
400max
240max
300max
360max
480max
96max
120max
144max
192max
500max (ACIN 100V, Io=100%)
20typ (ACIN 100V, Io=100%)
21.6 - 27.0
27.0 - 33.0
33.0 - 41.0
41.0 - 52.8
23.5 - 24.5
29.0 - 31.0
35.0 - 37.0
47.0 - 49.0
Works over 101% of peak current and recovers automatically
31 - 34.5
40 - 48
51 - 60
64 - 76
LED (Green)
Detecting low input voltage(PF), detecting low output voltage(LV). (Optional : -W, refer to Instruction Manual 5)
Requirement for external source (Option : -R, refer to Instruction Manual 5)
AC3,000V 1minute, Cutoff current = 10mA, DC500V 50MW min (At Room Temperature)
AC2,000V 1minute, Cutoff current = 10mA, DC500V 50MW min (At Room Temperature)
AC500V 1minute, Cutoff current = 100mA, DC500V 50MW min (At Room Temperature)
-10 to +71C, 20 - 90%RH (Non condensing) (Refer to DERATING CURVE), 3,000m (10,000feet) max
-20 to +75C, 20 - 90%RH (Non condensing), 9,000m (30,000feet) max
10 - 55Hz, 19.6m/s2 (2G), 3minutes period, 60minutes each along X, Y and Z axis
196.1m/s2 (20G), 11ms, once each X, Y and Z axis
UL60950-1, C-UL(CSA60950-1), EN60950-1, EN60065, EN50178 Complies with DEN-AN and IEC60950-1 (At only AC input)
Complies with FCC-B, CISPR22-B, EN55022-B, VCCI-B
Complies with IEC61000-3-2 *8
65X127X195mm [2.56X5X7.68 inches] (WXHXD) (without terminal block) /1.5kg max
Convection/Forced air
*1 The value is primary surge.The current of input surge to a built-in EMI/EMC Filter (0.2ms or
less) is excluded.
*2 Peak loading for 10sec.And Duty 35% max.Refer to Instruction Manual 4.Forced air is shown
in Instruction Manual 2.3.
*3 This is the value that measured on measuring board with capacitor of 22mF within 150mm
from output terminal.Measured by 20MHz oscilloscope or Ripple-Noise meter (Equivalent to
KEISOKU-GIKEN: RM101).
ADA-2
*4 Drift is the change in DC output for an eight hour period after a half-hour warm-up at 25C,
with the input voltage held constant at the rated input/output.
*5 Applicable when remote control (optional) is added.
*6 Derating is required.Consult us for details.
*7 Please contact us about safety approvals for the model with option.
*8 Please contact us about class C.
* A sound may occur from power supply at pulse loading.
ADA600F
Block diagram
Fuse
250V12A
Booster inductor
Noise
filter
AC IN 85 - 264V
Inrush
current
limitting
Detecting
current
Rectifier
Rectifier
&
Smooth
ADA
FG
Inverter
Option
Alarm
circuit
PF alarm
(-W)
Detecting
current
Control
Option
RC
(-R)
N+1
Redundancy
Control
External source
(-W)
Control
Current Balance (CB)
Master-Slave
circuit
Voltage Balance (VB)
Over voltage
protection
Inverter
Option
Detecting
output voltage
LV alarm (-W)
Rectifier
&
Smooth
DC OUT
External view
18.1 13
[0.71] [0.51]
(22.6)
4-M4
Mounting hole
(Bottom)
[0.89]
[1.14]
35 ±0.5
[1.89]
20
8-M4
Mounting hole
(Both sides)
Symbol
VB
CB
+V
+V
-V
-V
FG
N
L
Function
Voltage balance
Current balance
Output terminal(+)
Output terminal(+)
Output terminal(-)
Output terminal(-)
Frame ground
AC(N)
AC(L)
130.5 ±0.5
9
29±0.5 26.5
65 [1.04]
[2.56]
2-M4
Mounting hole
48
[5.14]
[0.35]
11
130.5 ±0.5
Terminal cover
[0.43]
M3.5
FG hole
2-M4
Mounting hole
¶ Pin assign
[5]
[4.13]
105 ±0.5
127
9 8
[9.06]
[1.38]
29
[1.14]
10
8.6 [0.39]
27.5
18
[0.71]
[1.08]
[0.35]
9
TB1
195
[0.75]
[0.35] [0.31]
VB
CB
+V
+V
-V
-V
FG
N
L
[4.51]
114.5
6.6
Name plate
[0.26]
LED
[0.64]
CN3(Option)
(19)
[0.79]
16.2
[0.34]
Voltage adjust
48
[5.14]
[1.89]
CN3(Option)
Screw type
M3
M4
Pin No.
2 1
4 3
6 5
8 7
10 9
12 11
14 13
Average 21A max per pin for TB1
1
RC+
Function
: Remote ON/OFF+(-R)
2
RC-
: Remote ON/OFF-(-R)
3-8
NC
: N.C.
9
LV+
: LV Alarm(-W)
10
LV-
: LV Alarm ground(-W)
11-12
NC
: N.C.
13
PF+
: PF Alarm(-W)
14
PF-
: PF Alarm ground(-W)
Connector
Terminal
Chain:SPHD-002T-P0.5
PHDR-14VS Loose:BPHD-001T-P0.5
BPHD-002T-P0.5 *1
*1 Ratchet Hand is nothing
CN3 S14B-PHDSS
Mating connector
Mfr.
J.S.T
¶ Tolerance : ±1 [±0.04]
¶ Weight : 1.5kg max
¶ PCB material / thickness : FR-4 / 1.6mm [0.06]
¶ Chassis and cover material : aluminium
¶ Dimensions in mm, [
]= inches
¶ Mounting torque : 1.2N • m(12.8kgf • cm) max
¶ Screw tighting torque
M4 : 1.6N • m(16.9kgf • cm) max , M3 : 0.8N • m(8.5kgf • cm) max
¶ I/0 terminal for option-J and -T is shown in Instruction Manual 5.
ADA-3
Ordering information
AC-DC Power Supplies Enclosed type
ADA750F
ADA 750
1
2
F
3
-24
4
Recommended EMI/EMC Filter
NAC-20-472
R
ADA
High voltage pulse noise type : NAP series
Low leakage current type : NAM series
*The EMI/EMC Filter is recommended
*to connect with several devices.
-O
5
1Series name
2Output wattage
3Universal input
4Output voltage
5Optional *7
G :Low leakage current
E :Low leakage current
and EMI class A
F :with Fan unit
T :Vertical terminal block
J :Connector type
C :with Coating
R :Remote ON/OFF
N1:DIN rail
W:Alarms and Redundant
operation
Specification is changed at
option,refer to Instruction
Manual.
Please refer to derating curve, because the rated load current depends on cooling method that is convection cooling or forced air.
SPECIFICATIONS
MODEL
VOLTAGE[V]
FREQUENCY[Hz]
ACIN 100V
ACIN 200V
ACIN 100V
POWER FACTOR
ACIN 200V
ACIN 100V *1
INRUSH CURRENT[A]
ACIN 200V *1
LEAKAGE CURRENT[mA]
VOLTAGE[V]
ACIN 100V *2
ACIN 100V *2
CURRENT[A]
ACIN 200V *2
ACIN 200V *2
LINE REGULATION[mV]
LOAD REGULATION[mV]
0 to +50C *3
RIPPLE[mVp-p]
-10 - 0C *3
0 to +50C *3
RIPPLE NOISE[mVp-p]
-10 - 0C *3
TEMPERATURE REGULATION[mV] 0 to +50C
*4
DRIFT[mV]
START-UP TIME[ms]
HOLD-UP TIME[ms]
OUTPUT VOLTAGE ADJUSTMENT RANGE[V]
OUTPUT VOLTAGE SETTING[V]
OVERCURRENT PROTECTION
OVERVOLTAGE PROTECTION[V]
OPERATING INDICATION
ALARM OUTPUT
REMOTE ON/OFF(RC)
*5
INPUT-OUTPUT -RC
INPUT-FG
*5
OUTPUT-RC-FG
OPERATING TEMP.,HUMID.AND ALTITUDE
STORAGE TEMP.,HUMID.AND ALTITUDE
VIBRATION
IMPACT
AGENCY APPROVALS
CONDUCTED NOISE
HARMONIC ATTENUATOR
CASE SIZE/WEIGHT
COOLING METHOD
EFFICIENCY[%]
INPUT
OUTPUT
PROTECTION
CIRCUIT AND
OTHERS
ISOLATION
ENVIRONMENT
SAFETY AND
NOISE
REGULATIONS
OTHERS
ADA750F-24
ADA750F-30
ADA750F-36
ADA750F-48
AC85 - 264 1f or DC 120 - 350 (AC64 or DC90 optionally available *6)
50/60 (47 - 63) or DC
86typ (Io=100%)
86typ (Io=100%)
87typ (Io=100%)
87typ (Io=100%)
88typ (Io=100%)
88typ (Io=100%)
89typ (Io=100%)
89typ (Io=100%)
0.99typ (Io=100%)
0.98typ (Io=100%)
20typ (Io=100%) (More than 3sec.to re-start)
40typ (Io=100%) (More than 3sec.to re-start)
0.75max (60Hz, According to IEC60950 and DEN-AN) (Io=100%)
24
30
36
48
17 (Peak 42) convection
13.5 (Peak 33.5) convection 11 (Peak 28) convection
8 (Peak 21) convection
25 (Peak 42) forced air
20 (Peak 33.5) forced air
16.5 (Peak 28) forced air
12.5 (Peak 21) forced air
19 (Peak 63) convection
15 (Peak 50) convection
12.5 (Peak 42) convection 9 (Peak 31.5) convection
31.5 (Peak 63) forced air
24.5 (Peak 50) forced air
20.5 (Peak 42) forced air
15.5 (Peak 31.5) forced air
96max
120max
144max
192max
150max
180max
240max
300max
120max
160max
200max
200max
160max
230max
260max
300max
150max
190max
230max
250max
180max
250max
280max
400max
240max
300max
360max
480max
96max
120max
144max
192max
500max (ACIN 100V, Io=100%)
20typ (ACIN 100V, Io=100%)
21.6 - 27.0
27.0 - 33.0
33.0 - 41.0
41.0 - 52.8
23.5 - 24.5
29.0 - 31.0
35.0 - 37.0
47.0 - 49.0
Works over 101% of peak current and recovers automatically
31 - 34.5
40 - 48
51 - 60
64 - 76
LED (Green)
Detecting low input voltage(PF), detecting low output voltage(LV). (Optional : -W, refer to Instruction Manual 5)
Requirement for external source (Option : -R, refer to Instruction Manual 5)
AC3,000V 1minute, Cutoff current = 10mA, DC500V 50MW min (At Room Temperature)
AC2,000V 1minute, Cutoff current = 10mA, DC500V 50MW min (At Room Temperature)
AC500V 1minute, Cutoff current = 100mA, DC500V 50MW min (At Room Temperature)
-10 to +71C, 20 - 90%RH (Non condensing) (Refer to DERATING CURVE), 3,000m (10,000feet) max
-20 to +75C, 20 - 90%RH (Non condensing), 9,000m (30,000feet) max
10 - 55Hz, 19.6m/s2 (2G), 3minutes period, 60minutes each along X, Y and Z axis
196.1m/s2 (20G), 11ms, once each X, Y and Z axis
UL60950-1, C-UL(CSA60950-1), EN60950-1, EN60065, EN50178 Complies with DEN-AN and IEC60950-1 (At only AC input)
Complies with FCC-B, CISPR22-B, EN55022-B, VCCI-B
Complies with IEC61000-3-2 *8
70X127X230mm [2.76X5X9.06 inches] (WXHXD) (without terminal block) /1.9kg max
Convection/Forced air
*1 The value is primary surge.The current of input surge to a built-in EMI/EMC Filter (0.2ms or
less) is excluded.
*2 Peak loading for 10sec.And Duty 35% max.Refer to Instruction Manual 4.Forced air is shown
in Instruction Manual 2.3.
*3 This is the value that measured on measuring board with capacitor of 22mF within 150mm
from output terminal.Measured by 20MHz oscilloscope or Ripple-Noise meter (Equivalent to
KEISOKU-GIKEN: RM101).
ADA-4
*4 Drift is the change in DC output for an eight hour period after a half-hour warm-up at 25C,
with the input voltage held constant at the rated input/output.
*5 Applicable when remote control (optional) is added.
*6 Derating is required.Consult us for details.
*7 Please contact us about safety approvals for the model with option.
*8 Please contact us about class C.
* A sound may occur from power supply at pulse loading.
ADA750F
Block diagram
Fuse
250V20A
Booster inductor
Noise
filter
AC IN 85 - 264V
Inrush
current
limitting
Detecting
current
Rectifier
Rectifier
&
Smooth
ADA
FG
Inverter
Option
Alarm
circuit
PF alarm
(-W)
Detecting
current
Control
Option
RC
(-R)
N+1
Redundancy
Control
External source
(-W)
Control
Current Balance (CB)
Master-Slave
circuit
Voltage Balance (VB)
Over voltage
protection
Inverter
Option
Detecting
output voltage
LV alarm (-W)
Rectifier
&
Smooth
DC OUT
External view
18.1 13
[0.71] [0.51]
(22.6)
Name plate
18
29
[0.71]
[1.14]
230
[0.75]
[9.06]
175.5 ±0.5
Terminal cover
[1.5]
20
35 ±0.5
2-M4
Mounting hole
175.5 ±0.5
8-M4
Mounting hole
(Both sides)
Symbol
VB
CB
+V
+V
-V
-V
FG
N
L
Function
Voltage balance
Current balance
Output terminal(+)
Output terminal(+)
Output terminal(-)
Output terminal(-)
Frame ground
AC(N)
AC(L)
9
[2.76]
2-M4
Mounting hole
¶ Pin assign
[5]
30.5
29 ±0.5
[1.14] 70 [1.2]
38
[6.91]
[0.35]
11
M3.5
FG hole
[0.43]
10
8.6 [0.39]
105 ±0.5
[4.13] 127
[0.35] [0.31]
9 8
(19)
[1.38]
TB1
[1.08]
27.5
[4.51]
VB
CB
+V
+V
-V
-V
FG
N
L
[0.35]
9
114.5
6.6
[0.64]
[0.26]
CN3(Option)
4-M4
Mounting hole
(Bottom)
LED
[0.34]
16.2
[0.79]
[0.89]
Voltage adjust
38
[6.91]
[1.5]
CN3(Option)
Screw type
M3
M4
Pin No.
2 1
4 3
6 5
8 7
10 9
12 11
14 13
Average 21A max per pin for TB1
¶ Tolerance : ±1 [±0.04]
¶ Weight : 1.9kg max
¶ PCB material / thickness : FR-4 / 1.6mm [0.06]
¶ Chassis and cover material : aluminium
¶ Dimensions in mm, [
]= inches
¶ Mounting torque : 1.2N • m(12.8kgf • cm) max
¶ Screw tighting torque
M4 : 1.6N • m(16.9kgf • cm) max , M3 : 0.8N • m(8.5kgf • cm) max
¶ I/0 terminal for option-J and -T is shown in Instruction Manual 5.
1
RC+
Function
: Remote ON/OFF+(-R)
2
RC-
: Remote ON/OFF-(-R)
3-8
NC
: N.C.
9
LV+
: LV Alarm(-W)
10
LV-
: LV Alarm ground(-W)
11-12
NC
: N.C.
13
PF+
: PF Alarm(-W)
14
PF-
: PF Alarm ground(-W)
Connector
Terminal
Chain:SPHD-002T-P0.5
PHDR-14VS Loose:BPHD-001T-P0.5
BPHD-002T-P0.5 *1
*1 Ratchet Hand is nothing
CN3 S14B-PHDSS
Mating connector
Mfr.
J.S.T
ADA-5
Ordering information
AC-DC Power Supplies Enclosed type
ADA1000F
ADA 1000
1
2
F
3
-24
4
Recommended EMI/EMC Filter
NAC-20-472
R
ADA
High voltage pulse noise type : NAP series
Low leakage current type : NAM series
*The EMI/EMC Filter is recommended
*to connect with several devices.
-O
5
1Series name
2Output wattage
3Universal input
4Output voltage
5Optional *7
G :Low leakage current
E :Low leakage current
and EMI class A
F :with Fan unit
T :Vertical terminal block
J :Connector type
C :with Coating
R :Remote ON/OFF
N1:DIN rail
W:Alarms and Redundant
operation
Specification is changed at
option,refer to Instruction
Manual.
Please refer to derating curve, because the rated load current depends on cooling method that is convection cooling or forced air.
SPECIFICATIONS
MODEL
VOLTAGE[V]
FREQUENCY[Hz]
ACIN 100V
ACIN 200V
ACIN 100V
POWER FACTOR
ACIN 200V
ACIN 100V *1
INRUSH CURRENT[A]
ACIN 200V *1
LEAKAGE CURRENT[mA]
VOLTAGE[V]
ACIN 100V *2
ACIN 100V *2
CURRENT[A]
ACIN 200V *2
ACIN 200V *2
LINE REGULATION[mV]
LOAD REGULATION[mV]
0 to +50C *3
RIPPLE[mVp-p]
-10 - 0C *3
0 to +50C *3
RIPPLE NOISE[mVp-p]
-10 - 0C *3
TEMPERATURE REGULATION[mV] 0 to +50C
*4
DRIFT[mV]
START-UP TIME[ms]
HOLD-UP TIME[ms]
OUTPUT VOLTAGE ADJUSTMENT RANGE[V]
OUTPUT VOLTAGE SETTING[V]
OVERCURRENT PROTECTION
OVERVOLTAGE PROTECTION[V]
OPERATING INDICATION
ALARM OUTPUT
REMOTE ON/OFF(RC)
*5
INPUT-OUTPUT -RC
INPUT-FG
*5
OUTPUT-RC-FG
OPERATING TEMP.,HUMID.AND ALTITUDE
STORAGE TEMP.,HUMID.AND ALTITUDE
VIBRATION
IMPACT
AGENCY APPROVALS
CONDUCTED NOISE
HARMONIC ATTENUATOR
CASE SIZE/WEIGHT
COOLING METHOD
EFFICIENCY[%]
INPUT
OUTPUT
PROTECTION
CIRCUIT AND
OTHERS
ISOLATION
ENVIRONMENT
SAFETY AND
NOISE
REGULATIONS
OTHERS
ADA1000F-24
ADA1000F-30
ADA1000F-36
ADA1000F-48
AC85 - 264 1f or DC 120 - 350 (AC64 or DC90 optionally available *6)
50/60 (47 - 63) or DC
86typ (Io=100%)
86typ (Io=100%)
87typ (Io=100%)
87typ (Io=100%)
88typ (Io=100%)
88typ (Io=100%)
89typ (Io=100%)
89typ (Io=100%)
0.99typ (Io=100%)
0.98typ (Io=100%)
20typ (Io=100%) (More than 3sec.to re-start)
40typ (Io=100%) (More than 3sec.to re-start)
0.75max (60Hz, According to IEC60950 and DEN-AN) (Io=100%)
24
30
36
48
21 (Peak 63) convection
16.5 (Peak 50) convection 14 (Peak 42) convection
10.5 (Peak 31.5) convection
33 (Peak 63) forced air
26 (Peak 50) forced air
22 (Peak 42) forced air
16.5 (Peak 31.5) forced air
25 (Peak 83) convection
20 (Peak 66) convection
16.5 (Peak 55) convection 11.5 (Peak 41.5) convection
42 (Peak 83) forced air
33.5 (Peak 66) forced air
28 (Peak 55) forced air
21 (Peak 41.5) forced air
96max
120max
144max
192max
150max
180max
240max
300max
120max
160max
200max
200max
160max
230max
260max
300max
150max
190max
230max
250max
180max
250max
280max
400max
240max
300max
360max
480max
96max
120max
144max
192max
500max (ACIN 100V, Io=100%)
20typ (ACIN 100V, Io=100%)
21.6 - 27.0
27.0 - 33.0
33.0 - 41.0
41.0 - 52.8
23.5 - 24.5
29.0 - 31.0
35.0 - 37.0
47 - 49
Works over 101% of peak current and recovers automatically
31 - 34.5
40 - 48
51 - 60
64 - 76
LED (Green)
Detecting low input voltage(PF), detecting low output voltage(LV). (Optional : -W, refer to Instruction Manual 5)
Requirement for external source (Option : -R, refer to Instruction Manual 5)
AC3,000V 1minute, Cutoff current = 10mA, DC500V 50MW min (At Room Temperature)
AC2,000V 1minute, Cutoff current = 10mA, DC500V 50MW min (At Room Temperature)
AC500V 1minute, Cutoff current = 100mA, DC500V 50MW min (At Room Temperature)
-10 to +71C, 20 - 90%RH (Non condensing) (Refer to DERATING CURVE), 3,000m (10,000feet) max
-20 to +75C, 20 - 90%RH (Non condensing), 9,000m (30,000feet) max
10 - 55Hz, 19.6m/s2 (2G), 3minutes period, 60minutes each along X, Y and Z axis
196.1m/s2 (20G), 11ms, once each X, Y and Z axis
UL60950-1, C-UL(CSA60950-1), EN60950-1, EN60065, EN50178 Complies with DEN-AN and IEC60950-1 (At only AC input)
Complies with FCC-B, CISPR22-B, EN55022-B, VCCI-B
Complies with IEC61000-3-2 *8
75X127X280mm [2.95X5X11.02 inches] (WXHXD) (without terminal block) /2.5kg max
Convection/Forced air
*1 The value is primary surge.The current of input surge to a built-in EMI/EMC Filter (0.2ms or
less) is excluded.
*2 Peak loading for 10sec.And Duty 35% max.Refer to Instruction Manual 4.Forced air is shown
in Instruction Manual 2.3.
*3 This is the value that measured on measuring board with capacitor of 22mF within 150mm
from output terminal.Measured by 20MHz oscilloscope or Ripple-Noise meter (Equivalent to
KEISOKU-GIKEN: RM101).
ADA-6
*4 Drift is the change in DC output for an eight hour period after a half-hour warm-up at 25C,
with the input voltage held constant at the rated input/output.
*5 Applicable when remote control (optional) is added.
*6 Derating is required.Consult us for details.
*7 Please contact us about safety approvals for the model with option.
*8 Please contact us about class C.
* A sound may occur from power supply at pulse loading.
ADA1000F
Block diagram
Fuse
250V25A
Booster inductor
Noise
filter
AC IN 85 - 264V
Inrush
current
limitting
Detecting
current
Rectifier
Rectifier
&
Smooth
ADA
FG
Inverter
Option
Alarm
circuit
PF alarm
(-W)
Detecting
current
Control
Option
RC
(-R)
N+1
Redundancy
Control
External source
(-W)
Control
Current Balance (CB)
Master-Slave
circuit
Voltage Balance (VB)
Over voltage
protection
Inverter
Option
Detecting
output voltage
LV alarm (-W)
Rectifier
&
Smooth
DC OUT
External view
19.1 13
[0.75] [0.51]
(23.6)
Name plate (19)
6.6
[0.26]
[4.13]
248 ±0.5
17
[9.76]
Terminal cover
[1.14]
[0.35]
30.5
[1.2]
[2.95]
248 ±0.5
[1.38]
2-M4
Mounting hole
35 ±0.5
Function
Voltage balance
Current balance
Output terminal(+)
Output terminal(+)
Output terminal(-)
Output terminal(-)
Frame ground
AC(N)
AC(L)
9
29 ±0.5
75
[0.67]
20
¶ Pin assign
[0.43]
11
[0.34]
M3.5
FG hole
2-M4
Mounting hole
8-M4
Mounting hole
(Both sides)
Symbol
VB
CB
+V
+V
-V
-V
FG
N
L
[5]
105 ±0.5
127
[0.35] [0.31]
9 8
29
[1.14]
10
8.6 [0.39]
27.5
18
[0.71]
[1.08]
[4.51]
Short piece
Don't take off
the short piece.
[0.35]
114.5
9
280
[11.02]
[0.75]
[0.79]
LED
VB
CB
+V
+V
-V
-V
FG
N
L
TB1
4-M4
Mounting hole
(Bottom)
Voltage adjust
[0.93]
CN3 17.2
(Option) [0.68]
17
[9.76]
[0.67]
CN3(Option)
Screw type
M3
M4
Pin No.
2 1
4 3
6 5
8 7
10 9
12 11
14 13
Average 21A max per pin for TB1
1
RC+
Function
: Remote ON/OFF+(-R)
2
RC-
: Remote ON/OFF-(-R)
3-8
NC
: N.C.
9
LV+
: LV Alarm(-W)
10
LV-
: LV Alarm ground(-W)
11-12
NC
: N.C.
13
PF+
: PF Alarm(-W)
14
PF-
: PF Alarm ground(-W)
Connector
Terminal
Chain:SPHD-002T-P0.5
PHDR-14VS Loose:BPHD-001T-P0.5
BPHD-002T-P0.5 *1
*1 Ratchet Hand is nothing
CN3 S14B-PHDSS
Mating connector
Mfr.
J.S.T
¶ Tolerance : ±1 [±0.04]
¶ Weight : 2.5kg max
¶ PCB material / thickness : FR-4 / 1.6mm [0.06]
¶ Chassis and cover material : aluminium
¶ Dimensions in mm, [
]= inches
¶ Mounting torque : 1.2N • m(12.8kgf • cm) max
¶ Screw tighting torque
M4 : 1.6N • m(16.9kgf • cm) max , M3 : 0.8N • m(8.5kgf • cm) max
¶ I/0 terminal for option-J and -T is shown in Instruction Manual 5.
ADA-7