Ordering information AC-DC Power Supplies Enclosed type FCA50F FCA FCA 1 50 2 F 3 -24 4 -O 5 1Series name 2Output wattage 3Universal input 4Output voltage 5Optional *6 N1 :with DIN rail attachment R MODEL MAX OUTPUT WATTAGE[W] DC OUTPUT FCA50F-24 50(Peak 160) 24V 2.1(Peak 6.7)A SPECIFICATIONS MODEL VOLTAGE[V] CURRENT[A] ACIN 240V ACIN 480V FREQUENCY[Hz] INPUT OUTPUT PROTECTION CIRCUIT AND OTHERS ISOLATION ENVIRONMENT SAFETY AND NOISE REGULATIONS OTHERS *1 *2 *3 *4 *5 *6 ACIN 240V ACIN 480V ACIN 240V INRUSH CURRENT[A] ACIN 480V LEAKAGE CURRENT[mA] VOLTAGE[V] *1 CURRENT[A] LINE REGULATION[mV] 0 - 2.1A LOAD REGULATION[mV] 0 - 6.7A 0 to +50C *2 RIPPLE[mVp-p] -10 - 0C *2 0 to +50C *2 RIPPLE NOISE[mVp-p] -10 - 0C *2 TEMPERATURE REGULATION[mV] -10 to +50C *5 DRIFT[mV] START-UP TIME[ms] HOLD-UP TIME[ms] OUTPUT VOLTAGE ADJUSTMENT RANGE[V] OVERCURRENT PROTECTION OVERVOLTAGE PROTECTION OPERATING INDICATION INPUT-OUTPUT INPUT-FG OUTPUT-FG OPERATING TEMP.,HUMID.AND ALTITUDE STORAGE TEMP.,HUMID.AND ALTITUDE *3 VIBRATION *3 IMPACT AGENCY APPROVALS CONDUCTED NOISE *4 CASE SIZE/WEIGHT COOLING METHOD EFFICIENCY[%] FCA50F-24 AC187 - 528 1f or DC265 - 746 0.55typ 0.30typ 50/60 (47 - 63) 82typ 78typ 25typ (At cold start) (At Room Temperature) 50typ (At cold start) (At Room Temperature) 0.75max (60Hz, According to IEC60950) 24 2.1 (Peak 6.7) 96max 150max 480max 240max 320max 680max 720max 600max 100max 800max (ACIN 240V, Io=100%) 10typ (ACIN 240V, Io=100%) 21.6 - 26.4 Works over 105% of peak current and recovers automatically Works at 115 - 140% of rating LED (Green) AC3,000V 1minute, Cutoff current = 10mA, DC500V 50MW min (At Room Temperature) AC2,000V 1minute, Cutoff current = 10mA, DC500V 50MW min (At Room Temperature) AC500V 1minute, Cutoff current = 100mA, DC500V 50MW min (At Room Temperature) -10 to +70C, 20 - 90%RH (Non condensing) (Refer to DERATING CURVE), 3,000m (10,000feet) max -20 to +75C, 20 - 90%RH (Non condensing), 9,000m (30,000feet) max 10 - 55Hz, 19.6m/s2 (2G), 3minutes period, 60minutes each along X, Y and Z axis 196.1m/s2 (20G), 11ms, once each X, Y and Z axis UL60950-1, C-UL, EN60950-1, EN50178 Complies with FCC-A, CISPR11-A, EN55011-A 50X125X124mm (WXHXD) / 640g max Convection Peak current for 150ms in a 30seconds period is acceptable. In case of rated input/output(ACIN240-480v/2.1A), either the 20MHz oscilloscope or the ripple noise meter(equivalent to Keisokugiken:RM101) is used. Option with DIN rail attachment(N1) is only for direction X(refer to sec4.2 in manual). Depth of power supply is 132mm with DIN rail attachment. Drift is the change in DC output for an eight hour period after a half-hour warm-up at 25C, with the input voltage held constant at the rated input/output. Please contact us about safety approvals for the model with option. FCA-2 FCA50F External view FCA 13max 50 30 (11.5) LED Voltage Adjust DIN Rail Attachment FCA50F-24-N1 only FG 125 (72) (102) AC(N) Spacer FCA50F-24-N1 only (7) 7 (34) AC(L) AC(N) Terminal Block (M4) (110) AC(L) (35.5) -V FG (116) +V 13 + - 10 FCA50F-24 (15.5) 16 (8) 124 (24.5) (22) (12) 119 3-M3 Mounting Hole 50 44.5 25.4 12.7 25.4±0.5 º3.8 71.1±0.5 Terminal Block Cover ¶Weight : 640g or less ¶Tolerance : ±1 ¶Mounting torque : 0.6N•m (6.3kgf•cm)max ¶Dimensions in mm. 45.9 18max Performance data ¡STATIC CHARACTERISTICS ¡RISE TIME & FALL TIME 24 Io=100% 14 Ripple 12 50 10 8 25 150 160 170 180 190 200 210 220 230 240 Io=100% Io=50% 10 5 0 AC Input ACIN 480V 250 ¡OVERCURRENT CHARACTERISTICS 26 50ms/DIV ¡INRUSH CURRENT Input Voltage AC480V 24 V 15 DC Output V 60Hz (AC 100V) INPUT VOLTAGE OUTPUT VOLTAGE V 75 OUTPUT VOLTAGE 16 20 22 20A/DIV OUTPUT VOLTAGE 18 100 RIPPLE mVp-p V 20 25 Output Voltage 22 60Hz Frequency 100% Load Input voltage AC480V 20 18 16 14 12 2 4 6 8 OUTPUT CURRENT A 10 12 50ms/DIV FCA-3 Ordering information AC-DC Power Supplies Enclosed type FCA75F FCA FCA 1 75 2 F 3 -24 4 -O 5 1Series name 2Output wattage 3Universal input 4Output voltage 5Optional *6 N1 :with DIN rail attachment R MODEL MAX OUTPUT WATTAGE[W] DC OUTPUT FCA75F-24 75(Peak 240) 24V 3.1(Peak 10)A SPECIFICATIONS MODEL VOLTAGE[V] CURRENT[A] ACIN 240V ACIN 480V FREQUENCY[Hz] INPUT OUTPUT PROTECTION CIRCUIT AND OTHERS ISOLATION ENVIRONMENT SAFETY AND NOISE REGULATIONS OTHERS *1 *2 *3 *4 *5 *6 ACIN 240V ACIN 480V ACIN 240V INRUSH CURRENT[A] ACIN 480V LEAKAGE CURRENT[mA] VOLTAGE[V] *1 CURRENT[A] LINE REGULATION[mV] 0 - 3.1A LOAD REGULATION[mV] 0 - 10A 0 to +50C *2 RIPPLE[mVp-p] -10 - 0C *2 0 to +50C *2 RIPPLE NOISE[mVp-p] -10 - 0C *2 TEMPERATURE REGULATION[mV] -10 to +50C *5 DRIFT[mV] START-UP TIME[ms] HOLD-UP TIME[ms] OUTPUT VOLTAGE ADJUSTMENT RANGE[V] OVERCURRENT PROTECTION OVERVOLTAGE PROTECTION OPERATING INDICATION INPUT-OUTPUT INPUT-FG OUTPUT-FG OPERATING TEMP.,HUMID.AND ALTITUDE STORAGE TEMP.,HUMID.AND ALTITUDE *3 VIBRATION *3 IMPACT AGENCY APPROVALS CONDUCTED NOISE *4 CASE SIZE/WEIGHT COOLING METHOD EFFICIENCY[%] FCA75F-24 AC187 - 528 1f or DC265 - 746 0.80typ 0.45typ 50/60 (47 - 63) 82typ 78typ 25typ (At cold start) (At Room Temperature) 50typ (At cold start) (At Room Temperature) 0.75max (60Hz, According to IEC60950) 24 3.1 (Peak 10) 96max 150max 480max 240max 320max 680max 720max 600max 100max 800max (ACIN 240V, Io=100%) 10typ (ACIN 240V, Io=100%) 21.6 - 26.4 Works over 105% of peak current and recovers automatically Works at 115 - 140% of rating LED (Green) AC3,000V 1minute, Cutoff current = 10mA, DC500V 50MW min (At Room Temperature) AC2,000V 1minute, Cutoff current = 10mA, DC500V 50MW min (At Room Temperature) AC500V 1minute, Cutoff current = 100mA, DC500V 50MW min (At Room Temperature) -10 to +70C, 20 - 90%RH (Non condensing) (Refer to DERATING CURVE), 3,000m (10,000feet) max -20 to +75C, 20 - 90%RH (Non condensing), 9,000m (30,000feet) max 10 - 55Hz, 19.6m/s2 (2G), 3minutes period, 60minutes each along X, Y and Z axis 196.1m/s2 (20G), 11ms, once each X, Y and Z axis UL60950-1, C-UL, EN60950-1, EN50178 Complies with FCC-A, CISPR11-A, EN55011-A 65X125X124mm (WXHXD) / 750g max Convection Peak current for 150ms in a 30seconds period is acceptable. In case of rated input/output(ACIN240-480v/3.1A), either the 20MHz oscilloscope or the ripple noise meter(equivalent to Keisokugiken:RM101) is used. Option with DIN rail attachment(N1) is only for direction X(refer to sec4.2 in manual). Depth of power supply is 132mm with DIN rail attachment. Drift is the change in DC output for an eight hour period after a half-hour warm-up at 25C, with the input voltage held constant at the rated input/output. Please contact us about safety approvals for the model with option. FCA-4 FCA75F External view FCA 13max 65 45 (11.5) LED DIN Rail Attachment FCA75F-24-N1 only Voltage Adjust AC(N) (35.5) (116) (72) AC(L) AC(N) Terminal Block (M4) Spacer FCA75F-24-N1 only (7) 7 (34) AC(L) 125 FG 13 -V FG (102) +V (110) + - 10 FCA75F-24 (15.5) (8) 124 (24.5) (37) 18 (12) 119 38.1±0.5 3-M3 Mounting Hole ¶Weight : 750g or less ¶Tolerance : ±1 ¶Mounting torque : 0.6N•m (6.3kgf•cm)max ¶Dimensions in mm. 12.7 31.75 64.5 59.5 º3.8 Terminal Block Cover 71.1±0.5 45.9 18max Performance data ¡STATIC CHARACTERISTICS ¡RISE TIME & FALL TIME 24 14 Io=100% 12 Ripple 50 10 8 25 150 160 170 180 190 200 210 220 230 240 Io=100% Io=50% 10 5 0 DC Output AC Input ACIN 480V 250 ¡OVERCURRENT CHARACTERISTICS 26 50ms/DIV ¡INRUSH CURRENT Input Voltage AC480V 24 V 15 V 60Hz (AC 200V) INPUT VOLTAGE OUTPUT VOLTAGE V 75 OUTPUT VOLTAGE 16 20 22 20A/DIV OUTPUT VOLTAGE 18 100 RIPPLE mVp-p V 20 25 Output Voltage 22 60Hz Frequency 100% Load Input voltage AC480V 20 18 16 14 12 2 4 6 8 OUTPUT CURRENT A 10 12 50ms/DIV FCA-5 Ordering information AC-DC Power Supplies Enclosed type FCA200F FCA FCA 200 1 2 F 3 -24 4 -O 5 1Series name 2Output wattage 3Universal input 4Output voltage 5Optional *6 N1:with DIN rail attachment R MODEL MAX OUTPUT WATTAGE[W] DC OUTPUT FCA200F-24 200 (Peak 1,008) 24V 8.4 (Peak 42)A SPECIFICATIONS MODEL VOLTAGE[V] CURRENT[A] ACIN 240V ACIN 480V FREQUENCY[Hz] INPUT OUTPUT PROTECTION CIRCUIT AND OTHERS ISOLATION ENVIRONMENT SAFETY AND NOISE REGULATIONS OTHERS *1 *2 *3 *4 *5 *6 ACIN 240V ACIN 480V ACIN 240V POWER FACTOR ACIN 480V ACIN 240V INRUSH CURRENT[A] ACIN 480V LEAKAGE CURRENT[mA] VOLTAGE[V] *1 CURRENT[A] LINE REGULATION[mV] LOAD REGULATION[mV] 0 - 8.4A 0 to +50C *2 RIPPLE[mVp-p] -10 - 0C *2 0 to +50C *2 RIPPLE NOISE[mVp-p] -10 - 0C *2 TEMPERATURE REGULATION[mV] -10 to +50C *5 DRIFT[mV] START-UP TIME[ms] HOLD-UP TIME[ms] OUTPUT VOLTAGE ADJUSTMENT RANGE[V] OVERCURRENT PROTECTION OVERVOLTAGE PROTECTION OPERATING INDICATION INPUT-OUTPUT INPUT-FG OUTPUT-FG OPERATING TEMP.,HUMID.AND ALTITUDE STORAGE TEMP.,HUMID.AND ALTITUDE *3 VIBRATION *3 IMPACT AGENCY APPROVALS CONDUCTED NOISE *4 CASE SIZE/WEIGHT COOLING METHOD EFFICIENCY[%] FCA200F-24 AC187 - 528 1f or DC265 - 530 1.10typ 0.55typ 50/60 (47 - 63) 81typ 81typ 0.98typ 0.93typ 25typ (At cold start) (At Room Temperature) 50typ (At cold start) (At Room Temperature) 1.5max (60Hz, According to IEC60950) 24 8.4 (Peak 42) 96max 150max 240max 320max 680max 720max 600max 100max 800max (ACIN 240V, Io=100%) 100typ (ACIN 240V, Io=100%) 21.6 - 26.4 Works over 105% of peak current and recovers automatically Works at 115 - 140% of rating LED (Green) AC3,000V 1minute, Cutoff current = 10mA, DC500V 50MW min (At Room Temperature) AC2,000V 1minute, Cutoff current = 10mA, DC500V 50MW min (At Room Temperature) AC500V 1minute, Cutoff current = 100mA, DC500V 50MW min (At Room Temperature) -10 to +60C, 20 - 90%RH (Non condensing) (Refer to DERATING CURVE), 3,000m (10,000feet) max -20 to +75C, 20 - 90%RH (Non condensing), 9,000m (30,000feet) max 10 - 55Hz, 19.6m/s2 (2G), 3minutes period, 60minutes each along X, Y and Z axis 196.1m/s2 (20G), 11ms, once each X, Y and Z axis UL60950-1, C-UL, EN60950-1 Complies with FCC-A, CISPR11-A, EN55011-A 150X125X125mm (WXHXD) / 1,700g max Convection Peak current for 50ms in a 30seconds period is acceptable. In case of rated input/output(ACIN240-480v/8.4A), either the 20MHz oscilloscope or the ripple noise meter(equivalent to Keisokugiken:RM101) is used. Option with DIN rail attachment(N1) is only for direction X(refer to sec4.2 in manual). Depth of power supply is 133mm with DIN rail attachment. Drift is the change in DC output for an eight hour period after a half-hour warm-up at 25C, with the input voltage held constant at the rated input/output. Please contact us about safety approvals for the model with option. FCA-6 FCA200F External view 3-Spacer FCA200F-O-N1 only FCA (35.5) (72) (7) (7) (50) 3-DIN Rail Attachment FCA200F-O-N1 only (50) 20max 125 (8) (23) (38) 2-Terminal Block Cover (98) (92.5) Name Plate 13 (20) LED for confirming of output 150 ¶ Mounting Hole 10 Voltage Adjust 101.6 t0.5 125 FCA200F 7-M4 V+ADJ FG (56) (73.5) (43) +V AC(L) +V AC(N) (12) ¶ Tolerance ±1 ¶ Material Electric galvanizing steel board ¶ Weight:1700g or less. ¶ Mounting torque:0.6N m(6.3kgf cm)max ¶ Dimensions in mm -V (20) (58) (97) (20) (11) 127t0.5 (29) (12.4) -V 4-M4 Mounting Hole Performance data ¡INPUT HARMONIC CURRENT (FCA200F-24 ) ¡RISE TIME & FALL TIME (FCA200F-24 ) 10 1 20 OUTPUT VOLTAGE V A HARMONIC CURRENT 25 Harmonic current standard class A (at odd number) Load factor 100% Input voltage AC 240V 0.1 0.01 0.001 0 10 20 30 15 Io=100% 10 5 DC Output 0 AC Input ACIN 480V 40 100ms/DIV HARMONIC ORDER ¡OVERCURRENT CHARACTERISTICS (FCA200F-24 ) ¡INRUSH CURRENT (FCA200F-24 ) 20A/DIV 30 Input Voltage AC480V OUTPUT VOLTAGE V 25 60Hz Frequency 100% Load Input voltage AC480V 20 15 10 5 20 40 OUTPUT CURRENT A 60 80 50ms/DIV FCA-7