VersaTRAK® IPm2m® RTU

Product Data Sheet
Industrial Automation
VersaTRAK® IPm2m® RTU
Sixnet's IPm2m® industrial RTU gives you a competitive edge...real-time information anytime and anywhere allows you
to make fast, cost-effective decisions. This industrial automation product is the “front-end” that brings real-time data
from distributed locations to the Internet or into your central information server.
Product Highlights
Overview
A Powerful Solution for Remote Site Management, IPm2m ® is an innovative combination of industrial RTU (Remote Terminal Unit), datalogger,
real-time database client and telemetry interface in a compact installation-ready package and features rugged, flexible performance.
Industrial RTU Product Highlights
Internet/Intranet connectivity (Ethernet and wireless)
Easy to configure datalogger
Advanced control capability
Advanced communications
Up to 5 com ports (1 Ethernet and 4 serial)
Modbus TCP/IP UDP/IP, ASCII, and RTU
DNP3
SNMP
PPP
IEC 60870-5-101/104
Highly scalable with additional I/O modules
26 I/O channels including counters and 16 bit analog
OEM packaging available
Flexible open source Linux Software
To learn more about our IPm2m ® Industrial RTU, simply contact [email protected] or call +1 (518) 877-5173.
Features
Industrial RTU Features
Diagnostic LEDs
Network status
Serial port activity
Discrete I/O status
Power status
PoE connected
Fast Ethernet
10/100 Base Tx
Auto cross-over
Auto-speed detecting
Flexible Communications
RS232 links to modems and other devices
RS485 for networking
Modbus device
Abundant I/O
8 DI, 4 DO, 8 AI, 2 AO
Flexible high speed counters
Time proportioned outputs
High resolution 16 bit analog
Configurable watch dog output
Mounting Options
Direct-panel mount
DIN-rail mounting: horizontal or vertical
Powerful CPU
32 bit processing
16 Meg Flash disk for programs and datalogging
32 Meg fast DRAM
Open Linux OS
Software Options
Flexible Software Options
Easy to use datalog wizard IEC61131-3 graphical programming including ladder logic, function blocks and more
C and C++ support (open Linux)
Optional user web pages
Service & Support
Long Term Support and Service Policy
Easy to Service
Hot swap module without disturbing wiring
Remote configuration and firmware updates
To learn more about our IPm2m ® Industrial RTU, simply contact [email protected] or call +1 (518) 877-5173.
Specs
Performance Specifications
Industrial power PC (32 bit data bus)
Operating system embedded Linux
Dynamic memory (RAM) 32 Mbytes - 32bit, 0 wait states
Program memory (Flash) 32 Mbytes
Retained memory (RAM) 512K (battery-backed)
Local I/O (on-board) 26 (see ordering info.)
I/O Expansion (up to 256) RS485 or Ethernet
Datalogging support
IEC 61131 programming
High Level C programming, Linux open source
Ethernet Port
10/100BaseTx (auto-detecting)
RJ45 connection (auto-crossover)
Protocols: TCP/IP, ARP, UDP, ICNP, DHCP, Modbus/TCP, Sixnet, and more
Serial Port
RS485 port A screws (485+, 485-, GND) (2-wire half-duplex)
RS232 Port B RJ45
(TD, RD, CTS, RTS, CD, DTR,DSR, GND)
Protocols: (master and slave) Sixnet and Modbus RTU/ASCII; many others available in Linux
Flow control hardware, software, RTS-party (for radios and RS485)
Discrete Inputs
12 channels (sinking or sourcing)
Guaranteed ON voltage 9 VDC
Maximum voltage 30 VDC
Guaranteed OFF voltage and current 5.0 VDC and 1.5 mA DC
Input resistance 10K Ohms
Input current @ 24 VDC 3 mA
Filtered ON/OFF delay 25 mS (20 Hz max. counting)
Fast ON/OFF delay 4 mS (100 Hz max. counting)
Count rate (channels 1 - 8) see above (10 KHz on channel 1)
Discrete Outputs
4 channels (10-30 VDC)
Maximum output per channel 1 Amp
Maximum output per module 4 Amps
Max. OFF state leakage 0.05 mA
Minimum load 1 mA
Inrush current 5 Amps (100 mS surge)
Typical ON resistance 0.3 Ohms
Typical ON voltage (@1A) 0.3 VDC
Analog Inputs
8 channels (4-20 mA)
A/D resolution 16 bits (0.003%)
Full scale accuracy +/-0.1% (@20°C)
Span and offset temp. coef. +/-50 ppm per °C
Input impedance 100 Ohm
Current protection Self-resetting fuses
DMRR (differential mode rejection) 66 dB at 50/60 Hz
CMRR (common mode rejection) Not applicable since analog inputs are single ended.
Analog Outputs
up to 2 channels (4-20 mA)
D/A resolution 16 bits (less than 1 mA)
Full scale accuracy (@ 20°C) +/- 0.02%
Span and offset temp. coef. +/- 50 ppm per °C typical
Max. output settling time 5 mS (to .05%)
Load resistance range (@ +24 VDC supply) 0-750 Ohms
Short circuit protection current limiting
Environmental
DIN-rail or flat-panel mount
Input power: 10-30 VDC
Input current: 100 mA @ 24 VDC (typical)
Temperature: -40 to 70°C (-40 to 85°C storage)
Humidity: 5% to 95% RH (non-condensing)
Flammability: UL 94V-0 materials
Electrical safety: UL 508, CSA C22.2/14; EN610101; (IEC1010)
EMI emissions: FCC part 15, ICES-003, Class A; EN55022; EN61326-1
EMC immunity: EN61326-1 (EN61000-4-2,3,4,6)
Surge withstand: IEEE-472 (ANSI C37.90)
Vibration: IEC68-2-6
Hazardous locations: (Class 1, Div 2, Groups A,B,C,D) UL 1604, CSA C22.2/213, Cenelec EN50021 Zone 2
Tested to Marine/offshore standards
To learn more about our IPm2m ® Industrial RTU, simply contact [email protected] or call +1 (518) 877-5173.
Add I/O
Part Number
(Module with wiring
base)
Part Number
(Including PoE)
DI DO
AI
AO
Description
E2-MIX24880-D
EB-MIX24880-D
24
8
8
0
Combination I/O module with 1 isolated
input counter *
E2-MIX24882-D
EB-MIX24882-D
24
8
8
2
Combination I/O module with 2 analog
outputs **
E2-32DI24-D
EB-32DI24-D
32
-
-
-
32 inputs (10-30 VDC)
E2-16DI24-D
EB-16DI24-D
16
-
-
-
16 individually isolated channels, 10-30
VDC/VAC with counters
16
-
-
-
16 individually isolated inputs,120 VAC
nominal
E2-16DIAC-D
-
E2-32DO24-D
EB-32DO24-D
-
32
-
-
High density discrete outputs
E2-16DO24-D
EB-16DO24-D
-
16
-
-
Individually isolated 1 Amp outputs with
self-resetting fuses
E2-32AI20M-D
EB-32AI20M-D
-
-
32
-
High density 16 bit 4-20mA inputs with
self-resetting fuses
E2-32AI10V-D
EB-32AI10V-D
-
-
32
-
Voltage inputs
E2-16AI20M-D
EB-16AI20M-D
-
-
16
-
16 channels 4-20mA inputs with
self-resetting fuses
E2-8AO20M-D
EB-8AO20M-D
-
-
-
8
4-20mA analog outputs
E2-16AI-8AO-D
EB-16AI-8AO-D
-
-
16
8
16 4-20mA inputs plus 8 4-20mA outputs
E2-16ISOTC-D***
EB-16ISOTC-D***
-
-
16TC
-
Instrumentation thermocouples
E2-8ISOTC-D***
EB-8ISOTC-D***
-
-
8TC
-
Instrumentation thermocouples
E2-16ISO20M-D ***
EB-16ISO20M-D ***
-
-
16
-
Isolated 4-20mA inputs
E2-10RTD-D
EB-10RTD-D
-
-
10
RTD
-
RTD (100 Ohm platinum), -200 to 850°C.
Note: * 24 maximum DI’s are listed, 8 of which can be configured as either DI or DO. The discrete outputs are protected by self-resetting fuses. ** EB part number prefix (above) is for modules
that include the optional PoE feature. Standard product part numbers begin with E2. *** Please check factory for availability
To learn more about our IPm2m ® Industrial RTU, simply contact [email protected] or call +1 (518) 877-5173.
Usage
How Much Datalogged Information Can be Stored?
Each Sixlog file is allocated a fixed amount of memory. Each record typically contains a time stamp (4 bytes), analog values (2 bytes each), and
discrete values (8 per byte). The size of the record is automatically computed and displayed for you by the Sixlog software. The overall storage time
(until the oldest data in a full file is overwritten by new data) is computed as:
Longest storage = (file size) x (capture interval) / (bytes per record)
Example:
16 analog values plus a time stamp ( 32 + 4 = 36 bytes) are logged every 5 minutes into a 400K file.
Oldest data = 400,000 (approx) x 5 minutes / 36 bytes/record = 55,555 Minutes (38 days)
By default, the VersaTRAK® IPm2m has more than 400K for datalogging.
Adding I/O modules to a VersaTRAK IPm2m Industrial RTU
Any combination of EtherTRAK-2 , EtherTRAK and RemoteTRAK I/O modules can be connected to a VersaTRAK® IPm2m
A single VersaTRAK® IPm2m supports up to 256 EtherTRAK and/or RemoteTRAK I/O.
Why VersaTRAK® IPm2m Instead of other Sixnet Controllers?
VersaTRAK® IPm2m offers 32 Megabytes of fast dynamic memory and 64 Megabytes of Flash disk.
VersaTRAK® IPm2m includes bundled software applications (AGA gas calculations and DNP-3 time stamped communications) for the utility industries
make your job easier.
VersaTRAK® IPm2m offers built-in I/O, Ethernet and up to four serial ports.
The embedded LINUX operating system in the VersaTRAK® IPm2m offers greater programming flexibility and performance than the legacy VersaTRAK /
Mini-VersaTRAK RTUs.
To learn more about our IPm2m ®Industrial RTU, simply contact [email protected] or call +1 (518) 877-5173.
Order Guide
Part Number
DI
DO
AI
AO
RS
232
RS
Eth
485
Memory
IPm2m RTU and Datalogger
VT-IPM2M-113-D
12
4
8
0
1
1
1
32MB Flash & DRAM
VT-IPM2M-213-D
12
4
8
2
1
1
1
32MB Flash & DRAM
VT-MIPM-135-D
12
8
6
0
2
1
1
512KB
NVRAM
64MB Flash 32MB DRAM
VT-MIPM-245-D
12
4
8
2
2
2
1
512KB
NVRAM
64MB Flash 32MB DRAM
8
4
2
0
2
1
1
Mini IPms
VT-uIPm RTUs
VT-UIPM-431-H
Legacy RTUs:
Legacy RTU
Part Numbers
16MB Flash & DRAM
RS RS
Eth
232 485
DI
DO
AI
AO
Memory
VT-MIPM-131-D
12
8
6
0
2
1
1
512KB
NVRAM
16MB Flash & DRAM
VT-MIPM-241-D
12
4
8
2
2
2
1
512KB
NVRAM
16MB Flash & DRAM
8
4
0
0
3
1
1
Mini IPms
VT-uIPm RTUs
VT-UIPM-441-H
Replacement Guide:
Legacy Product
16MB Flash & DRAM
Replacement RTUs
ST-IPm-1350
ST-IPm-6350
ST-IPm-2350
ST-IPm-6350
VT-IPm-2410
ST-IPm-6350 or VT-IPm-1410
VT-MIPm-131-D
VT-MIPm-135-D
VT-MIPm-241-D
VT-MIPm-245D
To learn more about our IPm2m ® Industrial RTU, simply contact [email protected] or call +1 518 877 5173