EtherTRAK®-2 Ethernet I/O Module Industrial Automation

D ATA S H E E T
EtherTRAK®-2 Ethernet I/O Module
Industrial Automation
Sixnet’s EtherTRAK®-2 Ethernet I/O modules provide a simple and secure way to reliably monitor
remote sites located in harsh environments. Offering the lowest cost per I/O point and rugged
environmental ratings, EtherTRAK-2 modules are ideal for both control rooms and extreme locations
across industries that include oil & gas, power & energy, transportation, mining, maritime and water/
wastewater.
Our compact DIN-rail modules support open-standard protocols to provide flexible communication
options for existing or newly installed Ethernet networks. By seamlessly replacing external devices such
as switches, data concentrators and protocol converters, EtherTRAK-2 modules transcend simple I/O
capabilities to cost-effectively streamline systems and improve reliability.
PRODUCT HIGHLIGHTS
mix of I/O channels support
• allFlexible
instrumentation needs
• Real-Time Ring™ for fast redundancy
independent Ethernet ports
• Dual
enable flexible networking
security proactively blocks
• Built-in
unwanted access
health diagnostics and
• Extensive
reporting reduce downtime
Modbus protocols provide
• Standard
universal compatibility
design supports extreme
• Rugged
temperatures and hazardous
Control
Center
IPm
Controller
Ring
Switch
locations
IPm
Controller
Service
Room
Ring
Switch
Real-Time
Ring
APPLICATIONS
• Oil & Gas
& Energy
• Power
- Transmission
EtherTRAK-2
I/O Modules
EtherTRAK-2
I/O Modules
- Distribution
•Transportation
•Mining
•Maritime
• Water/Wastewater
CONNECT. MONITOR. CONTROL.
Pump
Room
Engine
Room
Off-Shore Oil Rig
EtherTRAK-2 Ethernet I/O Module
Industrial Automation
INDUSTRIAL AUTOMATION
Sixnet’s rugged RTUs and I/O
provide a simple yet powerful
means to reliably monitor and
control remote sites around the
clock in the harshest environments.
Our compact automation systems
can start small and grow as needs
increase without requiring hardware
replacement. Virtually unlimited
scalability means organizations have
fewer restrictions on the number
of remote sites or devices that are
supported. “Best of both worlds”
programming combines Windows
ease of use with the future-proof
security of an embedded Linux OS.
FEATURES & BENEFITS
High-Performance, Flexible I/O
Configuration Maintenance & Monitoring
• Provides high-speed functionality
• Lowers overall cost per I/O point
–Flexible mix of up to 34 I/O supports
DI, DO, AI, AO, temperature (RTD and
thermocouples)
–High resolution 16-bit analog or high-speed
10-bit analog
–Fast I/O polling of up to 1mS
–Advanced counter functions with
32-bit reporting
–Time proportioned outputs simplify
high-speed pulse rate functions
• Delivers cross-platform configuration
• Offers easy-to-use software tools
– Configuration and monitoring via standard
web browser
– On-board storage for project documentation
– Project-based software tools
– User-based history tracks changes
– Per-channel calibration
– Configuration archiving
– Module hot-swap capabilities
Rugged, Compact Design
• Supports harsh environments
• Delivers proven reliability
– Industrial -40 to 75°C operating range
– UL/CSA (CUL), FCC and CE rated
– Hazardous locations rated for Class I,
Div 2 (Zone 2) areas
– Vibration resistant IEC68-2-6
– Self-resetting fuses protect I/O
Built-In Security
• Prevents unwanted intrusion
• Guards against unauthorized users
– User-assigned permissions
– Firewall protection
Flexible, Redundant Networking
• Simplifies connectivity by replacing Ethernet
switches
• Ensures reliability without additional cost
–Real-Time Ring switch mode for fast
redundancy
–Switch elimination mode enables
daisy-chaining
–Dual independent Ethernet ports
–Ethernet, RS-485 and USB connections
–Optional Power over Ethernet (PoE)
–Embedded data concentrator
Watchdog Monitoring & Reporting
• Provides health reports of various module
functions
• Reduces maintenance downtime
– CPU health
– Dual-power status
– PoE status
– Port link status
• Fail-safe outputs
– Communication activity
– Heartbeat watchdog monitor
NETWORKING OPTIONS
Break in Cable
Active Data Path
Real-Time Ring Switch Mode
Create redundant Ethernet reliability
without additional cost
Backup Data Path
Switch Elimination Mode
Daisy-chain modules without external
switches to save money and simplify
connectivity
LAN A
LAN B
Two Networks Mode
CONNECT. MONITOR. CONTROL.
Each Ethernet port has a unique MAC
and IP address for connection to two
independent physical networks
SPECIFICATIONS
General I/O Performance
Discrete Input Channels
• Power supply voltage: 10-30 VDC
• Input current requirement: 75 mA @ 24 VDC typical with no loads
• PoE power (EB modules only): 10 watts at 60°C for user loads
• De-rate: up to 5 watts at 75°C
• I/O: 512 discrete inputs and outputs plus 256 analog input and
output registers
• Unique station addresses: 16,000+ (Sixnet or 247 Modbus)
•
•
•
•
Ethernet Performance
• Ethernet ports: 10/100BaseTx (auto-detecting)
• Connection: RJ45 (auto-crossover)
• Isolation: 1500 volts RMS 1 minute (60 Hz.)
• Message response time: <1 mS per message
• Diagnostic LEDs: solid indicates link, blinking indicates activity
• Protocol support: TCP/IP, ARP, UDP, ICMP, DHCP, HTTP, Modbus
UDP/TCP slave mode, Modbus UDP master mode, Sixnet UDR UDP/
TCP slave mode, Sixnet UDR UDP master mode
• Real-Time Ring: 5ms per hop recovery time
• Independent networks: 1 or 2 with unique MAC and IP addres
Serial Ports
• RS-485 port: screw terminals (485+, 485-, GND; 2-wire halfduplex, not isolated)
• RS-485 networking: up to 32 (full load) stations
• RS-485 distance: up to 0.5 miles (baud-rate dependent)
• Baud rates: from 300 to 57,600 baud
• Protocols: TCP/IP, ARP, UDP, ICMP, DHCP, HTTP, Modbus UDP/
TCP slave mode, Modbus UDP master mode, Sixnet UDR UDP/TCP
slave mode, Sixnet UDR UDP master mode
• Protocols: master and slave; Sixnet and Modbus RTU/ASCII
• Diagnostic LEDs: transmit (TD) and receive (RD)
Analog Output Channels
•
•
•
•
•
•
•
Analog output range: 4-20 mA
D/A resolution: 16 bits (less than 1 uA)
Full scale accuracy: +/-0.02% (at 20°C)
Span and offset temperature: +/- 50 ppm per °C
Load resistance (@ 24 V): 0-750 Ohms
Current: limiting short circuit protection
Refer to user manual for additional specifications
Analog Input Channels
•
•
•
•
•
•
•
•
•
•
•
•
Input range: 4-20mA, 0-10VDC, RTD, thermocouple and 250mV
A/D resolution: 16 bits (0.003%); 10 bits (1mS fast option)
Input impedance (resistance): 100 ohms or 200 Kohms
Fuses: self-resetting short circuit protection (4-20 mA inputs)
DMRR (differential mode): 66 db at 50/60 Hz
Update time: from 880 mS to 1 mS (depending configuration)
Temperature accuracy: typical uncalibrated +/-0.5°C
RTD type: 100 Ohm platinum
RTD alpha: 0.00385 or 0.00392
RTD connections: 2 or 3-wire
RTD input range: -200 to 850°C
Refer to user manual for additional specifications
•
•
•
•
Voltage range: 10–30 VDC or 60–140 VAC
Input isolation: 150 volts (16 channel modules only)
Input resistance: 10 Kohms
Slow response (software configurable): 25 mS (20 Hz. maximum
counting rate)
Fastest response (software configurable): 1 mS (400 Hz. maximum
counting rate)
Special fast counting rate: up to 50 KHz on channels 1 and 2
Count up: pulse timing and pulse rate 16 or 32-bit reporting
Refer to user manual for additional specifications
Discrete Output Channels
•
•
•
•
•
•
Output voltage range: 10-30 VDC or 10-30VDC/AC
Maximum output power: up to 1A per channel
Short circuit protection: self-reset fuses (trip above 1.5 Amp)
Input isolation: 150 volts (16 channel modules only)
All channels scan rate: 1 mS
Refer to user manual for additional specifications
Web Interface
• Secure web access with password protection for multiple users
• 1 simultaneous user
• 750K memory for user pages (more with special order)
Environmental
• Operating temperature: -40 to 75°C (-40 to 85°C storage)
• Humidity: 5 to 95% RH (non-condensing; optional conformal
coating)
• Flammability: UL 94V-0 materials
• Vibration: IEC68-2-6
Standards Compliance
• Electrical safety : UL 508, CSA C22.2/14; EN61010-1 (IEC1010); CE
• EMI emissions: FCC part 15, ICES-003, Class A; EN55022;
EN61326-1; CE
• EMC immunity : EN61326-1 (EN61000-4-2,3,4,6); CE
• Hazardous locations: Class 1, Div 2, Groups A, B, C, D; UL 1604;
CSA C22.2/213; Cenelec EN50021 Zone 2
• Marine and offshore: tested and/or verified to meet various
standards such as DNV No. 2.4, Lloyds and ABS
Physical
• Mounting: DIN rail (EN50022), direct to panel or flat panel
• Packaging: impact resistant Lexan® polycarbonate
• Dimensions (module and base): 5.5”L x 3.5”W x 5.1”H (14cm x
8.9cm x 13cm)
Warranty
• 2 years on design and manufacturing defects
All specifications are subject to change. Contact Sixnet to learn more.
EtherTRAK-2 Ethernet I/O Module
Industrial Automation
ORDER GUIDE
PART NUMBER
DI
DO
AI
E2 or EB-MIX24880-D
24
8
8
AO
DESCRIPTION
E2 or EB-MIX24882-D
24
8
8
E2 or EB-32DI24-D
32
32 discrete inputs (10-30 VDC) including 16 multifunction counters
E2 or EB-16DI24-D
16
16 individually isolated discrete inputs (10-30 VDC) with counters
E2 or EB-16DIAC-D
16
16 individually isolated discrete inputs (120 VAC nominal; 10-30
32 channel combination I/O with 1 isolated input counter
2
34 channel combination I/O with 2 analog outputs
VDC) with counters
E2 or EB-32DO24-D
32
32 discrete outputs (10-30 VDC) 0.5 Amp each, 8 Amps total
E2 or EB-16DO24-D
16
16 individually isolated discrete ouputs (10-30VDC) 1 Amp outputs,
16 Amps total
E2 or EB-16DORLY
16
16 individually isolated discrete outputs (10-30VDC/VAC relay) 1
Amp outputs, 16 Amps total
E2 or EB-32AI20M-D
32
32 analog inputs (4-20 mA) with 16-bit accuracy
E2 or EB-32AI10V-D
32
32 analog inputs (0-10VDC)
E2 or EB-16AI20M-D
16
16 analog inputs (4-20 mA)
E2 or EB-8AO20M-D
E2 or EB-16AI-8AO-D
16
8
8 analog outputs (4-20 mA)
8
24 channel combination, 16 analog inputs (4-20 mA) and 8 analog
outputs (4-20 mA)
E2 or EB-16ISOTC-D
16TC
16 individually isolated analog inputs (thermocouple and
+/- 250 mV) with J, K, E, R, T, C, N, S
E2 or EB-8ISOTC-D
8TC
8 individually isolated analog inputs (thermocouple and
+/- 250 mV) with J, K, E, R, T, C, N, S
E2 or EB-16ISO20M-D
16
E2 or EB-10RTD-D
10RTD
About Red Lion
As the global experts in
communication, monitoring
and control for industrial
automation, Red Lion has been
delivering innovative solutions
to customers for forty years.
Our award-winning technology
enables companies worldwide
to gain real-time data visibility
that drives productivity. Product
brands include Red Lion, Sixnet
and N-Tron. With headquarters in
York, Pennsylvania, the company
has offices across the Americas,
Asia-Pacific and Europe. Red Lion
is a Spectris company.
For more information,
visit www.redlion.net/sixnet,
call +1 (518) 877-5173 or
email [email protected]
16 individually isolated analgo inputs (4-20 mA)
10 analog inputs (100 Ohm platinum RTD), rang is -200 to 850°C
MECHANICAL DRAWING
www.redlion.net/sixnet
+1 (518) 877-5173 | [email protected]
CONNECT. MONITOR. CONTROL.
© 2011 Sixnet. All Rights Reserved. OCT2012