PRODUCT DATASHEET E2- or EB- EtherTRAK-2 FAULT TOLERANT I/O HIGH PERFORMANCE, FLEXIBLE I/O n 32 I/O channels in a space-saving package– just 9 cm on a DIN rail n Flexible mix of functions in a single module n 16 bit analog I/O for extreme accuracy n 1 mS I/O polling for lightning fast performance n Advanced counter functions with 32 bit reporting n Watchdog monitoring and reporting n Vibration tolerant, Small, modular footprint PRODUCT HIGHLIGHTS n Module Health Reporting on the operational status of the I/O module itself. n Hot swap for instant installation and maintenance n Self-resetting fuses protect I/O against short circuits n Fast analog inputs report time integrated, and very stable 16 bit results. n Web-based I/O configuration and monitoring. n Stores project documentation in a quick-access web server. n Real-time RingTM switch for fault tolerant redundancy n Dual Ethernet Ports eliminate the need for switches n Easy to view LEDs provide complete status info. n Power over Ethernet (PoE) reduces cabling costs n OEM customizable components and labeling, web pages can include your logo and identification, part numbers, etc. n RS485, USB and optional RS232 ports for flexibility n Supports industry standard Modbus messaging n Embedded I/O concentrator polls additional I/O n n n I/O Concentrator can poll other Modbus or Sixnet I/O devices and report I/O status of as many as 512 discrete and 256 analog registers from 16 remote devices. FLEXIBLE, REDUNDANT, “MULTIPORT” COMMUNICATIONS TYPICAL APPLICATIONS n Process Automation Time proportioned outputs can be configured to pulse on with a duty cycle proportional to analog output register. n Distributed I/O System n Computer-based Systems 20 year support policy – making your job easier forever! n Fast Response Materials Handling Ring Switch Mode – Connect the last device back to the first to form a Real-time Ring™ creating redundant Ethernet reliability without additional cost. Our Real-time Ring™ Switches enable you to add any Ethernet devices to the ring. All specifications are subject to change. Consult factory for latest info. Industrial & Commercial Networking www.sixnet.com EtherTRAK-2 FAULT TOLERANT I/O SPECIFICATIONS GENERAL I/O MODULE CHARACTERISTICS n Power supply voltage: 10-30 VDC n Input current requirement: 75 mA @ 24 VDC typical w/ no loads n Etherbus® PoE power (EB- only) 10 Watts at 60°C for user loads n De-rate to 5 Watts at 75°C n I/O registers available for addnl expansion I/O: 512 discrete inputs and outputs plus n 256 analog inputs and output registers n Unique station addresses 16,000+ (Sixnet or 247 Modbus) ETHERNET – 2 PORTS Ethernet Port(s): 10/100BaseTx (auto-detecting) Connection: RJ45 (auto-crossover) Isolation: 1500 Volts RMS 1 minute (60 Hz.) Message response time is less than 1 mS per message Diagnostic LED’s, solid indicates link, blinking indicates activity Protocols supported: TCP/IP, ARP, UDP, ICMP, DHCP, Modbus/TCP, Sixnet, & more Real-time Ring™ 5ms per hop recovery time n Independent networks, 1 or 2 with unique MAC & IP address n n n n n n n SERIAL PORTS n RS485 port, Screw terminals (485+, 485-, GND) (2-wire half-duplex, not isolated) n n n n n n n n RS485 networking, Up to 32 (full-load) stations RS485 distance, Up to 0.5 miles (baud rate dependant) Baud Rates from 300 to 57,600 baud RS232 Port (optional) (TD, RD, CTS, RTS, GND) 2nd RS232 Port (special order) RJ45 (TD, RD, CTS, RTS, CD, DTR, DSR, GND) Protocols: master & slave: Sixnet & Modbus RTU/ASCII Diagnostic LEDs: Transmit (TD) & Receive (RD) Flow Control, RTS-party (for radios and RS485) WEB INTERFACE n Secure Web Access with Password protection for multiple users n 1 Simultaneous User n 750K Memory for User Pages (more with special order) ENVIRONMENTAL n n n n n n n n n n n n Mounting DIN rail (EN50022) or direct to panel or flat panel mount Operating temperature of -40 to 75°C (-40 to 85°C storage) Humidity 5 to 95% RH (non-condensing) (optional conformal coating) Flammability UL 94V-0 materials Electrical Safety UL 508, CSA C22.2/14; EN61010-1 (IEC1010); CE EMI emissions FCC part 15, ICES-003, Class A; EN55022; EN61000-6-4; CE EMC immunity EN61000-6-2; EN61000-4-2,3,4,6,8; CE Vibration: IEC68-2-6000 Hazardous locations UL1604, CSA C22.2/213 (class 1, div. 2), Cenelec EN60079-15 (zone 2; category 3) Marine & offshore tested and/or verified to meet various marine and maritime standards such as DNV No. 2.4, Lloyds & ABS Packaging Impact resistant Lexan® polycarbonate Module & Base: 5.5”L x 3.5”W x 5.1”H (14cm x 8.9cm x 13cm) ORDERING GUIDE Part # Prefix 2 E2- or EB- E2- or EBE2- or EBE2- or EB- E2E2- or EBE2- or EB- E2- or EB- E2- or EB- E2- or EB- E2- or EBE2- or EBE2- or EB- E2- or EB- E2- or EBE2- or EB- Part # Module w/base MIX24880-D MIX24882-D 32DI24-D 16DI24-D 16DIAC-D 32DO24-D 16DO24-D 32AI20M-D 32AI10V-D 16AI20M-D 8AO20M-D 16AI-8AO-D 16ISOTC-D3 8ISOTC-D3 16ISO20M-D3 10RTD-D n Input Polarity: Sourcing (apply power to active) or sinking (ground closure) on 8 n n n n n n n n n n n inputs Input isolation: 150 Volts (16 channel modules only) Guaranteed ON voltage: 9 VDC (55 VAC – AC module) Guaranteed OFF voltage: 5.0 VDC (35VAC – AC module) Guaranteed OFF current: 2 mA DC Input resistance: 10 Kohms Input current (@ 24 VDC) 3 mA Filtered ON/OFF delay: 25 mS (20 Hz. max. counting rate) Fastest response: 1 mS (400 Hz. max. counting rate) Special fast counting rate: Up to 50 KHz on channels 1 and 2 Count up, pulse timing and pulse rate 16 or 32 bit reporting Scan rate (all channels) 1 mS DISCRETE OUTPUT CHANNELS n Output voltage range 10-30 VDC n Max. output power: n n n n n n n p E2-32DO24: .5A per channel, 8A per module 1A per channel, 16A per module, .8A at 60ºC 1 channel, .4A at 60ºC 8 channels at 24VDC p E2-MIX24880 and MIX24882: 1A per channel, 8A per module, .8A at 60ºC 1 channel, .4A at 60ºC 8 channels at 24VDC Max. off state leakage: 0.01 mA (less than 10 μA) Short circuit protection, self-reset fuses (trip above 1.5 Amp) Min. load: 1 mA Inrush current: 5 Amps (100 mS surge) Typical on resistance: 0.3 Ohms (Drop 0.3 VDC @ 1 Amp) Input isolation: 150 Volts (16 channel modules only) All channels Scan rate: 1 mS p E2-16DO24: ANALOG OUTPUT CHANNELS n n n n n n Analog output range 4-20 mA D/A resolution 16 bits (less than 1 uA) Full scale accuracy +/-0.02% (at 20°C) Span and offset temp. +/- 50 ppm per °C typ. Max. output settling time 5 mS (to .05%) Load resistance (@ 24 V) 0-750 Ohms n Current limiting short circuit protection ANALOG INPUT CHANNELS n n n n n Standard ranges 4-20 mA or 0 to +10 VDC A/D resolution 16 bits (0.003%) 10 bits (fast option) Full scale accuracy +/- 0.02% (at 20 °C, 16 bit mode) Temperature coefficient +/- 50 ppm per °C (span and offset) Input impedance (resistance) 100 ohms (4-20 mA input range) 200 Kohms (10 volt input range) n Self-resetting short circuit protection fuses (4-20 mA inputs) n DMRR (differential mode) 66 db at 50/60 Hz n Fastest update time [# of chan.] 880 mS [all] -16-bit; 145ms [all] -14-bit; 1 ms [2] -10-bit 0 Combination I/O w/one isolated input counter 1 2 Combination I/O w/two analog outputs 2 32 inputs (10-30 VDC) including 16 multifunction counters 16 individually isolated 10-30 VAC/VDC w/counters 16 individually isolated 120 VAC (nominal) inputs High density discrete outputs (0.5 Amp each, 8 Amp total) Individually isolated 1 Amp outputs w/self-resetting fuses High density 16 bit 4-20 mA inputs w/self-resetting fuses Voltage inputs (other ranges available special order) 16 channels 4-20 mA inputs w/self-resetting fuses 8 4-20 mA analog outputs 8 16 4-20 mA analog inputs and 8 4-20 mA outputs 16 instrumentation inputs w/J,K,E,R,T,B,C,N,S thermocouples 8 instrumentation inputs w/J,K,E,R,T,B,C,N,S thermocouples Isolated 4-20mA inputs RTD (100 Ohm platinum), -200 to 850°C Mechanical drawing NOTES 1 24 maximum DI’s are listed, 8 of which can be configured as either DI or DO. The discrete outputs are protected by self-resetting fuses. 2 EB part number prefix is for modules that include the optional Etherbus® PoE feature. Standard product part numbers begin with E2. 3 Please check factory for availability. Sixnet Technology Park 331 Ushers Road • Ballston Lake, NY 12019 • USA +1.518.877.5173 • Fax +1.518.877.8346 • [email protected] Industrial & Commercial Networking E2- OR EB- DISCRETE INPUT CHANNELS n Voltage range E2-16DIAC-D only: 10 – 30 VDC (others on special order) 60 – 140 VAc DI1 DO AI AO Description 24 8 8 24 8 8 32 16 16 32 16 32 32 16 16 16TC 8TC 16 10RTD Datasheet E2-EB Rev: March, 2010 www.sixnet.com