Specifications - Electrocomponents

DC/DC Converters
THB 10 Series, 10 Watt
CB
Scheme
Features
◆ Supplementary and reinforced insulation
◆ I/O isolation 4000 VACrms rated for
IEC 60950-1
IEC 60601-1
UL 60950-1
ES 60601-1
300 Vrms working voltage
◆ 2 x MOOP Medical safety according to
AAMI/ANSI ES 60601-1:2005(R) and
IEC/EN 60601-1 3rd edition
◆ Industrial safety to UL/IEC/EN 60950-1
◆ Wide 2:1 input voltage ranges
◆ Extended operating temperature range
–40°C to 75°C max.
◆ Input filter meets EN55022, class A
◆ Continuous short-circuit protection
◆ High reliability
◆ 3-year product warranty
The THB 10 series is a range of high performance DC/DC converter modules
with double reinforced insulation system. It complies to latest medical safety
standard IEC 60950-1 3rd edition for MOOP (Means of Operator Protection). The product comes in a 2”x1” industry standard package. All 12 models features wide 2:1 input voltage range and fully regulated output voltage.
The converters offer an economical solution for demanding applications in
industrial and medical instrumentation.
Models
Order code
Input voltage range
THB 10-1211
Output voltage
Output current max.
Efficiency typ.
5.1 VDC
1600 mA
75 %
THB 10-1212
9 - 18 VDC
12.0 VDC
835 mA
80 %
THB 10-1222
(12 VDC nominal)
±12.0 VDC
±417 mA
80 %
±15.0 VDC
±333 mA
81 %
THB 10-1223
THB 10-2411
5.1 VDC
2000 mA
76 %
THB 10-2412
18 - 36 VDC
12.0 VDC
835 mA
81 %
THB 10-2422
(24 VDC nominal)
±12.0 VDC
±417 mA
81 %
THB 10-2423
±15.0 VDC
±333 mA
82 %
THB 10-4811
5.1 VDC
2000 mA
76 %
THB 10-4812
36 - 75 VDC
12.0 VDC
835 mA
81 %
THB 10-4822
(48 VDC nominal)
±12.0 VDC
±417 mA
81 %
±15.0 VDC
±333 mA
82 %
THB 10-4823
http://www.tracopower.com
Page 1 of 3
DC/DC Converters
THB 10 Series
10 Watt
Input Specifications
Input current at no load 12 V models: 30 mA typ.
24 V models: 20 mA typ.
48 V models: 10 mA typ.
Start up voltage / under voltage shutdown (hysteresis)
long term operation with under-voltage may cause demage
12 Vin models: 9.0 / 8.5 VDC (or lower)
24 Vin models: 18 / 16 VDC (or lower)
48 Vin models: 36 / 34 VDC (or lower)
Recommanded external input fuse (slow blow)
12 Vin models: 3 A
24 Vin models: 1.5 A
48 Vin models: 0.75 A
Surge voltage (1 sec. max.) 12 Vin models: 25 VDC max.
24 Vin models: 50 VDC max.
48 Vin models: 100 VDC max.
Input filter EN 55022 class A and FCC, level A
Output Specifications
Voltage set accuracy ±1.0 %
Regulation
– Input variation Vin min. to Vin max. 0.5 % max.
– Load variation 15 – 100 %: single output models: 1.0 % max.
dual output models: 2.0 % max. balanced load
Minimum load no minimum load required
Ripple and noise (20 MHz bandwidth)
5 VDC models: 100 mVp-p max.
other models: 150 mVp-p max.
Transient Response (25% load step change) 600 µs max.
Current limitation >120 % Iout max.
Short circuit protection continuous
Capacitive load
5 VDC output models: 1000 µF max.
12 VDC output models: 470 µF max.
dual output models: 220 µF max. (each output)
Isolation / Safety Standards
Isolation test voltage (flash tested 1 sec.) 6000 Vpk
I/O isolation voltage (50Hz, 60sec.) 4000 VAC
Leakage current (at 240VAC, 60Hz) 10 µA
I/O isolation capacity (at 100KHz, 1V) 60 pF typ.
I/O isolation resistance (at 500VDC) >10 Gohm
Safety standards IEC/EN 60950-1, IEC/EN 60601-1 3rd Edition,
ANSI/AAMI ES60601-1 and CAN/CSA-C22.2 No. 60601-1, Medical Electrical Equipment Part 1: General Requirements for Basic Safety
and Essential Performance
Safety approvals www.tracopower.com/products/thb10-cb60950.pdf
www.tracopower.com/products/thb10-cb60601.pdf
www.ul.com/database File: e188913 - QQGQ2
www.ul.com/database File: e188913 - QQHM2
–
–
–
–
CB test certificate according IEC 60950-1
CB test certificate according IEC 60601-1
UL online certification to UL 60950-1 (entry pending)
UL online certification to ES 60601-1 (entry pending)
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.
http://www.tracopower.com
Page 2 of 3
DC/DC Converters
THB 10 Series
10 Watt
General Specifications
Temperature ranges
– Operating –40°C to +75°C
– Case +95°C max.
– Storage –50°C to +125°C
Derating 2.5 %/K above 55°C
Humidity (non condensing) 95 % rel H max.
Altitude during operation 4000 m
Temperature coefficient ±0.02 %/K typ.
Reliability, calculated MTBF (MIL-HDBK-217F @ 25°C, ground benign) >1’000’000 h
Switching frequency 150 kHz typ. (puls width modulation)
Casing material non conductive plastic (UL 94V-0-rated)
Pin Material copper alloy with gold plate over nickel subplate
Weight 24.5 g (0.86 oz)
Soldering temperature max. 260°C / 10 sec.
Outline Dimensions
5.08
(0.2)
(0.1)
2.5 (0.1)
50.8 (2.0)
45.72 (1.8)
2 1
Bottom Viiew
5
4
5.08
(0.2)
Pin-Out
2.54
Pin
Single
Dual
1
+Vin (Vcc)
+Vin (Vcc)
2
-Vin(GND)
-Vin(GND)
3
+Vout
+Vout
4
No pin
Common
5
-Vout
-Vout
3
10.16
12.0
(0.47)
20.32
(0.4)
(0.8)
25.4
(1.0)
Dimensions in [mm], () = Inch
Pin diameter ø 1.0 ±0.05 (0.04 ±0.002)
Tolerances ±0.25 (±0.01)
Pin pich tolerances ±0.13 (±0.005)
Specifications can be changed without notice! Make sure you are using the latest documentation, downloadable at www.tracopower.com
www.tracopower.com
Rev. December 06. 2013
Page 3 of 3