INSTALLATION INSTRUCTIONS TBL Series Industrial and Residential Power Supply Rated Values AC-Input Voltage Range Order Code Output Power max. TBL 015-105 12 Watt TBL 015-112 Nominal 100Vac – 240Vac 50 – 60Hz TBL 015-124 TBL 030-112 TBL 030-124 15 Watt TBL 060-112 TBL 060-124 TBL 090-112 TBL 090-124 TBL 150-112 TBL 150-124 Nominal 100-120/220-240Vac 50 – 60Hz Operation 85-132/187-263Vac 47-63Hz * Output Voltage Adjustment Range 5.0Vdc / 2.4A recommended Circuit breaker (Characteristic C) 5.0 - 5.2Vdc 12.0Vdc / 1.25A 12.0 – 16.0Vdc 24.0Vdc / 0.63A 24.0 – 28.0Vdc 12.0Vdc / 2.5A 12.0 – 16.0Vdc 24.0Vdc / 1.25A 24.0 – 28.0Vdc 54 Watt 12.0Vdc / 4.5A 12.0 – 16.0Vdc 60 Watt 24.0Vdc / 2.5A 24.0 – 28.0Vdc 72 Watt 12.0Vdc / 6.0A 12.0 – 16.0Vdc 90 Watt 24.0Vdc / 3.75A 24.0 – 28.0Vdc 12.0Vdc / 10.0A 12.0 – 16.0Vdc 24.0Vdc / 6.25A 24.0 – 28.0Vdc 30 Watt Operation 85Vac – 263Vac 47 – 63Hz Output 6A 150 Watt * Adjustable by potentiometer with a screwdriver. Typical Reference Values Input current: @ Vin=115VAC @ Vin=230VAC Power Consumption @ Vin=115VAC @ Vin=230VAC TBL 015-105 0.25A typ. 0.17A typ. TBL 015-105 16.3 Watt typ. 16.6 Watt typ. TBL 015-1xx 0.29A typ. 0.20A typ. TBL 015-1xx 18.7 Watt typ. 19.3 Watt typ. TBL 030-xxx 0.57A typ. 0.39A typ. TBL 030-xxx 35.8 Watt typ. 36.3 Watt typ. TBL 060-112 1.00A typ. 0.68A typ. TBL 060-112 64.4 Watt typ. 65.5 Watt typ. TBL 060-124 1.10A typ. 0.70A typ. TBL 060-124 68.0 Watt typ. 69.0 Watt typ. TBL 090-112 1.40A typ. 0.90A typ. TBL 090-112 84.0 Watt typ. 84.0 Watt typ. TBL 090-124 1.60A typ. 1.07A typ. TBL 090-124 104 Watt typ. 104.5 Watt typ. TBL 150-112 1.84A typ. 0.98A typ. TBL 150-112 144 Watt typ. 147 Watt typ. TBL 150-124 2.80A typ. 1.8A typ. TBL 150-124 160 Watt typ. 162 Watt typ. Operating temperature range: Natural Air Convection Cooling -25°C – +60°C max at nominal load, above +60°C see derating below -13°F – +140°F max at nominal load, above +140°F see derating below Output Power Derating: above +60°C 2.5%/°C up to +70°C above 140°F 1.4%/°F up to +158°F Storage temperature range: Wire recommendation: <90Vac input voltage output power has to be derated by 5%/V for continuous operation -25°C – +85°C max -13°F – +185°F max 0.518 – 3.31mm2 AWG: 24 – 12 TBL 015-xxx & TBL 030-xxx: 0.518 – 3.31mm2 AWG: 24 – 12 TBL 060-xxx & TBL 090-xxx: 0.518 – 3.31mm2 AWG: 24 – 12 ** TBL 150-xxx 2.080 – 3.31mm2 AWG: 14 – 12 Use: Strand / solid copper wire Wire temperature specification: 70°C minimum (>70°C) ** TBL150-xxx - wire temperature specification 75°C minimum Wire material: Copper Input wire: Output wire: Connections: Screw type terminal COMBICON. Recommended tightening torque 0.5 to 0.7Nm (6.0lb.in.) Case material: Grey Plastic http://www.tracopower.com Rev: 1.9 /3611 Safety Instructions: Before installation read these instructions carefully and completely. This installation instruction cannot account for every possible condition of installation, operation or maintenance. Further information can be obtained from your local distributor’s office or from the product datasheet, which can be downloaded, from the Internet at http://tracopower.com/products/tbl.pdf. You will find additional information in our Instruction Manual, which can also be downloaded from the Internet at: http://www.tracopower.com/products/tbl_manual.pdf. The mains supply voltage connection, must be in accordance to IEC 62103, EN 50178 and IEC 60364, VDE 100. Before any installation, maintenance or modification work ensure that the main switch is switched off and prevented from being switched on again. Non-observance, touching of any live components or improper handling of this power supply can result in death, severe personal injury or substantial property damage. Proper and safe operation is dependent on proper storage, handling, installation and operation. Compliance with the relevant national regulations (in the USA, Europe and other countries) must be ensured. Before operation is started the following conditions must be ensured: Connection to mains supply in compliance with national regulations (VDE0100 and EN50178). By use of stranded wires, all strands must be fastened in the terminal blocks. (Potential danger of contact with the case) Power supply and mains cables must be sufficiently fused. Degree of protection II to IEC536. (Protection Class II). All output wires must be rated for the power supply output current and must be connected with the correct polarity. Sufficient cooling must be ensured. Warning: Hazardous voltages and components storing a very substantial amount of energy are present in this power supply during normal operating conditions. However, these are inaccessible. Improper handling may result in an electric shock or serious burns! Do not open the power supply until at least 5 minutes after it has been disconnected from the mains on all poles. Only trained personnel may open the power supply. Do not introduce any objects into the power supply. The output voltage adjustment potentiometer may only be actuated using an insulated screwdriver. Keep away from fire and water Installation Instructions: This power supply is designed for professional indoor systems. The unit shall be mounted in an enclosure without openings in the end application. In operation the power supply must not be accessible. It may be installed and put into service by qualified personnel only. The correct mounting position for optimal cooling performance must be observed. Do not cover any ventilation holes. Leave a free space of minimum 50mm (2in.) above and below the power supply. Observe power derating. The internal fuse is not accessible, as it may not be replaced by the user. If this internal fuse has blown, the power supply has an internal defect and, for safety reasons, must be shipped to the local distributor. In case this internal fuse has to be replaced in the field, replace only with same type and rating of fuse for continued protection against risk of fire. Recycling: The unit contains elements that are suitable for recycling, and components that need special disposal. You are therefore requested to make sure that the power supply will be recycled at the end of its service life. Never work on the power supply if power is supplied! Risk of electric arcs and electrical shock, which can cause death, severe personal injury or substantial property damage. http://www.tracopower.com Rev: 1.9 / 3611