QUICKTRONIC PROFESSIONAL QTP5

QUICKTRONIC PROFESSIONAL QTP5
osram.com
QUICKTRONIC PROFESSIONAL
QTP5
ECG for T5/16mm, T8/26mm, DULUX L
fluorescent lamps
QTP5
®
i.e. LUMILUX T5 HO ES
GL LB EU&LM FT, Edition: 13.03.2012. Subject to change without notice. Despite careful review, the possibility of mistakes cannot be excluded – no guaranty will be provided.
TECHNICAL INFORMATION
01
QUICKTRONIC PROFESSIONAL QTP5
Product Features:










Up to 100.000 hours lifetime1
Lamp start with optimized filament preheating within 1 sec.
Suitable for lighting with very high switching cycles
Reliable lamp ignition between -20°C...+50°C
Cut-off Technology
Suitable for luminaries of protection classes I and II2
CELMA Energy Efficiency Index A2 BAT (Best Available Technology)3
Automatic safety shut-down in case of a defect or at the end of the lamp’s life (EoL T.2)
Automatic restart after lamp replacement
Suitable for emergency installations (DC operation)
Technical Data
Max. cable diameter
for IDC-contakt [mm2]:
„s“4: 0.5; „f“5: 0.75
Max. cable diameter for
push-in contact [mm2]:
„s“4: 0.5…1.0
Starting time:
t: < 1 sec.
(<0.3 sec. in case of line interruptions/switchover of <0.5 sec.)
Line voltage:
220 - 240 V
Voltage range (AC):
198 - 264 V
Voltage range (DC):
176 - 276 V
Line frequency:
0, 50 - 60 Hz
Operating frequency:
Electrical strength:
40 - 50 kHz
300 V  permanent, 320 V  48 hours, 350 V  2 hours
Ambient temperature ta:
-20 °C to +50 °C
Measuring point temperature tc:
U-OUT:
1
2
3
4
5
Max. +75 °C
330 V
430 V
QTP5 1x14-35
QTP5 2x14-35
QTP5 1x24-39
QTP5 2x24-39
QTP5 1x49
QTP5 2x49
QTP5 1x54
QTP5 2x54
QTP5 1x80
QTP5 3x14, 4x14
at T = 65°C @ Tc. 50.000 h with max. 10% failure rate at tc = 75°C max
No need to connect (functional) earth in suitable luminaires of protection class II
EEI: A2 for QTP5 1x24-39
“s” = solid wire
“f” = flexible wire
GL LB EU&LM FT, Edition: 13.03.2012. Subject to change without notice. Despite careful review, the possibility of mistakes cannot be excluded – no guaranty will be provided.
TECHNICAL INFORMATION
02
QUICKTRONIC PROFESSIONAL QTP5
Inrush current and max. number of ECG per circuit breaker
ECG
QTP5
QTP5
QTP5
QTP5
QTP5
QTP5
QTP5
QTP5
QTP5
QTP5
Inrush Current
1x14-35
2x14-35
3x14, 4x14
1x24-39
2x24-39
1x49
2x49
1x54
2x54
1x80
Ip [A]
24
40
40
24
40
24
53
40
53
40
Max. number of ECG per circuit breaker
TH [µs]
230
200
200
230
200
230
190
200
190
200
B: 10A
17
12
12
17
12
17
8
12
8
12
B: 16A
28
19
19
28
19
28
13
19
13
19
C: 16 A
47
32
32
47
32
47
21
32
21
32
Standards and approval marks
Safety:
acc. to EN 61347-2-3 / IEC 61347-2-3
Radio interference:
acc. EN 55015: 2006 + A1: 2007 + A2: 2009
Harmonic content:
acc. to EN 61000-3-2 / IEC 61000-3-2
Immunity:
acc. to EN 61547 / IEC 61547
Approval marks:
Dimensions & weight
Description
Description
Length
[mm]
width [mm]
height [mm]
distance
Weight [g]
mounting
holes [mm]
QTP5 1x14-35
280
30
21
270
180
QTP5 2x14-35
360
30
21
350
255
QTP5 3x14, 4x14 280
40
21
270
240
QTP5 1x24-39
280
30
21
270
180
QTP5 2x24-39
360
30
21
350
255
QTP5 1x49
280
30
21
270
180
QTP5 2x49
360
30
21
350
255
QTP5 1x54
280
30
21
270
180
QTP5 2x54
360
30
21
350
255
QTP5 1x80
360
30
21
350
255
GL LB EU&LM FT, Edition: 13.03.2012. Subject to change without notice. Despite careful review, the possibility of mistakes cannot be excluded – no guaranty will be provided.
TECHNICAL INFORMATION
03
QUICKTRONIC PROFESSIONAL QTP5
Lamp wiring
QTP5 1x…
Max. permitted cable length in between ECG and lamp: 2.0 m (PIN 21, 22); 1.0 m (PIN 23, 24)
QTP5 2x…
Max. permitted cable length in between ECG and lamp: 2.0 m (PIN 21, 22, 25, 26); 1.0 m (PIN 23, 24)
QTP5 3x14, 4x14 – 3 lamp operation
Max. permitted cable length in between ECG and lamp: 1.5 m (PIN 4, 5, 21, 22, 23, 24); 1.0 m (PIN 6, 7, 25, 26)
GL LB EU&LM FT, Edition: 13.03.2012. Subject to change without notice. Despite careful review, the possibility of mistakes cannot be excluded – no guaranty will be provided.
TECHNICAL INFORMATION
04
QUICKTRONIC PROFESSIONAL QTP5
QTP5 3x14, 4x14 – 4 lamp operation
1 ~
2
3 ~
220...
240 V
QTP5 3x14, 4x14
4
5
6
7
21
22
23
24
25
26
L
L
L
L
Max. permitted cable length in between ECG and lamp: 1.5 m (PIN 4, 5, 21, 22, 23, 24); 1.0 m (PIN 6, 7, 25, 26)
Logistic Data
Description
EAN 10
EAN 40
Packaging Unit
QTP5 1x14-35
4008321329035
4008321329042
20
QTP5 2x14-35
4008321329073
4008321329080
20
QTP5 3x14, 4x14
4008321484598
4008321484604
20
QTP5 1x24-39
4008321329110
4008321329127
20
QTP5 2x24-39
4008321329417
4008321329424
20
QTP5 1x49
4008321329370
4008321329387
20
QTP5 2x49
4008321123831
4008321123848
20
QTP5 1x54
4008321329394
4008321329400
20
QTP5 2x54
4008321329097
4008321329103
20
QTP5 1x80
4008321329059
4008321329066
20
Lifetime
Measuring point
temperature tc:
Lifetime
with max. 10% failure rate
75 °C
50,000 h
65 °C
100,000 h
GL LB EU&LM FT, Edition: 13.03.2012. Subject to change without notice. Despite careful review, the possibility of mistakes cannot be excluded – no guaranty will be provided.
TECHNICAL INFORMATION
05
QUICKTRONIC PROFESSIONAL QTP5
Lamp/ECG System Combination
ECG
QTP5 1x14-35
QTP5 2x14-35
QTP5 3x14, 4x14
Lamp
HE 14
HE 21
HE 28
HE 35
DL28
HE 13 ES6
HE 19 ES6
HE 25 ES6
HE 32 ES6
DL 16 HE6
DL 22 HE6
DL 26 HE6
2x HE14
2x HE21
2x HE28
2x HE35
2x DL28
2x HE 13 ES6
2x HE 19 ES6
2x HE 25 ES6
2x HE 32 ES6
2x DL 16 HE6
2x DL 22 HE6
2x DL 26 HE6
3x HE14
4x HE14
3x HE 13 ES6
4x HE 13 ES6
HF lamp
wattage [W]
14
21
28.5
35
28
13
19
25
32
15
22
26
2x 13.5
2x 20.5
2x 28
2x 34.5
2x 28
26
38
50
64
32
44
52
3x 14
4x 14
3x 12.9
4x 12.5
System
wattage [W]
16
24
31
38
31
15
22
27
34
18
24
29
30
45
60
75
60
28
42
54
68
34
48
57
48
63
43
56
Line current [A]
0.08
0.11
0.14
0.17
0.14
0.075
0.10
0.12
0.15
0.08
0.11
0.13
0.14
0.20
0.26
0.33
0.26
0.13
0.185
0.24
0.30
0.15
0.21
0.26
0.28
0.22
0.19
0.25
Luminous flux at
25°C [lm]
1200
1900
2600
3320
2800
1150
1800
2450
3100
1500
2055
2470
2x 1200
2x 1900
2x 2600
2x 3320
2x 2800
2x 1150
2x 1800
2x 2450
2x 3100
2x 1500
2x 2055
2x 2470
3x 1200
4x 1200
3x 1150
4x 1100
Luminous flux at
35°C [lm]
1350
2100
2900
3650
1350
2100
2900
3650
1600
2200
2600
2x 1350
2x 2100
2x 2900
2x 3650
2x 1350
2x 2100
2x 2900
2x 3650
2x 1600
2x 2200
2x 2600
3x 1350
4x 1350
3x 1350
3x 1290
Power factor
[λ]
0.90c
0.95
0.96
0.97
0.95
0.90c
0.95
0.96
0.97
0.92
0.95
0.95
0.98
0.98
0.98
0.98
0.98
0.95
0.98
0.98
0.98
0.95
0.96
0.95
0.95
0.97
0.95
0.97
GL LB EU&LM FT, Edition: 13.03.2012. Subject to change without notice. Despite careful review, the possibility of mistakes cannot be excluded – no guaranty will be provided.
TECHNICAL INFORMATION
06
QUICKTRONIC PROFESSIONAL QTP5
ECG
QTP5 1x24-39
QTP5 2x24-39
QTP5 1x49
QTP5 2x49
QTP5 1x54
QTP5 2x54
QTP5 1x80
Lamp
HO 24
HO 39
L 30
HO 20 ES6
HO 34 ES6
T8 L 36 W6
2x HO 24
2x HO 39
2x L 30
6
2x HO 20 ES
6
2x HO 34 ES
2x T8 L 36 W6
HO 49
HO 45 ES6
2x HO 49
2x HO 45 ES6
HO 54
HO 50 ES6
T8 L 586
DL 556
2x HO 54
2x HO 50 ES6
2x T8 L 586
2x DL 556
HO 80
DL 80
HO 73 ES6
HF lamp
wattage [W]
23
38
30
20
34
32
2x 22.5
2x 38
2x 28.5
2x 21
2x 35
64
49
45
2x 49.5
92
54
50
50
50
2x 54
100
100
102
80
80
73
System
wattage [W]
26
41
33
23
37
36
49
82
62
45
75
70
53
49
106
100
59
54
55
54
115
108
109
110
86
86
79
Line current [A]
0.12
0.18
0.15
0.105
0.165
0.16
0.23
0.36
0.27
0.195
0.32
0.31
0.24
0.22
0.49
0.44
0.26
0.24
0.25
0.24
0.50
0.46
0.48
0.48
0.38
0.38
0.35
Luminous flux at
25°C [lm]
1750
3100
3000
1650
3250
3200
2x 1750
2x 3100
2x 2850
2x1650
2x3250
2x 3200
4310
4310
2x 4310
2x 4310
4450
4450
5000
4450
2x 4450
2x 4450
2x 5000
2x 4500
6150
6000
6150
Luminous flux at
35°C [lm]
2000
3500
2000
3500
2x 2000
2x 3500
2x2000
2x3500
4900
4900
2x 4900
2x 4900
5000
5000
2x 5000
2x 5000
7000
7000
Power factor
[λ]
0.95
0.98
0.97
0.95
0.98
0.97
0.95
0.98
0.98
0.95
0.98
0.98
0.95
0.95
0.97
0.99
0.98
0.98
0.97
0.98
0.99
0.99
0.97
0.99
0.98
0.99
0.98
For more information on ECG refer to http://www.osram.com/ecg
For more information on System Guarantee refer to http://www.osram.com/guarantee
6
Additional Lamp-ballast combination without ENEC
GL LB EU&LM FT, Edition: 13.03.2012. Subject to change without notice. Despite careful review, the possibility of mistakes cannot be excluded – no guaranty will be provided.
TECHNICAL INFORMATION
07