POWERTRONIC Technical Information

POWERTRONIC

Technical
Information
for HID lamps 70 W
PTU 70/220-240
Edition: Juli 2005
Subject to change
Technical Data:
Reference:
For lamp (wattage):
PTU 70/220-240
HCI-TS 70 W, HCI-T 70 W, HCI-TC 70 W, HCI-PAR 70 W,
HCI-E/P 70 W, HQI-TS 70 W, HQI-T 70 W, HQI-E 70 W
(NAV on request) and other similar commercially available lamps
Line voltage:
220 - 240 V∼
Perm. voltage fluctuations:
198-254 V∼
Line frequency:
50 / 60 Hz
Line current at 230V:
0,36 A
Power factor:
>0.95c
Inrush current:
45 A/130 µs
System wattage:
80 W ± 3 W
Losses:
7W±1W
Lamp wattage:
73 W ± 3 W
Operating frequency:
130 Hz
Microprocessor
reliable cut off of defective lamps or for tc > 83°C
Time to reset the ECG (by mains interrupt)
> 0,5 s
Ignition voltage:
5 kVp
Electronic unit/Ignition unit:
3,0 m
(Max. capacity of wire ECG/lamp
200 pF)
Ignition time is limited:
18 min
Max. temperature in point tc
80 °C
Max. ambient temperature ta
50 °C
Min. ambient temperature ta:
-25 °C
Overheating protection
power reduction at tc= 80°C, switch off at t c = 83°C
Dimensions*)
134 mm x 88 mm x 39 mm
Weight
≈ 350 g
Terminal: permitted wiring cross section
0,5-4mm2
Radio interference suppression:
EN 55015
Harmonics of line current:
EN 61000-3-2
Immunity:
EN 61547
Approval: Safety according to EN 61347-1;…-2-1;…-2-3
VDE-registration-no.:
40004469
Cable Clamp Reference
PTU-SR
mains:
mains looping possible,use only one terminal for earthing
cable: e.g.: H03VV-F 2 x 0,5; 2x0,75; 2x1,0; 2x1,5
3x0,50; 3x0,75; 3x1,0; 3x1,5
NYM 3x1,5
Output:
*)See drawing
∅ max.10 mm
e.g.: SIHY-Cu vz 3x0,75
POWERTRONIC

Technical
Information
for HID lamps 70 W
PTU 70/220-240
Edition: Juli 2005
39
Subject to change
tc
88
134
78
1
16
120
PTU 70/220-240 with cable clamp
Thermal characteristics:
Ballast losses and lamp heat radiation can lead to heat accumulation in a complete closed case.
Therefore it is necessary to ensure, that the temperature at the measuring point tc does not exceed
the maximum value.
Attention:
Disconnect the device before replacing the lamp.
Stand-alone installation possible:
The cable clamp with covering plate is available separately. For ceiling cut outs of > 94 mm.