SMS Relay Box (Complete Assembly) Data Sheet

RAD-SYS-NEMA4X-SMS
NEMA 4X enclosure with DC power supply and
SMS relay
INTERFACE
Data sheet
2928_en_B
1
© PHOENIX CONTACT 2011-09-27
Description
The prewired control cabinet provides a 24 V DC power
supply, surge protection for the line power and terminal
blocks for easy connectivity, all mounted on standard NS 35
mounting rail. The 0.75 A power supply provides sufficient
power for the radio and several additional components, if
necessary, which can be mounted on the 25 cm (10 in.) of
available rail mounting space.
The selected components provide a robust, consistent
signal acquisition system for remote data collection. Simply
connect the sensors to the system, plug in the GSM SIM,
and enter some simple configuration details to complete the
system.
2
–
–
–
–
–
–
Features
1 amp fuse
MAINS-PLUGTRAB surge protection for the line input
(100 - 240 V AC)
Prewired cabinetry with extra terminal blocks for simple,
flexible installation
NEMA 4X enclosure provides protection against the
weather
Panel and pole mounting kits available
2 dBi low-profile antenna
The PSI-MODEM-SMS-REL/6ADI/4DO/DC is a compact,
remote control and signalling station. Six configurable
analog/digital inputs and four relay outputs with PDT
contacts are monitored and controlled via SMS messages
with any GSM mobile phone network. Up to 50 numbers can
be entered and programmed to receive SMS messages.
Additional information regarding the PSI-MODEM-SMS-REL/6ADI/4DO/DC can be found at
www.phoenixcontact.net/catalog.
Make sure you always use the latest documentation.
It can be downloaded at www.phoenixcontact.net/catalog.
This data sheet is valid for all products listed on the following page:
RAD-SYS-NEMA4X-SMS
3
Ordering data
Products
Description
Type
Order No.
Pcs./Pkt.
Enclosure, with SMS relay includes power supply and surge protection
RAD-SYS-NEMA4X-SMS
2917189
1
Accessories
Description
Type
Order No.
Pcs./Pkt.
Pole mounting kit
RAD-SYS-BKT
2900038
1
GSM/GPRS antenna, omnidirectional, 2 m cable with SMA round connector PSI-GSM/UMTS-QB-ANT
2313371
1
GSM/GPRS antenna, Yagi, 8 dBi with N-type male connector
RAD-ANT-GSM/UMTS-QB-YAGI-8
2901561
1
Cable, D-SUB to USB, includes DB-9 to DB-25 adapter
CM-KBL-RS232/USB
2881078
1
4
Technical data
General data
Dimensions (H x W x D)
359 x 311 x 156 mm (14.1 x 12.3 x 6.1 in.)
Material
Fiberglass
Conduit connections
1/2-in. NPT
Antenna connection
SMA, female
STEP-PS/1AC/24DC/0.75 (Order No. 2868635)
Input voltage range nominal
100 - 240 V DC
Current consumption, typical
0.25 A @ 230 V AC
0.37 A @ 120 V AC
Output current, typical
0.75 A (-25…70°C)
0.83 A (-25…40°C)
Output current, maximum
1.4 A
Nominal output voltage
24 V DC
PSI-GSM/UMTS-QB-ANT (Order No. 2313371)
Frequency range
850/900/1800/1900/2100 MHz
VSWR, typical
<2.0
Gain, typical
1.0 dB
Operating temperature
-40…105°C
PT 2-PE/S-230AC-ST (Order No. 2839347)
Maximum continuous operating voltage
253 V AC
Leakage current @ MCOV (L-N)
< 1.1 mA
Leakage current to ground
< 1.5 µA
Maximum discharge surge current (8/20 µs) per mode
10 kA
2928_en_B
PHOENIX CONTACT
2
RAD-SYS-NEMA4X-SMS
5
Technical data of PSI-MODEM-SMS-REL/6ADI/4DO/DC
General data
Housing
DIN 43880 housing system
Housing dimensions (W x H x D)
88 x 90 x 60 mm
Mounting
NS35 according to EN 60715
Connection
Screw terminal block 2.5 mm², 0.5 Nm, Pozidrive/slotted head
Degree of protection
IP20
Housing material
Noryl SE1, Lexan® EXL9330
Weight
120 g (approximately)
Ambient temperature (storage)
-40°C … +85°C
Ambient temperature (operation)
-25°C … +55°C
Relative humidity
0 … 90% (no condensation)
Transient protection
Single pulse 2.5 kV/2.5 Ws
Electrical data
Nominal operating voltage
12 … 48 V DC
Operating voltage
10 … 60 V DC
Standby current consumption, approximate
15 mA at 24 V DC
Conditions: Dialed into the GSM network, no communication active, inputs not
controlled, relay disabled
25 mA at 12 V DC
Nominal current consumption
15 mA
Inrush current surge
2.6 A, τ = 0.4 ms
Analog inputs (IN 1 … 6)
Control voltage range
12 … 48 V DC
Input voltage range
0 … 60 V DC
Operate threshold
9.5 V DC
Hysteresis, approximate
5V
Current consumption
1.5 mA/24 V
Permissible residual current
20 µA
Inductive parallel load energy
50 mWs/1 Hz (2.5 kV)
Digital inputs (IN 1 … 6)
Nominal input range
0 … 10 V DC
Effective input range
0 … 12 V DC
Maximum input voltage
60 V DC
Resolution
10 bits, LSB 12.5 mV approximately
Input impedance
142 kΩ
Error limit, with reference to input range
±1%
Time data
Supply startup time (Ri = 0)
≤25 s
Minimum control duration for input (AC, DC)
≥200 ms
Mains reliability
≥15 ms
2928_en_B
PHOENIX CONTACT
3
RAD-SYS-NEMA4X-SMS
Relay outputs (OUT 1 … 4)
Contact type
Single contact, 4PDT
Limiting continuous current
10 A (total current 20 A maximum)
Inrush current
15 A/20 ms
Maximum switching voltage
250 V AC
Maximum switching power
250 W
Minimum switching voltage
12 V
Minimum switching current
10 mA
Contact material
AgNi 90/10
Mechanical service life
30 x 106 cycles
Test voltage
Device - contact
2.5 kV (50 Hz, 1 min.)
Contact - contact
2.5 kV (50 Hz, 1 min.)
Wireless interface
Antenna
50 Ω impedance SMA female antenna connector, GSM interface
Frequency
850 MHz at 2 W (EGSM)
900 MHz at 2 W (EGSM)
1800 MHz at 1 W (EGSM)
1900 MHz at 1 W (EGSM)
Standards
Safety
EN 60730-1:2000
EMC, immunity to interference
EN 6100-6-2:2005
EMC, noise emission
EN 6100-6-3:2007
Approvals, conformance, marking
c U
Conformance with R&TTE directive 1999/5/EC
Yes
2928_en_B
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany • Phone: +49-(0) 5235-3-00
PHOENIX CONTACT • P.O. Box 4100 • Harrisburg • PA 17111-0100 • USA • Phone: +717-944-1300
www.phoenixcontact.com
4