RAD-WHG/WLAN-XD - Configurators

RAD-WHG/WLAN-XD
WirelessHART® gateway with
integrated WLAN (802.11b/g)
INTERFACE
Data Sheet
2720_en_C
1
© PHOENIX CONTACT 2011-06-07
Description
The RAD-WHG/WLAN-XD is a WirelessHART® gateway
with integrated 802.11b/g WLAN transceiver. It can connect
up to 250 WirelessHART field devices and convert the
HART® data to Modbus® TCP for easy integration into
almost any asset management system. The connection can
be made via the onboard Ethernet port or the WLAN client
transceiver, and the HART to Modbus TCP mapping is
automatic.
2
–
–
–
–
–
–
Features
WirelessHART gateway supports up to 250
WirelessHART devices
Integrated 802.11b/g with 802.11i security
Converts HART to Modbus TCP
Simple programming via embedded web server
128-bit AES encryption
WEP, WPA or WPA2/802.11i encryption
The RAD-WHG/WLAN-XD is configurable via an embedded
web server. System diagnostics are also available through
the web server or locally, an RF Link relay indicates if the
WLAN connection is present, and the strength of the WLAN
signal can be measured at the RSSI test point as an analog
voltage.
The WirelessHART data is protected with 128-bit AES
encryption and the WLAN data utilizes WEP, WPA™, or
WPA2™/802.11i for encryption.
Make sure you always use the latest documentation.
It can be downloaded at www.phoenixcontact.net/catalog.
This data sheet is valid for all products listed on the following page:
RAD-WHG/WLAN-XD
3
Ordering Data
Products
Description
Gateway, WirelessHART with integrated 802.11b/g and Modbus TCP
conversion
Accessories
Description
Type
Order No.
Pcs./Pkt.
RAD-WHG/WLAN-XD
2900178
1
Type
Order No.
Pcs./Pkt.
Omnidirectional antenna, IP55, 6 dBi gain, linear vertical, N (female)
connection
RAD-ISM-2400-ANT-OMNI-6-0
2885919
1
Omnidirectional antenna with vandalism protection, gain 3 dBi, IP55,
1.5 m cable length, SMA (male) connection
RAD-ISM-2400-ANT-VAN-3-0-SMA
2885867
1
Parabolic antenna, IP65, 19 dBi gain, linear vertical, N (female) connection
RAD-ISM-2400-ANT-PAR-19-0
2867885
1
Antenna cable, EF 393, with 3 m cable, N (male) connection
RAD-CAB-EF393-3M
2867649
1
Surge protective device, Lambda/4, N (female) connection
CN-LAMBDA/4-5.9-BB
2838490
1
Adapter, RSMA female to SMA female
RAD-ADP-RSMA/F-SMA/F
2884538
1
4
Technical Data
General Data
Material
Polyamide PA, non-reinforced
Degree of protection
IP20
Mounting
NS 35
Mounting position
Any
Dimensions (W x H x D)
45 x 99 x 114.5 mm
Weight
215 g
Operating temperature
-40… 70°C
Storage temperature
-40… 85°C
Relative humidity, non-condensing
10… 90%
Electrical Data
Nominal voltage
24 V DC
Supply voltage
9… 30 V DC
Power consumption, typical
4.1 W
Power consumption, maximum
7.2 W
Conductor size, solid, stranded, AWG
0.2… 2.5 mm², 0.2… 2.5 m², 24… 12 AWG
WirelessHART Radio Interface
Frequency range
2.4000…2.4835 GHz
Channel separation
5 MHz
Number of channels
15
Transmission power
0… 10 dBm
Receiver sensitivity
-90 dBm
Antenna connection
RP-SMA female
LEDs
Status
2720_en_C
PHOENIX CONTACT
2
RAD-WHG/WLAN-XD
WLAN (802.11) Radio Interface
Frequency range
2.4… 2.4720 GHz
Channel separation
5 MHz
Number of channels
13
Transmission power
802.11b
+17 dBm
802.11g
+17 dBm (6-36 Mbps)
+15 dBm (48-54 Mbps)
Receiver sensitivity
802.11b
1 Mbps -94 dBm
11 Mbps -87 dBm
802.11g
6 Mbps -89 dBm
9 Mbps -88 dBm
12 Mbps -86 dBm
18 Mbps -85 dBm
24 Mbps -88 dBm
36 Mbps -78 dBm
48 Mbps -74 dBm
54 Mbps -72 dBm
Antenna connection
RP-SMA female (2x)
Ethernet Interface
Port connection
RJ45 female (autocross)
Transmission rate
10/100 Mbps (auto negotiate)
HART Interface
Connection
Test loops
Signal
HART FSK
Indicators
ST (green)
Flashing - device initializing
On - power/device active
MESH (green)
On - WirelessHART device(s) connected
Off - No WirelessHART devices found
LINK (green)
On - LAN connected
DATA (yellow)
Flashing - Tx/Rx on LAN connection
ERR (red)
Off - no errors
On - internal error
RF LINK (green)
On - WLAN connected
Flashing - No WLAN link
RF DATA (yellow)
Flashing - Tx/Rx on WLAN connection
RF Link (floating N/O contact)
Maximum switching voltage
30 V DC
Maximum switching current
150 mA
RSSI test voltage range
0… 3.5 V DC
Approval/Conformance
Conformance
c
Conformance with R&TTE directive
99/5/EC
Conformance with LVD directive
2006/95/EC
Conformance with EMC directive
2004/108/EC
Conformance with ATEX directive
94/9/EC
Conformance with IEC
60079-0, 60079-15
,
Canada: Class I, Division 2 Groups A,B,C,D Ex nA IIC T5
USA: Class I, Zone 2, Group IIC; AEx nA IIC T5
ATEX
Ex nA IIC T4 Gc; Sira 10ATEX4252X
IECEx
Ex nA IIC T4; IECEx CSA 10.0008X
2720_en_C
PHOENIX CONTACT
3
RAD-WHG/WLAN-XD
Application Examples
Host
Ethernet
5
ST
1
MESH
2
3
4
5
6
7
B(-)
A(+)
B(-)
8
10/100
A
+24V GND
LINK
Power
FLBL-3104-03R1
ANT 1
ERR
ANT 2
+24V GND A
Power
B
RF Link
A(+)
Transmit Transmit
STATUS
RS-485 RX
RS-485 TX
B
RF Link
RS-232 RX
RF LINK
RS-232 TX
RF DATA
WAN SPEED
5
9
4
WAN LINK
8
3
7
2
6
1
RSSI
RAD-80211-XD/HP-BUS
WLAN Access
Point
ST
MESH
10/100
LINK
ERR
+24V GND A
Power
Figure 1
B
RF Link
WirelessHART network with 802.11 backhaul connection
Ethernet
Host
ST
MESH
10/100
LINK
ERR
+24V GND A
Power
Figure 2
2720_en_C
B
RF Link
WirelessHART network connected directly to Ethernet network
PHOENIX CONTACT
4
RAD-WHG/WLAN-XD
6
Installation Notes
Installation, operation, and maintenance may only be
carried out by qualified electricians. Follow the installation
instructions described. When installing and operating the
device, the applicable regulations and safety directives
(including national safety directives), as well as general
technical regulations, must be observed. Observe the
technical data in this data sheet and subsequent
documentation (www.phoenixcontact.com).
– In order to protect the modules against electrostatic
discharge when working on control cabinets, the
operating personnel must remove electrostatic
discharge before opening control boxes or control
cabinets and before touching the modules.
– The modules are snapped onto a DIN rail within a
control cabinet or control box. The control cabinet/box
must meet the requirements of EN/IEC 60950-1:2001 in
terms of fire protection shielding.
– The device must not be opened or modified. Do not
repair the device yourself; replace it with an equivalent
device. Repairs may only be carried out by Phoenix
Contact. The manufacturer is not liable for damage
resulting from violation.
– The IP20 degree of protection (EN/IEC 60529) of the
device is intended for use in a clean and dry
environment. The device must not be subject to any
strain or load, which exceeds the limits described.
– In the electrical system of the building, a 2-pos.
disconnecting device must be provided to isolate the
equipment from the supply circuit.
WARNING:
Correct usage in potentially explosive areas.
– The device is not designed for use in
atmospheres with a danger of dust
explosions.
– Observe the specified conditions for use in
potentially explosive areas.
– Install the device in housing (control or
distributor box) that meets the requirements
of EN/IEC 60079-15 and has at least IP54
protection (EN/IEC 60529).
– Only passive antennas may be operated on
the devices.
– When installing and connecting the supply
and signal circuits, observe the requirements
of EN/IEC 60079-14. Only devices which are
designed for operation in Ex zone 2 and are
suitable for the conditions at the installation
location may be connected to the circuits in
zone 2.
The device is designed for installation in zone 2 potentially
explosive areas.
2720_en_C
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany • Phone: +49-(0) 5235-3-00
PHOENIX CONTACT • P.O. Box 4100 • Harrisburg • PA 17111-0100 • USA • Phone: +717-944-1300
www.phoenixcontact.com