ALTECH DIN-Rail Power Supplies

ALTECH DIN-Rail Power Supplies
ENERGY
SAVER
Choose your product from a wide range of features
and options, suitable for almost all applications.
Slimline
6-19
• Small in size - narrow footprint
• Powerful with generous power reserves
• Simple usage
• 10W to 100W
Single Phase Low Profile
20-33
• Installs in seconds
• Simple usage
• Robust plastic case
• 15W to 100W
Industrial Metal Case Single Phase
34-43
• Single Phase Power Supply (75 to 480W)
• Rugged metal case
Industrial Metal Case Three Phase
44-59
• Three Phase Power Supply (240 to 960 W)
• Rugged metal case
High Efficiency Compact Housing
Universal input voltage
60-71
• Rugged metal case
• 150% peak load capacity
Wide input voltage
72-81
• Rugged metal case
• 120W to 480W
Accessories
82-91
• Redundancy Buffer Module
• UPS Module
Frequently Asked Questions
Selection Guide
Index
Terms and Conditions
92-94
95
94-97
98
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822 • Phone (908)806-9400
3
DIN Rail Power Supplies
ENERGY
SAVER
• Din Rail mount,
• Wide Power Range
(10W-960W)
• Wide Adjustment Range
• Rugged for Industrial Use
• High Efficiency
• Lightweight and
compact Design
• 3 year warranty
• Short circuit Protection
• Overvoltage Protection
• Overload Protection
• Overtemperature Protection
• Cooling by free air convection
• Worldwide approvals
• UL508 Listed and/or
UL60950-1 recognized
Rugged Metal Case
Multiple output connector
for easy wiring
Adjustable DC output voltage
DC (on) LED indicator
Easy to understand layout panel
UL508 Listed
CE compliance
Universal Input
Narrow for maximized panel space
4
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
Altech Power Supplies ...
...Easy to Use & Reliable!
SPECIFICATIONS
Input
Output
• Input Voltage
• 90-264V AC for single phase
• 100-550V AC for wide input
• 340-550V AC for three phase
• Input Frequency: 47-63 Hz
• Input Current: 0.6 A to 8A
• Inrush Current: cold start up to 60 A max
• Power Factor: All units are
EN61000-3-2 compliant
General
• Efficiency: 72-94% (see data sheets)
• Isolation: 3000V AC Input to Output
1500V AC Input to Ground
500V AC Output to Ground
Environmental
Power supplies can run at 100% capacity
inside the panel, there is no need for
oversizing. See derating curves for more
information.
• Operating Temperature:
-20 to +60°C (-4° to +140°F)
• Operating Humidity:
90% RH, non-condensing
• Storage Temperature:
-20 °C to +85 °C (-4° to +185°F)
• Vibration: 2G, 10 Hz to 500 kHz,
10 min/cycle for 60 minutes each axis
• Output Voltage: 5V; 12V; 15V; 24V; 48V
• Output Voltage Adjustment Range: ±10%
• Initial Set Accuracy: ±2% max
• Ripple & Noise: See data sheet
• Over-voltage Protection: 115-135%
• Overload Protection: 105-150%,
constant current with auto recovery
EMC & Safety
• Emissions: EN55022/55011, Class B
• EN61000-3-2, -3
• Voltage Flicker: EN61000-3-3
• ESD Immunity: EN61000-4-2, level 3
• Radiated Immunity: EN61000-4-3, 10 V/m
• EFT/Burst: EN61000-4-4, level 3
• Surge: EN61000-4-5, level 3
• Conducted Immunity:
EN61000-4-6, 10 V rms,
• Safety Approvals:
EN60950
UL508
UL60950
CE marked
• Military Standard
MIL-HDBK-217F
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
5
Slim line Single Phase Power Supply
ALTECH’s slim type DIN rail switching power supply, PS-S Series designed for the fast
growing demand of low wattage DIN rail applications. These 10W to 100W models are
enclosed with fully isolated plastic case to prevent users from hazardous shock. The design
complies with the slim trend that the precious space on the industrial rail can be saved
effectively. Featuring up to 84% of efficiency, this series is cooled by only free air
convection up to 70°C that significantly increase the reliability and lifetime of the power
supply. Another important feature of PS-S Series is its low power consumption (<0.75W).
This unique characteristic can significantly expand the application of PS-S series beyond
just heavy industrial field, but can also be implied to datacom or IT applications that
require green power to save the energy and to obey the anticipated government laws in
the near future!
Short circuit protection, overload protection, over voltage protection, and the DC OK signal
for monitoring the status of power supply are standard functions for the PS-S Series.
Typical applications includes factory automation, process control, electro-mechanical
industry, datacom and IT.
• Input voltage range:
• AC inrush current (max): Cold start:
• DC adjustment range:
• Overload protection:
• Over-voltage protection:
• Setup, rise, time (max):
• Withstand voltage:
• Working temperature:
• Safety standards:
• EMC standards:
• Military Standard
6
85-264V AC; 120-370V DC
20A at 115V AC,; 40A at 230V DC
±10% rated output voltage
105%-160% constant current limiting (auto- recovery)
115%-135% rated output voltage
500ms, 30ms/230V AC
1000ms, 30ms/115V AC, at full load
I/P-O/P: 3KV AC, I/P-FG:1.5KV AC, O/P-FG:0.5KV AC
-20 to +70°C (-4° to +158°F), refer to output
derating curve
UL508, EN60950-1
EN55022 class B
EN61000-4-2,3,4,5,6,8,11
ENV50204; EN55024; EN61000-6-1; EN61204-3;
Light Industry Level criteria A
MIL-HDBK-217F
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
PS-S Series
ENERGY
SAVER
Features:
• Universal AC input/Full range
• Protections: Short circuit / Overload / Overvoltage
• Cooling by free air convection
• DIN rail mountable
• NEC class 2 / LPS compliant (12V,24V,48V only)
• LED indicator for power on
• DC OK relay contact
• No load power consumption<0.75W
• 100% full load burn-in test
• 3 year warranty
Multiple output connector
for easy wiring on PS-S40,
PS-S60 and PS-S100 models
DC on LED signal
35mm DIN Rail
Mounting
Adjustable DC output voltage
Easy to understand layout panel
CE Compliance
UL508 Listed
Robust plastic housing
Universal Input
Slim Series - narrow
for maximized panel space
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
7
10-100W Slimline
POWER SUPPLIES
ENERGY
SAVER
10W Single Output Industrial DIN Rail Power Supply
Cat. No.
Output
V DC
A
Tol.
%
Ripple &
Noise
Efficiency
PS-S1005
5V DC
2A
±5%
80 mVp-p
77%
PS-S1012
12V DC
0.84A
±3%
120 mVp-p
81%
PS-S1015
15V DC
0.67A
±3%
120 mVp-p
81%
PS-S1024
24V DC
0.42A
±2%
150 mVp-p
84%
NOTES
20W Single Output Industrial DIN Rail Power Supply
Cat. No.
Output
V DC
A
Tol.
%
Ripple &
Noise
Efficiency
PS-S2005
5V DC
3A
±2%
80 mVp-p
76%
PS-S2012
12V DC
1.67A
±1%
120 mVp-p
80%
PS-S2015
15V DC
1.34A
±1%
120 mVp-p
81%
PS-S2024
24V DC
1A
±1%
150 mVp-p
84%
NOTES
40W Single Output Industrial DIN Rail Power Supply
Cat. No.
PS-S4005
Output
V DC
A
Tol.
%
Ripple &
Noise
Efficiency
5V DC
6A
±2%
80 mVp-p
78%
PS-S4012
12V DC
3.33A
±1%
120 mVp-p
86%
PS-S4024
24V DC
1.7A
±1%
150 mVp-p
88%
PS-S4048
48V DC
0.83A
±1%
200 mVp-p
88%
NOTES
60W Single Output Industrial DIN Rail Power Supply
Cat. No.
Output
V DC
A
Tol.
%
Ripple &
Noise
Efficiency
PS-S6005
5V DC
10A
±2%
80 mVp-p
78%
PS-S6012
12V DC
5A
±1%
120 mVp-p
86%
PS-S6024
24V DC
2.5A
±1%
150 mVp-p
88%
PS-S6048
48V DC
1.25A
±1%
200 mVp-p
87%
NOTES
100W Single Output Industrial DIN Rail Power Supply
Cat. No.
8
Output
V DC
A
Tol.
%
Ripple &
Noise
Efficiency
PS-S10012
12V DC
7.5A
±1%
120 mVp-p
85%
PS-S10024
24V DC
4A
±1%
150 mVp-p
86%
PS-S10048
48V DC
2A
±1%
200 mVp-p
88%
For more information please visit www.altechcorp.com
NOTES
SPECIFICATIONS
xx01S-SP
22.5
100
90
PS-S10
Series
3 AC/L
2 AC/N
1 FG
Pin No. Assignment
6 DC OK SIGNAL
5 DC OUTPUT -V
4 DC OUTPUT +V
Pin No. Assignment
Terminal Pin. No Assign. (TB1) Terminal Pin. No Assign. (TB2)
Terminal Pin. No Assign. (TB1)
Pin No.
1
2
3
10
0
PS-S10xx
90
.5
22
Assignment
FG
AC/N
AC/L
Terminal Pin. No Assign. (TB2)
Pin No. Assignment
4
DC OUTPUT +V
DC OUTPUT -V
5
DC OK SIGNAL
6
Universal Input: 85-264V AC, 120-370V DC full range;
0.33A @ 110V AC; 0.21A @ 230V AC
Connection: Input - 2 poles, Output – 2 poles, single screw terminal
Size (WxHxD): 22.5x90x100mm (0.89x3.54x3.94 inches)
Packaging: 1/box; 0.37lbs / 0.17Kg
xx02S-SP
22.5
100
90
PS-S20
Series
3 AC/L
2 AC/N
1 FG
Pin No. Assignment
6 DC OK SIGNAL
5 DC OUTPUT -V
4 DC OUTPUT +V
Pin No. Assignment
Terminal Pin. No Assign. (TB1) Terminal Pin. No Assign. (TB2)
Terminal Pin. No Assign. (TB1)
Pin No.
1
2
3
10
0
PS-S20xx
90
.5
22
Assignment
FG
AC/N
AC/L
Terminal Pin. No Assign. (TB2)
Pin No. Assignment
4
DC OUTPUT +V
DC OUTPUT -V
5
DC OK SIGNAL
6
Universal Input: 85-264V AC, 120-370V DC full range;
0.55A @ 110V AC; 0.35A @ 230V AC
Connection: Input - 2 poles, Output – 2 poles, single screw terminal
Size (WxHxD): 22.5x90x100mm (0.89x3.54x3.94 inches)
Packaging: 1/box; 0.42lbs / 0.19Kg
40
xx04S-SP
100
90
3 AC/L
2 AC/N
1 FG
Pin No. Assignment
5/6 DC OK Relay Contact
3/4 DC OUTPUT -V
1/2 DC OUTPUT +V
Pin No. Assignment
Terminal Pin. No Assign. (TB1) Terminal Pin. No Assign. (TB2)
Terminal Pin. No Assign. (TB1)
PS-S40
Series
Pin No.
1
2
3
90
Assignment
FG
AC/N
AC/L
Terminal Pin. No Assign. (TB2)
Pin No. Assignment
DC OUTPUT +V
1/2
DC OUTPUT -V
3/4
DC OK Relay Contact
5/6
PS-S40xx
Universal Input: 85-264V AC, 120-370V DC full range;
1.1A @ 115V AC, 0.7A @ 370V AC
Connection: Input - 2 poles, Output – 2 poles, double screw terminal
Size (WxHxD): 40x90x100mm (1.57x3.54x3.94 inches)
Packaging: 1/box; 0.66lbs / 0.3Kg
10
0
40
3 AC/L
2 AC/N
1 FG
Pin No. Assignment
5/6 DC OK Relay Contact
3/4 DC OUTPUT -V
1/2 DC OUTPUT +V
Pin No. Assignment
Terminal Pin. No Assign. (TB1) Terminal Pin. No Assign. (TB2)
40
xx06S-SP
100
90
Terminal Pin. No Assign. (TB1)
PS-S60
Series
Pin No.
1
2
3
90
Assignment
FG
AC/N
AC/L
Terminal Pin. No Assign. (TB2)
Pin No. Assignment
1/2
DC OUTPUT +V
DC OUTPUT -V
3/4
DC OK Relay Contact
5/6
PS-S60xx
Universal Input: 85-264V AC, 120-370V DC full range;
1.8A @ 115V AC, 1A @ 370V AC
Connection: Input - 2 poles, Output – 2 poles, double screw terminal
Size (WxHxD): 40x90x100mm (1.57x3.54x3.94 inches)
Packaging: 1/box; 0.73lbs / 0.33Kg
10
0
40
3 AC/L
2 AC/N
1 FG
Pin No. Assignment
5/6 DC OK Relay Contact
3/4 DC OUTPUT -V
1/2 DC OUTPUT +V
Pin No. Assignment
Terminal Pin. No Assign. (TB1) Terminal Pin. No Assign. (TB2)
55
xx001S-SP
100
90
Terminal Pin. No Assign. (TB1)
PS-S100
Series
Pin No.
1
2
3
PS-S100xx
90
10
0
55
Assignment
FG
AC/N
AC/L
Terminal Pin. No Assign. (TB2)
Pin No. Assignment
1/2
DC OUTPUT +V
DC OUTPUT -V
3/4
DC OK Relay Contact
5/6
Universal Input: 85-264V AC, 120-370V DC full range;
1.3A @ 115V AC, 0.8A @ 230V AC
Connection: Input - 2 poles, Output – 2 poles, double screw terminal
Size (WxHxD): 55x90x100mm (2.17x3.54x3.94 inches)
Packaging: 1/box; 0.93lbs / 0.42Kg
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
9
PS-S10 Series
Features:
Specifications
•
•
•
•
•
•
•
•
•
•
SAVER
ENERGY
ENERGY
SAVER
OUTPUT
OUTPUT
Universal AC input / full range
Protections: Short Circuit / Overload / Overvoltage
Cooling by free air convection
DIN rail mountable
NEC class 2 / LPS compliant
Built in DC OK active signal
LED indicator for power on
No load power consumption < 0.75W
100% full load burn-in test
3 year warranty
Cat. No.
PS-S1005
PS-S1012
PS-S1015
PS-S1024
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
RIPPLE & NOISE (max)
5V
2A
0~2A
10W
80mVp-p
12V
0.84A
0~0.84A
10W
120mVp-p
15V
0.67A
0~0.67A
10W
120mVp-p
24V
0.42A
0~0.42A
10W
150mVp-p
VOLTAGE TOLERANCE
±5.0%
Ripple & noise are measured at 20MHz of bandwidth by using a 12 twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor
±3.0%
±3.0%
±2.0%
Tolerance: includes set up tolerance, line regulation and load regulation.
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
±1.0%
±1.0%
±1.0%
±5.0%
±3.0%
±3.0%
500ms, 30ms/230VAC; 1000ms, 30ms/115VAC at full load
HOLD UP TIME (Typ.)
120ms/230VAC; 25ms/115VAC at full load
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
AC CURRENT (max.)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
85~264VAC; 120~370VDC
47~63Hz
77%
81%
0.33A/115VAC; 0.21A/230VAC
COLD START: 35A/115VAC; 70A/230VAC
<1mA/ 240VAC
±1.0%
±2.0%
Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.
INPUT
INPUT
PROTECTION
PROTECTION
OVERLOAD PROTECTION
81%
84%
Above 105% rated output power
Protection type: Hiccup mode, recovers automatically after fault condition is removed
OVERVOLTAGE PROTECTION
5.75~6.75V
13.8~16.2V
17.25~20.25V
27.6~32.4V
Protection type: Shut down overvoltage, re-power on to recover
OVER TEMPERATURE PROTECTION
ENVIRONMENT
ENVIRONMENT
SAFETY & EMC
SAFETY & EMC
DC OK AKTIV SIGNAL (max.)
Power supply shut down at 70˚C constant current limiting / output voltage goes to 0;
re-power on to recover
3.75~6V (50mA)
9~13.5V (40mA)
11.5~16.5V (40mA)
18~27V (20mA)
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP. / HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MOUNTING
-20 ~ +70˚C (Refer to output load derating curve)
20 ~ 90% RH non-condensing
-40 ~ +85˚C; 10 ~ 95% RH
±0.03% ˚C (0 ~ 50˚C)
Component: 10 ~ 500Hz, 2G 10min. / 1cycle, 60 min. each long X,Y, Z axes
Compliance to IEC60068-2-6
SAFETY STANDARDS
UL508
EN60950-1compliant
NEC class2 / LPS compliant
I/P-O/P: 3KVAC I/P-FG: 1.5KVAC O/P-FG: 0.5KVAC
I/P-O/P, I/P-FG, O/P-FG: 100M Ohms/500VDC
Compliance to EN55011
EN55022 (CISPR22)
EN61204-3 Class B
Compliance to EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11; EN55024; ENV50204; EN61000-6-1;EN61204-3;
light industry level; criteria A
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION
HARMONIC CURRENT
EMS IMMUNITY
The power supply is considered a component which will installed into a final equipment. The final equipment must be re-confirmed
OTHERS
OTHERS
that is still meets EMC directives.
MTBF
DIMENSION
PACKING
584K hrs min. MIL-HDBK-217K (25˚C)
22.5x90x100mm (WxHxD)
0.17Kg; 72pcs / 13.2Kg / 0.91CUFT
All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
10
Mechanical Specification
100
22.5
5 5
Terminal Pin. No Assign. (TB1)
Pin No.
1
2
3
+V -V DC
OK
Assignment
FG
AC/N
AC/L
90
Terminal Pin. No Assign. (TB2)
Pin No. Assignment
DC OUTPUT +V
4
DC OUTPUT -V
5
DC OK SIGNAL
6
N L
5 5
Block Diagram
RECTIFIERS
&
FILTER
EMI
FILTER
I/P
RECTIFIERS
&
FILTER
POWER
SWITCHING
+V
-V
DETECTION
CIRCUIT
CONTROL
O.L.P.
O.V.P.
Application of DC OK Signal
Model
5V
12V
15V
24V
R
5.1V
R
200
1.5K
2K
3.9K
R
V-
R
1K
2.4K
3K
4.7K
Model
5V
12V
15V
24V
Relay
Model
5V
12V
15V
24V
RL
RL
120
700
700
1.2K
V-
V-
Derating Curve
Output Derating VS Input Voltage
Ta=25
100
100
Others
80
90
80
5V
60
70
60
40
50
20
-20
40
0
10
20
30
40
50
60
70 (VERTICAL)
85
95
100 115
120 140
160 180
200 220
240
264
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
11
PS-S20 Series
Specifications
ENERGY
SAVER
OUTPUT
Features:
•
•
•
•
•
•
•
•
•
•
Universal AC input / full range
Protections: Short Circuit / Overload / Overvoltage
Cooling by free air convection
DIN rail mountable
NEC class 2 / LPS compliant
Built in DC OK active signal
LED indicator for power on
No load power consumption < 0.75W
100% full load burn-in test
3 year warranty
Cat. No.
PS-S2005
PS-S2012
PS-S2015
PS-S2024
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
RIPPLE & NOISE (max)
5V
3A
0~3A
15W
80mVp-p
12V
1.67A
0~1.67A
20W
120mVp-p
15V
1.34A
0~1.34A
20W
120mVp-p
24V
1A
0~1A
24W
150mVp-p
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE
4.75 ~ 5.5V
±2.0%
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
±1.0%
±1.0%
±1.0%
±1.0%
±1.0%
±1.0%
500ms, 30ms/230VAC; 1000ms, 30ms/115VAC at full load
HOLD UP TIME (Typ.)
50ms/230VAC; 20ms/115VAC at full load
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
AC CURRENT (max.)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
85~264VAC 120~370VDC
47~63Hz
76%
80%
0.55A/115VAC; 0.35A/230VAC
COLD START: 20A/115VAC; 40A/230VAC
≤1mA/ 240VAC
Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor
10.8 ~ 13.2V
±1.0%
13.5 ~ 16.5V
±1.0%
21.6 ~ 26.4V
±1.0%
Tolerance: includes set up tolerance, line regulation and load regulation.
±1.0%
±1.0%
Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.
INPUT
PROTECTION
OVERLOAD PROTECTION
81%
84%
105% ~ 160% rated output power
Protection type: Constant current limiting, recovers automatically after fault condition is removed
OVERVOLTAGE PROTECTION
5.75~6.75V
13.8~16.2V
17.25~20.25V
27.6~32.4V
Protection type: Shut down overvoltage, re-power on to recover
OVER TEMPERATURE PROTECTION
ENVIRONMENT
SAFETY & EMC
DC OK AKTIV SIGNAL (max.)
Power supply shut down at 70˚C constant current limiting / output voltage goes to 0;
re-power on to recover
3.75~6V (50mA)
9~13.5V (40mA)
11.5~16.5V (40mA)
18~27V (20mA)
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MOUNTING
-20 ~ +70˚C (Refer to output load derating curve)
20 ~ 90% RH non-condensing
-40 ~ +85˚C, 10 ~ 95% RH
±0.03% ˚C (0 ~ 50˚C)
Component: 10 ~ 500Hz, 2G 10min. / 1cycle, 60 min. each long X,Y, Z axes
Compliance to IEC60068-2-6
SAFETY STANDARDS
UL508
EN60950-1approved
NEC class2 / LPS compliant
I/P-O/P: 3KVAC I/P-FG: 1.5KVAC O/P-FG: 0.5KVAC
I/P-O/P, I/P-FG, O/P-FG: 100M Ohms/500VDC
Compliance to EN55011
EN55022 (CISPR22)
EN61204-3 Class B
Compliance to EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11; EN55024; ENV50204; EN61000-6-1;EN61204-3;
light industry level; criteria A
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION
HARMONIC CURRENT
EMS IMMUNITY
The power supply is considered a component which will installed into a final equipment. The final equipment must be re-confirmed
that is still meets EMC directives.
OTHERS
MTBF
DIMENSION
PACKING
236.9K hrs min. MIL-HDBK-217K (25˚C)
22.5x90x100mm (WxHxD)
0.19Kg; 72pcs / 14.7Kg / 0.91CUFT
All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature
12
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
Mechanical Specification
100
22.5
5 5
+V -V DC
OK
Terminal Pin. No Assign. (TB1)
Assignment
FG
AC/N
AC/L
+
+V ADJ
90
Pin No.
1
2
3
Terminal Pin. No Assign. (TB2)
Pin No. Assignment
4
DC OUTPUT +V
DC OUTPUT -V
5
DC OK SIGNAL
6
N L
5 5
Block Diagram
RECTIFIERS
&
FILTER
EMI
FILTER
I/P
POWER
SWITCHING
RECTIFIERS
&
FILTER
+V
-V
DETECTION
CIRCUIT
O.L.P.
CONTROL
O.V.P.
Application of DC OK Signal
Model
5V
12V
15V
24V
R
5.1V
R
200
1.5K
2K
3.9K
R
V-
R
1K
2.4K
3K
4.7K
Model
5V
12V
15V
24V
Relay
Model
5V
12V
15V
24V
RL
RL
120
700
700
1.2K
V-
V-
Derating Curve
Output Derating VS Input Voltage
Ta=25
100
100
90
80
80
70
60
60
40
50
20
-20
40
0
10
20
30
40
50
60
70 (VERTICAL)
85
95
100 115
120 140
160 180
200 220
240
264
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
13
PS-S40 Series
Features:
Specifications
ENERGY
SAVER
OUTPUT
•
•
•
•
•
•
•
•
•
Universal AC input/full range
Protections: Short Circuit / Overload / Overvoltage
Cooling by free air convection
DIN rail mountable
NEC class 2 / LPS compliant (12V,24V,48V only)
LED indicator for power on DC OK relay contact
No load power consumption < 0.75W
100% full load burn-in test
3 year warranty
Cat. No.
PS-S4005
PS-S4012
PS-S4024
PS-S4048
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
RIPPLE & NOISE (max)
5V
6A
0~6A
30W
80mVp-p
12V
3.33A
0~3.33A
40W
120mVp-p
24V
1.7A
0~1.7A
40.8W
150mVp-p
48V
0.83A
0~0.83A
39.8W
200mVp-p
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE
5 ~ 6V
±2.0%
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
±1.0%
±1.0%
±1.0%
±1.0%
±1.0%
±1.0%
500ms, 30ms/230VAC; 500ms, 30ms/115VAC at full load
HOLD UP TIME (Typ.)
50ms/230VAC; 20ms/115VAC at full load
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
AC CURRENT (max)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
85~264VAC 120~370VDC
47~63Hz
78%
86%
1.1A/115VAC; 0.7A/230VAC
COLD START: 30A/115VAC; 60A/230VAC
≤1mA/ 240VAC
Ripple & noise are measured at 20MHz of bandwidth by using a 12 twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor
12 ~ 15V
±1.0%
24 ~ 30V
±1.0%
48 ~ 56V
±1.0%
Tolerance: includes set up tolerance, line regulation and load regulation.
±1.0%
±1.0%
Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.
INPUT
PROTECTION
OVERLOAD PROTECTION
88%
88%
105% ~ 150% rated output power
Protection type: Constant current limiting, recovers automatically after fault condition is removed
OVERVOLTAGE PROTECTION
6.25~7.25V
15.6~18V
31.2~36V
57.6~64.8V
Protection type: Shut down overvoltage, re-power on to recover
OVER TEMPERATURE PROTECTION
ENVIRONMENT
SAFETY & EMC
DC OK AKTIV SIGNAL (max.)
Power supply shut down at 70˚C constant current limiting / output voltage goes to 0;
re-power on to recover
Relay contact rating (max.): 30V/ 1A resistive
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MOUNTING
-20 ~ +70˚C (Refer to output load derating curve)
20 ~ 90% RH non-condensing
-40 ~ +85˚C, 10 ~ 95% RH
±0.03% ˚C (0 ~ 50˚C)
Component: 10 ~ 500Hz, 2G 10min. / 1cycle, 60 min. each long X,Y, Z axes
Compliance to IEC60068-2-6
SAFETY STANDARDS
UL508
UL60950-1
EN60950-1approved
NEC class2 / LPS compliant (12V, 24V, 48V only)
I/P-O/P: 3KVAC I/P-FG: 1.5KVAC O/P-FG: 0.5KVAC
I/P-O/P, I/P-FG, O/P-FG: ≥100M Ohms/500VDC (25°C; 70% RH)
Compliance to EN55011
EN55022 (CISPR22)
EN61204-3 Class B
Compliance to EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11; EN55024; ENV50204 ; EN61000-6-2; EN61204-3;
light industry level; criteria A
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION
HARMONIC CURRENT
EMS IMMUNITY
The power supply is considered a component which will installed into a final equipment. The final equipment must be re-confirmed
that is still meets EMC directives.
OTHERS
MTBF
DIMENSION
PACKING
301.7K hrs min. MIL-HDBK-217K (25˚C)
40x90x100mm (WxHxD)
0.3Kg; 42pcs / 13.6 Kg / 0.82CUFT
All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature.
14
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
Mechanical Specification
40
100
5 5 5 5 5
+V +V-V -V
Terminal Pin. No Assign. (TB1)
Pin No.
1
2
3
Assignment
FG
AC/N
AC/L
+
+V ADJ
90
Terminal Pin. No Assign. (TB2)
Pin No. Assignment
1,2
DC OUTPUT +V
DC OUTPUT -V
3,4
DC OK RELAY CONTACT
5,6
N
L
7.5 7.5
Block Diagram
RECTIFIERS
&
FILTER
EMI
FILTER
I/P
POWER
SWITCHING
RECTIFIERS
&
FILTER
+V
-V
O.C.P.
DETECTION
CIRCUIT
O.L.P.
CONTROL
O.V.P.
DC OK Relay Contact
age.
Derating Curve
Output Derating VS Input Voltage
Ta=25
100
100
90
80
80
70
60
60
40
50
20
-20
40
0
10
20
30
45
55
60
70 (VERTICAL)
85
95
100 115
120 140
160 180
200 220
240
264
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
15
PS-S60 Series
Features:
Specifications
•
•
•
•
•
•
•
•
•
ENERGY
SAVER
OUTPUT
Universal AC input/full range
Protections: Short Circuit / Overload / Overvoltage
Cooling by free air convection
DIN rail mountable
NEC class 2 / LPS compliant (24V,48V only)
LED indicator for power on
No load power consumption < 0.75W
100% full load burn-in test
3 year warranty
Cat. No.
PS-S6005
PS-S6012
PS-S6024
PS-S6048
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
NOISE (max)
5V
10A
0 ~ 10A
50W
80mVp-p
12V
5A
0 ~ 5A
60W
120mVp-p
24V
2.5A
0 ~ 2.5A
60W
150mVp-p
48V
1.25A
0 ~ 1.25A
60WRIPPLE &
200mVp-p
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE
5 ~ 6V
±2.0%
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
±1.0%
±1.0%
±1.0%
±1.5%
±1.0%
±1.0%
500ms, 30ms/230VAC; 500ms, 30ms/115VAC at full load
HOLD UP TIME (Typ.)
50ms/230VAC / 20ms/115VAC at full load
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
AC CURRENT (max)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
85 ~ 264VAC 120 ~ 370VDC
47~63Hz
78%
86%
1.8A/115VAC; 1A/230VAC
COLD START: 60A/230VAC
≤1mA/ 240VAC
Ripple & noise are measured at 20MHz of bandwidth by using a 12 twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor
12 ~ 15V
±1.0%
24 ~ 30V
±1.0%
48 ~ 56V
±1.0%
Tolerance: includes set up tolerance, line regulation and load regulation.
±1.0%
±1.0%
Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.
INPUT
PROTECTION
OVERLOAD PROTECTION
88%
87%
105% ~ 150% rated output power
Protection type: Constant current limiting, recovers automatically after fault condition is removed
OVERVOLTAGE PROTECTION
6.25 ~ 7.25V
15.6 ~ 18V
31.2 ~ 36V
57.6 ~ 64.8V
Protection type: Shut down overvoltage, re-power on to recover
OVER TEMPERATURE PROTECTION
ENVIRONMENT
SAFETY & EMC
DC OK AKTIV SIGNAL (max.)
Power supply shut down at 70˚C constant current limiting / output voltage goes to 0;
re-power on to recover
Relay contact rating (max.): 30V/1A resistive
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MOUNTING
-20 ~ +70˚C (Refer to output load derating curve)
20 ~ 90% RH non-condensing
-40 ~ +85˚C, 10 ~ 95% RH
±0.03% ˚C (0 ~ 50˚C)
Component: 10 ~ 500Hz, 2G 10min. / 1cycle, 60 min. each long X,Y, Z axes
Compliance to IEC60068-2-6
SAFETY STANDARDS
UL508
UL60950-1
EN60950-1approved
NEC class2 / LPS compliant (24V, 48V only)
I/P-O/P: 3KVAC I/P-FG: 1.5KVAC O/P-FG: 0.5KVAC
I/P-O/P, I/P-FG, O/P-FG: ≥100M Ohms/500VDC (25°C; 70% RH)
Compliance to EN55011
EN55022 (CISPR22)
EN61204-3 Class B
Compliance to EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11; EN55024; ENV50204; EN61000-6-2; EN61204-3;
light industry level; criteria A
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION
HARMONIC CURRENT
EMS IMMUNITY
The power supply is considered a component which will installed into a final equipment. The final equipment must be re-confirmed
that is still meets EMC directives.
OTHERS
MTBF
DIMENSION
PACKING
299.2K hrs min. MIL-HDBK-217K (25˚C)
40x90x100mm (WxHxD)
0.33Kg; 42pcs / 14.8Kg / 0.82CUFT
All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature
16
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
Mechanical Specification
40
100
5 5 5 5 5
+V +V-V -V
Terminal Pin. No Assign. (TB1)
Assignment
FG
AC/N
AC/L
Pin No.
1
2
3
+
90
Terminal Pin. No Assign. (TB2)
+V ADJ
Pin No. Assignment
1,2
DC OUTPUT +V
DC OUTPUT -V
3,4
DC OK RELAY CONTACT
5,6
N
L
7.5 7.5
Block Diagram
RECTIFIERS
&
FILTER
EMI
FILTER
I/P
POWER
SWITCHING
RECTIFIERS
&
FILTER
+V
-V
O.C.P.
DETECTION
CIRCUIT
CONTROL
O.L.P.
O.V.P.
DC OK Relay Contact
age.
Derating Curve
Output Derating VS Input Voltage
Ta=25
100
100
12V,24V,48V
90
80
80
70
60
50
5V
60
40
50
20
-20
40
0
10
20
30
45
55
60
70 (VERTICAL)
85
95
100 115
120 140
160 180
200 220
240
264
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
17
PS-S100 Series
Specifications
SAVER
ENERGY
ENERGY
SAVER
OUTPUT
OUTPUT
Features:
• Universal AC input / full range
• Protections: Short Circuit / Overload / Overvoltage /
Over temperature
• ZCS/ZVS technology to reduce power dissipation
• Cooling by free air convection
• DIN rail mountable
• DC OK relay contact
• No load power consumption < 1W
• LED indicator for power on
• 100% full load burn-in test
• 3 year warranty
Cat. No.
PS-S10012
PS-S10024
PS-S10048
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
RIPPLE & NOISE (max)
12V
7.5A
0 ~ 7.5A
90W
120mVp-p
24V
4A
0 ~ 4A
96W
150mVp-p
48V
2A
0 ~ 2A
96W
200mVp-p
Ripple & noise are measured at 20MHz of bandwidth by using a 12 twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor.
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE
12 ~ 15V
±1.0%
24 ~ 30V
±1.0%
48 ~ 56V
±1.0%
Tolerance: includes set up tolerance, line regulation and load regulation.
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
±1.0%
±1.0%
±1.0%
±1.0%
3000ms, 50ms/230VAC; 3000ms, 50ms/115VAC at full load
±1.0%
±1.0%
Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.
INPUT
INPUT
HOLD UP TIME (Typ.)
VOLTAGE RANGE
50ms/230VAC; 20ms/115VAC at full load
85 ~ 264VAC
120 ~ 370VDC
Deating maybe needed under low input voltages, please check the derating curve for more detail
PROTECTION
PROTECTION
FREQUENCY RANGE
POWER FACTOR (Typ.)
EFFICIENCY (Typ.)
AC CURRENT (max)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVERLOAD
47~63Hz
PF ≥ 0.95/230VAC; PF ≥ 0.98/115VAC at full load
85%
86%
1.3A/115VAC; 0.8A/230VAC
COLD START: 30A/115VAC; 60A/230VAC
≤1mA/ 240VAC
88%
105% ~ 150% rated output power
Protection type: Constant current limiting, recovers automatically after fault condition is removed
OVERVOLTAGE
15.6 ~ 18V
31.2 ~ 36V
57.6 ~ 64.8V
Protection type: Shut down overvoltage, re-power on to recover
OVERTEMPERATURE
90˚C ± 10˚C (RTH2) detect on heat sink of power transistor
Protection type: Shut down overvoltage, re-power on to recover
SHORT CUIRCUIT PROTECTION
ENVIRONMENT
ENVIRONMENT
SAFETY & EMC
SAFETY & EMC
DC OK AKTIV SIGNAL (max.)
Power supply shut down at 70˚C constant current limiting / output voltage goes to 0;
re-power on to recover
Relay contact rating (max.): 30V/1A resistive
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MOUNTING
-10 ~ +60˚C (Refer to output load derating curve)
20 ~ 90% RH non-condensing
-40 ~ +85˚C, 10 ~ 95% RH
±0.03% ˚C (0 ~ 50˚C)
Component: 10 ~ 500Hz, 2G 10min. / 1cycle, 60 min. each long X,Y, Z axes
Compliance to IEC60068-2-6
SAFETY STANDARDS
UL508
EN60950-1compliant
I/P-O/P: 3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG: ≥100M Ohms/500VDC/25˚C/70% RH
Compliance to EN55011
EN55022 (CISPR22)
EN61204-3 Class B
Compliance to EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11; EN55024; ENV50204; EN61000-6-2; EN61204-3;
light industry level; criteria A
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION
HARMONIC CURRENT
EMS IMMUNITY
The power supply is considered a component which will installed into a final equipment. The final equipment must be
re-confirmed that is still meets EMC directives.
OTHERS
OTHERS
MTBF
DIMENSION
PACKING
346K hrs min. MIL-HDBK-217K (25˚C)
55x90x100mm (WxHxD)
0.42Kg; 30pcs / 13.6Kg / 0.82CUFT
All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature.
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
18
Mechanical Specification
Terminal Pin. No Assign. (TB1)
Pin No.
1
2
3
Assignment
FG
AC/N
AC/L
Terminal Pin. No Assign. (TB2)
Pin No. Assignment
1,2
DC OUTPUT +V
DC OUTPUT -V
3,4
DC OK RELAY CONTACT
5,6
Block Diagram
DC OK Relay Contact
Derating Curve
Output Derating VS Input Voltage
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
19
Low Profile Single Phase
Power Supply (Class II)
The Low Profile Single Phase Power Supplies are 15W to 100W single output Class II DIN
rail switching power supplies. They are designed for the fast growing demand of the DIN
rail application with limited enclosure height. With Class II of protection level, low profile
series provide users a safer operating environment since the whole plastic case is free
from hazardous leakage current. Featuring up to 89% of high efficiency, this series can be
cooled by only free air convection that significantly increase the reliability and lifetime of
the power supply. Complying with the safety of the UL508 and EMC requirements of
EN50178 which is mainly for power distribution aspects, the low profile switching power
supplies are suitable to be installed in a power distribution box or a control cabinet and the
major application fields are building automation and household appliance control.
• Input voltage range:
• AC inrush current:
• DC adjustment range:
• Overload protection:
• Over-voltage protection:
• Setup, rise, hold up time:
• Withstand voltage:
• Working temperature:
• Safety standards:
• EMC standards:
• Military Standard:
20
85-264V AC; 120-370V DC
Cold start: 15A at 115V AC, 30A at 230V DC (PS-30xx)
±10% rated output voltage
105%-160% constant current limiting, auto-recovery
115%-135% rated output voltage
100ms, 30ms, 100ms at full loadand 230V AC (PS-30xx)
I/P-O/P:3KV AC, I/P-FG:1.5KV AC
-20 to +50°C (-4° to +122°F) at 100%
and +60°C (+140°F) at 80% load
UL60950-1, UL508
EN55022 class B
EN61000-4-2,3,4,5,6,8,11
ENV50204
EN61204-3
MIL-HDBK
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
PS Series - Low Profile
ENERGY
SAVER
Features:
• Universal AC input/Full range
• Protections: Short circuit / Overload / Overvoltage
• Cooling by free air convection
• DIN rail mountable
• Isolation class II
• LED indicator for power on
• 100% full load burn-in test
• 3 year warranty
Output connector
for easy wiring
DC on LED signal
Adjustable DC output voltage
35mm DIN Rail
Mounting
Easy to understand layout panel
UL508 Listed
Robust plastic housing
Universal Input
Compact Series - narrow
for maximized panel space
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
21
15-100W Low Profile
POWER SUPPLIES
15W Single Output Class II DIN Rail Power Supply
Cat. No.
Output
V DC
A
Tol.
%
Ripple &
Noise
Efficiency
PS-1505
5V DC 2.4A
±2%
80 mVp-p
77%
PS-1512
12V DC 1.25A
±1%
120 mVp-p
84%
PS-1515
15V DC 1A
±1%
120 mVp-p
83.5%
PS-1524
24V DC 0.63A
±1%
150 mVp-p
85%
ENERGY
SAVER
NOTES
30W Single Output Class II DIN Rail Power Supply
Cat. No.
Output
V DC
A
Tol.
%
Ripple &
Noise
Efficiency
PS-3005
5V DC 3A
±2%
80 mVp-p
74%
PS-3012
12V DC 2A
±1%
120 mVp-p
81%
PS-3015
15V DC 2A
±1%
120 mVp-p
82%
PS-3024
24V DC 1.5A
±1%
150 mVp-p
83%
NOTES
45W Single Output Class II DIN Rail Power Supply
Cat. No.
Output
V DC
A
Tol.
%
Ripple &
Noise
Efficiency
PS-4505
5V DC 5A
±2%
100 mVp-p
72%
PS-4512
12V DC 3.5A
±1%
200 mVp-p
77%
PS-4515
15V DC 2.8A
±1%
240 mVp-p
77%
PS-4524
24V DC 2A
±1%
480 mVp-p
80%
NOTES
60W Single Output Class II DIN Rail Power Supply
Cat. No.
Output
V DC
A
Tol.
%
Ripple &
Noise
Efficiency
PS-6005
5V DC 6.5A
±2%
80 mVp-p
76%
PS-6012
12V DC 4.5A
±1%
120 mVp-p
82%
PS-6015
15V DC 4.0A
±1%
120 mVp-p
83%
PS-6024
24V DC 2.5A
±1%
150 mVp-p
84%
100W Single Output Class II DIN Rail Power Supply
Cat. No.
22
Output
V DC
A
Tol.
%
Ripple &
Noise
Efficiency
PS-10012
12V DC
7.5A
±2%
120 mVp-p
87%
PS-10015
15V DC
6.5A
±1%
120 mVp-p
87%
PS-10024
24V DC
4.2A
±1%
150 mVp-p
89%
NOTES
ENERGY
SAVER
NOTES
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
SPECIFICATIONS
PS-15
Series
Terminal Pin. No Assignment
Pin No. Assignment Pin No. Assignment
AC/L
-V
1
3
AC/N
+V
2
4
93
Universal Input: 85-264V AC, 120-370V DC full range;
0.88A @ 115V AC; 0.48A @ 230V AC
Connection: Input - 2 poles, Output – 2 poles, single screw terminal
Size (WxHxD): 25x93x56mm (0.98x3.66x2.20 inches)
Packaging: 1/box; 0.22lbs / 0.1Kg
56
25
Terminal Pin. No Assignment
PS-30
Series
Pin No.
1
2
3,4
93
56
78
Assignment Pin No. Assignment
AC/L
5,6
-V
AC/N
LED
7
+V ADJ.
+V
8
Universal Input: 85-264V AC, 120-370V DC full range;
0.88A @ 115V AC; 0.48A @ 230V AC
Connection: Input - 2 poles, Output – 2 poles, double screw terminal
Size (WxHxD): 78x93x56mm (3.07x3.66x2.20 inches)
Packaging: 1/box; 0.60lbs / 0.27Kg
Terminal Pin. No Assignment
PS-45
Series
Pin Assignment
Pin
AC/L
1
6,7
AC/N
2
8
9
3 FG
4,5 DC OUTPUT-V
93
67
78
Assignment
DC OUTPUT+V
LED
+V ADJ.
Universal Input: 85-264V AC, 120-370V DC full range;
1.5A @ 115V AC, 0.75A @ 230V AC
Connection: Input - 3 poles, Output – 2 poles, double screw terminal
Size (WxHxD): 78x93x67mm (3.07x3.66x2.64 inches)
Packaging: 1/box; 0.68lbs / 0.31Kg
Terminal Pin. No Assignment
PS-60
Series
Pin No.
1
2
3,4
93
56
78
PS-100
Series
Assignment Pin No. Assignment
AC/L
5,6
-V
AC/N
LED
7
+V ADJ.
+V
8
Universal Input: 88-264V AC, 124-370V DC full range;
1.2A @ 115V AC, 0.8A @ 230V AC
Connection: Input - 2 poles, Output – 2 poles, double screw terminal
Size (WxHxD): 78x93x56mm (3.07x3.66x2.20 inches)
Packaging: 1/box; 0.66lbs / 0.30Kg
Terminal Pin. No Assignment
Pin No.
1
2
3,4
93
0
56
10
Assignment Pin No. Assignment
AC/L
5,6
-V
AC/N
LED
7
+V ADJ.
+V
8
Universal Input: 88-264V AC, 124-370V DC full range;
3A @ 115V AC, 1.6A @ 230V AC
Connection: Input - 2 poles, Output – 2 poles, double screw terminal
Size (WxHxD): 100x93x56mm (3.94x3.66x2.20 inches)
Packaging: 1/box; 0.77lbs / 0.35Kg
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
23
12
PS-15 Series
Features:
Specifications
•
•
•
•
•
•
•
•
•
ENERGY
SAVER
OUTPUT
Universal AC input / full range
Protections: Short Circuit / Overload / Over Voltage
Cooling by free air convection
DIN rail mountable
Isolation class II
LED indicator for power on
No load power consumption<0.5W
100% full load burn-in test
3 year warranty
Cat. No.
PS-1505
PS-1512
PS-1515
PS-1524
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
RIPPLE & NOISE (max)
5V
2.4A
0 ~ 2.4A
12W
80mVp-p
12V
1.25A
0 ~ 1.25A
15W
120mVp-p
15V
1A
0 ~ 1A
15W
120mVp-p
24V
0.63A
0 ~ 0.63A
15.2W
150mVp-p
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE
4.75 ~ 5.5V
±2.0%
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
±1.0%
±1.0%
±1.0%
±1.0%
±1.0%
±1.0%
1000ms, 50ms / 230VAC
1000ms, 50ms / 115VAC at full load
70ms / 230VAC
16ms / 115VAC at full load
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
AC CURRENT (max.)
INRUSH CURRENT (Typ.)
85 ~ 264VAC
120 ~ 370VDC
47 ~ 63Hz
77%
84%
0.88A / 115VAC
0.48A / 230VAC
COLD START 35A / 115VAC 65A / 230VAC
Ripple & noise are measured at 20MHz of bandwidth by using a 12 twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor
10.8 ~ 13.2V
±1.0%
13.5 ~ 16.5V
±1.0%
21.6 ~ 26.4V
±1.0%
Tolerance: includes set up tolerance, line regulation and load regulation.
INPUT
PROTECTION
OVERLOAD
83.50%
±1.0%
±1.0%
85%
105 ~ 160% rated output power
Protection type: Constant current limiting recovers automatically after fault condition is removed (Hiccup mode)
Constant current operation region is within 60 ~ 100% rated output voltage.
OVERVOLTAGE
5.75 ~ 6.75V
13.8 ~ 16.2V
17.25 ~ 20.25V
27.6 ~ 32.4V
Protection type: Shut down overvoltage, clamping by zener diode
ENVIRONMENT
SAFETY & EMC
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MOUNTING
-20 ~ +60˚C (Refer to output load derating curve)
20 ~ 90% RH non-condensing
-40 ~ +85˚C, 10 ~ 95% RH
±0.03% ˚C (0 ~ 50˚C)
Component: 10 ~ 500Hz, 2G 10min. / 1cycle, 60 min. each long X,Y, Z axes
Compliance to IEC60068-2-6
SAFETY STANDARDS
UL60950-1
EN60950-1approved
Design refer to EN50178
I/P-O/P: 3KVAC
I/P-O/P: 100M Ohms/500VDC (25˚C; 70% RH)
Compliance to EN55011
EN55022 (CISPR22); EN61204-3 Class B
Compliance to EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11; EN55024; ENV50204; EN61000-6-2; EN61204-3;
heavy industry level; criteria A
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION
HARMONIC CURRENT
EMS IMMUNITY
The power supply is considered a component which will installed into a final equipment.
OTHERS
The final equipment must be re-confirmed that is still meets EMC directives.
MTBF
DIMENSION
PACKING
1172.3K hrs min. MIL-HDBK-217K (25˚C)
25x93x56mm (WxHxD)
0.1Kg; 140pcs / 15Kg / 0.92CUFT
All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature
24
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
Mechanical Specification
56
25
47
26.7
5
-V
+V
LE D
Terminal Pin. No Assignment
67.2
93
44.2
Vadj.
Pin No. Assignment Pin No. Assignment
AC/L
-V
1
3
AC/N
+V
2
4
4
N
L
5
Block Diagram
RE CTIFIERS
&
FILTE R
EMI
FILTE R
I/P
RE CTIFIE RS
&
FILTE R
POWE R
SWITCHING
+V
-V
DE TE CTION
CIRCUIT
O.L.P.
CONTROL
O.V.P.
Derating Curve
Output Derating VS Input Voltage
Ta=25
100
100
90
LOAD (%)
LOAD (%)
80
60
40
80
70
60
50
20
-20
40
0
10
20
30
40
50
60
AMBIENT TEMPERATURE (°C)
70 (VERTICAL)
85
95
100
115
120
140
160
180
200
220
240
264
INPUT VOLTAGE (VAC) 60Hz
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
25
PS-30 Series
Features:
Specifications
OUTPUT
•
•
•
•
•
•
•
•
Universal AC input/ full range
Protections: Short Circuit / Overload / Over Voltage
Cooling by free air convection
DIN rail mountable
Isolation class II
LED indicator for power on
100% full load burn-in test
3 year warranty
Cat. No.
PS-3005
PS-3012
PS-3015
PS-3024
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
RIPPLE & NOISE (max)
5V
3A
0 ~ 3A
15W
80mVp-p
12V
2A
0 ~ 2A
24W
120mVp-p
15V
2A
0 ~ 2A
30W
120mVp-p
24V
1.5A
0 ~ 1.5A
36W
150mVp-p
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE
4.75 ~ 5.5V
±2.0%
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
±1.0%
±1.0%
100ms, 30ms / 230VAC
100ms / 230VAC
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
85 ~ 264VAC
120 ~ 370VDC
47 ~ 63Hz
74%
81%
0.88A / 115VAC
0.48A / 230VAC
COLD START 15A / 115VAC; 30A / 230VAC
Ripple & noise are measured at 20MHz of bandwidth by using a 12 twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor
10.8 ~ 13.2V
±1.0%
13.5 ~ 16.5V
±1.0%
21.6 ~ 26.4V
±1.0%
Tolerance: includes set up tolerance, line regulation and load regulation.
INPUT
PROTECTION
OVERLOAD
±1.0%
±1.0%
±1.0%
±1.0%
100ms, 30ms / 115VAC at full load
21ms / 115VAC at full load
82%
±1.0%
±1.0%
83%
105 ~ 160% rated output power
Protection type: Constant current limiting recovers automatically after fault condition is removed
OVERVOLTAGE
ENVIRONMENT
SAFETY & EMC
5.75 ~ 6.75V
13.8 ~ 16.2V
17.25 ~ 20.25V
27.6 ~ 32.4V
Protection type: Shut down overvoltage, clamping by zener diode
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MOUNTING
-20 ~ +60˚C (Refer to output load derating curve)
20 ~ 90% RH non-condensing
-40 ~ +85˚C, 10 ~ 95% RH
±0.03% / ˚C (0 ~ 50˚C)
Component: 10 ~ 500Hz, 2G 10min. / 1cycle, 60 min. each long X,Y, Z axes
Compliance to IEC60068-2-6
SAFETY STANDARDS
UL60950-1
EN60950-1approved
Design refer to EN50178
I/P-O/P: 3KVAC
I/P-O/P: 100M Ohms / 500VDC
Compliance to EN55011
EN55022 (CISPR22) Class B
Compliance to EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11; EN55024; ENV50204; EN61000-6-2; EN61204-3;
heavy industry level; criteria A
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION
HARMONIC CURRENT
EMS IMMUNITY
The power supply is considered a component which will installed into a final equipment. The final equipment must be re-confirmed
OTHERS
that is still meets EMC directives.
MTBF
DIMENSION
PACKING
441.5K hrs min. MIL-HDBK-217K (25˚C)
78x93x56mm (WxHxD)
0.27Kg; 48pcs / 14Kg / 1.02CUFT
All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature
26
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
Mechanical Specification
56
47
78
5
1
2
Terminal Pin. No Assignment
27.4
45
68
7
Assignment Pin No. Assignment
AC/L
5,6
-V
AC/N
LED
7
+V ADJ.
+V
8
93
Pin No.
1
2
3,4
5 5 5 12.2
3
4
5
6
37.75
3
8
Block Diagram
RE CTIFIE RS
&
FILTE R
E MI
FILTE R
I/P
POWE R
SWITCHING
R E CTIFIE R S
&
FILTE R
+V
-V
DE TE CTION
CIRCUIT
O.L.P.
CONTR OL
O.V.P.
Derating Curve
Output Derating VS Input Voltage
Ta=25
100
100
90
80
LOAD (%)
LOAD (%)
80
60
40
70
60
50
20
-20
40
0
10
20
30
40
50
60
AMBIENT TEMPERATURE (°C)
70 (VERTICAL)
85
95
100
115
120
140
160
180
200
220
240
264
INPUT VOLTAGE (VAC) 60Hz
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
27
PS-45 Series
Features:
Specifications
OUTPUT
• Universal AC input / full range
• Protections: Short Circuit / Overload / Over Voltage/
Overtemperature
• Cooling by free air convection
• DIN rail mountable
• UL508 approved
• LED indicator for power on
• Fix switching frequency at 100kHz
• 100% full load burn-in test
• 3 year warranty
Cat. No.
PS-4505
PS-4512
PS-4515
PS-4524
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
RIPPLE & NOISE (max)
5V
5A
0 ~ 5A
25W
100mVp-p
12V
3.5A
0 ~ 3.5A
42W
200mVp-p
15V
2.8A
0 ~ 2.8A
42W
240mVp-p
24V
2A
0 ~ 2A
48W
480mVp-p
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE
4.75 ~ 5.5V
±2.0%
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
±1.0%
±1.0%
±1.0%
±1.0%
800ms, 60ms / 230VAC at full load
60ms / 230VAC at full load
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
AC CURRENT (max.)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
85 ~ 264VAC
120 ~ 370VDC
47 ~ 63Hz
72%
77%
1.5A / 115VAC
0.75A / 230VAC
COLD START 28A / 115VAC; 56A / 230VAC
≤1mA / 240VAC
Ripple & noise are measured at 20MHz of bandwidth by using a 12 twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor
10.8 ~ 13.2V
±1.0%
13.5 ~ 16.5V
±1.0%
21.6 ~ 26.4V
±1.0%
Tolerance: includes set up tolerance, line regulation and load regulation.
INPUT
PROTECTION
OVERLOAD
±1.0%
±1.0%
±1.0%
±1.0%
77%
80%
105 ~ 160% rated output power
Protection type: Constant current limiting recovers automatically after fault condition is removed
OVERVOLTAGE
5.75 ~ 6.75V
13.8 ~ 16.2V
17.25 ~ 20.25V
27.6 ~ 32.4V
Protection type: Shut down overvoltage, clamping by zener diode
OVERTEMPERATURE
ENVIRONMENT
SAFETY & EMC
Tj 135˚C typically (U1) detect on heat sink of power transistor
Protection type: Shut down overvoltage, re-power on to recover
WORKING TEMPERATURE
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MOUNTING
-10 ~ +50˚C (Refer to output load derating curve)
20 ~ 90% RH non-condensing
-20 ~ +85˚C, 10 ~ 95% RH
±0.03% / ˚C (0 ~ 50˚C)
Component: 10 ~ 500Hz, 2G 10min. / 1cycle, 60 min. each long X,Y, Z axes
Compliance to IEC60068-2-6
SAFETY STANDARDS
UL508
EN60950-1 approved
I/P-O/P: 3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG: 100M Ohms / 500VDC (25°C; 70% RH)
Compliance to EN55011; EN55022 (CISPR22) Class B
Compliance to EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204; EN55024; EN61000-6-2;
heavy industry level; criteria A
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION
HARMONIC CURRENT
EMS IMMUNITY
The power supply is considered a component which will installed into a final equipment.
OTHERS
The final equipment must be re-confirmed that it still meets EMC directives.
MTBF
DIMENSION
PACKING
364.6K hrs min. MIL-HDBK-217K (25˚C)
93x78x67mm (LxWxH)
0.31Kg; 48pcs / 16.1Kg / 1.3CUFT
All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature
28
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
Mechanical Specification
67
78
29
9
7
8
5
6
3
4
1
2
7.5 8.5
Terminal Pin. No Assignment
93
Assignment
DC OUTPUT+V
LED
+V ADJ.
77
Pin Assignment
Pin
1
AC/L
6,7
2
AC/N
8
3 FG
9
4,5 DC OUTPUT-V
Block Diagram
RE CTIFIE RS
&
FILTE R
E MI
FILTE R
I/P
POWE R
SWITCHING
RE CTIFIE RS
&
FILTE R
PWM
CONTR OL
DE TE CTION
CIRCUIT
FG
Derating Curve
+V
-V
Static Characteristic (24V)
100
LOAD (%)
LOAD (%)
80
60
40
350
28
300
24
250
20
200
16
150
12
100
8
50
20
-10
0
10
20
30
40
50
60 (VERTICAL)
AMBIENT TEMPERATURE (°C)
70
80
OUTPUT RIPPLE (mVp-p)
Ta=25
32
100 120 140 160 180 200 220 240 260
INPUT VOLTAGE (VAC) 60Hz
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
29
PS-60 Series
Features:
Specifications
OUTPUT
•
•
•
•
•
•
•
•
Universal AC input / full range
Protections: Short Circuit / Overload / Over Voltage
Cooling by free air convection
DIN rail mountable
Isolation class II
LED indicator for power on
100% full load burn-in test
3 year warranty
Cat. No.
PS-6005
PS-6012
PS-6015
PS-6024
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
RIPPLE & NOISE (max)
5V
6.5A
0 ~ 6.5A
32.5W
80mVp-p
12V
4.5A
0 ~ 4.5A
54W
120mVp-p
15V
4A
0 ~ 4A
60W
120mVp-p
24V
2.5A
0 ~ 2.5A
60W
150mVp-p
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE
4.75 ~ 5.5V
±2.0%
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
±1.0%
±1.0%
100ms, 30ms / 230VAC
100ms / 230VAC
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
AC CURRENT (max.)
INRUSH CURRENT (Typ.)
85 ~ 264VAC
124 ~ 370VDC
47 ~ 63Hz
76%
82%
1.2A / 115VAC
0.8A / 230VAC
COLD START 18A / 115VAC; 36A / 230VAC
Ripple & noise are measured at 20MHz of bandwidth by using a 12 twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor
11.1 ~ 13.2V
±1.0%
13.5 ~ 16.5V
±1.0%
21.6 ~ 26.4V
±1.0%
Tolerance: includes set up tolerance, line regulation and load regulation.
INPUT
PROTECTION
OVERLOAD
±1.0%
±1.0%
±1.0%
±1.0%
200ms, 30ms / 115VAC at full load
23ms / 115VAC at full load
83%
±1.0%
±1.0%
84%
105 ~ 160% rated output power
Protection type: Constant current limiting recovers automatically after fault condition is removed
OVERVOLTAGE
ENVIRONMENT
SAFETY & EMC
5.75 ~ 6.75V
13.8 ~ 16.2V
17.25 ~ 20.25V
27.6 ~ 32.4V
Protection type: Shut down overvoltage, re-power on to recover
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MOUNTING
-20 ~ +60˚C (Refer to output load derating curve)
20 ~ 90% RH non-condensing
-40 ~ +85˚C, 10 ~ 95% RH
±0.03% / ˚C (0 ~ 50˚C)
10 ~ 500Hz, 2G 10min. / 1cycle, 60 min. each long X,Y, Z axes
Compliance to IEC60068-2-6
SAFETY STANDARDS
UL60950-1
EN60950-1approved
Design refer to EN50178
I/P-O/P: 3KVAC
I/P-O/P: 100M Ohms/500VDC (25°C; 70% RH)
Compliance to EN55011
EN55022 (CISPR22) Class B
Compliance to EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204; EN55024; EN61000-6-2; EN61204-3;
heavy industry level; criteria A
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION
HARMONIC CURRENT
EMS IMMUNITY
The power supply is considered a component which will installed into a final equipment. The final equipment must be re-confirmed
that is still meets EMC directives.
OTHERS
MTBF
DIMENSION
PACKING
216.2K hrs min. MIL-HDBK-217K (25˚C)
78x93x56mm (WxHxD)
0.3Kg; 48pcs / 15.4Kg / 1.02CUFT
All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature
30
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
Mechanical Specification
56
78
47
37.75
5 5 5 12.2
Terminal Pin. No Assignment
45
68
7
Assignment Pin No. Assignment
AC/L
5,6
-V
AC/N
LED
7
+V ADJ.
+V
8
93
Pin No.
1
2
3,4
27.4
3
4
5
6
1
2
5
3
8
Block Diagram
RE CTIFIE RS
&
FILTE R
E MI
FILTE R
I/P
POWE R
SWITCHING
O.L.P.
R E CTIFIE R S
&
FILTE R
+V
-V
DE TE CTION
CIRCUIT
PWM
CONTR OL
O.V.P.
Output Derating VS Input Voltage
Derating Curve
Ta=25
100
100
90
LOAD (%)
LOAD (%)
80
60
40
80
70
60
50
20
-20
40
0
10
20
30
40
50
60
AMBIENT TEMPERATURE (°C)
70 (VERTICAL)
85
95
100
115
120
140
160
180
200
220
240
264
INPUT VOLTAGE (VAC) 60Hz
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
31
PS-100 Series
Features:
• Universal AC input / full range
• Protections: Short Circuit / Overload /
Over Voltage / Overtemperature
• Cooling by free air convection
• DIN rail mountable
• Isolation class II
• LED indicator for power on
• No load power consumption<1W
• 100% full load burn-in test
• 3 year warranty
Specifications
SAVER
ENERGY
ENERGY
SAVER
OUTPUT
OUTPUT
Cat. No.
PS-10012
PS-10015
PS-10024
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
RIPPLE & NOISE (max)
12V
7.5A
0 ~ 7.5A
90W
120mVp-p
15V
6.5A
0 ~ 6.5A
97.5W
120mVp-p
24V
4.2A
0 ~ 4.2A
100.8W
150mVp-p
Ripple & noise are measured at 20MHz of bandwidth by using a 12 twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor.
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE
12 ~ 15V
±2.0%
15 ~ 18V
±1.0%
24 ~ 29V
±1.0%
Tolerance: includes set up tolerance, line regulation and load regulation.
INPUT
INPUT
PROTECTION
PROTECTION
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
±1.0%
±1.0%
2700ms, 80ms / 230VAC
50ms / 230VAC
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
AC CURRENT (max.)
INRUSH CURRENT (Typ.)
88 ~ 264VAC
124 ~ 370VDC
47 ~ 63Hz
87%
87%
3A / 115VAC
1.6A / 230VAC
COLD START 30A / 115VAC; 45A / 230VAC
OVERLOAD
±1.0%
±1.0%
2700ms, 80ms / 115VAC at full load
18ms / 115VAC at full load
±1.0%
±1.0%
89%
105 ~ 135% rated output power
Protection type: Constant current limiting recovers automatically after fault condition is removed
Under short circuit or overload ≥ 150% conditions, output voltage may shut down for 5 sec. and then go into constant
current protection mode
OVERVOLTAGE
16 ~ 20V
19 ~ 23V
30 ~ 35V
Protection type: Shut down overvoltage, re-power on to recover
OVERTEMPERATURE
90˚C ± 15˚C (RTH2) detect on heat sink of power transistor
Protection type: Shut down overvoltage, re-power on to recover
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MOUNTING
-20 ~ +60˚C (Refer to output load derating curve)
20 ~ 90% RH non-condensing
-40 ~ +85˚C, 10 ~ 95% RH
±0.03% / ˚C (0 ~ 50˚C)
10 ~ 500Hz, 2G 10min. / 1cycle, 60 min. each long X,Y, Z axes
Compliance to IEC60068-2-6
ENVIRONMENT
ENVIRONMENT
SAFETY & EMC
SAFETY & EMC
SAFETY STANDARDS
UL60950-1
EN60950-1compliant
Design refer to EN50178
WITHSTAND VOLTAGE
I/P-O/P: 3KVAC
ISOLATION RESISTANCE
I/P-O/P: 100M Ohms/500VDC (25°C; 70% RH)
EMI CONDUCTION & RADIATION Compliance to EN61204-3; EN55022 (CISPR22) Class B
HARMONIC CURRENT
Compliance to EN61000-3-2,-3
Harmonic current test @ 90% load
EMS IMMUNITY
The power supply is considered a component which will installed into a final equipment. The final equipment must be re-confirmed
that is still meets EMC directives.
OTHERS
OTHERS
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204; EN55024; EN61000-6-2; EN61204-3;
heavy industry level; criteria A
MTBF
DIMENSION
PACKING
NOTE
486K hrs min. MIL-HDBK-217K (25˚C)
100x93x56mm (WxHxD)
0.35Kg; 36pcs / 13.6Kg / 0.89CUFT
All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature.
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
32
Mechanical Specification
56
100
5
47
3
4
5
6
1
2
Terminal Pin. No Assignment
7
45
93
Assignment Pin No. Assignment
AC/L
5,6
-V
AC/N
LED
7
+V ADJ.
+V
8
68
Pin No.
1
2
3,4
27.4
5 5 5 7.5
64.75
3
8
Block Diagram
RECTIFIERS
&
FILTER
EMI
FILTER
I/P
RECTIFIERS
&
FILTER
POWER
SWITCHING
O.L.P.
+V
-V
DETECTION
CIRCUIT
PWM
CONTROL
O.V.P.
Derating Curve
Output Derating VS Input Voltage
Ta=25
100
100
90
LOAD (%)
LOAD (%)
80
60
40
80
70
60
50
20
-20
40
0
10
20
30
40 45 50
60
AMBIENT TEMPERATURE (°C)
70 (VERTICAL)
88
95
100 110
120 140
160 180
200 220
240
264
INPUT VOLTAGE (VAC) 60Hz
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
33
Industrial Metal Case Single Phase
and Three Phase Power Supply
The Altech Industrial metal case power supplies have been optimized for use in
practically any DC power applications, with a wide range of AC/DC inputs and an
extended temperature range of -20° C up to +70° C. These metal case power supplies
feature a small housing design and high power reserve. Excellent electrical
specifications and high immunity against fluctuations in input voltage make these metal
case modules the best choice to industrial automation. Altech’s metal case power
supplies are available in six single-phase and four three-phase models with 12VDC (75W
and 120W), 24 VDC and 48VDC output voltages, and up to 40A output currents. This
voltage range enables the Industrial metal case supplies to be used in virtually any
single-phase or three-phase application. The Industrial metal case power supply series
offers users easy wiring with screw terminal blocks and snap-on DIN-rail mounting.
Designed for use in numerous applications around the world, this power supplies are UL
and CSA approved, CE marked and ROHS compliant. They feature a rugged metal
housing, vibration- and shock-proof construction and provide a cost-effective power
delivery solution for basic functionality requirements.
Single Phase Power Supply:
• Input voltage range:
• AC inrush current: Cold start:
• Overload voltage protection:
• Over-voltage protection:
• Setup, rise, hold up time:
• Working temperature:
85-264V AC / 120-370V DC
20A at 115V AC, 40A at 230V AC
105%-160% constant current limiting auto-recovery
115%-135% rated output voltage
500ms; 70ms; 30ms at full load and 230V AC
-20 to +50°C (-4° to +122°F) at 100%
+60°C (+140°F) at 80% load
Three Phase Power Supply:
• Three phase input
• Input voltage range:
• AC inrush current:
• Overload voltage protection:
• Over-voltage protection:
• Setup, rise, hold up time:
• Working temperature:
• EMC standards:
340-550V AC / 480-760V DC
Cold start: 50A
105%-150% constant current limiting auto-recovery
115%-135% rated output voltage
1200ms, 40ms, 20ms @ 400V AC
800ms, 40ms, 40ms @ 500V AC full load
-20 to +70°C (-4 to +158°F) at 100%
EN61000-6-2 (EN50082-2)
Heavy Industrial Level; criteria A
Single Phase
75-240W.............................................................................pages 36-45
480W and 480W Switch Select..........................................pages 46-51
Three Phase
240-960W...........................................................................pages 52-59
34
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
PS Series - Metal Case
Features:
• Universal AC input / Full range
• Single phase or Three phase
• Built in active PFC function
• Protections: Short circuit / Overload / Overvoltage / Over temperature
• Cooling by free air convection
• DIN rail mountable
• UL 508 (industrial control equipment) approved
• LED indicator for power on
• 100% full load burn-in test
• 3 year warranty
DC on LED signal
Universal Input
35mm DIN Rail
mounting
Easy to understand layout panel
UL508 Compliance
CE Compliance
Rugged metal housing
Multiple output connector
for easy wiring
Narrow for maximized
panel space
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
35
75-240W Single Phase
POWER SUPPLIES
75W Single Output DIN Rail Power Supply
Cat. No.
Output
V DC
A
Tol.
%
Ripple &
Noise
Efficiency
PS-7512
12V DC
6.3A
±2%
100 mVp-p
76%
PS-7524
24V DC
3.2A
±1%
150 mVp-p
80%
PS-7548
48V DC
1.6A
±1%
240 mVp-p
81%
NOTES
120W Single Output DIN Rail Power Supply
Cat. No.
Output
V DC
A
Tol.
%
Ripple &
Noise
Efficiency
PS-12012
12V DC
10A
±2%
80 mVp-p
80%
PS-12024
24V DC
5A
±1%
80 mVp-p
84%
2.5A
±1%
100 mVp-p
85%
PS-12048
48V DC
NOTES
110/220V
SWITCH SELECT
120W High Input Single Output DIN Rail Power Supply
Cat. No.
PSH-12024
PSH-12048
Output
V DC
A
24V DC
48V DC
Tol.
%
Ripple &
Noise
Efficiency
5A
±1%
80 mVp-p
85%
2.5A
±1%
80 mVp-p
86%
NOTES
HIGH INPUT
240W Single Output DIN Rail Power Supply with PFC Function
Cat. No.
36
Output
V DC
A
Tol.
%
Ripple &
Noise
Efficiency
PSP-24024
24V DC
10A
±1%
80 mVp-p
84%
PSP-24048
48V DC
5A
±1%
150 mVp-p
85%
NOTES
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
SPECIFICATIONS
PS-75
Series
Terminal Pin. No Assign. (TB1)
12
Pin No.
1
2
3
5.2
Assignment
FG
AC/N
AC/L
Terminal Pin. No Assign. (TB2)
Pin No. Assignment
DC OUTPUT +V
1,2
DC OUTPUT -V
3,4
Universal Input:
10
0
.5
55
PS-120
Series
85-264V AC, 120-370V DC full range,
1.6A @ 115V AC, 0.96A @ 230V AC
Connection: Input - 3 poles, Output – 4 poles screw terminal
Size (WxHxD): 55.5x125x100mm (2.20x4.95x3.95 inches)
Packaging: 1/box; 1.35lbs / 0.60Kg
Terminal Pin. No Assign. (TB1)
Pin No.
1
2
3
(Switch Select)
12
5.2
10
PSH-120
High Input
Series
12
0
.5
65
Switch select Input: 88-132V AC / 176-264 V AC, 248-370V DC range,
2.6A @ 115V AC, 1.6A @ 230V AC
Connection: Input - 3 poles, Output – 4 poles screw terminal
Size (WxHxD): 65.5x125x100mm (2.56x4.95x3.95 inches)
Packaging: 1/box; 1.75lbs / 0.79Kg
Terminal Pin. No Assign. (TB1)
Assignment
1
FG
2
AC/N(L2)
3
AC/L(L1)
5.2
Terminal Pin. No Assign. (TB2)
Assignment
1,2
3,4
Universal Input:
10
0
.5
65
PSP-240
Series
340-550V AC, 480-780V DC range,
0.65A @ 400V AC, 0.6A @ 500V AC
Connection: Input - 3 poles, Output – 4 poles screw terminal
Size (WxHxD): 65.5x125x100mm (2.56x4.95x3.95 inches)
Packaging: 1/box; 1.65lbs / 0.75Kg
Terminal Pin. No Assign. (TB1)
Pin No.
1
2
3
25
Terminal Pin. No Assign. (TB2)
Pin No. Assignment
DC OUTPUT +V
1,2
DC OUTPUT -V
3,4
Assignment
FG
AC/N
AC/L
Assignment
FG
AC/N
AC/L
Terminal Pin. No Assign. (TB2)
Pin No. Assignment
DC OUTPUT +V
1,2
DC OUTPUT -V
3,4
.2
Universal Input:
10
0
5.5
12
85-264V AC, 120-370V DC full range,
2.8A @ 115V AC, 1.4A @ 230V AC
Built in active Power Factor Correction function. PF>0.95
Connection: Input - 3 poles, Output – 4 poles screw terminal
Size (WxHxD): 125x125x100mm (4.95x4.95x3.95 inches)
Packaging: 1/box; 2.7lbs / 1.2Kg
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
37
PS-75 Series
Features:
Specifications
OUTPUT
• Univers al AC input / full range
• Protections: Short Circuit / Over load /
Overvoltage / Over temperature
• Cooling by free air convection
• DIN rail mountable
• UL508 (industrial control equipment) approved
• LED indicator for power on
• 100% full load burn-in test
• Fix switching frequency at 50KHz
• 3 year warranty
Cat. No.
PS-7512
PS-7524
PS-7548
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
RIPPLE & NOISE (max)
12V
6.3A
0 ~ 6.3A
76W
100mVp-p
24V
3.2A
0 ~ 3.2A
76.8W
150mVp-p
48V
1.6A
0 ~ 1.6A
76.8W
240mVp-p
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE
12 ~ 14V
±2.0%
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
±0.5%
±1.0%
1000ms, 60ms / 230VAC
60ms / 230VAC
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
AC CURRENT (max.)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
85 ~ 264VAC
120 ~ 370VDC
47 ~ 63Hz
76%
1.6 A / 115VAC
0.96A / 230VAC
COLD START
20A / 115VAC
≤ 1mA / 240VAC
OVERLOAD
105 ~ 150% rated output power
OVERVOLTAGE
15 ~ 16.5V
Ripple & noise are measured at 20MHz of bandwidth by using a 12 twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor.
24 ~ 28V
±1.0%
48 ~ 53V
±1.0%
Tolerance: includes set up tolerance, line regulation and load regulation.
INPUT
PROTECTION
±0.5%
±1.0%
1800ms, 60ms / 115VAC at full load
12ms / 115VAC at full load
80%
±0.5%
±1.0%
81%
40A / 230VAC
Protection type: Constant current limiting, recovers automatically after fault condition is removed
29 ~ 34V
58 ~ 65V
Protection type: Shut down overvoltage, re-power on to recover
OVERTEMPERATURE
ENVIRONMENT
SAFETY & EMC
Protection type: Shut down overvoltage, recovers automatically after temperature goes down
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MOUNTING
-10 ~ +60˚C (Refer to output load derating curve)
20 ~ 90% RH non-condensing
-20 ~ +85˚C, 10 ~ 95% RH
±0.03% / ˚C (0 ~ 50˚C)
10 ~ 500Hz, 2G 10min./1cycle, 60 min. each long X,Y, Z axes
Compliance to IEC60068-2-6
SAFETY STANDARDS
UL508
EN60950-1 approved
I/P-O/P: 3KVAC I/P-FG: 1.5KVAC O/P-FG: 0.5KVAC
I/P-O/P, I/P-FG, O/P-FG: 100M Ohms / 500VDC
Compliance to EN55011; EN55022 (CISPR22) Class B
Compliance to EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204; EN55024; EN61000-6-2; (EN50082-2)
heavy industry level; criteria A
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION
HARMONIC CURRENT
EMS IMMUNITY
OTHERS
85˚C ± 5˚C (TSW1) detect on heat sink of power transistor
The power supply is considered a component which will installed into a final equipment. The final equipment must be re-confirmed
that it still meets EMC directives.
MTBF
DIMENSION
PACKING
123.1K hrs min. MIL-HDBK-217K (25˚C)
55.5x125.2x100mm (WxHxD)
0.6Kg; 20pcs / 13Kg / 1.29CUFT
All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature.
38
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
Mechanical Specification
55.5
1
2
3
125.2
TB1
TB2
4
3
2
1
LE D
100
Terminal Pin. No Assignment (TB2)
Terminal Pin. No Assignment (TB1)
Pin No.
1
2
3
Pin No.
1,2
3,4
Assignment
FG
AC/N
AC/L
Assignment
DC OUTPUT +V
DC OUTPUT -V
Block Diagram
RECTIFIERS
&
FILTER
EMI
FILTER
I/P
RECTIFIERS
&
FILTER
POWER
SWITCHING
+V
-V
DETECTION
CIRCUIT
FG
O.L.P.
O.T.P.
PWM
CONTROL
O.V.P.
Output Derating VS Input Voltage
Derating Curve
100
100
24V,48V
90
12V
LOAD (%)
LOAD (%)
80
60
40
80
70
60
50
20
-10
40
0
10
20
30
45
50
60 (VERTICAL)
AMBIENT TEMPERATURE (°C)
85
90
105
125
145
165
185
205
225
245 265
INPUT VOLTAGE (VAC) 60Hz
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
39
PS-120 Series
Features:
Specifications
• Universal AC input / full range
• Protections: Short Circuit / Over load /
Overvoltage/Over temperature
• Cooling by free air convection
• DIN rail mountable TS-35/ 7.5 or 1 5
• UL 508 (industrial control equipment) approved
• LED indicator for power on
• 100% full load burn-in test
• Fix switching frequency at 50KHz
• 3 year warranty
110/220V
SWITCH SELECT
OUTPUT
Cat. No.
PS-12012
PS-12024
PS-12048
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
RIPPLE & NOISE (max)
12V
10A
0 ~ 10A
120W
80mVp-p
24V
5A
0 ~ 5A
120W
80mVp-p
48V
2.5A
0 ~ 2.5A
120W
100mVp-p
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE
12 ~ 14V
±2.0%
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
±0.5%
±1.0%
500ms, 70ms / 230VAC
36ms / 230VAC
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
AC CURRENT (max.)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
88 ~ 132VAC / 176 ~ 264VAC by switch
47 ~ 63Hz
80%
84%
2.6 A / 115VAC
1.6A / 230VAC
COLD START
20A / 115VAC
40A / 230VAC
≤ 3.5mA / 240VAC
OVERLOAD
105 ~ 150% rated output power
OVERVOLTAGE
15 ~ 16.5V
Ripple & noise are measured at 20MHz of bandwidth by using a 12 twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor.
24 ~ 28V
±1.0%
48 ~ 53V
±1.0%
Tolerance: includes set up tolerance, line regulation and load regulation.
INPUT
PROTECTION
±0.5%
±1.0%
500ms, 70ms / 115VAC at full load
32ms / 115VAC at full load
±0.5%
±1.0%
248 ~ 370VDC
85%
Protection type: Constant current limiting, recovers automatically after fault condition is removed
29 ~ 33V
58 ~ 65V
Protection type: Shut down overvoltage, re-power on to recover
OVERTEMPERATURE
90˚C ± 5˚C (TSW1)
90˚C ± 5˚C (TSW1)
Protection type: Shut down overvoltage, recovers automatically after temperature goes down
ENVIRONMENT
SAFETY & EMC
85˚C ± 5˚C (TSW1)
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MOUNTING
-10 ~ +60˚C (Refer to output load derating curve)
20 ~ 90% RH non-condensing
-20 ~ +85˚C, 10 ~ 95% RH
±0.03% / ˚C (0 ~ 50˚C)
10 ~ 500Hz, 2G 10min./1cycle, 60 min. each long X,Y, Z axes
Compliance to IEC60068-2-6
SAFETY STANDARDS
UL508
UL60950-1
EN60950-1 approved
I/P-O/P: 3KVAC I/P-FG: 1.5KVAC O/P-FG: 0.5KVAC
I/P-O/P, I/P-FG, O/P-FG: 100M Ohms / 500VDC
Compliance to EN55011; EN55022 (CISPR22) Class B
Compliance to EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204; EN55024; EN61000-6-2; (EN50082-2);
heavy industry level; criteria A
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION
HARMONIC CURRENT
EMS IMMUNITY
The power supply is considered a component which will installed into a final equipment. The final equipment must be re-confirmed
that it still meets EMC directives.
OTHERS
MTBF
DIMENSION
PACKING
136.8K hrs min. MIL-HDBK-217K (25˚C)
65.5x125.2x100mm (WxHxD)
0.79Kg; 20pcs / 16.5Kg / 1.29CUFT
All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature.
40
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
Mechanical Specification
LE D
TB2
1
2
3
4
100
115VAC
1
2
3
TB1
125.2
230VAC
65.5
Terminal Pin. No Assignment (TB2)
Terminal Pin. No Assignment (TB1)
Pin No.
1
2
3
Pin No.
1,2
3,4
Assignment
FG
AC/N
AC/L
Block Diagram
Assignment
DC OUTPUT +V
DC OUTPUT -V
230
115
RECTIFIERS
&
FILTER
EMI
FILTER
I/P
RECTIFIERS
&
FILTER
POWER
SWITCHING
+V
-V
DETECTION
CIRCUIT
FG
O.L.P.
O.T.P.
Derating Curve
PWM
CONTROL
O.V.P.
Static Characterisitcs (24V)
48V
100
350
28
300
24
250
20
200
16
150
12
100
60
LOAD (%)
LOAD (%)
80
12V,24V
40
20
8
-10
0
10
20
30
45
50
AMBIENT TEMPERATURE (°C)
60 (VERTICAL)
80
80
160
85
170
90
180
95
190
100
200
105
210
110
220
115
230
120
240
125
250
OUTPUT RIPPLE (mVp-p)
Ta=25
32
130
260
INPUT VOLTAGE (VAC) 60Hz
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
41
PSH-120 High Input Series
Specifications
Features:
• Universal AC input / full range
• Protections: Short Circuit / Overload / Over Voltage /
Overtemperature
• Cooling by free air convection
• Built-in constant current limiting circuit
• DIN rail mountable
• EN61000-6-2(EN50082-2) industrial immunity level
• 100% full load burn-in test
• Fixed switching frequency at 70KHz
• 3 year warranty
HIGH INPUT
OUTPUT
Cat. No.
PSH-12024
PSH-12048
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
RIPPLE & NOISE (max)
24V
5A
0 ~ 5A
120W
80mVp-p
48V
2.5A
0 ~ 2.5A
120W
80mVp-p
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE
24 ~ 28V
±1.0%
LINE REGULATION
LOAD REGULATION
SETUP, RISE, HOLD UP TIME
±0.5%
±0.5%
1700ms, 120ms, 16ms / 400VAC
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
AC CURRENT (max.)
INRUSH CURRENT (max.)
LEAKAGE CURRENT
340 ~ 550VAC
480 ~ 780VDC
47 ~ 63Hz
85%
0.65A / 400VAC
0.6A / 500VAC
COLD START 50A
≤ 3.5 mA / 530VAC
OVERLOAD
105 ~ 160% rated output power
OVERVOLTAGE
30 ~ 36V
Ripple & noise are measured at 20MHz of bandwidth by using a 12 twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor.
48 ~ 55V
±1.0%
Tolerance: includes set up tolerance, line regulation and load regulation.
INPUT
PROTECTION
±0.5%
±0.5%
1000ms, 120ms, 30ms / 500VAC at full load
86%
Protection type: Constant current limiting, recovers automatically after fault condition is removed
59 ~ 66V
Protection type: Shut down overvoltage, re-power on to recover
OVERTEMPERATURE
85˚C ± 5˚C (TSW: detect on heat sink of power switch)
Protection type: Shut down overvoltage, recovers automatically after temperature goes down
ENVIRONMENT
SAFETY & EMC
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MOUNTING
-20 ~ +60˚C (Refer to output load derating curve)
20 ~ 90% RH non-condensing
-40 ~ +85˚C, 10 ~ 95% RH
±0.03% / ˚C (0 ~ 50˚C)
10 ~ 500Hz, 2G 10min./1cycle, 60 min. each long X,Y, Z axes
Compliance to IEC60068-2-6
SAFETY STANDARDS
UL60950-1 approved
IEC60950-1 CB approved by SIQ
I/P-O/P: 3KVAC I/P-FG: 1.5KVAC O/P-FG: 0.5KVAC
I/P-O/P, I/P-FG, O/P-FG: 100M Ohms / 500VDC (25˚C; 70% RH)
Compliance to EN55011 (CISPR11); EN55022 (CISPR22); EN61204-3 Class B
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204; EN61204-3; EN61000-6-2; (EN50082-2),
heavy industry level; criteria A
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION
EMS IMMUNITY
The power supply is considered a component which will installed into a final equipment. The final equipment must be re-confirmed
that it still meets EMC directives.
OTHERS
MTBF
DIMENSION
PACKING
178.7K hrs min. MIL-HDBK-217K (25˚C)
65.5x125.2x100mm (WxHxD)
0.75Kg; 20pcs / 16Kg / 1.29CUFT
All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature.
42
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
Mechanical Specification
TB1
1
2
3
125.2
LED
TB2
1
2
3
4
100
65.5
1
2
3
Assignment
Assignment
FG
AC/L2
AC/L1
1,2
3,4
Block Diagram
EMI
FILTER
I/P
RECTIFIERS
&
FILTER
POWER
SWITCHING
RECTIFIERS
&
FILTER
+V
-V
DETECTION
CIRCUIT
FG
CURRENT
LIMIT
O.L.P.
O.T.P.
PWM
CONTROL
O.V.P.
Derating Curve
100
80
60
50
40
20
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
43
PSP-240 Series
Features:
Specifications
OUTPUT
• Universal AC input / full range
• Built in active PFC function
• Protections: Short Circuit / Overload / Overvoltage /
Over temperature
• Cooling by free air convection
• DIN rail mountable
• UL 508(industrial control equipment)approved
• LED indicator for power on
• 100% full load burn-in test
• Fixed switching frequency at 100KHz
• 3 year warranty
Cat. No.
PSP-24024
PSP-24048
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
RIPPLE & NOISE (max)
24V
10A
0 ~ 10A
240W
80mVp-p
48V
5A
0 ~ 5A
240W
150mVp-p
Ripple & noise are measured at 20MHz of bandwidth by using a 12 twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor.
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE
24 ~ 28V
±1.0%
48 ~ 53V
±1.0%
Tolerance: includes set up tolerance, line regulation and load regulation.
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
INPUT
VOLTAGE RANGE
±0.5%
±1.0%
800ms, 40ms / 230VAC
24ms / 230VAC
85 ~ 264VAC
±0.5%
±1.0%
800ms, 40ms / 115VAC at full load
24ms / 115VAC at full load
120 ~ 370VDC
Derating may be needed under low input voltages, please check the derating curve for more detail
FREQUENCY RANGE
POWER FACTOR (Typ.)
EFFICIENCY (Typ.)
AC CURRENT (max.)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
PROTECTION
OVERLOAD
47 ~ 63Hz
0.96 / 230VAC
0.99 / 115VAC at full load
84%
2.8A / 115VAC; 1.4A / 230VAC
COLD START 27A / 115VAC
45A / 230VAC
≤ 3.5mA / 240VAC
85%
105 ~ 150% rated output power
Protection type: Constant current limiting, recovers automatically after fault condition is removed
OVERVOLTAGE
30 ~ 36V
54 ~ 60V
Protection type: Shut down overvoltage, re-power on to recover
OVERTEMPERATURE
100˚C ± 5˚C (TSW: detect on heat sink of power transistor)
Protection type: Shut down overvoltage, recovers automatically after temperature goes down
ENVIRONMENT
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MOUNTING
-10 ~ +70˚C (Refer to output load derating curve)
20 ~ 90% RH non-condensing
-20 ~ +85˚C, 10 ~ 95% RH
±0.03% / ˚C (0 ~ 50˚C)
10 ~ 500Hz, 2G 10min./1cycle, 60 min. each long X,Y, Z axes
Compliance to IEC60068-2-6
SAFETY STANDARDS
UL508
EN60950-1
EN60950-1 approved
I/P-O/P: 3KVAC I/P-FG: 1.5KVAC O/P-FG: 0.5KVAC
I/P-O/P, I/P-FG, O/P-FG: 100M Ohms / 500VDC
Compliance to EN55011; EN55022 (CISPR22) Class B
Compliance to EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204; EN55024; EN61000-6-2; (EN50082-2);
heavy industry level; criteria A
SAFETY & EMC
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION
HARMONIC CURRENT
EMS IMMUNITY
The power supply is considered a component which will installed into a final equipment. The final equipment must be re-confirmed
that it still meets EMC directives.
OTHERS
MTBF
DIMENSION
PACKING
289.9K hrs min. MIL-HDBK-217K (25˚C)
125.5x125.2x100mm (WxHxD)
1.2Kg; 12pcs / 15.5Kg / 1.29CUFT
All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature.
44
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
Mechanical Specification
125.5
100
125.2
TB1
LED
3 2 1
1
2
3
TB2
4 3 2 1
Assignment
Assignment
FG
AC/N
AC/L
1,2
3,4
Block Diagram
EMI FILTER
&
RECTIFIERS
I/P
PFC
CIRCUIT
RECTIFIERS
&
FILTER
POWER
SWITCHING
FG
O.L.P.
+V
-V
CONSTANT
CURRENT
LIMITING &
DETECTION
CIRCUIT
PWM & PFC
CONTROL
O.V.P.
O.T.P.
Derating Curve
Output Derating VS Input Voltage
Ta=25
100
100
230VAC
90
80
80
60
70
110VAC
60
40
50
20
40
-10
0
10
20
30
40
50 55 60
70 (VERTICAL)
Vin: -- 230VAC
110VAC
85
100
110
135
155
230
264
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
45
480W Single Phase
POWER SUPPLIES
480W 220V AC Single Output
DIN Rail Power Supply with PFC Function
Cat. No.
220V ONLY
Output
V DC
A
Tol.
%
Ripple &
Noise
Efficiency
PSP-48024
24V DC
20A
±1%
120 mVp-p
89%
PSP-48048
48V DC
10A
±1%
120 mVp-p
89%
NOTES
480W Switch Select 110/220V AC Single Output
DIN Rail Power Supply with PFC Function
110/220V
SWITCH SELECT
46
Cat. No.
Output
V DC
A
Tol.
%
Ripple &
Noise
Efficiency
PSP-480S24 24V DC
20A
±1%
120 mVp-p
89%
PSP-480S48 48V DC
10A
±1%
120 mVp-p
89%
NOTES
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
SPECIFICATIONS
PSP-480 Series
(220V AC input only)
TB1 Terminal Pin. No Assignment
Pin No. Assignment
1
2
3
12
5.2
7
22
10
0
AC/L
AC/N
FG
TB2 Terminal Pin. No Assignment
Pin No. Assignment
1,2
3,4
DC OUTPUT +V
DC OUTPUT -V
Wide range Input: 180-264V AC only, 250-370V DC, 4A @ 230V AC
Built in passive Power Factor Correction function compliance to EN61000-3-2,
PF>0.7
Connection: Input - 3 poles, Output – 4 poles screw terminal
Size (WxHxD): 227x125x100mm (8.95x4.95x3.95 inches)
Packaging: 1/box; 5.3lbs / 2.4Kg
PSP-480 with Switch Series
(110V AC and 220V input AC)
TB1 Terminal Pin. No Assignment
Pin No. Assignment
1
2
3
12
5.2
7
22
10
0
AC/L
AC/N
FG
TB2 Terminal Pin. No Assignment
Pin No. Assignment
1,2
3,4
DC OUTPUT +V
DC OUTPUT -V
Switch select Input: 90-132V AC / 180-264 V AC, 254-370V DC range
8A @ 115V AC, 3.2A @ 230V AC
Built in passive Power Factor Correction function compliance to EN61000-3-2,
PF>0.7/230V AC only
Connection: Input - 3 poles, Output – 4 poles screw terminal
Size (WxHxD): 227x125x100mm (8.95x4.95x3.95 inches)
Packaging: 1/box; 5.8lbs / 2.6Kg
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
47
PSP-480 Series
Specifications
220V ONLY
OUTPUT
Features:
• Built-in passive PFC function compliance to EN61000-3-2
• High efficiency 89% and low dissipation
• Protections: Short Circuit / Overload / Overvoltage /
Over temperature
• Cooling by free air convection
• Built-in constant current limiting circuit
• DIN rail mountable
• UL 508(industrial control equipment)approved
• EN61000-6-2(EN50082-2) industrial immunity level
• 100% full load burn-in test
• 3 year warranty
Cat. No.
PSP-48024
PSP-48048
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
RIPPLE & NOISE (max)
24V
20A
0 ~ 20A
480W
120mVp-p
48V
10A
0 ~ 10A
480W
120mVp-p
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE
24 ~ 28V
±1.0%
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
±0.5%
±1.0%
1200ms, 40ms / 230VAC at full load
16ms / 230VAC
VOLTAGE RANGE
FREQUENCY RANGE
POWER FACTOR (Typ.)
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
180 ~ 264 VAC by switch
250 ~ 370VDC
47 ~ 63Hz
≥0.7
89%
4A / 230VAC
COLD START 27A / 115VAC
45A / 230VAC
≤ 3.5mA / 240VAC
OVERLOAD
105 ~ 150% rated output power
OVERVOLTAGE
30 ~ 36V
Ripple & noise are measured at 20MHz of bandwidth by using a 12 twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor.
48 ~ 53V
±1.0%
Tolerance: includes set up tolerance, line regulation and load regulation.
INPUT
PROTECTION
±0.5%
±1.0%
Protection type: Constant current limiting, recovers automatically after fault condition is removed
54 ~ 60V
Protection type: Shut down overvoltage, re-power on to recover
OVERTEMPERATURE
100˚C ± 5˚C (TSW: detect on heat sink of power switch)
Protection type: Shut down overvoltage, recovers automatically after temperature goes down
ENVIRONMENT
SAFETY & EMC
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MOUNTING
-20 ~ +70˚C (Refer to output load derating curve)
20 ~ 95% RH non-condensing
-20 ~ +85˚C, 10 ~ 95% RH
±0.03% / ˚C (0 ~ 50˚C)
10 ~ 500Hz, 2G 10min./1cycle, 60 min. each long X,Y, Z axes
Compliance to IEC60068-2-6
SAFETY STANDARDS
UL508
EN60950-1
EN60950-1 approved
I/P-O/P: 3KVAC I/P-FG: 1.5KVAC O/P-FG: 0.5KVAC
I/P-O/P, I/P-FG, O/P-FG: ≥100M Ohms / 500VDC (25˚C; 70% RH)
Compliance to EN55022 (CISPR22); Class B
Compliance to EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204; EN61000-6-2 (EN50082-2);
heavy industry level; criteria A
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION
HARMONIC CURRENT
EMS IMMUNITY
OTHERS
The power supply is considered a component which will installed into a final equipment. The final equipment must be re-confirmed
that it still meets EMC directives.
MTBF
DIMENSION
PACKING
180.9K hrs min. MIL-HDBK-217K (25˚C)
227x125.2x100mm (WxHxD)
2.4Kg; 6pcs / 15Kg / 1.75CUFT
All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature.
48
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
Mechanical Specification
100
125.2
227
TB1
3 2 1
LE D
TB1 Terminal Pin. No Assignment
Pin No.
1
2
3
TB2
4 3 2 1
TB2 Terminal Pin. No Assignment
Assignment
AC/L
AC/N
FG
Pin No.
1,2
3,4
Assignment
DC OUTPUT +V
DC OUTPUT -V
Block Diagram
EMI
FILTER
I/P
RECTIFIERS
&
FILTER
PASSIVE
PFC
RECTIFIERS
&
FILTER
POWER
SWITCHING
+V
-V
DETECTION
CIRCUIT
FG
O.L.P.
O.T.P.
Derating Curve
CURRENT
LIMIT
PWM
CONTROL
O.V.P.
Output Derating VS Input Voltage
100
100
90
LOAD (%)
LOAD (%)
80
60
40
80
70
60
50
20
-20
40
0
10
20
30
40
50
60
70 (VERTICAL)
180
190
200
264
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
49
PSP-480S Series
Specifications
110/220V
SWITCH SELECT
OUTPUT
Features:
• AC input range selectable by switch
• Built-in passive PFC function compliance to EN61000-3-2
• High efficiency 89% and low dissipation
• Protections: Short Circuit / Overload / Overvoltage /
Over temperature
• Cooling by free air convection
• Built-in constant current limiting circuit
• DIN rail mountable
• UL 508(industrial control equipment)approved
• EN61000-6-2(EN50082-2) industrial immunity level
• 100% full load burn-in test
• 3 year warranty
Cat. No.
PSP-480S24
PSP-480S48
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
RIPPLE & NOISE (max)
24V
20A
0 ~ 20A
480W
120mVp-p
48V
10A
0 ~ 10A
480W
120mVp-p
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE
24 ~ 28V
±1.0%
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
±0.5%
±0.5%
±1.0%
±1.0%
1200ms, 40ms / 230VAC
1200ms, 40ms / 115VAC at full load
23ms / 230VAC 23ms / 115VAC at full load
VOLTAGE RANGE
FREQUENCY RANGE
POWER FACTOR (Typ.)
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
90 ~ 132VAC / 180 ~ 264 VAC by switch
254 ~ 370VDC
47 ~ 63Hz
≥0.7 / 230VAC only
89%
8A / 115VAC
3.2A / 230VAC
COLD START 27A / 115VAC
45A / 230VAC
≤ 3.5mA / 240VAC
OVERLOAD
105 ~ 150% rated output power
OVERVOLTAGE
30 ~ 36V
Ripple & noise are measured at 20MHz of bandwidth by using a 12 twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor.
48 ~ 55V
±1.0%
Tolerance: includes set up tolerance, line regulation and load regulation.
INPUT
PROTECTION
Protection type: Constant current limiting, recovers automatically after fault condition is removed
59 ~ 66V
Protection type: Shut down overvoltage, re-power on to recover
OVERTEMPERATURE
ENVIRONMENT
SAFETY & EMC
100˚C ± 5˚C (TSW: detect on heat sink of power switch)
Protection type: Shut down overvoltage, recovers automatically after temperature goes down
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MOUNTING
-20 ~ +70˚C (Refer to output load derating curve)
20 ~ 95% RH non-condensing
-40 ~ +85˚C, 10 ~ 95% RH
±0.03% / ˚C (0 ~ 50˚C)
10 ~ 500Hz, 2G 10min./1cycle, 60 min. each long X,Y, Z axes
Compliance to IEC60068-2-6
SAFETY STANDARDS
UL508
EN60950-1
EN60950-1 approved
I/P-O/P: 3KVAC I/P-FG: 1.5KVAC O/P-FG: 0.5KVAC
I/P-O/P, I/P-FG, O/P-FG: 100M Ohms / 500VDC / 25˚C / 70% RH
Compliance to EN55011 (CISPR11); EN55022 (CISPR22); EN61204-3 Class B
Compliance to EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204; EN61204-3; EN61000-6-2 (EN50082-2);
heavy industry level; criteria A
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION
HARMONIC CURRENT
EMS IMMUNITY
The power supply is considered a component which will installed into a final equipment. The final equipment must be re-confirmed
OTHERS
that it still meets EMC directives.
MTBF
DIMENSION
PACKING
187.9K hrs min. MIL-HDBK-217K (25˚C)
227x125.2x100mm (WxHxD)
2.6Kg; 6pcs / 16.6Kg / 1.75CUFT
All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature.
50
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
Mechanical Specification
100
56.6
227
10 6
125.2
12
230VAC
115VAC
TB1
3 2 1
LE D
TB1 Terminal Pin. No Assignment
Pin No.
1
2
3
TB2
4 3 2 1
TB2 Terminal Pin. No Assignment
Assignment
AC/L
AC/N
FG
Pin No.
1,2
3,4
Assignment
DC OUTPUT +V
DC OUTPUT -V
Block Diagram
230
115
EMI
FILTER
I/P
RECTIFIERS
&
FILTER
PASSIVE
PFC
POWER
SWITCHING
RECTIFIERS
&
FILTER
DETECTION
CIRCUIT
FG
O.L.P.
O.T.P.
CURRENT
LIMIT
PWM
CONTROL
Derating Curve
O.V.P.
Output Derating VS Input Voltage
100
100
180 ~ 264VAC
90 ~ 132VAC
90
80
LOAD (%)
LOAD (%)
80
60
40
20
-20
+V
-V
70
60
50
40
0
10
20
30
40
50
60
70 (VERTICAL)
90
180
100
190
115
230
132
264
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
51
240-960W Three Phase
POWER SUPPLIES
240W Three Phase Industrial DIN Rail Power Supply
Cat. No.
Output
V DC
A
Tol.
%
Ripple &
Noise
Efficiency
PST-24024
24V DC
10A
±1%
80 mVp-p
89%
PST-24048
48V DC
5A
±1%
80 mVp-p
89%
NOTES
480W Three Phase Industrial DIN Rail Power Supply
Cat. No.
Output
V DC
A
Tol.
%
Ripple &
Noise
Efficiency
PST-48024
24V DC 20A
±1%
80 mVp-p
89%
PST-48048
48V DC 10A
±1%
80 mVp-p
90%
NOTES
960W Three Phase Industrial DIN Rail Power Supply
Cat. No.
Output
V DC
A
Tol.
%
Ripple &
Noise
Efficiency
PST-96024
24V DC 40A
±1%
80 mVp-p
91%
PST-96048
48V DC 20A
±1%
80 mVp-p
92%
NOTES
960W Three Phase Industrial DIN Rail Power Supply
with PFC and Parallel Function (1+1)
Cat. No.
52
Output
V DC
A
Tol.
%
Ripple &
Noise
Efficiency
PST-960P24
24V DC 40A
±1%
80 mVp-p
91%
PST-960P48
48V DC 20A
±1%
80 mVp-p
92%
NOTES
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
SPECIFICATIONS
PST-240 Series
TB1 Terminal Pin. No Assignment
12
Pin No.
1
2
3
4
5.2
10
TB2 Terminal Pin. No Assignment
Pin No.
1,2
3,4
Assignment
DCOUTPUT +V
DCOUTPUT -V
Three phase input: 340-550V AC wide range, 480-780V DC
0.95A @ 400V AC, 0.75A @ 500V AC
Connection: Input - 4 poles, Output – 4 poles screw terminal
Size (WxHxD): 125x125x100mm (4.95x4.95x3.95 inches)
Packaging: 1/box; 2.87lbs / 1.3Kg
5.5
12
0
Assignment
FG
AC/L3
AC/L2
AC/L1
PST-480 Series
TB1 Terminal Pin. No Assignment
Pin No.
1
2
3
4
12
5.2
27
2
10
0
Assignment
AC/L1
AC/L2
AC/L3
FG
TB2 Terminal Pin. No Assignment
Pin No.
1,2
3,4
Assignment
DCOUTPUT +V
DCOUTPUT -V
Three phase input: 340-550V AC wide range, 480-780V DC
1.7A @ 400V AC, 1.3A @ 500V AC
Connection: Input - 4 poles, Output – 4 poles screw terminal
Size (WxHxD): 227x125x100mm (9.95x4.95x3.95 inches)
Packaging: 1/box; 5.5lbs / 2.5Kg
PST-960 Series
TB1 Terminal Pin. No Assignment
Pin No.
1
2
3
4
12
5.2
6
27
10
0
Assignment
AC/L1
AC/L2
AC/L3
FG
TB2 Terminal Pin. No Assignment
Pin No.
1,2,3
4,5,6
7
8
Assignment
DCOUTPUT+ V
DCOUTPUT - V
GND
P (Current Share)
}
Parallel Only
Three phase input: 340-550V AC wide range,
2.4A @ 400V AC, 1.9A @ 500V AC
Connection: Input - 4 poles, Output – 6 poles screw terminal
Size (WxHxD): 276x125x100mm (10.87x4.95x3.95 inches)
Packaging: 1/box; 7.3lbs / 3.3Kg
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
53
PST-240 Series
Specifications
OUTPUT
Features:
• Three-Phase AC 340 ~ 550V wide range input
• High efficiency 89% and low dissipation
• Protections: Short Circuit / Overload / Overvoltage /
Over temperature
• Cooling by free air convection
• Built-in constant current limiting circuit
• DIN rail mountable
• UL 508(industrial control equipment)approved
• EN61000-6-2(EN50082-2) industrial immunity level
• 100% full load burn-in test
• Fixed switching frequency at 70KHz
• 3 year warranty
Cat. No.
PST-24024
PST-24048
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
RIPPLE & NOISE (max)
24V
10A
0 ~ 10A
240W
80mVp-p
48V
5A
0 ~ 5A
240W
80mVp-p
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE
24 ~ 28V
±1.0%
LINE REGULATION
LOAD REGULATION
SETUP, RISE, HOLD UP TIME
±0.5%
±0.5%
±0.5%
±0.5%
1200ms, 40ms, 20ms / 400VAC; 800ms, 40ms, 40ms / 500VAC at full load
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
AC CURRENT
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
Three Phase 340 ~ 550VAC (Dual Phase operation possible)
Dual phase operation: derating of 20% is required
47 ~ 63Hz
89%
0.95A / 400VAC; 0.75 / 500VAC
COLD START 50A
≤ 3.5 mA / 530VAC
OVERLOAD
105 ~ 150% rated output power
OVERVOLTAGE
30 ~ 36V
Ripple & noise are measured at 20MHz of bandwidth by using a 12 twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor.
48 ~ 55V
±1.0%
Tolerance: includes set up tolerance, line regulation and load regulation.
INPUT
PROTECTION
480 ~ 780VDC
Protection type: Constant current limiting, recovers automatically after fault condition is removed
59 ~ 66V
Protection type: Shut down overvoltage, re-power on to recover
OVERTEMPERATURE
100˚C ± 5˚C (TSW) detect on heat sink of power switch
Protection type: Shut down overvoltage, re-power automatically after temperature goes down
ENVIRONMENT
SAFETY & EMC
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MOUNTING
-20 ~ +70˚C (Refer to output load derating curve)
20 ~ 90% RH non-condensing
-40 ~ +85˚C, 10 ~ 95% RH
±0.03% / ˚C (0 ~ 50˚C)
10 ~ 500Hz, 2G 10min./1cycle, 60 min. each long X,Y, Z axes
Compliance to IEC60068-2-6
SAFETY STANDARDS
UL508
EN60950-1approved
UL60950-1
I/P-O/P: 3KVAC I/P-FG: 1.5KVAC O/P-FG: 0.5KVAC
I/P-O/P, I/P-FG, O/P-FG: 100M Ohms / 500VDC (25˚C; 70% RH)
Compliance to EN55011 (CISPR11), EN55022 (CISPR22) Class B
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204; EN61000-6-2; (EN50082-2), EN61204-3;
heavy industry level; criteria A,
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION
EMS IMMUNITY
The power supply is considered a component which will installed into a final equipment. The final equipment must be re-confirmed
that it still meets EMC directives.
OTHERS
MTBF
DIMENSION
PACKING
114.6K hrs min. MIL-HDBK-217K (25˚C)
125.5x125.2x100mm (WxHxD)
1.3Kg; 12pcs / 16.6Kg / 1.29CUFT
All parameters NOT specially mentioned are measured at 400VAC input, rated load and 25˚C of ambient temperature.
54
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
Mechanical Specification
100
125.5
125.5
TB1
4 3 2 1
LE D
TB2
4 3 2 1
TB1 Terminal Pin. No Assignment
Pin No.
1
2
3
4
TB2 Terminal Pin. No Assignment
Assignment
FG
AC/L3
AC/L2
AC/L1
Assignment
DC OUTPUT +V
DC OUTPUT -V
Pin No.
1,2
3,4
Block Diagram
RECTIFIERS
&
FILTER
EMI
FILTER
I/P
RECTIFIERS
&
FILTER
POWER
SWITCHING
+V
-V
DETECTION
CIRCUIT
FG
CURRENT
LIMIT
O.L.P.
O.T.P.
PWM
CONTROL
Derating Curve
O.V.P.
Output Derating VS Input Voltage
100
100
90
80
LOAD (%)
LOAD (%)
80
60
40
20
-20
Three phase operation
Dual phase operation
70
60
50
40
0
10
20
30
40
50
60
70 (VERTICAL)
340
355
370
385
400
415 430
460 475
490
505 520 550
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
55
PST-480 Series
Specifications
OUTPUT
Features:
• Three-Phase AC 340 ~ 550V wide range input
• High efficiency 89% and low dissipation
• Protections: Short Circuit / Overload / Over Voltage /
Overtemperature
• Cooling by free air convection
• Built-in constant current limiting circuit
• DIN rail mountable
• UL 508(industrial control equipment)approved
• EN61000-6-2(EN50082-2) industrial immunity level
• 100% full load burn-in test
• 3 year warranty
Cat. No.
PST-48024
PST-48048
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
RIPPLE & NOISE (max)
24V
20A
0 ~ 20A
480W
80mVp-p
48V
10A
0 ~ 10A
480W
80mVp-p
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE
24 ~ 28V
±1.0%
LINE REGULATION
LOAD REGULATION
SETUP, RISE, HOLD UP TIME
±0.5%
±0.5%
±0.5%
±0.5%
1200ms, 40ms, 16ms / 400VAC; 800ms, 40ms, 35ms / 500VAC at full load
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
AC CURRENT
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
Three Phase 340 ~ 550VAC (Dual Phase operation possible)
Dual phase operation: derating of 20% is required
47 ~ 63Hz
89%
90%
1.7A / 400VAC; 1.3A / 500VAC
COLD START 50A
≤ 3.5mA / 530VAC
OVERLOAD
105 ~ 150% rated output power
OVERVOLTAGE
30 ~ 36V
Ripple & noise are measured at 20MHz of bandwidth by using a 12 twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor.
48 ~ 55V
±1.0%
Tolerance: includes set up tolerance, line regulation and load regulation.
INPUT
PROTECTION
480 ~ 780VDC
Protection type: Constant current limiting, recovers automatically after fault condition is removed
59 ~ 66V
Protection type: Shut down overvoltage, re-power on to recover
OVERTEMPERATURE
110˚C ± 5˚C (TSW) detect on heat sink of power switch
Protection type: Shut down overvoltage, recovers automatically after temperature goes down
ENVIRONMENT
SAFETY & EMC
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MOUNTING
-20 ~ +70˚C (Refer to output load derating curve)
20 ~ 90% RH non-condensing
-40 ~ +85˚C, 10 ~ 95% RH
±0.03% / ˚C (0 ~ 50˚C)
10 ~ 500Hz, 2G 10min./1cycle, 60 min. each long X,Y, Z axes
Compliance to IEC60068-2-6
SAFETY STANDARDS
UL508
EN60950-1approved
UL60950-1
I/P-O/P: 3KVAC I/P-FG: 1.5KVAC O/P-FG: 0.5KVAC
I/P-O/P, I/P-FG, O/P-FG: 100M Ohms / 500VDC (25˚C: 70% RH)
Compliance to EN55011 (CISPR11), EN55022 (CISPR22), EN61204-3 Class B
Compliance to EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204; EN61204-3; EN61000-6-2; (EN50082-2),
heavy industry level; criteria A
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION
HARMONIC CURRENT
EMS IMMUNITY
The power supply is considered a component which will installed into a final equipment. The final equipment must be re-confirmed
that it still meets EMC directives.
OTHERS
MTBF
DIMENSION
PACKING
91.1K hrs min. MIL-HDBK-217K (25˚C)
227x125.2x100mm (WxHxD)
2.5Kg; 6pcs / 16Kg / 1.75CUFT
All parameters NOT specially mentioned are measured at 400VAC input, rated load and 25˚C of ambient temperature.
56
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
Mechanical Specification
100
125.2
227
TB1
4 3 2 1
TB2
4 3 2 1
LED
TB1 Terminal Pin. No Assignment
Pin No.
1
2
3
4
TB2 Terminal Pin. No Assignment
Assignment
AC/L1
AC/L2
AC/L3
FG
Pin No.
1,2
3,4
Assignment
DC OUTPUT +V
DC OUTPUT -V
Block Diagram
RECTIFIERS
&
FILTER
EMI
FILTER
I/P
RECTIFIERS
&
FILTER
POWER
SWITCHING
+V
-V
DETECTION
CIRCUIT
FG
CURRENT
LIMIT
O.L.P.
O.T.P.
PWM
CONTROL
Derating Curve
Output Derating VS Input Voltage
100
100
Three phase operation
90
85
80
LOAD (%)
80
LOAD (%)
O.V.P.
60
40
Dual phase operation
70
60
50
20
-20
40
0
10
20
30
40
50
60
70 (VERTICAL)
340
355
370
385
400
415 430
460 475
490
505 520 550
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
57
PST-960 Series
Features:
Specifications
OUTPUT
• Three-Phase AC 340 ~ 550V wide range input
• High efficiency 91% and low dissipation
• Protections: Short Circuit / Overload / Over Voltage /
Overtemperature
• Optional parallel function(1+1)
• Cooling by free air convection
• DIN rail mountable
• UL 508(industrial control equipment) approved
• EN61000-6-2(EN50082-2) industrial immunity level
• 100% full load burn-in test
• 3 year warranty
Cat. No.
PST-96024 / PST-960P24*
PST-96048 / PST-960P48*
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
RIPPLE & NOISE (max)
24V
40A
0 ~ 40A
960W
80mVp-p
48V
20A
0 ~ 20A
960W
80mVp-p
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE
LINE REGULATION
LOAD REGULATION
SETUP, RISE, HOLD UP TIME
24 ~ 28V
48 ~ 55V
±1.0%
±1.0%
Tolerance: includes set up tolerance, line regulation and load regulation.
±0.5%
±0.5%
±0.5%
±0.5%
200ms, 60ms, 14ms / 400VAC
200ms, 60ms, 30ms / 500VAC at full load
VOLTAGE RANGE
Three Phase 340 ~ 550VAC (Dual Phase operation possible in connecting L1, L3, FG)
FREQUENCY RANGE
EFFICIENCY (Typ.)
AC CURRENT
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
47 ~ 63Hz
91%
2A / 400VAC;
COLD START 50A
≤ 3.5 mA / 530VAC
OVERLOAD
105 ~ 125% rated output power
OVERVOLTAGE
30 ~ 36V
Ripple & noise are measured at 20MHz of bandwidth by using a 12 twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor.
INPUT
Dual phase operation (connecting L1, L3, FG) is allowed under certain derating to output load. Please refer to the derating curves for details.
PROTECTION
92%
1.6A / 500VAC
Protection type: Constant current limiting, unit will shut down overvoltage after 3 sec., re-power on to recover
59 ~ 66V
Protection type: Shut down overvoltage, re-power on to recover
ENVIRONMENT
SAFETY & EMC
OVERTEMPERATURE
110˚C ± 5˚C (TSW1) detect on heat sink of power transistor
85˚C ± 5˚C (TSW2) detect on heat sink of power diode
Protection type: Shut down overvoltage, recovers automatically after temperature goes down
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MOUNTING
-20 ~ +60˚C (Refer to output load derating curve)
20 ~ 90% RH non-condensing
-40 ~ +85˚C, 10 ~ 95% RH
±0.03% / ˚C (0 ~ 50˚C)
10 ~ 500Hz, 2G 10min./1cycle, 60 min. each long X,Y, Z axes
Compliance to IEC60068-2-6
SAFETY STANDARDS
UL508
EN60950-1 approved
UL60950-1
I/P-O/P: 3KVAC I/P-FG: 1.5KVAC O/P-FG: 0.5KVAC
I/P-O/P, I/P-FG, O/P-FG: 100M Ohms / 500VDC (25˚C; 70% RH)
Compliance to EN55011 (CISPR11), EN55022 (CISPR22), EN61204-3 Class B
Compliance to EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204; EN61204-3; EN61000-6-2; (EN50082-2),
heavy industry level; criteria A
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION
HARMONIC CURRENT
EMS IMMUNITY
The power supply is considered a component which will installed into a final equipment. The final equipment must be re-confirmed
OTHERS
that it still meets EMC directives.
MTBF
DIMENSION
PACKING
122.5K hrs min. MIL-HDBK-217K (25˚C)
276x125.2x100mm (WxHxD)
3.3Kg; 4pcs / 14.2Kg / 1.14CUFT
All parameters NOT specially mentioned are measured at 400VAC input, rated load and 25˚C of ambient temperature.
*Special order required.
58
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
Mechanical Specification
100
125.2
276
TB1
4 3 2 1
TB2
6 5 4 3 2 1
ALARM
LE D
TB1 Terminal Pin. No Assignment
Pin No.
1
2
3
4
TB2 Terminal Pin. No Assignment
Pin No.
1,2,3
4,5,6
7
8
Assignment
AC/L1
AC/L2
AC/L3
FG
Assignment
DCOUTPUT+ V
DCOUTPUT - V
P (Current Share)
P (Current Share)
}
Parallel Only
Optional Parallel Function (1+1) - (Special order required)
PSU
PSU
TB2
8 7 6 5 4 3 2 1
TB1
4 3 2 1
TB2
8 7 6 5 4 3 2 1
TB1
4 3 2 1
LED
LED
+V
-V
LOAD
Block Diagram
RECTIFIERS
&
FILTER
EMI
FILTER
I/P
RECTIFIERS
&
FILTER
POWER
SWITCHING
+V
-V
DETECTION
CIRCUIT
O.T.P.
FG
CURRENT
LIMIT
PHASE-SHIFT
O.V.P.
Output Derating VS Input Voltage
Derating Curve
100
100
Three phase operation
90
80
LOAD (%)
LOAD (%)
80
60
50
40
20
-20
Dual phase operation
70
60
50
40
0
10
20
30
40 45 50
60
70 (VERTICAL)
340
355
380
385
400
415430
460
475 490
505 520 550
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
59
High Efficiency Compact Housing
Power Supply
This high performance single output compact DIN rail PS-C Series, with up-to-date
circuit design, possess up to 94% of high efficiency and works within 110 ~150% rated
output power for up to 3 seconds.
With built-in active PFC function, PS-C Series is a full range AC input switching power
supply that fulfills the requirement of EN61000-3-2 for harmonic current. The compact
design helps save the precious space on the rail and also makes it up to 50% smaller in
size compare to its predecessor model PS-Series. Meanwhile, PS-C also have 5~9%
higher efficiency than corresponding models of the PS-Series, which response to the
trend of green power with energy saving concept.
Other standard functions include DC OK relay contact, on panel LED indicator, and
protection for short-circuit, overload (constant current limiting, shut down if over 3
seconds), over voltage, and over temperature. To fulfill the requirements of marine and
semi-conductor related usage, PS-C Series also complies with GL and SEMI F47 norms
in addition to UL, CUL and CE certificates. Suitable applications are factory automation,
semi-conductor fabrication equipment, marine related installation, and electromechanical applications.
• Input voltage range:
• AC inrush current (typical):Cold start:
• DC adjustment range (typical):
• Overload protection (typical):
• Overvoltage protection (typical):
• Over temperature protection:
• Withstand voltage:
Working temperature:
Safety standards:
EMC standards:
60
88-264V AC; 124-370V DC
65A at 230V AC (PSC-240)
12V: 12-14V, 24V: 24-28V, 48V: 48-55V,
110%-150% rated output power
14-17V for 12V model (PSW-120),
29-33V for 24V model
56-65V for 48V model
95˚C ± 5˚C (PSC-120/240); 105˚C ± 5˚C
I/P-O/P:3KV AC, I/P-FG:1.5KV AC, O/P-FG:0.5KV AC,
-25 to +70°C (-4° to +158°F),
refer to output derating curve
UL508; EN60950-1 compliant
Compliance to EN55022 class B,
EN61000-4-2,3,4,5,6,8,11, ENV50204,
EN61000-6-2, EN61204-3, heavy Industry level,
SEMI F47, GL
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
PS-C Series
ENERGY
SAVER
Features:
• High efficiency up to 94% and low power dissipation
• Universal AC Input / Full Range
• 150% peak load capability
• Built-in active PFC function, PF>0.93
• Protections: Short circuit / Overload / Overvoltage / Over temperature
• Cooling by free air convection
• Din rail mountable
• LED indicator for power on
• UL 508 (industrial control equipment) approved
• EN61000-6-2(EN50082-2) industrial immunity level
• 100% full load burn-in test
• Built-in DC OK relay contact
• 3 year warranty
35mm DIN Rail
Mounting
Adjustable DC Output Voltage
DC on LED signal
Easy to understand layout panel
Rugged metal housing
CE Compliance
UL508 Compliance
Universal Input
Narrow for maximized
panel space
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
61
120-480W Single Phase
COMPACT SIZE POWER SUPPLIES
ENERGY
SAVER
120W Single Output DIN Rail Power Supply
Cat. No.
Output
V DC
A
Tol.
%
Ripple &
Noise
Efficiency
PS-C12012
12V DC 10A
±1%
100 mVp-p
89%
PS-C12024
24V DC 5A
±1%
100 mVp-p
91%
PS-C12048
48V DC 2.5A
±1%
120 mVp-p
91%
NOTES
240W Single Output DIN Rail Power Supply
Cat. No.
Output
V DC
A
Tol.
%
Ripple &
Noise
Efficiency
PS-C24024
24V DC 10A
±1%
100 mVp-p
94%
PS-C24048
48V DC 5A
±1%
120 mVp-p
94%
NOTES
480W Single Output DIN Rail Power Supply
Cat. No.
Output
V DC
A
Tol.
%
Ripple &
Noise
Efficiency
PS-C48024
24V DC 20A
±1%
100 mVp-p
94%
PS-C48048
48V DC 10A
±1%
120 mVp-p
94%
NOTES
480W Single Output DIN Rail Power Supply
with PFC and Parallel Function (1+7)
Cat. No.
62
Output
V DC
A
Tol.
%
Ripple &
Noise
Efficiency
PS-C480P24
24V DC 20A
±1%
100 mVp-p
94%
PS-C480P48
48V DC 10A
±1%
120 mVp-p
94%
NOTES
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
SPECIFICATIONS
PS-C120 Series
Terminal Pin. No Assign. (TB1)
Pin No.
1
2
3
Terminal Pin. No Assign. (TB2)
Pin No. Assignment
Relay Contact
1,2
DC OUTPUT -V
3
DC OUTPUT +V
4
Assignment
FG
AC/N
AC/L
5.2
12
11
3.5
40
Universal Input: 88-264V AC, 124-370V DC full range,
1.4A/115V AC, 0.7A/230V AC
Connection: Input - 3 poles, Output – 4 poles screw terminal
Size (WxHxD): 40x125.2x113.5mm (1.57x4.93x4.47 inches)
Packaging: 1/box; 1.48lbs / 0.67Kg
PS-C240 Series
Terminal Pin. No Assign. (TB1)
Pin No.
1
2
3
5.2
12
11
3.5
63
Assignment
FG
AC/N
AC/L
Terminal Pin. No Assign. (TB2)
Pin No. Assignment
Relay Contact
1,2
DC OUTPUT -V
3,4
DC OUTPUT +V
5,6
Switch select Input: 88-264V AC, 124-370V DC range,
2.6A/115V AC, 1.3A/230V AC
Connection: Input - 3 poles, Output – 6 poles screw terminal
Size (WxHxD): 63x125.2x113.5mm (2.48x4.93x4.47 inches)
Packaging: 1/box; 2.27lbs / 1.03Kg
PS-C480 Series
Terminal Pin. No Assign. (TB1)
Pin No.
1
2
3
Assignment
FG
AC/N
AC/L
5.2
Terminal Pin. No Assign. (TB2)
Pin No. Assignment
DC OUTPUT +V
1,2
DC OUTPUT -V
3,4
Relay Contact
5,6
NC
7,8
12
For Parallel Model
Terminal Pin. No Assign. (TB1)
12
8.5
.5
85
Pin No.
1
2
3
Assignment
FG
AC/N
AC/L
For Parallel Model
Terminal Pin. No Assign. (TB2)
Pin No. Assignment
1,2
DC OUTPUT +V
DC OUTPUT -V
3,4
Relay Contact
5,6
P+ (current share)*
7
P- (current share)*
8
* Only parallel function.
Universal Input: 90-264V AC, 127-370V DC full range,
5A/115V AC, 2.5A/230V AC
Connection: Input - 3 poles, Output – 12 poles screw terminal
Size (WxHxD): 85.5x125.2x128.5mm (3.37x4.93x5.06 inches)
Packaging: 1/box; 3.53lbs / 1.6Kg
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
63
Features:
PS-C120 Series
• High efficiency 91% and low power dissipation
• 150% peak load capability
• Built-in active PFC function, PF>0.93
• Protections: Short Circuit / Overload / Over Voltage /
Overtemperature
• Cooling by free air convection
• DIN rail mountable
• UL 508 (industrial control equipment) approved
• EN61000-6-2 (EN50082-2) industrial immunity level
• Built-in DC OK relay contact
• 100% full load burn-in test
• 3 year warranty
Specifications
ENERGY
SAVER
OUTPUT
Cat. No.
PS-C12012
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
PEAK CURRENT
PEAK POWER
12V
24V
10A
5A
0 ~ 10A
0 ~ 5A
120W
120W
15A
7.5A
180W (3 sec.)
3 seconds max., please refer to peak loading curves
100mVp-p
100mVp-p
RIPPLE & NOISE (max)
PS-C12024
PS-C12048
48V
2.5A
0 ~ 2.5A
120W
3.75A
120mVp-p
Ripple & noise are measured at 20MHz of bandwidth by using a 12 twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor.
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE
12 ~ 14V
±1.0%
24 ~ 28V
±1.0%
48 ~ 55V
±1.0%
Tolerance: includes set up tolerance, line regulation and load regulation.
INPUT
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
±0.5%
±1.0%
1500ms, 60ms / 230VAC
20ms / 230VAC
88 ~ 264VAC
±0.5%
±1.0%
3000ms, 60ms / 115VAC at full load
20ms / 115VAC at full load
±0.5%
±1.0%
124 ~ 370VDC
Deating may be needed under low input voltages, please check the derating curve for more detail
PROTECTION
FREQUENCY RANGE
POWER FACTOR (Typ.)
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
47 ~ 63Hz
0.93 / 230VAC
0.96 / 115VAC at full load
89%
91%
1.4A / 115VAC
0.7A / 230VAC
35A / 115VAC
70A / 230VAC
≤ 1 mA / 240VAC
OVERLOAD
Normally works within 110 ~ 150% rated output power for more than 3 seconds and then shut
down overvoltage
≥ 150% rated power, constant current limiting with auto-recovery within 3
seconds and shut down overvoltage after 3 seconds
14 ~ 17V
29 ~ 33V
56 ~ 65V
OVERVOLTAGE
90.50%
Protection type: Shut down overvoltage, re-power on to recover
OVERTEMPERATURE
95˚C ± 5˚C (TSW: detect on heat sink of power switch)
Protection type: Shut down overvoltage, re-power automatically after temperature goes down
DC OK RELAY CONTACT RATINGS (max.) 60VDC / 0.3A
ENVIRONMENT
WORKING TEMP.
30VDC / 1A
30VAC / 0.5A RESISTIVE LOAD
-25 ~ +70˚C (Refer to output load derating curve)
Installation clearances: 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded
permanently with full power. In case the adjacent device is a heat source, 15mm clearance is recommended
SAFETY & EMC
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MOUNTING
20 ~ 95% RH non-condensing
-40 ~ +85˚C, 10 ~ 95% RH
±0.03% / ˚C (0 ~ 50˚C)
10 ~ 500Hz, 2G 10min./1cycle, 60 min. each long X,Y, Z axes
Compliance to IEC60068-2-6
SAFETY STANDARDS
UL508
EN60950-1 compliant
I/P-O/P: 3KVAC I/P-FG: 1.5KVAC O/P-FG: 0.5KVAC O/P-DC OK: 0.5KVAC
I/P-O/P, I/P-FG, O/P-FG: ≥100M Ohms/500VDC (25˚C; 70% RH)
Compliance to EN55022 (CISPR22) Class B
Compliance to EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204; EN55024; EN61000-6-2; (EN50082-2);
EN61204-3; heavy industry level; criteria A, SEMI F47, GL approved
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION
HARMONIC CURRENT
EMS IMMUNITY
OTHERS
The power supply is considered a component which will installed into a final equipment. The final equipment must be re-confirmed
that it still meets EMC directives.
MTBF
DIMENSION
PACKING
289.9K hrs min. MIL-HDBK-217K (25˚C)
40x125.2x113.5mm (WxHxD)
0.67Kg; 20pcs / 14.4Kg / 1.16CUFT
All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature.
64
12
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
Mechanical Specification
113. 5
TB2
1
2
3
4
40
+V ADJ.
Assignment
FG
AC/N
AC/L
Assignment
1,2
3
4
TB1
1
2
3
125.2
1
2
3
+
DC OK Relay Contact
age.
Block Diagram
EMI FILTER
&
RECTIFIERS
I/P
RECTIFIERS
&
FILTER
POWER
SWITCHING
PFC
CIRCUIT
+V
-V
O.C.P.
U.V.P.
O.L.P.
FG
DETECTION
CIRCUIT
PWM & PFC
CONTROL
PFC
CONTROL
O.V.P.
Peak Loading
180W
180W
120W
60W
Derating Curve
Output Derating VS Input Voltage
Others
150
100
90
112.5
12V
Others
100
80
70
60
Continuous
75
12V
50
60
40
-25
0
10
20
30
40
50 55 60
70 (VERTICAL)
88
100
110
135
155
230
264
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
65
12
PS-C240 Series
Features:
Specifications
ENERGY
SAVER
OUTPUT
• High efficiency 94% and low power dissipation
• 150% peak load capability
• Built-in active PFC function, PF>0.93
• Protections: Short Circuit / Overload / Over Voltage /
Overtemperature
• Cooling by free air convection
• DIN rail mountable
• UL 508 (industrial control equipment) approved
• EN61000-6-2(EN50082-2) industrial immunity level
• Built-in DC OK relay contact
• 100% full load burn-in test
• 3 year warranty
Cat. No.
PS-C24024
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
PEAK CURRENT
PEAK POWER
24V
48V
10A
5A
0 ~ 10A
0 ~ 5A
240W
240W
15A
7.5A
360W (3 sec.)
3 seconds max., please refer to peak loading curves
100mVp-p
120mVp-p
RIPPLE & NOISE (max)
PS-C24048
Ripple & noise are measured at 20MHz of bandwidth by using a 12 twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor.
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE
24 ~ 28V
±1.0%
48 ~ 55V
±1.0%
Tolerance: includes set up tolerance, line regulation and load regulation.
INPUT
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
±0.5%
±1.0%
1500ms, 60ms / 230VAC
20ms / 230VAC
88 ~ 264VAC
±0.5%
±1.0%
3000ms, 60ms / 115VAC at full load
20ms / 115VAC at full load
124 ~ 370VDC
Deating may be needed under low input voltages, please check the derating curve for more detail
FREQUENCY RANGE
POWER FACTOR (Typ.)
EFFICIENCY (Typ.)
PROTECTION
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVERLOAD
OVERVOLTAGE
47 ~ 63Hz
0.93 / 230VAC
0.99 / 115VAC at full load
94%
After 30 minutes of burn-in.
2.6A / 115VAC
1.3A / 230VAC
33A / 115VAC
65A / 230VAC
≤ 1 mA / 240VAC
Normally works within 110 ~ 150% rated output power for more than 3 seconds and then shut
down overvoltage with auto-recovery
≥ 150% rated power, constant current limiting with autorecovery within 2 seconds and shut down overvoltage after 2 seconds
29 ~ 33V
56 ~ 65V
Protection type: Shut down overvoltage with auto-recovery
OVERTEMPERATURE
95˚C ± 5˚C (TSW: detect on heat sink of power switch)
Protection type: Shut down overvoltage, re-power automatically after temperature goes down
ENVIRONMENT
DC OK RELAY CONTACT RATINGS (max.) 60VDC / 0.3A 30VDC / 1A
30VAC / 0.5A RESISTIVE LOAD
WORKING TEMP.
-25 ~ +70˚C (Refer to output load derating curve)
Installation clearances: 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded
permanently with full power. In case the adjacent device is a heat source, 15mm clearance is recommended.
SAFETY & EMC
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MOUNTING
SAFETY STANDARDS
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION
HARMONIC CURRENT
EMS IMMUNITY
OTHERS
20 ~ 95% RH non-condensing
-40 ~ +85˚C, 10 ~ 95% RH
±0.03% / ˚C (0 ~ 50˚C)
10 ~ 500Hz, 2G 10min./1cycle, 60 min. each long X,Y, Z axes
Compliance to IEC60068-2-6
UL508
EN60950-1 compliant
I/P-O/P: 3KVAC I/P-FG: 1.5KVAC O/P-FG: 0.5KVAC O/P-DC OK: 0.5KVAC
I/P-O/P, I/P-FG, O/P-FG: ≥100M Ohms / 500VDC (25˚C; 70% RH)
Compliance to EN55022 (CISPR22) Class B
Compliance to EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204; EN55024; EN61000-6-2; (EN50082-2),
EN61204-3; heavy industry level; criteria A, SEMI F47, GL approved
The power supply is considered a component which will installed into a final equipment. The final equipment must be
re-confirmed that it still meets EMC directives.
MTBF
DIMENSION
PACKING
169.3K hrs min. MIL-HDBK-217K (25˚C)
63x125.2x113.5mm (WxHxD)
1.03Kg; 12pcs / 13.4Kg / 1.06CUFT
All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature.
66
12
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
113. 5
TB2
1
2
3
4
5
6
Mechanical Specification
1
TB1
3
Assignment
1,2
3,4
5,6
2
Assignment
FG
AC/N
AC/L
1
2
3
+
125.2
+V ADJ.
63
DC OK Relay Contact
age.
Block Diagram
EMI FILTER
&
RECTIFIERS
I/P
RECTIFIERS
&
FILTER
POWER
SWITCHING
PFC
CIRCUIT
+V
-V
O.C.P.
U.V.P.
O.L.P.
FG
DETECTION
CIRCUIT
PWM & PFC
CONTROL
PFC
CONTROL
O.V.P.
Peak Loading
360W
360W
240W
120W
Derating Curve
Output Derating VS Input Voltage
100
150
90
112.5
80
100
70
60
Continuous
75
50
60
40
-25
0
10
20
30
40
50
60
70 (VERTICAL)
88
100
110
135
155
230
264
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
67
12
PS-C480 Series
Features:
• High efficiency 94% and low power dissipation
• 150% peak load capability
• Built-in active PFC function, PF>0.94
• Protections: Short Circuit / Overload / Over Voltage /
Overtemperature
• Cooling by free air convection
• Built-in constant current limiting circuit
• DIN rail mountable
• UL 508(industrial control equipment) approved
• EN61000-6-2(EN50082-2) industrial immunity level
• Built-in DC OK relay contact
• 100% full load burn-in test
• 3 year warranty
Specifications
ENERGY
SAVER
OUTPUT
Cat. No.
PS-C48024
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
PEAK CURRENT
PEAK POWER
24V
48V
20A
10A
0 ~ 20A
0 ~ 10A
480W
480W
30A
15A
720W (3 sec.)
3 seconds peak power max. and the average output power should not exceed the rate power
100mVp-p
120mVp-p
RIPPLE & NOISE (max)
PS-C48048
Ripple & noise are measured at 20MHz of bandwidth by using a 12 twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor.
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE
24 ~ 28V
±1.2%
48 ~ 55V
±1.0%
Tolerance: includes set up tolerance, line regulation and load regulation.
INPUT
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
±0.5%
±0.5%
±1.0%
±1.0%
1500ms, 150ms / 230VAC
3000ms, 150ms / 115VAC at full load
14ms / 230VAC at full load
90 ~ 264VAC
127 ~ 370VDC
Deating may be needed under low input voltages, please check the derating curve for more detail
FREQUENCY RANGE
POWER FACTOR (Typ.)
EFFICIENCY (Typ.)
47 ~ 63Hz
0.94 / 230VAC
94%
0.99 / 115VAC at full load
After 30 minutes of burn-in
PROTECTION
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVERLOAD
OVERVOLTAGE
5A / 115VAC
2.5A / 230VAC
40A / 115VAC
80A / 230VAC
≤ 0.8 mA / 240VAC
Normally works within 110 ~ 150% rated output power for more than 3 seconds and then shut
down overvoltage with auto-recovery
≥ 150% rated power, constant current limiting with auto-recovery within 2 seconds and shut
down overvoltage after 2 seconds
29 ~ 33V
56 ~ 65V
Protection type: Shut down overvoltage with auto-recovery on re-power on to recovery
OVERTEMPERATURE
105˚C ± 5˚C (TSW: detect on heat sink of power switch)
Protection type: Shut down overvoltage, re-power automatically after temperature goes down
ENVIRONMENT
DC OK RELAY CONTACT RATINGS (max.) 60VDC / 0.3A; 30VDC / 1A; 30VAC / 0.5A resistive load
WORKING TEMP.
-25 ~ +70˚C (Refer to output load derating curve)
Installation clearances: 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded
permanently with full power. In case the adjacent device is a heat source, 15mm clearance is recommended.
SAFETY & EMC
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MOUNTING
SAFETY STANDARDS
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION
HARMONIC CURRENT
EMS IMMUNITY
OTHERS
20 ~ 95% RH non-condensing
-40 ~ +85˚C, 10 ~ 95% RH
±0.03% / ˚C (0 ~ 50˚C)
10 ~ 500Hz, 2G 10min./1cycle, 60 min. each long X,Y, Z axes
Compliance to IEC60068-2-6
UL508
EN60950-1 compliant
I/P-O/P: 3KVAC I/P-FG: 1.5KVAC O/P-FG: 0.5KVAC O/P-DC OK: 0.5KVAC
I/P-O/P, I/P-FG, O/P-FG: ≥100M Ohms/500VDC (25˚C; 70% RH)
Compliance to EN55022 (CISPR22) Class B
Compliance to EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204; EN55024; EN61000-6-2; (EN50082-2),
EN61204-3; heavy industry level; criteria A, SEMI F47, GL approved
The power supply is considered a component which will installed into a final equipment. The final equipment must be
re-confirmed that it still meets EMC directives.
MTBF
DIMENSION
PACKING
112.9K hrs min. MIL-HDBK-217K (25˚C)
85.5x125.2x128.5mm (WxHxD)
1.6Kg; 8pcs / 13.8Kg / 0.9CUFT
All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature.
68
12
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
Mechanical Specification
TB2
1
2
3
4
5
6
7
8
128.5
Assignment
1,2
3,4
5,6
7,8
3
TB1
2
+ +V ADJ
NC
1
Assignment
FG
AC/N
AC/L
125.2
1
2
3
85.5
DC OK Relay Contact
age.
Block Diagram
I/P
POWER
SWITCHING
PFC
CIRCUIT
&
RECTIFIERS
RECTIFIERS
&
FILTER
+V
-V
O.C.P.
U.V.P.
O.L.P.
DETECTION
CIRCUIT
FG
PFC
CONTROL
CONTROL
O.V.P.
Peak Loading
720W
720W
480W
240W
Derating Curve
Output Derating VS Input Voltage
100
150
90
120
80
100
70
60
Continuous
80
50
60
40
-25
0
10
20
30
40
50
60
70
(VERTICAL)
90
100
110
135
155
230
264
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
69
12
PS-C480P Series
Features:
• High efficiency 94% and low power dissipation
• 150% peak load capability
• Built-in active PFC function, PF>0.94
• Protections: Short Circuit / Overload / Over Voltage /
Overtemperature
• Cooling by free air convection
• Built-in constant current limiting circuit
• DIN rail mountable
• Current sharing up to 380W (1+7)
• UL 508(industrial control equipment)approved
• EN61000-6-2(EN50082-2) industrial immunity level
• Built-in DC OK relay contact
• 100% full load burn-in test
• 3 year warranty
With Parallel Function
Specifications
ENERGY
SAVER
OUTPUT
Cat. No.
PS-C480P24
PS-C480P48
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
PEAK CURRENT
PEAK POWER
24V
20A
0 ~ 20A
480W
30A
720W (3 sec.)
48V
10A
0 ~ 10A
480W
15A
3 seconds peak power max. and the average output power should not exceed the rate power
RIPPLE & NOISE (max)
100mVp-p
120mVp-p
Ripple & noise are measured at 20MHz of bandwidth by using a 12 twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor.
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE
24 ~ 28V
±1.2%
48 ~ 55V
±1.0%
Tolerance: includes set up tolerance, line regulation and load regulation.
INPUT
LINE REGULATION
LOAD REGULATION
SETUP, RISE, HOLD UP TIME
VOLTAGE RANGE
±0.5%
±1.0%
1500ms, 150ms, 14ms / 230VAC
90 ~ 264VAC
±0.5%
±1.0%
3000ms, 150ms / 115VAC at full load
127 ~ 370VDC
Deating may be needed under low input voltages, please check the derating curve for more detail
FREQUENCY RANGE
POWER FACTOR (Typ.)
EFFICIENCY (Typ.)
47 ~ 63Hz
0.94 / 230VAC
94%
0.99 / 115VAC at full load
After 30 minutes of burn-in.
PROTECTION
AC CURRENT (max.)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
5A / 115VAC
2.5A / 230VAC
40A / 115VAC
80A / 230VAC
≤ 0.6 mA / 240VAC
OVERLOAD
Normally works within 110 ~ 150% rated output power for more than 3 seconds and then shut down
overvoltage with auto-recovery
≥ 150% rated power, constant current limiting with auto-recovery within 2 seconds and shut down
overvoltage after 2 seconds
29 ~ 33V
56 ~ 65V
OVERVOLTAGE
Protection type: Shut down overvoltage with auto-recovery on re-power on to recovery
OVERTEMPERATURE
105˚C ± 5˚C (TSW: detect on heat sink of power switch)
Protection type: Shut down overvoltage, re-power automatically after temperature goes down
ENVIRONMENT
CURRENT SHARING
Please see function diagram
DC OK RELAY CONTACT RATINGS (max.) 60VDC / 0.3A; 30VDC / 1A; 30VAC / 0.5A resistive load
WORKING TEMP.
-25 ~ +70˚C (Refer to output load derating curve)
Installation clearances: 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded
permanently with full power. In case the adjacent device is a heat source, 15mm clearance is recommended.
SAFETY & EMC
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MOUNTING
20 ~ 95% RH non-condensing
-40 ~ +85˚C, 10 ~ 95% RH
±0.03% / ˚C (0 ~ 50˚C)
10 ~ 500Hz, 2G 10min./1cycle, 60 min. each long X,Y, Z axes
Compliance to IEC60068-2-6
SAFETY STANDARDS
UL508
EN60950-1 compliant
I/P-O/P: 3KVAC I/P-FG: 1.5KVAC O/P-FG: 0.5KVAC O/P-DC OK: 0.5KVAC
I/P-O/P, I/P-FG, O/P-FG: ≥100M Ohms/500VDC (25˚C; 70% RH)
Compliance to EN55022 (CISPR22) Class B
Compliance to EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204; EN55024; EN61000-6-2; (EN50082-2),
EN61204-3; heavy industry level; criteria A, SEMI F47, GL approved
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION
HARMONIC CURRENT
EMS IMMUNITY
The power supply is considered a component which will installed into a final equipment. The final equipment must be
re-confirmed that it still meets EMC directives.
OTHERS
MTBF
DIMENSION
PACKING
112.9K hrs min. MIL-HDBK-217K (25˚C)
85.5x125.2x128.5mm (WxHxD)
1.6Kg; 8pcs / 13.8Kg / 0.9CUFT
All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature.
70
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
Mechanical Specification
85.5
Terminal Pin No. Assignment (TB2)
DC OK
Assignment
DC OUTPUT +V
DC OUTPUT -V
Relay Contact
P+ (current share)
P- (current share)
DC OK
TB1
3
+V A D J
1
+
2
Pin No.
1,2
3,4
5,6
7
8
Assignment
FG
AC/N
AC/L
125.2
Terminal Pin No. Assignment (TB1)
Pin No.
1
2
3
TB2
1
2
3
4
5
6
7
8
128.5
DC OK Relay Contact
Peak Loading
(1)
720W
Contact Close
When the output voltage reaches the adjusted output volt age.
Contact Open
When the output voltage drop below 90% output voltage.
Contact Ratings (max.)
30V/1A resistive load
(2)
720W
480W
240W
50 sec.
3 sec.
15 sec. 3 sec.
DC OK
Block Diagram
EMI FILTER
&
RECTIFIERS
I/P
RECTIFIERS
&
FILTER
POWER
SWITCHING
PFC
CIRCUIT
+V
-V
O.C.P.
U.V.P.
O.L.P.
FG
DETECTION
CIRCUIT
PWM & PFC
CONTROL
PFC
CONTROL
O.V.P.
Function Diagram
1. Current sharing
(1)Parallel operation is available by connecting the units shown
as below (P+,P- are connected mutually in parallel):
(2)The voltage difference among each output should be
minimized that less than 2% is required.
(3)The total output current must not exceed the value determined
by the following equation (Output current at parallel operation)
=(The rated current per unit) x (Number of unit) x 0.9.
(4) In parallel operation 8 units is the maximum, please consult
the manufacture for other applications.
(5) When in parallel operation, the minimum output load should
be greater than 3% of total output load.
(Min. load > 3% rated current per unit x number of unit)
+
LOAD
-
+ - DC OK P+ P-
+ - DC OK P+ P-
+ - DC OK P+ P-
+ - DC OK P+ P-
+ - DC OK P+ P-
+ - DC OK P+ P -
+ - DCOK P+ P -
+ - DCOK P+ P -
PSU
PSU
PSU
PSU
PSU
PSU
PSU
PSU
Derating Curve
Output Derating VS Input Voltage
100
150
90
For3 sec. (typ.)
120
80
70
100
60
Continuous
80
50
60
-25
40
0
10
20
30
40
50
60
70 (VERTICAL)
90
100
110
135
155
230
264
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
71
Wide Input Compact Housing
Power Supply
With the PSW family, AC/DC compact DIN rail switching power supplies with single phase
wide input range, Altech further expanded the power supply line. Built-in active PFC
function, these high efficient power units meet the harmonic current limitation per
EN61000-3-2. Equipped with 180 to 550Vac single phase wide input range, they can be
used in general power system applications with single phase 230Vac input or can
capture two phases from the 220~550Vac three-phase power system, which can greatly
increase the flexibility of system deployment.
With up-to-date circuit design PSW series possess up to 93% of extremely high
efficiency and can provide 100% power continuously at 50*C by only free air convection,
or operate under 70*C ambient temperature by suitable power derating. The compact
design in width helps save the precious space on the rail and also makes it up to 50%
smaller in size compare to its predecessor models. Meanwhile, with wider input range
the PSW series also has 3% higher efficiency than corresponding models, which
response to the trend of green power with energy saving concept. Other standard
functions include DC OK relay contact alarm signal output, front panel DC voltage
adjustment , as well as protection for short-circuit, overload (constant current mode, shut
down if over 3 seconds), over voltage, and over temperature. The PSW series comply
with UL508, IEC60950-1 (CB), and CE certificates and also meet the EMC requirements
of heavy industrial immunity level (EN61000-6-2). Suitable applications include industrial
control system, semi-conductor fabrication equipment, factory automation, electromechanical applications, and marine related installation.
• Input voltage range:
180~550V AC; 254-780V DC
• AC inrush current (typical):Cold start: 50A at 400V AC
• DC adjustment range (typical):
12V: 12-15V, 24V: 24-29V, 48V: 48-58V,
• Overload protection (typical):
105%-130% rated output
• Over-voltage protection (typical):
16-18V for 12V model (PSW-120),
31-37V for 24V model; 60-67V for 48V model
• Setup, rise, time (typical):
2000ms, 70ms at full load and 230V AC (PSW-120)
2000ms, 150ms at full load and 230V AC (PSW240/480)
• Withstand voltage:
I/P-O/P:3KV AC, I/P-FG:1.5KV AC, O/P-FG:0.5KV AC,
• Working temperature:
-20 to +70°C (-4° to +158°F),
refer to output derating curve (PSW-120)
• DC OK signal
Relay contact
• Safety standards:
UL508 (PSW-240 pending)
• EMC standards:
Compliance to EN55011 (CISPR11), EN55022 class B,
EN61000-4-2,3,4,5,6,8,11, ENV50204, EN55024,
EN61000-6-2, EN61204-3, heavy Industry Level criteria A
• Military standard:
MIL-HDBK-217K
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
72
12
PSW Series
SAVER
ENERGY
ENERGY
SAVER
•
•
•
•
•
•
•
•
•
•
•
Single and two phase wide input range 180~550VAC
Universal AC Input / Full Range
High efficiency up to 93% and low power dissipation
Protections: Short circuit / Overload / Overvoltage / Over temperature
Cooling by free air convection
DIN rail mountable
UL 508 (industrial control equipment) approved
EN61000-6-2(EN50082-2) industrial immunity level
Built-in DC OK relay contact
100% full load burn-in test
3 year warranty
Multible output connector for
easy wiring
35mm DIN Rail
Mounting
Adjustable DC Output Voltage
DC on LED signal
Easy to understand layout panel
Rugged metal housing
CE Compliance
UL508 Compliance
Universal Input
Narrow for maximized
panel space
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
73
12
120-480W Single Phase
WIDE INPUT POWER SUPPLIES
SAVER
ENERGY
ENERGY
SAVER
120W Single Output DIN Rail Power Supply
Cat. No.
Output
V DC
A
Tol.
%
Ripple &
Noise
Efficiency
PSW-12012
12V DC 10A
±1.5%
120 mVp-p
89.5%
PSW-12024
24V DC 5A
±1%
120 mVp-p
91%
PSW-12048
48V DC 2.5A
±1%
150 mVp-p
92%
NOTES
240W Single Output DIN Rail Power Supply
Cat. No.
Output
V DC
A
Tol.
%
Ripple &
Noise
Efficiency
PSW-24024
24V DC 10A
±1%
120 mVp-p
90%
PSW-24048
48V DC 5A
±1%
120 mVp-p
90%
NOTES
480W Single Output DIN Rail Power Supply
(Also available with Optional Parallel Function (7+1))
Cat. No.
Output
V DC
A
Tol.
%
Ripple &
Noise
Efficiency
PSW-48024
24V DC 20A
±1%
100 mVp-p
94%
PSW-48048
48V DC 10A
±1%
120 mVp-p
94%
NOTES
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
74
12
SPECIFICATIONS
PSW-120 Series
40
113.5
125.2
3 AC/L1
2 AC/L2
1 FG
Pin No. Assignment
4 DC OUTPUT +V
3 DC OUTPUT -V
1,2 Relay Contact
Pin No. Assignment
Terminal Pin. No Assign. (TB1) Terminal Pin. No Assign. (TB2)
Terminal Pin. No Assign. (TB1)
Pin No.
1
2
3
5.2
12
11
3.5
Terminal Pin. No Assign. (TB2)
Pin No. Assignment
Relay Contact
1,2
DC OUTPUT -V
3
DC OUTPUT +V
4
Assignment
FG
AC/L2
AC/L1
Universal Input: 180-550V AC, 254-780V DC full range,
0.55A/400V AC, 1.2A/230V AC
Connection: Input - 3 poles, Output – 4 poles screw terminal
Size (WxHxD): 40x125.2x113.5mm (1.57x4.93x4.47 inches)
Packaging: 1/box; 1.433lbs / 0.65Kg
40
PSW-240 Series
63
113.5
125.2
3 AC/L1
2 AC/L2
1 FG
Pin No. Assignment
5,6 DC OUTPUT +V
3,4 DC OUTPUT -V
1,2 Relay Contact
Pin No. Assignment
Terminal Pin. No Assign. (TB1) Terminal Pin. No Assign. (TB2)
Terminal Pin. No Assign. (TB1)
Pin No.
1
2
3
5.2
12
11
3.5
Terminal Pin. No Assign. (TB2)
Pin No. Assignment
Relay Contact
1,2
DC OUTPUT -V
3,4
DC OUTPUT +V
5,6
Assignment
FG
AC/L2
AC/L1
Universal Input: 180-550V AC, 254-780V DC full range,
1A/400V AC, 2A/230V AC
Connection: Input - 3 poles, Output – 6 poles screw terminal
Size (WxHxD): 63x125.2x113.5mm (2.48x4.93x4.47 inches)
Packaging: 1/box; 2.337lbs / 1.06Kg
63
* Only parallel function.
3 AC/L1
2 AC/L2
1 FG
Pin No. Assignment
Terminal Pin. No Assign. (TB1)
For Parallel Model
3 AC/L
2 AC/N
1 FG
Pin No. Assignment
Terminal Pin. No Assign. (TB1)
PSW-480 Series
85.5
128.5
125.2
5,6 Relay Contact
3,4 DC OUTPUT -V
1,2 DC OUTPUT +V
Pin No. Assignment
Terminal Pin. No Assign. (TB2)
For Parallel Model
5,6 Relay Contact
3,4 DC OUTPUT -V
1,2 DC OUTPUT +V
Pin No. Assignment
Terminal Pin. No Assign. (TB2)
Terminal Pin. No Assign. (TB1)
Pin No.
1
2
3
For Parallel Model
Terminal Pin. No Assign. (TB1)
Pin No.
1
2
3
5.2
12
Assignment
FG
AC/L2
AC/L1
Terminal Pin. No Assign. (TB2)
Pin No. Assignment
DC OUTPUT +V
1,2
DC OUTPUT -V
3,4
Relay Contact
5,6
Assignment
FG
AC/N
AC/L
For Parallel Model
Terminal Pin. No Assign. (TB2)
Pin No. Assignment
1,2
DC OUTPUT +V
DC OUTPUT -V
3,4
Relay Contact
5,6
* Only parallel function.
12
8.5
8
5.5
Universal Input: 180-550V AC, 254-780V DC full range,
1.6A/400V AC, 4A/230V AC
Connection: Input - 3 poles, Output – 12 poles screw terminal
Size (WxHxD): 85.5x125.2x128.5mm (3.37x4.93x5.06 inches)
Packaging: 1/box; 3.748lbs / 1.7Kg
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
75
12
PSW-120 Series
Features:
Specifications
SAVER
ENERGY
ENERGY
SAVER
OUTPUT
OUTPUT
• Single and two phase wide input range 180 ~ 550VAC
• Protections: Short Circuit / Overload / Over Voltage /
Overtemperature
• Cooling by free air convection
• Built-in constant current limiting circuit
• DIN rail mountable
• UL508 (industrial control equipment) approved
• EN61000-6-2 (EN50082-2) industrial immunity level
• 100% full load burn-in test
• Built-in DC OK relay contact
• 3 year warranty
Cat. No.
PSW-12012
PSW-12024
PSW-12048
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
RIPPLE & NOISE (max)
12V
10A
0 ~ 10A
120W
120mVp-p
24V
5A
0 ~ 5A
120W
120mVp-p
48V
2.5A
0 ~ 2.5A
120W
150mVp-p
Ripple & noise are measured at 20MHz of bandwidth by using a 12 twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor.
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE
12 ~ 15V
±1.5%
24 ~ 29V
±1.0%
48 ~ 58V
±1.0%
Tolerance: includes set up tolerance, line regulation and load regulation.
LINE REGULATION
LOAD REGULATION
SETUP, RISE HOLD UP TIME
±0.5%
±0.5%
2000ms, 70ms, 50ms / 400VAC
±0.5%
±0.5%
±0.5%
±0.5%
2000ms, 70ms, 10ms / 230VAC at full load
INPUT
Length of set up time is measured at cold first start. Turning ON/OFF the power supply very quick may lead to increase of the set up time.
INPUT
PROTECTION
PROTECTION
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
AC CURRENT
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVERLOAD
180 ~ 550VAC
254 ~ 780VDC
47 ~ 63Hz
89.5% / 400V
91% / 400V
0.55A / 400VAC
1.2A / 230VAC
COLD START 50A
≤ 3.5 mA / 530VAC
92% / 400V
105 ~ 130% rated output power
Protection type: Constant current limiting, recovers automatically after fault condition is removed
OVERVOLTAGE
16 ~ 18V
31 ~ 37V
60 ~ 67V
Protection type: Shut down overvoltage, re-power on to recover
OVERTEMPERATURE
105˚C ± 5˚C (12V), 110˚C ± 5˚C (24V) (TSW1) detect on heat sink of power switch transistor;
100˚C ± 5˚C (48V) (TSW1) detect on heat sink of power diode
Protection type: Shut down overvoltage, re-power automatically after temperature goes down
ENVIRONMENT
ENVIRONMENT
SAFETY & EMC
SAFETY & EMC
DC OK SIGNNAL
Relay contact rating (max.): 30V / 1A resistive
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
-25 ~ +70˚C (Refer to output load derating curve)
20 ~ 90% RH non-condensing
-40 ~ +85˚C, 10 ~ 95% RH
±0.03% / ˚C (0 ~ 50˚C)
10 ~ 500Hz, 2G 10min./1cycle, 60 min. each long X,Y, Z axes Mounting clip: Compliance to IEC60068-2-6
SAFETY STANDARDS
UL508 approved
IEC60950-1 compliant
WITHSTAND VOLTAGE
I/P-O/P: 3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC O/P-DC OK:0.5KVAC
ISOLATION RESISTANCE
I/P-O/P, I/P-FG, O/P-FG: 100M Ohms/500VDC (25˚C; 70% RH)
EMI CONDUCTION & RADIATION Compliance to EN55011 (CISPR11), EN55022 (CISPR22), EN61204-3 Class B
EMS IMMUNITY
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204; EN61204-3; EN61000-6-2; (EN50082-2),
heavy industry level; criteria A,
OTHERS
The power supply is considered a component which will installed into a final equipment. The final equipment must be
OTHERS
re-confirmed that it still meets EMC directives.
MTBF
DIMENSION
PACKING
268K hrs min. MIL-HDBK-217K (25˚C)
40x125.2x113.5mm (WxHxD)
0.65Kg; 20pcs / 14Kg / 1.16CUFT
All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature.
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
76
-25
0
10
20
30
40
50
60
180
70 (VERTICAL)
190
200
250
290
310360
400
450 490
500
520 550
40
20
50
40
60
12V
60
70
80
80
90
100
Others
100
Derating Curve
Static Characteristics
O.V.P.
CONTROL
PWM
O.L.P.
O.T.P.
LIMIT
CURRENT
FG
I/P
CIRCUIT
DETECTION
FILTER
&
RECTIFIERS
FILTER
EMI
FILTER
&
RECTIFIERS
SWITCHING
POWER
-V
+V
DC OK
Block Diagram
3
2
1
Pin No.
AC/L1
AC/L2
FG
Assignment
TerminalP in No. Assignment (TB1)
4
3
1,2
Pin No.
DC OUTPUT+V
DC OUTPUT -V
Relay Contact
Assignment
TerminalP in No. Assignment (TB2)
2.521
1
2
3
1BT
40
DC OK
+
1
2
3
4
2BT
+V ADJ.
DC OK
113. 5
Mechanical Specification
Mechanical Specification
TB2
1
2
3
4
113. 5
DC OK
+V ADJ.
+
TB1
1
2
3
125.2
DC OK
40
TerminalP inNo. Assignment (TB2)
TerminalP inNo. Assignment (TB1)
PinNo.
1
2
3
PinNo. Assignment
1,2
RelayContact
DC OUTPUT -V
3
DC OUTPUT+V
4
Assignment
FG
AC/L2
AC/L1
Block Diagram
DC OK
RECTIFIERS
&
FILTER
EMI
FILTER
I/P
RECTIFIERS
&
FILTER
POWER
SWITCHING
+V
-V
DETECTION
CIRCUIT
FG
CURRENT
LIMIT
PWM
CONTROL
O.L.P.
O.T.P.
O.V.P.
Derating Curve
Static Characteristics
Others
100
100
90
80
80
12V
60
70
60
40
50
20
-25
40
0
10
20
30
40
50
60
70 (VERTICAL)
180
190
200
250
290
310360
400
450 490
500 520 550
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
77
PSW-240 Series
Specifications
SAVER
ENERGY
ENERGY
SAVER
OUTPUT
OUTPUT
Features:
• Single and two phase wide input range 180~550VAC
• High efficiency 91% and low power dissipation
• Protections: Short Circuit / Overload / Over Voltage /
Overtemperature
• Cooling by free air convection
• DIN rail mountable
• UL 508 (industrial control equipment) approved
• EN61000-6-2 (EN50082-2) industrial immunity level
• Built-in DC OK relay contact
• 100% full load burn-in test
• 3 year warranty
Cat. No.
PSW-24024
PSW-24048
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
RIPPLE & NOISE (max)
24V
10A
0 ~ 10A
240W
150mVp-p
48V
5A
0 ~ 5A
240W
150mVp-p
Ripple & noise are measured at 20MHz of bandwidth by using a 12 twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor.
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE
24 ~ 28V
±1.0%
48 ~ 55V
±1.0%
Tolerance: includes set up tolerance, line regulation and load regulation.
INPUT
INPUT
LINE REGULATION
LOAD REGULATION
SETUP, RISE, HOLD UP TIME
VOLTAGE RANGE
±0.5%
±1.0%
800ms, 150ms, 18ms / 400VAC
180 ~ 550VAC
±0.5%
±1.0%
1500ms, 150ms, 18ms / 230VAC at full load
254 ~ 780VDC
Derating may be needed under low input voltage. Please check the derating curve for more details
PROTECTION
PROTECTION
FREQUENCY RANGE
EFFICIENCY (Typ.)
AC CURRENT
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVERLOAD
47 ~ 63Hz
91%
1A / 400VAC
COLD START 50A
≤ 3.5 mA / 530VAC
2A / 230VAC
105 ~ 130% rated output power
Protection type: Constant current limiting, unit will shut down after 3 sec.; auto recovery after 1 minute if the fault condition is removed
OVERVOLTAGE
29 ~ 33V
56 ~ 65V
Protection type: Shut down overvoltage, re-power on to recovery
Under over-voltage condition, If input voltage ≤ 200VAC, the power supply will shut down and then may have auto-recovery
after several seconds
OVERTEMPERATURE
ENVIRONMENT
ENVIRONMENT
90˚C ± 5˚C (TSW) detect on heat sink of power switch
Protection type: Shut down overvoltage, recovers automatically after temperature goes down
DC OK RELAY CONTACT RATINGS (max.) 60VDC / 0.3A; 30VDC / 1A; 30VAC / 0.5A resistive load
WORKING TEMP.
-30 ~ +70˚C (Refer to output load derating curve)
Installation clearances: 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded
permanently with full power. In case the adjacent device is a heat source, 15mm clearance is recommended.
SAFETY & EMC
SAFETY & EMC
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MOUNTING
20 ~ 95% RH non-condensing
-40 ~ +85˚C; 10 ~ 95% RH
±0.03% / ˚C (0 ~ 50˚C)
10 ~ 500Hz, 2G 10min./1cycle, 60 min. each long X,Y, Z axes
Compliance to IEC60068-2-6
SAFETY STANDARDS
UL508 approved
IEC 60950-1 compliant
Design refer to GL
I/P-O/P: 3KVAC I/P-FG: 1.5KVAC O/P-FG :0.5KVAC O/P-DC OK: 0.5KVAC
I/P-O/P, I/P-FG, O/P-FG: ≥ 100M Ohms / 500VDC (25˚C; 70% RH)
EN55022 (CISPR22), Class B
Compliance to EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204; EN 55024; EN61000-6-2; (EN50082-2);
EN61204-3; heavy industry level; criteria A approved;
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION
HARMONIC CURRENT
EMS IMMUNITY
The power supply is considered a component which will installed into a final equipment. The final
equipment must be re-confirmed that is still meets EMC directives.
OTHERS
OTHERS
MTBF
DIMENSION
PACKING
141.1K hrs min. MIL-HDBK-217K (25˚C)
63x125.2x113.5mm (WxHxD)
1.06Kg; 12pcs / 13.7Kg / 1.06CUFT
All parameters NOT specially mentioned are measured at 400VAC input, rated load and 25˚C of ambient temperature.
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
78
-30
0
10
20
30
40
50
60
180
70(VERTICAL)
200
300
400
450
500
550
40
20
50
40
60
70
60
80
80
90
100
100
Output Derating VS Input Voltage
Derating Curve
DC OK Relay Contact
O.V.P.
CONTROL
PFC
CONTROL
PWM & PFC
FG
U.V.P.
CIRCUIT
DETECTION
O.L.P.
O.C.P.
I/P
RECTIFIERS
&
EMI FILTER
CIRCUIT
PFC
FILTER
&
RECTIFIERS
SWITCHING
POWER
-V
+V
Block Diagram
3
2
1
5,6
3,4
1,2
AC/L1
AC/L2
FG
Assignment
Assignment
3
2
2.521
1
1BT
63
+
1
2
3
4
5
6
2BT
+V ADJ.
Mechanical Specification
113. 5
Mechanical Specification
TB2
1
2
3
4
5
6
113. 5
+
3
2
TB1
1
125.2
+V ADJ.
63
1
2
3
Assignment
FG
AC/L2
AC/L1
Assignment
1,2
3,4
5,6
Block Diagram
I/P
EMI FILTER
&
RECTIFIERS
RECTIFIERS
&
FILTER
POWER
SWITCHING
PFC
CIRCUIT
+V
-V
O.C.P.
U.V.P.
O.L.P.
FG
DETECTION
CIRCUIT
PWM & PFC
CONTROL
PFC
CONTROL
O.V.P.
DC OK Relay Contact
Output Derating VS Input Voltage
Derating Curve
100
100
90
80
80
60
70
60
40
50
20
40
-30
0
10
20
30
40
50
60
70(VERTICAL)
180
200
300
400
450
500
550
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
79
PSW-480 Series
Specifications
SAVER
ENERGY
ENERGY
SAVER
OUTPUT
OUTPUT
Features:
• Single and two phase wide input range 180~550VAC
• High efficiency 93% and low power dissipation
• Protections: Short Circuit / Overload / Over Voltage /
Overtemperature
• Cooling by free air convection
• DIN rail mountable
• UL 508(industrial control equipment) approved
• EN61000-6-2 (EN50082-2) industrial immunity level
• Built-in DC OK relay contact
• 100% full load burn-in test
• 3 year warranty
Cat. No.
PSW-48024
PSW-48048
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
RIPPLE & NOISE (max)
24V
20A
0 ~ 20A
480W
100mVp-p
48V
10A
0 ~ 10A
480W
150mVp-p
Ripple & noise are measured at 20MHz of bandwidth by using a 12 twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor.
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE
24 ~ 28V
±1.0%
48 ~ 55V
±1.0%
Tolerance: includes set up tolerance, line regulation and load regulation.
INPUT
INPUT
LINE REGULATION
LOAD REGULATION
SETUP, RISE, HOLD UP TIME
VOLTAGE RANGE
±0.5%
±1.0%
800ms, 150ms, 18ms / 400VAC
180 ~ 550VAC
±0.5%
±1.0%
2000ms, 150ms, 16ms / 230VAC at full load
254 ~ 780VDC
Derating may be needed under low input voltage. Please check the derating curve for more details
PROTECTION
PROTECTION
FREQUENCY RANGE
EFFICIENCY (Typ.)
AC CURRENT
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVERLOAD
47 ~ 63Hz
92%
1.6A / 400VAC
COLD START 50A
≤ 3.5 mA / 530VAC
93%
4A / 230VAC
105 ~ 130% rated output power
Protection type: Constant current limiting, unit will shut down after 3 sec.; auto recovery after 1 minute if the fault condition is removed
OVERVOLTAGE
29 ~ 33V
56 ~ 65V
Protection type: Shut down overvoltage; auto recovery after 1 minute if the fault condition is removed
Under over-voltage condition, If input voltage ≤ 200VAC, the power supply will shut down and then may have auto-recovery after
several seconds.
OVERTEMPERATURE
95˚C ± 5˚C (TSW) detect on heat sink of power switch
Protection type: Shut down overvoltage, recovers automatically after temperature goes down
ENVIRONMENT
ENVIRONMENT
DC OK RELAY CONTACT RATINGS (max.) 60VDC / 0.3A; 30VDC / 1A; 30VAC / 0.5A resistive load
WORKING TEMP.
-30 ~ +70˚C (Refer to output load derating curve)
Installation clearances: 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded
permanently with full power. In case the adjacent device is a heat source, 15mm clearance is recommended.
SAFETY & EMC
SAFETY & EMC
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MOUNTING
20 ~ 95% RH non-condensing
-40 ~ +85˚C; 10 ~ 95% RH
±0.03% / ˚C (0 ~ 50˚C)
10 ~ 500Hz, 2G 10min./1cycle, 60 min. each long X,Y, Z axes
Compliance to IEC60068-2-6
SAFETY STANDARDS
UL508 approved
IEC 60950-1 compliant
Design refer to GL
I/P-O/P: 3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC O/P-DC OK:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG: 100M Ohms / 500VDC (25˚C; 70% RH)
EN55022 (CISPR22), EN61204-3 Class B
Compliance to EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204; EN 55024; EN61000-6-2; (EN50082-2);
EN61204-3; heavy industry level; criteria A approved;
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION
HARMONIC CURRENT
EMS IMMUNITY
The power supply is considered a component which will installed into a final equipment. The final equipment must be
re-confirmed that is still meets EMC directives.
OTHERS
OTHERS
MTBF
DIMENSION
PACKING
112.8K hrs min. MIL-HDBK-217K (25˚C)
85.5x125.2x128.5mm (WxHxD)
1.7Kg; 8pcs / 14.6Kg / 0.9CUFT
All parameters NOT specially mentioned are measured at 400VAC input, rated load and 25˚C of ambient temperature.
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
80
-30
0
10
20
30
40
50
60
70
180
(VERTICAL)
200
300
400
450
500
550
40
20
50
40
60
70
60
80
80
90
100
100
Output Derating VS Input Voltage
Derating Curve
DC OK Relay Contact
O.V.P.
CONTROL
PFC
CONTROL
PWM & PFC
CIRCUIT
DETECTION
FG
U.V.P.
O.L.P.
O.C.P.
I/P
RECTIFIERS
&
EMI FILTER
CIRCUIT
PFC
FILTER
&
RECTIFIERS
SWITCHING
POWER
-V
+V
Block Diagram
3
2
1
AC/L1
AC/L2
FG
Assignment
5,6
3,4
1,2
Assignment
3
2
1
1BT
85.5
1
2
3
4
5
6
2BT
2.521
+ +V ADJ
Mechanical Specification
128.5
Mechanical Specification
125.2
TB2
1
2
3
4
5
6
128.5
3
2
TB1
1
+ +V ADJ
85.5
1
2
3
Assignment
Assignment
FG
AC/L2
AC/L1
1,2
3,4
5,6
Block Diagram
EMI FILTER
&
RECTIFIERS
I/P
RECTIFIERS
&
FILTER
POWER
SWITCHING
PFC
CIRCUIT
+V
-V
O.C.P.
U.V.P.
O.L.P.
DETECTION
CIRCUIT
FG
PWM & PFC
CONTROL
PFC
CONTROL
O.V.P.
DC OK Relay Contact
Output Derating VS Input Voltage
Derating Curve
100
100
90
80
80
60
70
60
40
50
20
40
-30
0
10
20
30
40
50
60
70 (VERTICAL)
180
200
300
400
450
500
550
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
81
Accessories
Power Supply Redundancy Buffer Module
PS-RDN20 is a 20A redundancy (decoupling) module for the 24V DC power system. Containing 2
sets of 20A Or-ing diodes with wonderful heat dissipation deployment, PS-RDN20 give you a new
option for safe connection of 1+1 redundant set-up. Not only perfectly decouple power sources
from each other as well as from the load, PS-RDN20 also provides users monitoring signals for
both input channels through the built-in relays. Since there’s no switching components inside the
module, PS-RDN20 will not arise additional EMI issues and should provide you a worry-free
application platform!
DC input voltage range
Reverse voltage
DC output current
DC output voltage drop
Input voltage alarm
Relay contact rating
Working Temperature
EMC standards
Connection
21~28V, 20A max. x 2 channels
30V
20A max.
0.5V max.
When input is > 20V(±5%) or <30V(±5%), relay contacts
30VDC, 1A
-20~+70°C
EN55022 class B, EN61000-4-2,3,4,5,6,8, ENV50204
I/P: 4 poles, O/P: 2 poles screw DIN terminal,
Single output: 4 poles
UPS Battery Module
PS-UPS40 is a 40A max. DC UPS (battery control) module for the 24 V DC power system.
Accompany with external batteries, it can back-up up to 40A of current to critical loads for
certain period of time depending on the capacity of batteries. With complete monitoring signals
and LED indicators for DC BUS OK, Battery Fail, Battery Discharge and the repeated Battery Test
function to check the situation of external batteries. Users can customize their own DC UPS
system to back up critical loads and capture the status of the whole system easily.
DC input / DC bus
Battery inout voltage
Battery input current
Charge current (typ.)
External battery (typ.)
DC bus ok
Battery fail
Battery discharge
Working temperature
EMC standards
Connection
82
24~29V, 40A max.
21~29V
0~40A
2A
24V, 4AH / 7AH / 12AH
Relay status: Short when DC voltage between 21~29V(±3%),
relay contacts
Relay status: Short when battery failure is observed through the
battery test function, relay contacts
LED (red): Battery over-discharge warning or battery broken: light;
battery OK: dark
Relay status: Short when battery in discharge condition,
relay contacts
LED (yellow): Battery discharging: light; battery is not discharging
or discharging current <2A: dark
-20~+70°C
EN55022 class B, EN61000-4-2,3,4,5,6,8, ENV50204
I/P: 2 poles, O/P: 2 poles screw DIN terminal, Single output: 6 poles
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
Redundancy Buffer Module
UPS Battery Module
Redundancy Buffer Module Features:
• Suitable for redundant operation of 24V system
• Installed on 35 x 7.5 mm or 35 x 15 mm DIN Rail
• Relay contact signal output and LED indicator for input failure alarm
• Cooling by free air convection
• 3 year warranty
UPS Battery Module Features:
• Battery controller for DIN Rail UPS system
• Installed on 35 x 7.5 mm or 35 x 15 mm DIN Rail
• Parallel connection to DC BUS
• Suitable for 24V system up to 40A
• Built-in battery test function
• Battery polarity protection
• Relay contact signal output and LED indicator for DC BUS OK, battery fail
and battery discharge
• Cooling by free air convection
• 3 year warranty
35mm DIN Rail
mounting
Alarm A and B
Relay Contact
LED indicator for input
failure alarm
(or DC BUS OK)
Easy to understand
layout panel
CE Compliance
Input Terminals
Rugged metal housing
Narrow for maximized
panel space
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
83
Accessories
• REDUNDANCY BUFFER MODULE
• UPS MODULE
Power Supply Redundancy Buffer Module
PS-RDN20 is a 20A redundancy (decoupling) module for the 24V DC power system.
Containing 2 sets of 20A Oring diodes with excellent heat dissipation deployment. PSRDN20 give you a new option for safe connection of 1+1 redundant set-up. Not only
perfectly decouple power sources from each other as well as from the load, PS-RDN20
also provides users monitoring signals for both input channels through the built-in
relays. Since there’s no switching components inside the module, PS-RDN20 will not
arise additional EMI issues and should provide you a worry-free application platform!
Cat. No.
Voltage Range
Current Range
PS-RDN20
21-28V DC
0-20A
NOTES
Connection: Terminal 1 - 4 poles, Terminal 2 - 6 poles
Size (WxHxD): 55.5x125x100mm (2.19x4.95x3.95 inches)
Packaging: 1/box; 1.1lbs / 0.5Kg
DC Fail Block Diagram
40 AMP UPS Battery Controller
PS-UPS40 is a 40A max. DC UPS (battery control) module for the 24 V DC power
system. Accompany with external batteries, it can back-up up to 40A of current to
critical loads for certain period of time depending on the capacity of batteries. With
complete monitoring signals and LED indicators for DC BUS OK, Battery Fail, Battery
Discharge and the repeated Battery Test function to check the situation of external
batteries. Users can customize their own DC UPS system to back up critical loads and
capture the status of the whole system easily.
Cat. No.
Voltage Range
PS-UPS40
21-29V (Battery)
24-29V (DC)
Current Range
NOTES
0 - 40A
Connection: Terminal 1 - 4 poles, Terminal 2 - 6 poles
Size (WxHxD): 55.5x125x100mm (2.19x4.95x3.95 inches)
Packaging: 1/box; 1.21lbs / 0.55Kg
84
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
SPECIFICATIONS
12
Terminal Pin. No Assign. (TB1)
Assignment
Vout+
1
Vout2
Vin3,4
5
Vin A+
6
5.2
Derating Curve
100
80
LOAD (%)
PS-RDN20 Series
Terminal Pin. No Assign. (TB2)
60
40
Assignment
10
0
1
2
3
4
5.5
5
20
Alarm A1
Alarm A2
-10
0
10
20
30
40
50
60
Applications:
PS U
PSU
70 (VERTICAL)
AMBIENT TEMPERATURE (°C)
PSU
PS U
PS U
PS U
PS U
PSU
..............
Vin A
PS U
PSU
Vin A
Vin A
Vin A
Vin A
Vout
Vout
Vout
Vout
Vout
Vout
Load
Load
Load
PS-UPS40 Series
Terminal Pin. No Assign. (TB1)
Assignment
BATTERY INPUT +
BATTERY INPUT -
1
2
3
4
100
80
LOAD (%)
12
Derating Curve
Terminal Pin. No Assign. (TB2)
5.2
Assignment
10
0
1
2
3
4
5
6
.5
55
-10
0
10
20
30
40
50
60
70 (VERTICAL)
AMBIENT TEMPERATURE (°C)
2. Combine redundancy module (PS-RDN20) to back up AC interruption or failure of PSU
PS-UPS40
PS-UPS40
PSU
24V/40Amax
BAT
+ -
40
20
1. Backup connection for AC interruption
24V
Battery
60
Load
PS-RDN20
24V
Battery
DC
- +
PSU
BAT
DC
- - +
+
Vout
Load
Vin
+ - - - B+ A+
-
+
+
-
+
-
-
+
+
-
-
+
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
85
PS-RDN20
Features:
Specifications
OUTPUT
• Suitable for redundant operation of 24V system
• Installed on DIN Rail TS35 / 7.5 or 15
• Relay contact signal output and LED indicator for input
failure alarm
• Cooling by free air convection
• 3 year warranty
Cat. No.
PS-RDN20
REVERSE VOLTAGE (max.)
OUTPUT CURRENT (max.)
VOLTAGE DROP
LED INDICATORS
30V
20A
0.5V
Two green LED’s indicating each input is OK or fail
INPUT VOLTAGE RANGE
NUMBER OF INPUTS
INPUT CURRENT (max.)
21 ~ 28V
Two
20A per input
INPUT VOLTAGE ALARM
RELAY CONTACT RATING (max.)
When input is ≥ 20V (±5%) or ≤ 30V (±5%) relay contacts
30VDC, 1A
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
VIBRATION
MOUNTING
-20 ~ +70˚C
20 ~ 90% RH non-condensing
-40 ~ +85˚C, 10 ~ 95% RH
10 ~ 500Hz, 2G 10min./1cycle, 60 min. each long X,Y, Z axes
Compliance to IEC60068-2-6
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION
EMS IMMUNITY
Terminal- Chassis: 0.5KVAC, Relay Contacts- Terminal: 0.5KVAC
Terminal- Chassis: ≥100M Ohms / 500VDC (25˚C; 70% RH)
Compliance to EN55022 (CISPR22) Class B
Compliance to EN61000-4-2,3,4,5,6,8; ENV50204; heavy industry level; criteria A,
MTBF
DIMENSION
PACKING
996.8Khrs min. MIL-HDBK-217K (25˚C)
55.5x125.2x100mm (WxHxD)
0.5Kg; 20pcs / 11Kg / 1.29CUFT
INPUT
FUNCTION
ENVIRONMENT
SAFETY & EMC
OTHERS
All parameters NOT specially mentioned are measured at 24V DC input, rated load and 25˚C of ambient temperature.
86
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
Mechanical Specification
TB2
1
2
3
4
5
6
TB1
125.2
LED
1
2
3
4
100
55. 5
Terminal Pin. No Assignment (TB1)
Pin No. Assignment
Vout+
1
Vout2
Vin3,4
5
Vin B+
Vin A+
6
Terminal Pin. No Assignment (TB2)
Pin No. Assignment
Alarm B1
1
Alarm B2
2
Alarm A1
3
Alarm A2
4
Block Diagram
Vout+
+
RELAY
B
Vin/Vout-
+
RELAY
A
Alarm A
Vin A+
Derating Curve
100
80
60
40
20
-20
0
10
20
30
45
50
60
70
(VERTICAL)
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
87
PS-UPS40
Specifications
DC INPUT /
DC BUS
BATTERY
IN / OUTPUT
FUNCTION
Features:
• Battery controller for DIN Rail UPS system
• Parallel connection to DC BUS
• Suitable for 24V system up to 40A
• Installed on DIN Rail TS35/ 7.5 or 15
• Built-in battery test function
• Battery polarity protection
• Relay contact signal output and LED indicator for DC BUS OK,
• Battery fail, and battery discharge
• Cooling by free air convection
• 3 year warranty
Cat. No.
PS-UPS40
DC VOLTAGE (Typ.)
RATED CURRENT
24 ~ 29V
40A
VOLTAGE RANGE (Typ.)
CURRENT RANGE
CHARGE CURRENT (Typ.)
EXTERNAL BATTERY (Typ.)
21 ~ 29V
0 ~ 40A
2A
4 / 7 / 12AH / 24V
RELAY CONTACT RATING (max.)
DC BUS OK
30VDC, 1A
Relay contact: Short when DC voltage between 21 ~ 29V (±3%), relay contacts
LED (Green): DC BUS OK: light; DC BUS fail: dark
Relay contact: Short when battery failure is observed through the battery test function, relay contacts
LED (Red): Battery over- discharge warning or battery broken: light; Battery OK: dark
BATTERY FAIL
Every 25 seconds, unit will send out test signal through Battery Fail relay contact and LED indicator
once the battery is fail.
ENVIRONMENT
BATTERY DISCHARGE
Relay contact: Short when battery in discharge condition, relay contacts
LED (Yellow): Battery discharging: light; Battery is not discharging or discharging current ≤2.0A: dark
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
VIBRATION
MOUNTING
-20 ~ +70˚C
20 ~ 90% RH
-20 ~ +85˚C, 10 ~ 95% RH
10 ~ 500Hz, 2G 10min./1cycle, 60 min. each long X,Y, Z axes
Compliance to IEC60068-2-6
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION
EMS IMMUNITY
Terminal- Chassis: 0.5KVAC, Relay Contacts- Terminal: 0.5KVAC
Terminal- Chassis: ≥100M Ohms / 500VDC (25˚C; 70% RH)
Compliance to EN55022 (CISPR22) Class B
Compliance to EN61000-4-2,3,4,5,6,8; ENV50204; heavy industry level; criteria A
MTBF
DIMENSION
PACKING
161.9Khrs min. MIL-HDBK-217K (25˚C)
55.5x125.2x100mm (WxHxD)
0.55Kg; 20pcs / 12Kg / 1.29CUFT
SAFETY & EMC
OTHERS
All parameters NOT specially mentioned are measured at rated load and 25˚C of ambient temperature.
88
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
Mechanical Specification
100
4
3
2
1
TB1
125.2
LED
TB2
1
2
3
4
5
6
55. 5
Terminal Pin. No Assignment (TB1)
Pin No. Assignment
BATTERY INPUT +
1
BATTERY INPUT 2
3
DC INPUT 4
DC INPUT +
Terminal Pin. No Assignment (TB2)
Pin No. Assignment
BAT DISC 1
1
BAT DISC 2
2
BAT OK 1
3
BAT OK 2
4
DC OK 1
5
DC OK 2
6
Block Diagram
25Ax2
LOAD
+
+
BAT.
TEST
CHARGE
CIRCUIT
LIMIT
INPUT
POWER
SUPPLY
24V
BATTERY
DETECTION
CIRCUIT
DISCHARGE
Derating Curve
100
80
60
40
20
-20
0
10
20
30
45
50
60
70
(VERTICAL)
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
89
Accessories
POWER SUPPLIES
DIN MOUNTING RAILS
Altech DIN Rails comply with DIN 50045, 50022 and 50035 Standards. The use of DIN Rails
enhances design capabilities, saves space and reduces labor.
Standard rails are made of steel with zinc plating and chromate passivation and are available in
various configurations.
DIN Rails are 35mm wide and available in 7.5 and 15mm depths. They are supplied in 1 m (3'3")
and 2 m (6’6) lengths. Upon request they can be cut to custom lengths and punched with holes or
perforations.
DIN35
DIN35
(15 mm deep)
(7.5 mm deep)
Type
Cat. No.
Perforated Steel
2511120
2511120/1M
2m
1m
Unperforated
Steel
2511110
2511110/1M
2m
1m
Type
Cat. No.
20
40
Perforated Steel
CA701-15/S-2M
CA701-15/S
2m
1m
12
24
20
40
Unperforated
Steel
CA701-15-2M
CA701-15
2m
1m
12
24
Length Std. Pk.
Length Std. Pk.
SUPPORT BRACKETS
Support Brackets elevate DIN Rails away from the panel to facilitate component mounting and to
increase wiring access. Angled brackets tilt the rail by 45° to improve visibility. Straight brackets
are available in three heights for optimum positioning of the rail.
Brackets mount with 2 screws to any panel or flat surface and have tapped center holes for rail
mounting. Bracket material is steel, zinc plated yellow chromate.
DIN35
DIN35
Cat. No.
CA603
90
Std. Pk.
25
Height
Cat. No.
Std. Pk.
1
2
3
CA703
CA803
CA903
25
25
25
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
END STOPS and SPACER
End Stops prevent power supplies and other DIN Rail mount
components and devices from moving laterally on the rail. They are
available in polyamide 6.6 and metal configurations for 35mm DIN rails.
CA802 is a small endstop for the smaller power supplies.
CA202 is a large endstop for larger power supplies.
CA202
CA802
CA302 is used with 7.5mm deep DIN rail and the CA402 is used with
15mm deep rail.
DIN Rail mountable spacers (CASP and 15.960) are generally used to
ensure cooling space for the small power supply.
CA302
CASP
CA402
15.960
Polyamide 6.6
Polyamide 6.6
Steel
Steel
Polyamide 6.6
Polyamide 6.6
44.5 x 50 x 9.5 mm
32 x 45 x 8 mm
27 x 39.5 x 16 mm
27 x 39.5 x 16 mm
29 x 43 x 8 mm
69 x 55 x 9 mm
Cat. No.
CA202
Cat. No.
CA802
Cat. No.
CA302
Cat. No.
CA402
Cat. No.
CASP
Std. Pk.
50
Std. Pk.
50
Std. Pk.
50
Std. Pk.
50
Std. Pk.
50
Cat. No.
15.960
Std. Pk.
10
GROUND BLOCKS for DIN Rail
Use ground blocks instead of grounding studs and wire lugs to terminate ground wires, saving installation and wiring time.
Ground blocks clamp mechanically onto the DIN Rail by tightening the center mounting screw, making a reliable electrical connection between the cage clamp
terminals and the DIN Rail. The rail serves as a busbar and automatically distributes ground potential to all other ground terminals on the same rail.
Ground blocks can also be used as end
stops, preventing other terminal blocks
and components from moving laterally
on the DIN Rail.
CGT4N
CGT6N
CGT10U
They are supplied with a standard
green/yellow housing for easy
identification.
AEx eII EEx eII
Terminal Width
6 mm
8 mm
10 mm
Height x Length
45.4 x 54.2 mm
47 x 54.5 mm
49.5 x 45 mm
Stripping Length
9 mm
12 mm
12 mm
Insulation Material
Polyamide 6.6
Polyamide 6.6
Polyamide 6.6
Type of Connection
2 screw clamps
2 screw clamps
2 screw clamps
Approvals
C
US
C
US
Wire Range
22-10 AWG 0.5-4 sq.mm 22-10 AWG
22-8 AWG
Torque
7 lb-in
14 lb-in
0.8 Nm
7 lb-in
C
1.5-6 sq.mm
22-8 AWG
0.8 Nm
14 lb-in
US
22-6 AWG 1.5-10 sq.mm 16-8 AWG
14 lb-in
1.2 Nm
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
14 lb-in
91
Frequently Asked Questions
Notes on choosing a switching power supply?
• To increase the reliability of the switching power supply, we suggest users choose a unit that has a rating of
30% more power than actual need. For example, if the system needs a 90W source, we suggest that users choose
a switching power supply with 120W of output power or more. By doing this, you can effectively boost the reliability
of the switching power supply in your system.
• We also need to consider about ambient temperature of the switching power supply and whether there is
additional device for dissipating the heat. If the switching power supply is working in a high temperature
environment, we need to make some derating to the output power. The derating curve of "ambient temperature"
versus "output power" can be found on our spec sheets.
• Choosing functions based on your application:
• Protection function:
• Overvoltage Protection (OVP)
• Overtemperature Protection (OTP)
• Overload Protection (OLP)
• Short Circuit Protection (SCP)
• Application function:
• Signaling Function (Power Good, Power Fail)
• DC OK Signal
• Special function:
• Power Factor Correction (PFC)
• Uninterruptible Power Supply (UPS) function
• Pick Load Capability
• Make sure that the model qualifies for the safety standards and EMC regulations you need.
How do we choose a power supply to charge a battery?
ALTECH does not have power supplies designed for battery charging. If you like to choose a Power Supply as a
battery charger, our advice is to pick a power supply with over load protection (OLP) which mode is constant
current limiting. The models in this mode provide constant current even when the protection circuit is triggered.
The second choice is fold-back current limiting or constant wattage model. In this model, when a battery is running
low, the output current of the power supply will gently increase. The level of increase depends on battery's
capacity and degree of exhaustion.
Hiccup or shut down model are not recommended because it will stop to generate current when OLP happens.
Does Altech carry class 2 power supplies?
Selected models of the Altech slim line series (PS-S…) is NEC class 2 / LPS compliant, but they are not UL1310
tested. More information can be found on the individual specification sheets.
Can ALTECH's power supply be used in the range of 45Hz ~ 440Hz? If YES, what will happen?
ALTECH's power supply can be used within this frequency range. But if the frequency is too low, the efficiency will
also be lower. For example, when a PS-12024 is operated under 230VAC and rated load, if the frequency of AC
input is 60 Hz, the efficiency is around 84%; however, if the frequency of AC input reduces to 50 Hz, the efficiency
will be around 83.8%. If the frequency is too high, the power factor of the switching power supply with PFC (power
factor correction) function will reduce and this also will cause higher leakage current. For example, when a PS12024 is operated under 230VAC and rated load, if the frequency of AC input is 60 Hz, the power factor is 0.93
and the leakage current is around 0.7mA; however, if the frequency of AC input increase to 440 Hz, the power
factor will decrease to 0.75 and the leakage current will rise to around 4.3mA.
If we need a 24V output power supply, but ALTECH does not have this model, can we use two 12V power
supplies connecting in series instead of one 24V power supply?
YES, basically you can do this to get the right output voltage, but be careful that the rated output current of the
series system should be the rating of the minimum one in these series connected power supplies. Furthermore,
we like you to parallel a diode at the output of power supply to prevent possible damage of internal capacitors.
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
92
Why I cannot turn on the power supply smoothly when the loads are motors, light bulbs or capacitive loads?
If you connect the switching power supply to motors, light bulbs, or high capacitive loads, you will have a high output surge current when you turn on the
S.P.S. and this high surge current will cause failure of start up. We suggest using switching power supply with over load protection and constant current limiting
protection to deal with these loads.
Why did the power supply shuts down during operation and after turning it off, I can restart the power supply again?
In general there are two circumstances that will cause the power supply to shut down. The first one is the activation of the over-load-protection (OLP). To deal
with this situation, we suggest increasing the rating of the output power or modifying the OLP point. The second one is the activation of over-temperature
protection (OTP) when the internal temperature reaches the pre-set value. All of these conditions will let the switching power supply enter protection mode
and shut down. After these conditions are removed, the switching power supply will be back to normal.
The output ground (GND) and frame ground (FG) is the same point in my system, can ALTECH's power supplies be used in such system?
Yes. Since our products are designed based on isolation concept, it will be no problem that the output ground (GND) and frame ground (FG) is the same point
in your system. But, EMI may be affect by this connection.
During the operation of ALTECH power supply, there is some leakage current on the case. Is this normal? Will this leakage current hurt human body?
Due to the requirement of EMI, there will be some Y capacitors between line and neutral to the FG (case) to improve EMC. These Y capacitors will cause some
leakage current flow from line or neutral to the case (normally case will be connected to earth ground). For example, IEC-60950-1 requires that this current
should be less than 3.5mA for IT equipment, so basically the leakage current you find on the case will not hurt human body. Proper connection to Earth ground
will solve the leakage current problem.
What should be noticed when installing a power supply in vertical and horizontal directions?
Most small wattage power supplies are mainly installed in the horizontal position. If you have to install it vertically because of mechanical limitation, you should
consider the output derating due to the heat concern. The temperature derating curve can be found on the spec sheet.
What is "Input - Inrush Current"? What will we notice?
At input side, there will be (1/2 ~1 cycle, ex. 1/120 ~ 1/60 seconds for 60 Hz AC source) large pulse current (20~60A based on the design of S.P.S.) at the
moment of power on and then back to normal rating. This "Inrush Current" will appear every time you turn on the power. Although it will not damage the power
supply, we suggest not turning the power supply ON/OFF very quickly within a short time. Besides, if there are several power supplies turning on at the same
time, the circuit breaker of AC source may shut off and go into protection mode because of the huge inrush current. It is suggested that these power supplies
start up one by one if possible.
What is PFC?
PFC stands for Power Factor Correction. The purpose of PFC is to improve the ratio of apparent power and real power. The power factor is only 0.4~0.6 in
non-PFC models. In PFC models, the power factor can reach above 0.95. The calculation formulas are as below:
Apparent Power=Input Voltage x Input Current (VA)
Real Power= Input Voltage x Input Current x Power Factor (W)
From the environment friendly point, the electric power plant needs to generate a power which is higher than apparent power in order to steadily provide
electricity to the market. The real usage of electricity should be defined by real power. Assuming the power factor is 0.5, the power plant needs to produce
more than 2VA to satisfy 1W real power. On the contrary, if the power factor is 0.95, the power plant only needs to generate more than 1.06VA to provide 1W
real power need. It will be more effective.
What is the difference between -V, +V and COM which are marked on the output side? COM(COMMON) means common ground.
Single output: Positive pole (+V), Negative pole (-V)
+V; COM and –V can be attained by using two switching power supplies in series. Example: (2x PS-S2012)
+ –
+
–
In ALTECH's catalog, we see AC and DC at input, what is it all about?
Due to different circuit designs, ALTECH power supply's input consists of three types as below:
(√2=1,414 → 1.414 x AC = DC)
+12V
COM
-12V
A.85~264VAC;120~370VDC
B.176~264VAC;250~370VDC
C.85~132VAC/176~264VAC by Switch; 250~370VDC
• In the case of option A and B inputs models, power supply can work properly no matter under AC or DC input. Some models need correct connection of
input poles, positive pole connects to AC/L; negative pole connects to AC/N. Others may require opposite connection, positive pole to AC/N; negative
pole to AC/L. If customers make a wrong connection, the power supply will not be broken. You can just reverse the input poles and power supply will
still work.
• In the case of option C input models, please make sure that you switch the 115/230V input correctly. If the switch is on the 115V side and the real
input is 230V, the power supply will be damaged.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
93
Frequently Asked Questions
Why the input voltage marked on the spec. sheet is 88~264 VAC while the label on the power supply says
that it is 100~240VAC?
During safety verification process, the agency will use a stricter standard -- ±10%(IEC60950 uses +6%, -10%) of
the input voltage range labeled on the power supply to conduct the test. So, operating at the wider input voltage
range as specified on the spec. sheet should be fine. The narrower range of input voltage labeled on the power
supply is to fulfill the test standard of safety regulation and make sure that users insert input voltage correctly.
Will ALTECH’s products with CE marking meet the EMC requirements after assembling into my system?
We cannot guarantee 100% that the final system can still meet the EMC requirements. The location, wiring and
grounding of the switching power supply in the system may influence its EMC characteristics. In different
environment or applications, the same switching power supply may have different outcomes. Our test results are
based on setup shown in the EMC report.
What is different between information (EN60950-1) and medical (EN60601-1) safety standard?
According to safety standard, the leakage current in EN60950-1 Class I cannot exceed 3.5mA. Many of ALTECH’s
power supplies meet this requirement but may not meet the EN60601-1. Others criteria like safe distance and
numbers of fuse are also different. Please consult the diagram below:
Subjects
Creepage distance/
Clearance distance
Working Voltage:
Max. 250Vrms
Electric Strength Test
IEC60950-1
IEC60601-1
Basic Insulation
2.5mm/2mm
4mm/2.5mm
Supplementary
Insulation
5mm/4mm
8mm/5mm
Basic Insulation
1500Vac
1500Vac
Supplementary
Insulation
3000Vac
4000Vac
Handheld: 0.75mA
—
Leakage current
of grounding
0.3mA
Leakage current
of grounding
0.1mA
0.25mA
Leakage current
of grounding
0.1mA
Number of Fuse
1
2
The Lowest Ambient Temperature
Refer to the definition
of Manufacturer
40°C
CLASS I
Leakage Current
CLASS II
Others: 3.5mA
What is MTBF? Is it different from Life Cycle?
MTBF and Life Cycle are both indicators of reliability. Altech uses MIL-HDBK-217F as the core of MTBF. An expected
reliability is forecasted through accounting component's number. The exact meaning of MTBF is after continuously using
of power supply in a certain time, the probability of operating properly is 36.8%(e-1=0.368). If power supply is
continuously used at double the MTBF time, the probability of operating properly becomes 13.5%(e-2=0.135).
Life Cycle is found through using the temperature rise of electrolytic capacitor to estimate the approximate life of power
supply. For example, PS-S10 series MTBF=584K hours; electrolytic capacitor C108 Life Cycle=202K hours (Ta=45° C).
POWER SUPPLY LEGAL DISCLAIMER
Power supply data sheet specifies devices but can not promise to deliver any specific characteristics. No warranty or
guaranty is given regarding performance or suitability. The customer shall test and ensure that each power supply would
work for the anticipated use. Altech Corp. reserves the right to make modification to its power supply data sheets or
specifications at any time without prior notice. Please visit www.altechcorp.com/power for more information.
94
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
Selection Guide
SIG = DC OK signal
X* = selected items, see data sheet
X
X
PS-C480Pxx
X
PS-C480xx
X
PS-C240xx
X
PS-C120xx
X
X
PST-960Pxx
X
PST-960xx
X
PST-480xx
X
PST-240xx
X
PSP-480Sxx
X
PSP-480xx
X
PSP-240xx
X
PSH-120xx
X
PS-120xx
X
PS-75xx
X
X
PS-100xx
PS-60xx
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
5
X
WR
X
WR
X
WR
X
X
X
X
X
X
X
X
X
X
X
X
15 24
X
X
X
X
X
X
X
X
X
X DBO
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
V
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
48
X
X
X
TP
TP
X
X
X
X
X
TP
TP
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
12
Output voltage
X
X
X
X
X*
X
X
X*
X
X
X*
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
SIG
X
X
X
X
X
X
X
X
X
X
X
SIG
X
X
X
X
X
Output voltage
U
ni
ve
r
Sw sal
itc Inp
u
h
U
Se t
L
50 lec
U 8 L t In
L
60 iste put
d
N 950
EC
-1
C Cla Rec
E
.
m ss
ar 2 C
R
k
oh
ed om
s
pl
R Co
ia
ea
nt
m
ch p
l
i
D
a
C Co nt
m
O
pl
Sh K
ia
nt
or
t
O Cir
ve
c
rlo uit
a
O
ve d
r
O Vol
ve ta
ge
r
EM Tem
pe
C
ra
C
tu
B
re
X
PSW-120xx
PS-45xx
PS-30xx
PS-15xx
PS-S20xx
PS-S10xx
nU
vi
re
as S
Il
iw
pn ct
h
tu
S LU
le
ce 05
It L8 U
L
pn si
tu det 06
9
N
05
1- CE
e R lC C
.c sa E
s
2 ram
oC ek oR
m d sh
oC eR
m a
lp hc
ai C
D
C
tn o
m O
lp K S
ai
oh
tn
tr
iC O
cr ev
tiu olr
da vO
re
V
lo O
at rev
eg T
e E
m M
ep C
ar
C
B
ut
er
X
PSW-240xx
PS-S100xx
PS-S60xx
PS-S40xx
DBO = DC bus OK
V = 220V INPUT ONLY
21-28
21-28
PSW-480xx
lp
ai
tn
WR = wide range input
TP = three phase input
PS-UPS
PS-RDN
5
12
15 24 48
PS-S10xx
X
X
X
X
X
X
X
X
X
X SIG
X
X
X
X
X
PS-S20xx
X
X
X
X
X
X
X
X
X
X SIG
X
X
X
X
X
PS-S40xx
X
X
X
X
X
X
X
X*
X
X
X
X
X
X
X
X
X
PS-S60xx
X
X
X
X
X
X
X
X*
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X*
X
X
X
X
X
X
X
X
X
PS-S100xx
X
PS-15xx
X
X
X
X
X
X
X
X
X
X
X
X
X
X
PS-30xx
X
X
X
X
X
X
X
X
X
X
X
X
X
X
PS-45xx
X
X
X
X
X
X
X
X
X
X
X
X
X
PS-60xx
X
X
X
X
X
X
X
X
X
X
X
X
X
X
PS-100xx
X
X
X
X
X
X
X
X
X
X
X
X
X
X
PS-75xx
X
X
X
X
X
X
X
X
X
X
X
X
PS-120xx
X
X
X
X
X
X
X
X
X
X
X
X
X
PSH-120xx
X
X
X
X
X
X
X
X
X
X
X
X
X
PSP-240xx
X
X
X
X
X
X
X
X
X
X
X
X
X
X
PSP-480xx
X
X
V
X
X
X
X
X
X
X
X
X
X
X
PSP-480Sxx
X
X
X
X
X
X
X
X
X
X
X
X
X
PST-240xx
X
X
TP
X
X
X
X
X
X
X
X
X
X
X
PST-480xx
X
X
TP
X
X
X
X
X
X
X
X
X
X
X
PST-960xx
X
X
TP
X
X
X
X
X
X
X
X
X
X
X
PST-960Pxx
X
X
TP
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
PS-C240xx
X
X
X
X
X
X
X
X
X
X
X
X
X
X
PS-C480xx
X
X
X
X
X
X
X
X
X
X
X
X
X
X
PS-C480Pxx
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X WR
X
X
X
X
X
X
X
X
X
X
X
PSW-240xx
X
X WR
X
X
X
X
X
X
X
X
X
X
X
PSW-480xx
X
X WR
X
X
X
X
X
X
X
X
X
X
X
PS-C120xx
PSW-120xx
X
X
X
X
X
X
X
X
X
PS-RDN
21-28
X
X
X
X
PS-UPS
21-28
X
X
X DBO
X
TP = three phase input
WR = wide range input
X* = selected items, see data sheet
SIG = DC OK signal
V = 220V INPUT ONLY
DBO = DC bus OK
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
95
Index
Part No.
Page
PS-10012 .........................................22,
PS-10015 .........................................22,
PS-10024 .........................................22,
PS-12012 .........................................36,
PS-12024 .........................................36,
PS-12048 .........................................36,
PS-1505 ...........................................22,
PS-1512 ...........................................22,
PS-1515 ...........................................22,
PS-1524 ...........................................22,
PS-3005 ...........................................22,
PS-3012 ...........................................22,
PS-3015 ...........................................22,
PS-3024 ...........................................22,
PS-4505 ...........................................22,
PS-4512 ...........................................22,
PS-4515 ...........................................22,
PS-4524 ...........................................22,
PS-6005 ...........................................22,
PS-6012 ...........................................22,
PS-6015 ...........................................22,
PS-6024 ...........................................22,
PS-7512 ...........................................36,
PS-7524 ...........................................36,
PS-7548 ...........................................36,
PS-C12012 ......................................62,
PS-C12024 ......................................62,
PS-C12048 ......................................62,
PS-C24024 ......................................62,
PS-C24048 ......................................62,
PS-C48024 ......................................62,
PS-C48048 ......................................62,
PS-C480P24 ....................................62,
PS-C480P48 ....................................62,
PS-RDN20 .......................................84,
PS-S10012.........................................8,
PS-S10024.........................................8,
PS-S10048.........................................8,
PS-S1005...........................................8,
PS-S1012...........................................8,
PS-S1015...........................................8,
PS-S1024...........................................8,
PS-S2005...........................................8,
PS-S2012...........................................8,
PS-S2015...........................................8,
PS-S2024...........................................8,
PS-S4005...........................................8,
PS-S4012...........................................8,
PS-S4024...........................................8,
PS-S4048...........................................8,
96
Part No.
32
32
32
40
40
40
24
24
24
24
26
26
26
26
28
28
28
28
30
30
30
30
38
38
38
64
64
64
66
66
68
68
70
70
86
18
18
18
10
10
10
10
12
12
12
12
14
14
14
14
Page
PS-S6005...........................................8, 16
PS-S6012...........................................8, 16
PS-S6024...........................................8, 16
PS-S6048...........................................8, 16
PS-UPS40........................................84, 88
PSH-12024 ......................................36, 42
PSH-12048 ......................................36, 42
PSP-24024.......................................36, 44
PSP-24048.......................................36, 44
PSP-48024.......................................46, 48
PSP-48048.......................................46, 48
PSP-480S24 ....................................46, 50
PSP-480S48 ....................................46, 50
PST-24024 .......................................52, 54
PST-24048 .......................................52, 54
PST-48024 .......................................52, 56
PST-48048 .......................................52, 56
PST-96024 .......................................52, 58
PST-96048 .......................................52, 58
PST-960P24 .....................................52, 58
PST-960P48 .....................................52, 58
PSW-12012......................................74, 76
PSW-12024......................................74, 76
PSW-12048......................................74, 76
PSW-24024......................................74, 78
PSW-24048......................................74, 78
PSW-48024......................................74, 80
PSW-48048......................................74, 80
Accessories:
15.960 ....................................................91
2511110 .................................................90
2511110/1M...........................................90
2511120 .................................................90
2511120/1M...........................................90
CA202 ....................................................91
CA302 ....................................................91
CA402 ....................................................91
CA603 ....................................................90
CA701-15...............................................90
CA701-15-2M ........................................90
CA701-15/S ...........................................90
CA701-15/S-2M.....................................90
CA703 ....................................................90
CA802 ....................................................91
CA803 ....................................................90
CA903 ....................................................90
CASP .....................................................91
CGT10U .................................................91
CGT4N ...................................................91
CGT6N ...................................................91
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
97