y Pr el im in ar DRD40 SERIES DC - DC DIN RAIL MOUNTABLE POWER SUPPLY INDUSTRIAL CONTROL EQUIPMENT FEATURES ‧4:1 WIDE INPUT RANGE ‧SHORT CIRCUIT PROTECTION ‧INTERNAL INPUT FILTER ‧REMOTE ON / OFF ‧LOW PROFILE ‧3 YEARS WARRANTY Vo C a US UL 60950-1 EN 60950-1 IND. CONT. EQ. UL 508 MODEL LIST MODEL NO. INPUT INPUT OUTPUT OUTPUT OUTPUT CURRENT VOLTAGE (typ.) (max.) WATTAGE VOLTAGE CURRENT EFF. (min.) EFF. (typ.) 79% 80% 82% 82% 83% 81% 82% 84% 84% 85% max. unit 300 KHz VDC Single Output Models DRD40-05 DRD40-09 DRD40-12 DRD40-15 DRD40-24 10-32 VDC 10-32 VDC 10-32 VDC 10-32 VDC 10-32 VDC 1.6 A 1.8 A 2.1 A 2.1 A 2.1 A 3.8 A 4.5 A 5A 5A 5A 30 WATTS 36 WATTS 40 WATTS 40 WATTS 40 WATTS + 5 VDC + 9 VDC + 12 VDC + 15 VDC + 24 VDC 6A 4A 3.4 A 2.7 A 1.7 A SPECIFICATION All Specifications Typical At Nominal Line, Full Load, 25oC Unless Otherwise Noticed GENERAL Characteristics Switching frequency Isolation voltage Isolation resistance Ambient temperature Derating (see derating curve) Storage temperature Relative humidity Temperature coefficient 100 -40 Altitude during operation IEC 60068-2-13 MΩ o C % / oC + 71 2.5 + 85 95 ± 0.03 -40 20 Vi nom, Io nom Vi nom, Io min Bellcore Issue 6 @40 oC, GB typ. 100 1,500 Vi nom, from +51 oC to +71 oC Non operational MTBF Dimension Cooling Installation position Pollution degree min. Conditions Vi nom, Io nom Input-Output Input-Output, @ 500VDC Operating at Vi nom o C % RH % / oC 576,000 560,000 568,000 580,000 605,000 5V 9V 12V 15V 24V Hours Hours Hours Hours Hours m mm 4,850 L91 x W53 x D56.5 Free air convection Vertical ( other direction may derating using ) 2 INPUT SPECIFICATIONS Characteristics Input voltage range No load input current Input voltage w/o damage Startup voltage Input filter www.chinfa.com 2014.09.01 Conditions Ta min ... Ta max, Io nom Vi nom, Io = 0 Io nom Io nom Pi type min. typ. max. unit 10 24 32 40 40 VDC mA VDC VDC 9.5 [email protected] P1 DRD40 SERIES SPECIFICATION All Specifications Typical At Nominal Line, Full Load, 25oC Unless Otherwise Noticed OUTPUT SPECIFICATIONS Characteristics Conditions Output voltage accuracy Vi nom, Io max Minimum load Line regulation Load regulation Voltage trim range Vi nom Io nom, Vi min ...Vi max Vi nom, Io min ...Io nom Vi nom, 0.8 Io nom Rated continuous loading Vi nom Startup time Transient recovery time Ripple & noise Power back immunity Vi nom, Io nom Vi nom, 1~0.5 Io nom Vi nom, Io nom, BW = 20MHz Vi nom, Io nom Capacitor load Vi nom, Io nom DC ON indicator threshold at start up (Green LED) Vi nom, Io nom DC LOW indicator threshold after start up (Red LED) Vi nom, Io nom Efficiency Vi nom, Io nom, Po / Pi typ. min. max. unit +1 % % % % VDC VDC VDC VDC VDC 0 0 5V 9V 12V 15V 24V 5V 9V 12V 15V 24V 4.75 8.55 11.4 14.25 22.8 ±1 ±1 5.5 9.9 13.8 16.5 27.6 6 A @ 5Vdc / 5.4 A @ 5.5 Vdc 4 A @ 9Vdc / 3.6 A @ 9.9 Vdc 3.4 A @ 12Vdc / 2.9 A @ 13.8 Vdc 2.7 A @ 15Vdc / 2.4 A @ 16.5 Vdc 1.7 A @ 24Vdc / 1.45 A @ 27.6 Vdc ms ms 50 1 100 5V 9V 12V 15V 24V 5V 9V 12V, 15V 24V 5V 9V 12V 15V 24V 5V 9V 12V 15V 24V mV VDC VDC VDC VDC VDC μF μF μF μF 7.5 15 18 22 35 3,500 2,200 1,000 470 4.5 VDC 3.5 VDC 6.8 8.1 VDC 10.8 9 VDC 13.5 11 VDC 19.2 21.6 4.5 VDC 3.5 VDC 6.8 8.1 VDC 10.8 9 VDC 13.5 11 VDC 19.2 21.6 Up to 85%, See model list and typ efficiency curve CONTROL AND PROTECTION Characteristics typ. min. Conditions Input fuse Internal surge voltage protection IEC 61000-4-5 Rated over load protection Vi nom (see typ current limited curve) Over voltage protection Vi nom,0.8 Io nom (Auto Recovery) Remote ON / OFF max. unit T10A / 63VDC internal Varistor 110 165 % 5V 5.75 6.5 VDC 9V 10.35 11.7 VDC 12V 14.4 16.2 VDC 15V 17.25 19.5 VDC 24V 28.8 32.4 VDC ON : opened or 8 ~ 10VDC applied, reference to input GND OFF : -0.3 ~ 2VDC applied, reference to input GND Output short circuit Current limited (Auto-recovery) Degree of protection IP20 www.chinfa.com 2014.09.01 [email protected] P2 DRD40 SERIES SPECIFICATION o All Specifications Typical At Nominal Line, Full Load, 25 C Unless Otherwise Noticed APPROVALS AND STANDARDS UL / cUL UL 508 CTUVUS UL 60950-1 TUV EN 60950-1 CE EN 61000-6-3, EN 55022 Class B EN 61000-6-2, EN 55024, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4 EN 61000-4-5, EN 61000-4-6, EN61000-4-8, ENV 50204, EN 61204-3 Vibration resistance meet IEC 60068-2-6 (Mounting on rail : 10-500 Hz, 2G, along X, Y, Z each Axis, 60 min for each Axis ) Shock resistance meet IEC 60068-2-27 (15G, 11ms, 3 Axis, 6 Faces, 3 times for each Face) PHYSICAL CHARACTERISTICS 91 x 53 x 56.5 mm (3.58 x 2.09 x 2.22 inches) Case size Case material Weight Packing Plastic 180g 0.24kg ; 64 / 14kg / 2.28CUFT MECHANISM & PIN CONFIGURATION mm [inch] CONSTRUCTION 53.00 [2.09] Easy snap-on mounting onto the DIN-Rail (TS35/7.5 or TS35/15), unit sits safely and firmly on the rail; no tools required even to remove INSTALLATION 12.00 [0.47] 11.00 [0.43] 4 3 2 1 45.00 [1.77] ++ ON / OFF + 5 6 91.00 [3.58] 56.50 [2.22] 48.90 [1.93] 32.40 [1.28] 51.50 [2.02] 91.00 [3.58] Vout ADJ. DC LO DC ON Ventilation / Cooling Normal convection All sides 25m/m free space For cooling recommended Connector size range AWG24-12 (0.2~2.5mm2) flexible / solid cable -Connector can withstand torque at maximum 6 pound-inches. 7 m/m stripping at cable end recommends. Use copper conductors only, 60/75 oC GENERAL TOLERANCE 0.00[0.00] - 30.00[1.18] ±0.30[0.01] 30.00[1.18] - 120.00[4.72] ±0.50[0.02] 7 PIN ASSIGNMENT 1, 2 3, 4 Designation Description OUT PIN NO. 6 IN 5 OTHER 7 www.chinfa.com 2014.09.01 - Negative output terminal + Positive output terminal ON / OFF Remote ON / OFF terminal + Positive input terminal - Negative input terminal Vout ADJ. Trimmer-potentiometer for Vout adjustment DC ON Operation indicator LED DC LO DC Low indicator LED [email protected] P3 DRD40 SERIES CIRCUIT SCHEMATIC ‧Block diagram for DRD40 series Fuse Vi + Vo + Line Filter Switching Device Rectifier Vi - Vo PWM controller ON / OFF Opto Isolation Reference & Error Amp. Opto Isolation Over Voltage Detection Vout ADJ. Output Level Detection DC ON (Green LED) DC LO (Red LED) DERATING CURVE Input Voltage : 10V ~ 28V Input Voltage : >28V but 32V 100 Power out [ % ] Power out [ % ] 100 50 Safe Operating Area 0 -40 51 Safe Operating Area 40 0 -40 71 41 o 71 Temperature [ oC ] Temperature [ C ] o Ta : 50 C Power out [ % ] 100 80 Safe Operating Area 0 28 Input Voltage [ V ] 10 32 DERATING AND EFFICIENCY CURVE 87 90 86 85 85 Efficiency [ % ] Efficiency [ % ] Efficiency Vs Input Voltage DRD40-12 84 83 82 81 Efficiency Vs Output Load DRD40-12 80 75 70 65 60 Io : Full Load 10 12 www.chinfa.com 2014.09.01 14 16 18 20 22 24 Input Voltage (V) 26 28 30 32 55 Vi : 24VDC 10 20 30 40 50 60 70 Output Load (%) 80 90 100 [email protected] P4