High Current & High Voltage resin Sealed Filters

High Current/High Voltage
Resin Sealed Filters
High current filters are ideal for use in high current
5 volt logic buss, but also can be used for ±48 VDC
telephone rack buss, high current switch mode power
supplies and DC charging systems. High voltage filters
find use in high voltage power supplies and applications
requiring U.L. Hi-Pot.
Installation Notes
for Figure 1 & 2 — see below (Figure 3 see page CF6)
Features
■
Current ratings up to 100 Amps
■
Continuous voltage ratings up to
1250 VDC/240 VAC (400Hz)
1. Mounting installation torque
Method A: Mounting in full threaded through-hole
Maximum torque: 96 in-lbs
■
U.L. 1459 recognized and CSA C22.2 approved
versions available
■
Rugged bolt-in style for easy installation
Method B: Mounting w/hardware
Maximum torque: 84 in-lbs
2. Terminal installation torque
Maximum torque: 20 in-lbs
Note: Use two-wrench method to install
terminal hardware
1-1/2 Imperfect Thds.
5/16–24 Unf–2A Thd.
.250
(6.35)
.060 Max., Typ.
ø .062 ± .005
(1.58 ± .13)
Typ.
.250
(6.35)
Min.
.250
(6.35)
.250
(6.35)
Min.
Typ.
.
.250
(6.35)
Figure 3
.815
(
Hex.
.500
(12.7)
Hex.
.563
(
Dimensions in inches (mm)
API TECHNOLOGIES • 8061 Avonia Rd. • Fairview, PA 16415 • Ph: 814-474-1571 • Fax: 814-474-3110 • eis.apitech.com
API TECHNOLOGIES’ SPECTRUM CONTROL GmbH • Hansastrasse 6 • 91126 Schwabach, Germany • Phone: (49)-9122-795-0 • Fax: (49)-9122-795-58
LP24
High Current/High Voltage
Resin Sealed Filters
High Current High Voltage Feed-through
1.000 ± .031
(25.4 ± .79)
1.250 ± .031
(31.8 ± .79)
.312
(7.93)
.375
(9.53)
.250 Flats
ø .051 ± .005
(ø 1.30 ± .13)
.327 Max.
(8.30 Max.)
.578 Max.
(14.68 Max.)
Mounting Surface
5/16–24 Unf–2A
Figure 4
.990 ± .031
(25.15 ± .79)
.500
(12.7)
.325
(8.26)
ø .057 ± .005
(ø 1.45 ± .13)
.075
(1.91)
.740 ± .031
(18.61 ± .79)
Mounting Surface
3/8–32unef–2A Thd.
.375
(9.53)
.500
(12.70)
.689 ± .031
(17.5 ± .79)
.937 ± .031
(23.8 ± 79)
.020
(.51)
Figure 5
.125
(3.18)
3/8–32 Unef–2A Thd.
Figure 6
Dimensions in inches (mm)
Rated Voltage
125°C
DC
AC***
60
—
I
Amp
50
CKT
C
Min
Cap
0.22 µF
Minimum Insertion Loss (dB)
10
1
3
1
10
30 100 300
MHz MHz MHz MHz MHz MHz GHz GHz
50
50
40
50
50
50
30
20
54-848-005*
Figure
1
54-853-001*
2
60
—
50
C
0.22 µF
20
30
40
50
50
50
50
50
54-853-004 €
2
200
140
100
C
0.22 µF
20
30
40
50
50
50
50
50
54-848-008
1
200
140
100
C
0.22 µF
20
30
40
50
50
50
50
50
54-844-001**
3
600
240
25
C
4700 pF ± 20%
—
—
12
20
30
33
50
50
54-844-002**
3
600
240
25
C
0.01 µF ± 20%
3
7
20
25
35
40
57
57
54-763-008
4
750
—
25
C
1000 pF
—
—
—
10
20
28
28
28
54-763-009
4
750
—
25
C
4000 pF
—
—
10
22
32
35
35
40
54-789-003
5
1250
—
25
C
4000 pF
—
—
6
20
30
35
35
35
✝ 1280-060 €
6
2500
—
25
Pi
1500 pF
—
—
5
15
50
50
50
50
Part Number
✝ Also available through API’s authorized distributors.
€ Also available through API’s authorized European distributors/agents.
* Denotes parts that are UL recognized to UL 60950 and certified to CSA C22.2
** Denotes parts that meet 1500 VAC Dielectric Withstanding Voltage per UL 1283
*** AC Voltage to be 400Hz
and CSA C22.2
API TECHNOLOGIES • 8061 Avonia Rd. • Fairview, PA 16415 • Ph: 814-474-1571 • Fax: 814-474-3110 • eis.apitech.com
API TECHNOLOGIES’ SPECTRUM CONTROL GmbH • Hansastrasse 6 • 91126 Schwabach, Germany • Phone: (49)-9122-795-0 • Fax: (49)-9122-795-58
LP25