Carling Circuit Protection Selector Guide [pdf]

HYDRAULIC–MAGNETIC
Circuit Protection
SELECTOR GUIDE
M-Series
MS-Series
H-Series
A-Series
1-3
1-3
1-6 (handle)
1-3 (rocker & metal toggle)
sealed metal toggle
handle
rocker
curved & flat
sealed metal toggle
handle
rocker
paddle
AC/DC: instantaneous, short,
medium, hi-inrush
DC: instantaneous,
short & medium
AC, DC: instantaneous,
ultra-short, short, medium
& long
Max Current &
Voltage Ratings
1 Pole:
0.02-15FLA@32VDC,125VAC
15.1-25GPA@32VDC,125VAC
0.02-12FLA@250VAC
0.02-7.5GPA@50VDC
0.02-30GPA@65VDC, 80VDC
2 Pole:
0.02-15FLA@65VDC, 250VAC
15.1-25GPA@65VDC, 250VAC
Parallel Pole:
31-50GPA@80VDC
0.2-30A@65VDC
240VAC, 120/240VAC
1-35A@65VDC, 80VDC,
250VAC
Max Interrupting
Capacity
1 Pole:
1,000A@32VDC
1,000A@125VAC
2 Pole:
1,000A@65VDC
1,000A@250VAC
Parallel Pole:
600A@80VDC
3000A, U1@65VDC
2000A, U1@240VAC
2000A,
U1@120/240VAC
3000A@65VDC
1000A@80VDC
1500A@250VAC
Auxiliary Switch
Rating
7A@250VAC
0.1A@125VAC (gold contacts)
7A (res.)@28VDC
4A (ind.)@28VDC
0.25A@80VDC
5A@125VAC
3A@32VDC
.1A@125VAC, 32VDC
1.0A@65VDC/0.5A@80VDC,
0.1A@125VAC (gold contacts)
10.1A@125VAC
0.1A@125VAC (gold contacts)
0.5A@65VDC
0.1A@80VDC
series, shunt, relay, switch
only, series with remote
shutdown, relay & shunt trip
dual coil
Number of Poles
1-2
Actuator Style
solid color: angled rocker, paddle,
baton, push-to-reset pushbutton,
push-pull pushbutton
two color: visi-rocker
illuminated: angled rocker, flat rocker
Available Delays
AC, DC, AC/DC: instantaneous,
ultra-short, short, medium &
long
AC, DC: high inrush-short,
medium & long
0.02-30A@277VAC, 80VDC
31.0-50A@125/250VAC, 65VDC
7500A@80VDC, UL only
3000A@120/250VAC, UL only
5000A@277VAC, with fuse
backup
Available Circuits
series and switch only parallel pole
series and switch only
series, switch only, relay trip
/ v coil
Terminal Options
.250” QC tabs
8-32 screw with upturned lugs
8-32, 10-32 screw (bus type)
push in stud terminals
.250” QC tabs
8-32 screw & solder
type
.250” QC tabs
8-32 & 10-32 screw (&
metric), PCB
.250” QC tabs
8-32 & 10-32 screw (& metric),
PCB
Mounting Method
snap-in front panel threaded bushing
front panel
threaded inserts
threaded inserts:
front panel snap-in
Agency Approvals
UL recognized, CSA, VDE, TUV,
UL489A listed
UL 1077, cUL
UL recognized, CSA
accepted, TUV certified &
CCC certified
UL, CSA, VDE, TUV (rocker),
UL1500, UL489A
www.carlingtech.com
B-Series
C-Series
G-Series
D-Series
Number of Poles
1-6
1-6 (handle)
1-3 (rocker & metal toggle)
1-4 (handle)
1-3 (rocker)
1-3 (UL Listed)
1-4 (UL Recognized)
Actuator Style
handle
rocker
sealed metal toggle
handle
rocker
solid color curved rocker (1 per unit)
two color visi-rocker (1 per unit)
handle (1 per pole or 1 per unit)
handle
AC, DC, AC/DC:
instantaneous, ultra-short,
short, medium & long
AC, DC, AC/DC: instant,
ultrashort, short, medium & long
Available Delays
AC, DC: high inrush-short,
medium & long
Max Current &
Voltage Ratings
Max Interrupting
Capacity
0.02-30A@277VAC, 80VDC
0.02-30A@125/250VAC,
65VDC
7500A@80 VDC, UL only
3000A@125/250VAC, UL only
5000A@277VAC, with fuse
backup
AC, DC: high inrush-short,
medium & long
UL Listed:
0.02-250A@80VDC
0.1-100A@125VDC
0.02-70A@120VAC
0.02-20A@240VAC
UL Recognized:
0.02-30A@480WYE/277VAC
2 Pole, 1Ø
3 Pole, 3Ø
0.02-50A@277VAC
0.02-100A@250VAC, 80VDC
0.02-100A@120/240VAC, 65VDC
UL Listed:
50000A@80VDC, 1 pole only
10000A@120VAC
5000A@125VDC/240VAC
UL Recognized:
7500A@80VDC
3000A@125/250VAC, UL only
5000A@250VAC listed construction
5000A@480WYE/277VAC with
AC, DC, AC/DC: instant, ultrashort, short, medium, long (motor
loads)
AC, DC: instantaneous,
ultrashort, short, medium
& long
AC, DC, AC/DC: high inrushshort, medium, long
AC, DC: high inrushshort, medium & long
0.02-50A@277VAC,65VDC
0.02-30A@ 480WYE/277VAC
2 Pole 1Ø
3 Pole 3Ø
1,500A@65VDC, 250VAC, VDE only
5,000A@65 VDC
5,000A@480WYE/277VAC with
fuse back up
3,000A@125/250VAC, UL only with
fuse back up
fuse backup
UL Listed:
1-50A@80VDC
1-50A@125VDC
1-50A@120VAC
1-50A@120/240VAC
1-25A@240VAC
UL Recognized:
0.1-63A@80VDC
0.1-63A@240VAC
0.1-63A@480YVAC
UL Listed:
5000A@80VDC
5000A@125VDC
5000A@120VAC
5000A@120/240VAC
5000A@240VAC
UL Recognized:
3000A@80VDC
3000A@240VAC
1500A@480VAC
Auxiliary Switch
Rating
10.1A@125VAC
0.1A@125VAC (gold contacts)
0.5A@65VDC
0.1A@80VDC
10.1A@250VAC
0.1A@125VAC (gold contacts)
0.5A@80VDC
n/a
3A@125VAC
2A@30VDC
Available Circuits
series, shunt, relay, switch
only, series with remote
shutdown, relay & shunt
trip dual coil, mid-trip with
alarm switch
series, shunt, relay, switch only,
series with remote shutdown,
relay & shunt trip dual coil, midtrip with alarm switch
series, switch only, series with
remote shutdown
series, switch only
Terminal Options
.250” QC tabs, 8-32 & 1032 screw (& metric), PCB
10-32 stud, 1/4-20 stud,
10-32 screw with saddle clamp,
7/16 clip & push-In
recessed wire-ready, pressure
plate type screw terminals
recessed wire-ready,
pressure plate type
screw terminals
Mounting Method
threaded inserts:
front panel snap-in
threaded inserts
rear mounted on DIN rail or front
panel mounted
rear mounted on DIN rail
Agency Approvals
UL, CSA, VDE, TUV (rocker),
UL1500, UL489, UL489A
UL, CSA, VDE, TUV,
UL1500, UL489, UL489A
UL recognized, CSA, VDE
UL1077, cUL, TUV,
UL489
www.carlingtech.com
NEW
L-Series
N-Series
CX-Series
E-Series
F-Series
Number of Poles
1-3
1-2
1-2, + auxiliary switch
pole
1-6
1-3
Actuator Style
rocker, with or without
guard
flush rocker, with or
without push to reset
guard
handle, 1 per pole
handle
handle
Available Delays
AC: ultrashort, short,
medium, long, short-high
inrush, medium-high
inrush, long-high inrush
AC: ultrashort, short,
medium, long, short-high
inrush, medium-high
inrush, long-high inrush
Max Current &
Voltage Ratings
Max Interrupting
Capacity
.1-32A@120/240VAC
.1-20A@415/240VAC,
3 pole
5000 amps
1-20A@240/277VAC
1-30A@120/240VAC
22,000 amps
DC: instant, ultrashort,
short, medium & long
UL Recognized
0.2-115A@600VDC
UL Listed
0.2-15A@250/500VDC
0.2-50A@205/410VDC
UL Listed and UL
Recognized
up to 10,000 amps
AC, DC, AC/DC: instant,
short, medium & long
AC, DC, AC/DC: high
inrush-short, medium
& long
UL Listed
0.02-100A@240VAC,
80VDC, 125VDC
UL Recognized
0.02-100A@277VAC,
160VDC, 1 pole
0.02-100A@600VAC,
2 Pole 1Ø, 3 pole 3Ø
0.02-120A@125VDC,
1 pole
UL Listed
50000A@80VDC
10000A@125VDC &
240VAC-5KA
UL Recognized
5000A@125VDC
5000A@600VAC, without
AC, DC: short, medium
& long
UL489 Listed:
50-250A@125VDC
100-250A@120/240VAC
100-250A@277VAC
100-250A@208Y/120,
3ØVAC
UL489A Listed
250-700A@125VDC
50000A@125VDC
10000A@120/240, 277,
208Y/120VAC
fuse backup
10000A@600VAC,
with fuse backup
Auxiliary Switch
Rating
n/a
n/a
20A@80VDC (GO circuit)
10.1A@250VAC
1.0A@65VDC
0.1A@80VDC
10.1A@250VAC
0.5A@65VDC
0.1A@80VDC
Available
Circuits
series trip
series trip
series trip
series, shunt,relay,
switch only, series
with remote shutdown
series & switch only
with or without metering
shunt
Terminal Options
10-32, 8-32, M5 & M4
screw
screw terms
10-32 or M5 screw
terminals 1/4-20 or M6
threaded stud
10-32 stud, 1/4-20 stud
0-32 screw, 1/420 screw, box wire
connector
3/8-16 stud, 3/8-16
screw & box wire
connector
Mounting
Method
threaded insert: #6-32
UNC-2B, or M3X0.5-6H
B ISO (2 per pole)
threaded insert: #6-32
x .195 inches ISO M3 x
5mm
threaded insert: #6-32
UNC-2B, or M3X0.56H B ISO (2 per pole)
rear or front panel
rear or front panel
Agency
Approvals
UL 489, cUL, TUV
(EN60934-2)
UL489, TUV (EN60947-2)
UL489, UL1077, TUV
(EN60934-2)
UL, CSA, VDE, UL1500,
UL489
cUL,TUV, UL489,
UL489A
*Manufacturer reserves the right to change product information without prior notice
HYMAG-SG_02_2016
60 Johnson Avenue | Plainville, CT 06062 | Phone: (860) 793-9281 | Fax: (860) 793-9231 | Email: [email protected]