PSC-60

PowerSupplies_2013.QXD_PowerSupplies(v5).QXD 9/18/13 5:03 PM Page 26
PSC-60 Series
Type
Approved
OUTPUT
E361935
E205412
Features:
•
•
•
•
•
•
•
•
•
•
•
•
ENERGY
SAVER
Universal AC input (88-264V AC)
Protections: Short Circuit / Overload / Overvoltage
Brown-out protection
Installed on DIN rail TS35 / 7.5 or 15
True DC OK signal output
All wiring 105°C long life electrolytic capacitors
High operation temperature up to 70°C
Withstands 2G vibration test
High efficiency, long life and high reliability
3 year warranty
UL1310 Class 2 Power unit / LPS pass
UL508 (Industrial control equipment) listed
Cat. No.
PSC-6012
PSC-6015
PSC-6024
PSC-6048
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
RIPPLE & NOISE (max)
12V
5A
0 ~ 5A
60W
100mVp-p
15V
4A
0 ~ 4A
60W
100mVp-p
24V
2.5A
0 ~ 2.5A
60W
120mVp-p
48V
1.25A
0 ~ 1.25A
60W
180mVp-p
Ripple & noise are measured at 20MHz of bandwidth by using a 12” twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE
10.8 ~ 13.2V
±1.0%
13.5 ~ 16.5V
±1.0%
21.6 ~ 26.4V
±1.0%
43.2 ~ 52.8V
±1.0%
Tolerance: includes set up tolerance, line regulation and load regulation.
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
±1.0%
±1.0%
±1.0%
±1.0%
< 800ms, < 50ms / 230VAC at full load
±1.0%
±1.0%
±1.0%
±1.0%
Length of set up time is measured at sold first start. Turning ON/OFF the power supply may lead to increase of the set up time.
INPUT
HOLD UP TIME (Typ.)
VOLTAGE RANGE
> 32ms / 230VAC; >16ms / 115VAC at full load
88 ~ 264VAC; 124 ~ 370VDC
Derating may apply in low input voltage. Please check the derating curve for more details.
PROTECTION
FREQUENCY RANGE
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVER LOAD PROTECTION
47~63Hz
86%
87%
1.3 A / 115VAC; 0.6A / 230VAC
COLD START 30A / 115VAC; 60A / 230VAC
<1mA / 230VAC
87%
88%
> 102% rated output power
Protection type: Constant current limiting, recovers automatically after fault condition is removed
OVER VOLTAGE PROTECTION
115% ~ 150% rated output voltage
Protection type: latch-off mode
ENVIRONMENT
SAFETY & EMC
OTHERS
OVER TEMPERATURE PROTECTION
Power supply shut down at 70˚C constant current limiting / output voltage goes to 0;
re-power on to recover
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP. / HUMIDITY
TEMP. COEFFICIENT
VIBRATION
-20 ~ +70˚C (Refer to output load derating curve)
20 ~ 90% RH non-condensing
-40 ~ +85˚C; 10 ~ 95% RH
±0.03% / ˚C (0 ~ 50˚C)
10 ~ 500Hz, 2G 10min. / 1cycle, 60 min. each long X,Y, Z axes
SAFETY STANDARDS
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION
HARMONIC CURRENT
EMS IMMUNITY
UL508, TUV EN60950-1:2006+A11, UL1310 NEC class 2 compliant
I/P-O/P: 4242DC, I/P-FG: 2121DC 1minute
I/P-O/P, I/P-FG, O/P-FG: 100M Ohms/500VDC
EN55022: 2006 Class B
EN61000-3-2: 2006 Class A, EN61000-3-3: 1995+A1: 2001+A2: 2005
EN61204-3: 2000, EN55024: 1998+A1:2001+A2: 2003 light industry level, criteria A
The power supply is considered a component which will installed into a final equipment. The final equipment must be re-confirmed
that is still meets EMC directives.
DC OK Signal
MTBF
DIMENSION
PACKING
CONNECTION
COOLING
Relay contact (24VDC / 1A, 120VAC / 1A)
944.6K HRS MIL-HDBK-217F
40x90x99 mm (WxHxD)
0.3kg; 27pcs / 9.3kg
I/P: 3 poles, O/P: 6 poles screw DIN terminal
Free air convection
All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature.
26
For the latest on Altech Power Supplies please visit www.altechcorp.com/power.
PowerSupplies_2013.QXD_PowerSupplies(v5).QXD 9/18/13 3:42 PM Page 27
PSC-60 Series
Type
Approved
E361935
E205412
ENERGY
SAVER
Mechanical Specification
Unit : mm / inch
40
99
Terminal Pin. No Assign. (TB1)
Assignment
FG
AC/N
AC/L
90
Pin No.
1
2
3
Terminal Pin. No Assign. (TB2)
Pin No.
1,2
3,4
5,6
Assignment
DC OUTPUT +V
DC OUTPUT -V
DC OK RELAY CONTACT
N
L
Block Diagram
DC O K
R E C T IF IE R S
&
F I LT E R
E MI
F I LT E R
I /P
R E C T IF IE R S
&
F I LT E R
P OWE R
S W IT C H IN G
+V
-V
DC O K
O .C .P .
D E T E C T IO N
C IR C U IT
O .L .P .
C O NT R O L
O .V .P .
DC OK Relay Contact
Contact Close
When the output voltage reaches the adjusted output voltage
Contact Open
When the output voltage drop below 90% rated output voltage
Contact Ratings (max.)
30V / 1A resistive load
Derating Curve
Load V .S Temp.
Load V .S I/P V oltage
Ta=25°C
100
100
90
Load (%)
Load (%)
80
60
80
70
60
40
50
20
-20
40
0
10
20
30
40
50
Ambient Temperature (°C)
60
70
85
100
110
120
264 VAC
Input Voltage(VAC)60Hz
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490