6073205039en

Technical Data
Safety switch
Series SK - ASI – with separate actuator
Description
Article number
ASI SK M D
Operating symbol
6073205039
Terminal screw
according to DIN 912
M
Ø5,5 fixed location
for safety application
Operating diagram
Actuator
withdrawn
inserted
Tolerances
Operating point: ± 0,25 mm
ON
OFF
Electrical data
Operating voltage
Operating current
AS-i Specifications
AS-i Inputs
Parameter bits
AS-i Address
U
I
26,5 … 31,6 V; via AS-interface, reverse-polarity proof
< 30 mA
Profile S-0.B
IO-Code: 0x0
ID-Code: 0xB
ID-Code1: 0xF
ID-Code2: 0xE
Contact 1: Date bits D0/D1 = static 00
or dynamic code transmission
Contact 2: Date bits D2/D3 = static 00
or dynamic code transmission
no function
preset address: 0
This document will not become the contractual basis; the details included herein do not constitute any descriptions of expected conditions, so that warranties/claims
for defects on account of possible variations of the actual qualities from the qualities described herein are explicitly excluded. All rights reserved. Specifications
subject to change without notice!
Date of issue: 07.07.2011 / Page 1 of 2
Document : 6073205039_en / Last update: 1 / 2366-11
Bernstein AG, Tieloser Weg 6, D-32457 Porta Westfalica / www.bernstein.eu
Vorlage : 0850174285 Orig. 2
Technical Data
Safety switch
Mechanical data
Enclosure
Cover
Indication
Actuator
Extraction force
Ambient air temperature
Contact type
Mechanical life
Switching frequency
Assembly
Safety switch
Actuator
Connection
Line Type
Weight
Installation position
Protection type
Thermoplastic, glass fibre reinforced (UL94-V0)
Thermoplastic, glass fibre reinforced (UL94-V0)
LEDs for slave and bus state
Separate actuator (St-stainless steel)
10N
-25° C … +70° C
2 NC (slow-action, Zb)
1 x 106 switch operations
≤ 30 / min.
2 x M5
2 x M5
Contacted via piercing technology
AS-Interface ® ribbon cable
yellow
≈ 0,14 kg
Operator definable
IP65 acc. to IEC/EN 60529
Actuation
Turning the cap (pos A/B) allows 4 different directions of drive.
Cover (1) has to be opened before turning the cap (2).
Insert the screwdriver into the gap between housing and cap and
turn until the cap snaps off.
Remove the cap, turn it 180° (4), latch it into the housing and close
the cover.
Standards
VDE 0660 T100, DIN EN 60947-1, IEC 60947-1
VDE 0660 T200, DIN EN 60947-5-1, IEC 60947-5-1
EN 50295, EN ISO 13849-1
EU Conformity
acc. to EMC Directive
Safety Classification
according 13849-1 to PL e
MTTFd = high
PFD
= 2,49 * 10-10
Notes
The degree of protection specified (IP code) applies only to a properly closed cover.
The switch may not be used as a mechanical stop.
Radial actuation may reduce the mechanical life.
The min. radius refers to a pivot at the top of the cap (S0).
Tapped holes not in use must be closed with blind plugs.
This document will not become the contractual basis; the details included herein do not constitute any descriptions of expected conditions, so that warranties/claims
for defects on account of possible variations of the actual qualities from the qualities described herein are explicitly excluded. All rights reserved. Specifications
subject to change without notice!
Date of issue: 07.07.2011 / Page 2 of 2
Document : 6073205039_en / Last update: 1 / 2366-11
Bernstein AG, Tieloser Weg 6, D-32457 Porta Westfalica / www.bernstein.eu
Vorlage : 0850174285 Orig. 2