Control Panels for North America Interactive Animation on the subject

Industrial Control Panels for North America
Interactive animation on the subject
© Siemens AG 2012. All rights reserved.
Industrial Control Panels for North America
Interactive animation on the subject
The animation is based on 2 Control Panels (control cabinets), one built conforming to the IEC standard and
the other conforming to the UL standard. The user will be able to navigate through the animation interactively,
thus gaining a better understanding of UL specifics in the context of Industrial Control Panels.
PROCEDURE:
Click one of the devices installed in the Panels (either the IEC or the UL Panel) to display both information
about that device and the corresponding device in the other Panel.
Click the device again to display both detailed information (technical data, for example) and the UL specifics.
Use the
buttons to scroll through the animation. The
any page in the animation.
Click the
General information about UL
button takes you back to the start page from
button for general information about the UL market.
PRESS HERE TO START
© Siemens AG 2012. All rights reserved.
Industry Sector
General information about UL
Device selection
Open the doors
© Siemens AG 2012. All rights reserved.
Industry Sector
General information about UL
Device selection
Close the doors
© Siemens AG 2012. All rights reserved.
Industry Sector
Device selection
Protection devices
Switching devices/
load feeders
Monitoring devices
and control devices
Safety systems
Other devices
and accessories
3VL circuit breaker
3RT contactor
3RR monitoring relay
3TK28 safety relay
8US busbar system
3RV1 circuit breaker
3RW soft starter
SIMOCODE 3UF7
3RK3 modular
safety system
8US19 infeed system
3RV2 circuit breaker
3RF solid-state contactor
Miniature circuit breaker
3RA motor feeder
3RA68 infeed system
SITOR fuse
3RA6 compact starter
8US busbar adapter
Fuse system
class CC
ET 200S motor starter
Receptacle
NEOZED fuse system
comfort base
3NP1 fuse switch
disconnector
3RV29 infeed system
3SE5 position switch
ALPHA FIX terminal blocks
Expansion module for
SIMOCODE 3UF7
SITOP power supply
NEOZED fuse system
bus-mounting base
7km PAC measuring
instrument
DIAZED fuse system
bus-mounting base
8UC7 rotary operating
mechanism
3RB overload relay
© Siemens AG 2012. All rights reserved.
Industry Sector
General information about UL
Line system configurations
Organizations and standards
Branch Circuit – Feeder Circuit
UL marks
SCCR (short-circuit current rating)
Degrees of protection
Control circuits
Lines/cables
Commissioning/acceptance
© Siemens AG 2012. All rights reserved.
Industry Sector
Line system configurations
IEC (a grounded wye system is usually present)
 TT system, TN system (grounded wye)
 IT system (ungrounded wye)
UL (various line system configurations exist)
 Some line system configurations not used in the context of IEC
 Information about all voltages present in the system,
e.g. 480Y/277 V (slash rating) or 480 V (straight rating)
 When selecting short-circuit devices, it is sufficient to differentiate simply
between slash and straight rating
© Siemens AG 2012. All rights reserved.
Industry Sector
Line system configurations
Grounded wye
 Slash rating: e.g. 480Y/277V
480V
480V
277V
 Devices with the following ratings are permitted: 480/277V, 600/347V,
600V, 480V
277V
 Straight rating: e.g. 480V, 600V
Corner grounded delta
480V
480V
 Devices with the following ratings are permitted: 480V, 600V
 Devices with the following ratings are not permitted:
480/277V, 600/347V
 Single-phase/2-pole transformer with central tap
Residential
 e.g.: 240/120V; single-phase
 Devices with 240V, if the devices are connected between the line
conductors
240V
120V
 Devices with 120V, if the devices are connected between the line
conductors and central tap
© Siemens AG 2012. All rights reserved.
Industry Sector
Line system configurations
Ungrounded wye
 Straight rating: e.g. 480V, 600V
480V
480V
480V
 Devices with the following ratings are permitted: 600V, 480V
 Devices with the following ratings are not permitted: 600/377V,
480/277V
 Straight rating: e.g. 480V, 600V
Ungrounded delta
480V
480V
480V
 Devices with the following ratings are permitted: 480V, 600V
 Devices with the following ratings are not permitted:
480/277V, 600/347V
© Siemens AG 2012. All rights reserved.
Industry Sector
Organizations and standards
NFPA - National Fire Protection Association
Organization active in the fire protection sector with members from fire departments, authoritative bodies, test
laboratories, insurers, and consumer organizations. Issues various regulations and guidelines including
NEC, NFPA79, etc.
UL - Underwriter Laboratories
Underwriter Laboratories publishes standards and approves products in accordance with its own and third-party
standards (CSA, IEC, EN, etc.).
CSA – Canadian Standard Association
The Canadian Standard Association publishes standards and approves products in accordance with its own and
third-party standards (UL, IEC, etc).
NRTL – National Recognized Testing Laboratories
A test center recognized by the US government's OSHA (Occupational Safety and Health Administration)
e.g. UL, CSA, TÜV Rheinland of North America and many more.
© Siemens AG 2012. All rights reserved.
Industry Sector
Organizations and standards
NEC = NFPA 70
NFPA 79
UL 489
UL 508
IEC 60364-1
IEC 60204-1
IEC 61439-1
UL 508A
UL 98
UL 248
UL xxx
IEC xxxxx
© Siemens AG 2012. All rights reserved.
Industry Sector
Branch and Feeder Circuit
Feeder Circuit
Feeder Circuit
Starting from the load, all devices and
components upstream of the first
overcurrent protective device in the branch
(Branch Circuit Protective Device)
 See the next slide for clearances and
creepage distances
Branch Circuit
Starting from the load, all devices and
components up to the first
overcurrent protective device in the branch
(Branch Circuit Protective Device)
Branch Circuit
Branch Circuit
 See the next slide for clearances and
creepage distances
© Siemens AG 2012. All rights reserved.
Industry Sector
Branch and Feeder Circuit
The new edition of UL 508A defines the required clearances and creepage distances for the
Feeder and Branch Circuit in detail for the first time
Spacings required in infeed and distribution (Feeder Circuit) according to UL 508A Table 10.2 (extract)
0-125 V
126-250 V
inch
mm
inch
mm
251-600 V
inch
mm
Through air
1/2
12.7
3/4
19.1
1
25.4
Over surface
3/4
19.1
1-1/4
31.8
2
50.8
Between uninsulated live
parts and enclosure
1/2
12.7
1/2
12.7
1
25.4
Spacings in branch circuits according to UL 508A Table 10.1 (extract)
0-50 V
51-150 V
inch
mm
inch
mm
151-300 V
inch
mm
301-600 V
inch
mm
Through air
1/16
1.6
1/8
3.2
1/4
6.4
3/8
9.5
Over surface
1/16
1.6
1/4
6.4
3/8
9.5
1/2
12.7
Between uninsulated live parts and
enclosure
1/4
6.4
1/2
12.7
1/2
12.7
1/2
12.7
© Siemens AG 2012. All rights reserved.
Industry Sector
UL marks
UL listing test symbol
Any devices or appliances bearing this mark meet all UL safety regulations and can be universally installed without any restriction of their usability and
without any additional instructions.
C-UL listing test symbol
This mark is applied to products tested for compliance with Canadian UL safety requirements.
C
C-UL listing test symbol
C
US
This symbol identifies devices that comply with both CSA regulations for the Canadian market and UL regulations for the USA.
Recognized Component test symbol
This symbol is for components or devices used in machines and systems. These components may have restrictions on their performance or may be incomplete
in construction. Only specialists working in compliance with the condition of acceptability are permitted to install such components and devices.
Canadian Recognized Component test symbol
Components bearing this symbol have been approved for the Canadian market and are subject to similar restrictions as components with the Recognized
Component test symbol.
C
Recognized Component test symbol for Canada and the United States
C
US
Components bearing this mark meet the requirements of both the Canadian and US markets for Recognized Components.
© Siemens AG 2012. All rights reserved.
Industry Sector
SCCR
Requirement from NEC 2011 Art. 409.110 and UL 508A, Art. 52:
 Among the requirements to be met is that the SCCR
(short-circuit current rating) of the entire Control Panel must be marked on each Industrial Control Panel.
 The SCCR value shall ensure that the Panel is only connected to systems where the prospective short-circuit
current will be less than or equal to the value on the rating plate.
Based on NEC 2011 Art. 409.110, there are essentially 3 different ways in which the SCCR value of a Panel can be
determined:
Option 1:
Option 2:
Option 3:
The SCCR value of each individual Panel or
Panel unit is officially listed by a laboratory in
the presence of UL test engineers from UL.
Using pre-tested versions or buying such pretested Standard Industrial Control Panels.
Complete analysis of the Industrial Control
Panel in accordance with UL 508A SB4.
 This method is the one used most often.
 It is described below.
© Siemens AG 2012. All rights reserved.
Industry Sector
SCCR
Determination of the short-circuit current (SCCR) in accordance with NEC 409.110 (4)
Step 1 (mandatory):
 Listing of the SCCR values of the devices (values on the device or in the UL report)
 The smallest value determines the total short-circuit rating of the Panel!
Step 2 (mandatory):
 Listing of the SCCR values of the devices from UL 508A Table SB 4.1 (if an SCCR value has not been specified)
Step 3 (optional):
 Listing of the SCCR values of switchgear assemblies
 Series Rating Tests (series connection of at least 2 devices which can respond to a short circuit instantaneously)
 Combination tests (series connection of devices of any type)
© Siemens AG 2012. All rights reserved.
Industry Sector
Degrees of protection
↔
Enclosure types (UL)
IP degree of protection (IEC)
 "Enclosure type" degree of protection is associated with specific protection properties.
 Some UL enclosure ratings can be transposed to IP degrees of protection, but IP degrees of protection cannot be transposed to UL enclosure ratings.
 According to UL, an enclosure with only IP ratings is automatically given enclosure rating 1
?
UL/NEMA
(typical application)
Protection against
Comparable
IP degree of protection
General use
Indoors
Accidental contact with live parts and ingress of falling dirt
IP 20
2
Protection against dripping water
Indoors
Ingress of dripping water and falling dirt
IP 22
3R
Rain, hail, ice
Outdoors
(starters for pump)
Ingress of dust and rain blown by the wind, and protection from icing
over
IP 54
4
Dustproof, waterproof
Indoors, outdoors
(food industry)
Ingress of falling rain, splash water and jet water, no damage should ice
form
IP 65
4x
Dustproof, waterproof, resistant to
corrosion
Indoors, outdoors
(sewage treatment plants)
Ingress of falling rain, splash water and jet water, no damage should ice
form, anti-corrosion protection
Not available
12
Protection against dripping water,
dustproof, oil and cooling-water proof
Indoors
(machine tools)
Ingress of dripping water, dust, oil and cooling liquid
IP 54 (IP 55)
13
Protection against dripping water,
dustproof, oil and cooling-water proof
Indoors (command devices on
machine tools)
Ingress of dripping water, dust, spraying oil and cooling liquid
IP54+
Type
1
Installation site
x
© Siemens AG 2012. All rights reserved.
Industry Sector
Control circuits
Class 1 Control Circuit
Class 1 Control
Circuit
Class 2 Control Circuit
© Siemens AG 2012. All rights reserved.
Industry Sector
Control circuits - Definition
Class 1 Control Circuit (UL 508A § 2.6) = general control circuits
 A control circuit connected to the load side of a BCPD (branch circuit protection device)
 Maximum voltage: 600 V
 Maximum current/power: Unrestricted (usually limited to 15 A)
 Control circuits connected to the outgoing side of a load transformer
 Control circuits connected at the outgoing side of a control transformer/power supply
© Siemens AG 2012. All rights reserved.
Industry Sector
Control circuits - Definition
Class 2 Control Circuit (UL 508A § 2.7) = control circuits with limited power
 Devices approved "...for use with class 2..." may only be used in these
control circuits with limited power
 Control circuit supplied with power by an energy source (power supply devices certified acc. to UL1310,
UL5085-1 & 3, UL60950-1, UL1950) with max. 30 Vrms
 Devices that are used entirely in a "Class 2 circuit" do not have to be checked via the AHJ  Unlisted
components can be used
Low –Voltage Limited Energy Circuit (UL 508A § 2.32)
 Control circuit with a "protected" extra-low-voltage
 Control circuit with max. 30 Vrms or 42 V peak voltage or DC direct voltage
 with a max. power of 100 VA (5 A at 20 V or less)
 Devices that are used entirely in a "Limited circuit" do not have to be checked via the AHJ  Unlisted
components can be used
© Siemens AG 2012. All rights reserved.
Industry Sector
Lines/cables
Basic requirements
All wires and busbars must be made of copper. (UL 508A Art. 29)
EXCEPTION: Busbars in the Panel can also be made of aluminum.
Internal wires
All internal wires must be approved for at least 90 °C and correspond to one of the
following types (UL 508A Art. 29/NFPA 79, Chapter 13):
1. Machine tool wire (MTW) according to UL 1063
2. Rubber insulated wire according to UL 44
3. Thermoplastic insulation according to UL 62
4. Appliance wiring material (acc. to NFPA 79 the line must be suitable for the application observe the style number)
5. Welding cable/diesel-locomotive wire
Wiring methods
See NFPA 79, Art. 13 and UL 508A, Art. 28, 29, 38
Wire sizes
Acc. to UL 508A wires in the main circuit must not be any smaller than 14 AWG (2.1 mm²). Wire size data is listed in the table on the
next slide.
© Siemens AG 2012. All rights reserved.
Industry Sector
Lines/cables
Wire sizes and current carrying capacity - UL 508A, Table 28.1 (extract)
Wire size
AWG/kcmil
14
12
10
8
6
4
3
2
1
1/0
2/0
3/0
4/0
250 (kcmil)
300
350
400
500
600
700
750
800
900
60°C (140°F)
[mm²]
(2.1)
(3.3)
(5.3)
(8.4)
(13.3)
(21.2)
(26.7)
(33.6)
(42.4)
(53.3)
(67.4)
(85.0)
(107.2)
(127)
(152)
(177)
(203)
(253)
(304)
(355)
(380)
(405)
(456)
Copper [A]
15
20
30
40
55
70
85
95
110
-
75°C (167°F)
Aluminum [A]
15
25
30
40
55
65
75
85
-
Copper [A]
15
20
30
50
65
85
100
115
130
150
175
200
230
255
285
310
335
380
420
460
475
490
520
Aluminum [A]
15
25
40
50
65
75
90
100
120
135
155
180
205
230
250
270
310
340
375
385
395
425
© Siemens AG 2012. All rights reserved.
Industry Sector
Commissioning/Acceptance
Every electrical machine or system in the USA is checked by an inspector known as the AHJ (Authority
Having Jurisdiction) before it can be commissioned.
Acceptance is based on the NEC (National Electrical Code, also known as NFPA 70), the relevant
application-specific guidelines such as NFPA 79, as well as any local standards or specifications.
 In the USA, acceptance is a legal requirement.
The next graphic (see next slide) outlines four possible ways of arranging acceptance.
© Siemens AG 2012. All rights reserved.
Industry Sector
Commissioning/Acceptance
Acceptance options for OEMs
Panel listed
with label by
NRTL
Certified
control manufacturer
Preliminary acceptance by
UL inspector at his/her
premises
On-site field
inspection by
AHJ in USA
On-site acceptance by AHJ
Costs involved
Time involved in on-site acceptance
Modification possible
Not possible
Possible, together with
manufacturer
Possible, field inspection
required
Possible, repeat field inspection
Recommendation
Very high quantities
Many different systems
Little UL knowledge
Good UL knowledge
Operating permission from AHJ
End-customer precondition for commissioning
© Siemens AG 2012. All rights reserved.
Industry Sector
Miniature circuit breaker
Miniature circuit breaker
© Siemens AG 2012. All rights reserved.
Industry Sector
Miniature circuit breaker
Technical data
Approvals
Device selection
To IEC standard:
5SY4 miniature circuit breaker
To UL standard:
5SJ4 miniature circuit breaker
© Siemens AG 2012. All rights reserved.
Industry Sector
Miniature circuit breaker
Technical data
5SY4 miniature circuit breaker
5SJ4 miniature circuit breaker
 Rated current from 0.3 to 63 A
 Circuit breaker according to UL 489
 Rated switching capacity 10 kA to 15 kA
according to EN 60898-1
 Rated current from 0.3 to 63 A
 Rated switching capacity up to 14 kA acc. to UL 489
 Rated switching capacity 25 kA according to
EN 60947-2
 Rated switching capacity up to 15 kA
according to IEC 60947-2
 Rated voltage up to 440 V DC/up to 400 V AC
 Rated voltage 480Y/277 V AC
 Rated voltage DC:
up to 125 V (UL 489)
up to 60 V (IEC 60898 -1)
© Siemens AG 2012. All rights reserved.
Industry Sector
Miniature circuit breaker
Approvals
5SY4 miniature circuit breaker
5SJ4 miniature circuit breaker
 Approval to IEC 60898-1 and IEC 60947-2
 Approval to IEC 60898-1 and IEC 60947-2
 Approval to CSA C22.2 No. 235
 Approval to CSA C22.2 No. 5-02
 Approval to UL 1077 for use as supplementary
protector
 Approval to UL 489 as circuit breaker
 Use as branch circuit protection
 Can be used for the protection of control circuits if:
 On the primary side: Control circuit is branched
downstream of the BCPD
See UL report (UL File No. E243414) for further information
 On the secondary side: Control circuit remains in Panel
© Siemens AG 2012. All rights reserved.
Industry Sector
3VL circuit breaker
Main switch
(3VL circuit breaker)
© Siemens AG 2012. All rights reserved.
Industry Sector
3VL circuit breaker
Technical data
Approvals
Device selection
To IEC standard:
3VL circuit breaker
To UL standard:
3VL circuit breaker
© Siemens AG 2012. All rights reserved.
Industry Sector
3VL circuit breaker
Technical data
3VL circuit breaker
3VL circuit breaker
 Rated current from 16 A to 1,600 A
 Rated current from 16 A to 1,600 A
 Rated voltage
up to max. 690 V AC/max. 600 V DC
 Rated voltage
up to max. 600 V AC/max. 500 V DC
 Rated switching capacity at 400 V 100 kA
 Rated switching capacity at 400 V 100 kA
 3- and 4-pole device versions
 3-pole device version
 The set value IR for the overcurrent release
in percent
 The set value IR for the overcurrent release
in ampere
© Siemens AG 2012. All rights reserved.
Industry Sector
3VL circuit breaker
Approvals
3VL circuit breaker
3VL circuit breaker
 Approval to IEC 60947--2
 Approval to IEC 60947--2
 Main and emergency off switch
 Approval to UL 489 as circuit breaker
 System and generator protection
 Approval to CSA C22.2 No. 5-02
 Starter combinations
 Main and emergency off switch
 Non-automatic circuit breakers
 System and generator protection
 Motor protection
 Starter combinations
 Non-automatic circuit breakers
See UL report (UL File No. E10848) for further information
© Siemens AG 2012. All rights reserved.
Industry Sector
3RV2 circuit breaker
3RV2 circuit breaker
as system protection
© Siemens AG 2012. All rights reserved.
Industry Sector
3RV2 circuit breaker
Technical data
Approvals
Device selection
To IEC standard:
3RV2 circuit breaker
as system protection
To UL standard:
3RV27/28 circuit breaker
as system protection
© Siemens AG 2012. All rights reserved.
Industry Sector
3RV2 circuit breaker
Technical data
3RV20 circuit breaker
3RV27/28 circuit breaker
 Rated current up to 40 A
(depending on the size)
 Rated current up to 22 A
 Rated voltage up to
max. 690 V AC (IEC)/600 V AC (UL, CSA)
 Short-circuit strength up to 100 kA
(depending on the voltage)
 Screw terminal connections (up to 40 A), springloaded connection system and ring cable lug
connection (up to 32 A)
 Use of practical conductor cross-sections possible:
size S00 max. 4 mm2/
size S0 max. 10 mm2
 Rated voltage IEC:
max. 690 V AC
 Rated voltage UL:
max. 600Y/477 V (slash rating only)
 Short-circuit strength up to 65 kA
(at 480 Y/277 V to UL)
 Screw terminal connections
 Size S00 and S0
For further information, go to www.siemens.de/sirius
© Siemens AG 2012. All rights reserved.
Industry Sector
3RV2 circuit breaker
Approvals
3RV20 circuit breaker
3RV27/28 circuit breaker
 Approval to IEC 60947-1, IEC 60947-2
and IEC 60947-4-1 as:
 Approval to IEC 60947-1
and IEC 60947-2
 Short-circuit and motor protection
 Approval to CSA C22.2 No.5-02
 System and transformer protection
 Approval to UL 489 as
circuit breaker
 Main and emergency off protection
 Also approved to UL 508 as motor circuit breaker:
 System and transformer protection
 „Manual Motor Controller“
 "Self Protected Combination Motor Controller" when
using 3RV29 28-1H terminal block
or 3RV29 28-1K phase barriers
See UL report (UL File No. E47705) for further information
© Siemens AG 2012. All rights reserved.
Industry Sector
3RV1 circuit breaker
3RV1 circuit breaker
© Siemens AG 2012. All rights reserved.
Industry Sector
3RV1 circuit breaker
Technical data
Approvals
Device selection
To IEC standard:
3RV10 circuit breaker
To UL standard:
3RV17 circuit breaker
© Siemens AG 2012. All rights reserved.
Industry Sector
3RV1 circuit breaker
Technical data
3RV10 circuit breaker
3RV17 circuit breaker
 Rated current up to 100A
(depending on the size)
 Rated current up to 100 A
 Rated voltage up to max.
690 V AC (IEC)/600 V AC (UL, CSA)
 Short-circuit strength up to 100 kA
(depending on the voltage)
 Screw terminal connections
 Use of practical conductor cross-sections possible:
size S2 max. 35 mm2/
size S3 max. 70 mm2
 Rated voltage max.
690 V AC (IEC)/600 V AC (UL, CSA)
 Short-circuit strength
up to 65 kA at 480 Y/277 V and 480 V
 Screw terminal connections
 Use of practical conductor cross-sections possible:
size S2 max. AWG 2/0
For further information, go to www.siemens.de/sirius
© Siemens AG 2012. All rights reserved.
Industry Sector
3RV1 circuit breaker
Approvals
3RV10 circuit breaker
3RV17 circuit breaker
 Approval to IEC 60947-1,
IEC 60947-2 and IEC 60947-4-1
 Approval to IEC 60947-1
and IEC 60947-2
 Short-circuit and motor protection
(also with overload function)
 System and transformer protection
 Main and emergency off protection
 Approval to CSA C22.2 No. 5-02
 Approval to UL 489 as
circuit breaker
 System and transformer protection
 Approval to CSA C22.2 No. 14 and UL 508 as:
 „Manual Motor Controller“
See UL report (UL File No. E47705) for further information
 "Self-Protected Combination Motor Controller" when
using terminal block
3RT 1946-4GA07
© Siemens AG 2012. All rights reserved.
Industry Sector
5TE6 socket
5TE6 socket
© Siemens AG 2012. All rights reserved.
Industry Sector
5TE6 socket
Technical data
Approvals
Device selection
To IEC standard:
5TE6 800 socket
To UL standard:
5TE6 804 socket
© Siemens AG 2012. All rights reserved.
Industry Sector
5TE6 socket
Technical data
5TE6 800 socket
5TE6 804 socket
 Rated operational voltage
230 V AC
 Rated operational voltage
125 V AC
 Rated operational current 16 A
 Rated operational current 15A
 Conductor cross-sections
up to 6 mm²
 Conductor cross-sections
up to AWG 10
 Ambient temperature
from -10 °C to +55 °C
 Ambient temperature
from -10 °C to +55 °C
 Degree of protection IP 20
For further information, go to www.siemens.de/sirius
© Siemens AG 2012. All rights reserved.
Industry Sector
5TE6 socket
Approvals
5TE6 800 socket
5TE6 804 socket
 Approval to IEC 60204-1
 Approval to UL 498
 Suitable for mounting in
distribution boards acc. to DIN 43880
 Approval to
CSA C22.2 No.182.3M
 Suitable for installation on
DIN rails in switchboards and
distribution boards acc. to DIN 60715
 Connection of plug-and-play communication devices
in switchboards
 Connection of plug-and-play
communication devices in
switchboards
See UL report (UL File No. E258598) for further information
© Siemens AG 2012. All rights reserved.
Industry Sector
Busbar system
Busbar system
© Siemens AG 2012. All rights reserved.
Industry Sector
Busbar system
Technical data
Approvals
Device selection
To IEC standard:
8US busbar
system (40 mm)
To UL standard:
8US busbar
system (60 mm)
© Siemens AG 2012. All rights reserved.
Industry Sector
Busbar system
Technical data
8US busbar system (40 mm busbar center-to-center spacing)
8US busbar system (60 mm busbar center-to-center spacing)
 Rated insulation voltage
Ui 1,000 V AC
 Rated insulation voltage
Ui 1,000 V AC
 Rated current
up to 400 A (40 mm)
 Rated current up to 630 A
(60 mm, basic profile)
 Short-circuit strength
to IEC see characteristics
 Rated current up to 1,600 A
(60 mm, special profile)
For further information, go to www.siemens.de/lowvoltage
 Short-circuit strength
to IEC see characteristics
For further information, go to www.siemens.de/lowvoltage
SC characteristics (IEC)
© Siemens AG 2012. All rights reserved.
Industry Sector
Busbar system
Approvals
8US busbar system (40 mm busbar center-to-center spacing)
8US busbar system (60 mm busbar center-to-center spacing)
 Approval
to EN 13601
 Approval
to IEC 60439-1
and IEC 61439-2
 Approval
to IEC 60439-1
and IEC 61439-2
 Approval to UL 508 only for use
in the branch circuit
 Approval to CSA C22.2 No.14/ No.39
 Approval to UL 508:
 Use in feeder and branch circuit
See UL report (UL File No. E148698) for further information
© Siemens AG 2012. All rights reserved.
Industry Sector
Busbar system
Characteristics for rated peak withstand current
40 mm busbar system
60 mm busbar system
 The characteristics are only applicable for IEC applications!
 They must not be used for UL applications!!
© Siemens AG 2012. All rights reserved.
Industry Sector
3RT2 contactor
3RT2 contactor
© Siemens AG 2012. All rights reserved.
Industry Sector
3RT2 contactor
Technical data
Approvals
Device selection
3RT2 contactor
© Siemens AG 2012. All rights reserved.
Industry Sector
3RT2 contactor
Technical data
3RT2 contactor
 Sizes S00 and S0
 Screw terminal, spring-loaded, ring cable lug, and
solder pin (S00) connections
IEC – ratings
 Rated operational current up to max. 50 A
(depending on the size and operating temperature)
 Rated operational voltage up to max. 690 V AC
 Rated frequency 50/60 Hz
CSA and UL – ratings
 Rated operational current up to max. 42 A
(depending on the size and operating temperature)
 Rated operational voltage up to max. 600 V AC
 Rated frequency 60 Hz
 Horsepower rating up to max. 25 hp (depending on the size and operating voltage)
For further information, go to www.siemens.de/sirius
© Siemens AG 2012. All rights reserved.
Industry Sector
3RT2 contactor
Approvals
3RT2 contactor
 Approval to IEC 60947-1 and DIN EN 60947-1
 Approval to IEC 60947-4-1 and DIN EN 60947-4-1
 Approval to IEC 60947-5-1 and DIN EN 60947-5-1 (auxiliary switch)
 Approval to CSA C22.2 No. 14
 Approval to UL 508
See UL report (UL File No. E31519) for further information
© Siemens AG 2012. All rights reserved.
Industry Sector
3RA2 load feeder with 3RV29 infeed system
3RA2 load feeder
(3RV2 motor starter protector + 3RT2 contactor)
with 3RV29 infeed system
© Siemens AG 2012. All rights reserved.
Industry Sector
3RA2 load feeder with 3RV29 infeed system
3RA2 load feeder
with 3RV29 infeed system
© Siemens AG 2012. All rights reserved.
Industry Sector
3RA2 load feeder
Technical data
Approvals
Device selection
3RA2 load feeder
© Siemens AG 2012. All rights reserved.
Industry Sector
3RV29 infeed system
Technical data
Approvals
Device selection
3RV29 infeed system
© Siemens AG 2012. All rights reserved.
Industry Sector
3RA2 load feeder
Technical data
3RA2 load feeder
 Fuseless load feeder consisting of
3RV2 circuit breaker and 3RT2 contactor
 Rated current up to max. 32 A (depending on the size)
 For rated currents > 32 A up to 100 A,
3RA1 load feeders can be used
 Available as a pre-assembled complete unit or for customer assembly
(up to 40 A)
 Rated voltage up to max. 690 V AC
 Short-circuit strength up to 150 kA at 400 V AC 50/60 Hz
 Screw terminal and spring loaded connections
(customer assembly)
 Sizes S00 and S0
For further information, go to www.siemens.de/sirius
© Siemens AG 2012. All rights reserved.
Industry Sector
3RA2 load feeder
Approvals
3RA2 load feeder
 Approval to IEC 60947-1, IEC 60947-2, and IEC 60947-4-1
 Exhibits isolating features conforming to IEC 60947-2
and can be used as a main switch according to DIN EN 60204
 Approval to CSA C22.2 No. 14
 Approval to UL 508 as:
 Combination Motor Controller Type F
See UL report (UL File No. E156943) for further information
© Siemens AG 2012. All rights reserved.
Industry Sector
3RV29 infeed system
Technical data
3RV29 infeed system
 High flexibility for installation and expansion
 Compact design saves space
 Infeed either on the left or right with conductor cross-section up to 25 mm2
 Spring-loaded and screw terminal connections
 Sizes S00 and S0
 Current carrying capacity up to max. 63 A
For further information, go to www.siemens.de/sirius
© Siemens AG 2012. All rights reserved.
Industry Sector
3RV29 infeed system
Approvals
3RV29 infeed system
 Approval to IEC 60947-1, IEC 60947-2, IEC 60947-4-1
 Approval to UL 508 for the installation of:
 Self Protected Combination Motor Controller Type E
 Self Protected Combination Motor Controller Type F
(corresponds to type E + contactor)
See UL report (UL File No. E148698) for further information
© Siemens AG 2012. All rights reserved.
Industry Sector
ALPHA Fix terminal blocks
ALPHA Fix terminal blocks
© Siemens AG 2012. All rights reserved.
Industry Sector
ALPHA FIX terminal blocks
Technical data
Approvals
Device selection
ALPHA FIX terminal blocks
© Siemens AG 2012. All rights reserved.
Industry Sector
ALPHA Fix terminal blocks
Technical data
ALPHA Fix terminal blocks
 Space-saving connection of incoming and outgoing lines in
switchboards and Control Panels
 Connection method: Screw terminal and spring-loaded
connections, in-push-out terminal, combination plug-in
terminal, and insulation displacement termination
 Quick installation saving time with high contact
reliability
 Rated uninterrupted current up to 192 A
 Rated insulation voltage up to 800 V
 Ratings may vary (IEC/UL)!!
For further information, go to www.siemens.de/lowvoltage/support
© Siemens AG 2012. All rights reserved.
Industry Sector
ALPHA FIX Terminal Blocks
Technical Data
8WA1 screw-type terminal
 The tried-and-tested screw-type connection system features double insulation
and is closed on both sides. These terminals are particularly stable and offer a
high mechanical and thermal resistance.
 Available as through-type, PE and PEN terminals in various terminal sizes
 2.5 mm², 4 mm², 6 mm², 16 mm², 35 mm², 70 mm²
8WH1 screw-type terminal
 The screw-type connection system offers a convincing compact design and optimum ease
of handling. The clamping body's plasticity prevents clamped wires from slipping.
 Support of applications up to 1,000 V DC
 Available as through-type and PE terminals in various terminal sizes
 2.5 mm², 4 mm², 6 mm², 10 mm², 16 mm², 35 mm²
For further information, see www.siemens.com/lowvoltage
© Siemens AG 2012. All rights reserved.
Industry Sector
ALPHA FIX Terminal Blocks
Technical Data
8WA2 spring-loaded terminal
 With the spring-loaded connection system, constant pressure is applied to the
conductor by the tension spring, which results in outstanding contact reliability
– also with vibration-sensitive applications.
 Available as through-type and PE terminals in various terminal sizes
(2.5 mm², 4 mm², 6 mm², 16 mm², 35 mm²)
 Accessories for 8WA and 8WH
Various accessories for terminal blocks, 8WH labeling accessories and mounting
accessories, labeling plates with inscription, 8WA mounting accessories
For further information, see www.siemens.com/lowvoltage
© Siemens AG 2012. All rights reserved.
Industry Sector
ALPHA Fix terminal blocks
Approvals
ALPHA Fix terminal blocks
 Approval to IEC 60947-7-1
 Approval to UL 1059 (UL recognized)
 Conditions of acceptability must be observed
when using the components
 Approval to CSA 6228-01
See UL report (UL File No. E80027) for further information
© Siemens AG 2012. All rights reserved.
Industry Sector
3RA6 compact starter with 3RA68 infeed system
3RA6 compact starter
with 3RA68 infeed system
© Siemens AG 2012. All rights reserved.
Industry Sector
3RA6 compact starter with 3RA68 infeed system
3RA6 compact starter
with 3RA68 infeed system
© Siemens AG 2012. All rights reserved.
Industry Sector
3RA6 compact starter
Technical data
Approvals
Device selection
3RA6 compact starter
© Siemens AG 2012. All rights reserved.
Industry Sector
3RA6 compact starter
Technical data
3RA6 compact starter
 Universal fuseless motor feeder
 Combines the functions of a circuit breaker, a contactor,
and an overload relay in a single enclosure
 Rated voltage up to 690 V
 Rated current up to 32 A
 For load feeders > 32 A up to 100 A 3RA1 series
 For load feeders > 100 A, 3VL circuit breakers
and 3RT contactors can be used
 Rated frequency 50/60 Hz
 Rated short-circuit breaking capacity at AC 50/60 Hz
400 V up to 53 kA
 Connection method: Screw terminal connection, spring-loaded connection
For further information, go to www.siemens.de/sirius
© Siemens AG 2012. All rights reserved.
Industry Sector
3RA6 compact starter
Approvals
3RA6 compact starter
 Approval to IEC 60947-6-2 and IEC 60947-2
 Exhibits isolating features conforming to IEC 60947-2
and can be used as a main switch according to
DIN EN 60204
 Approval to UL 508 (when using the corresponding infeed system
e.g. 3RA68 12 - 8AB/8AC) as:
 Manual Motor Controller
 Self Protected Combination Motor Controller Type E
 Group Application
 Suitable for Tap Conductor Protection
See UL report (UL File No. E47705) for further information
© Siemens AG 2012. All rights reserved.
Industry Sector
3RA68 infeed system for 3RA6 compact starter
Technical data
Approvals
Device selection
3RA6 compact starter
with 3RA68 infeed system
© Siemens AG 2012. All rights reserved.
Industry Sector
3RA68 infeed system for 3RA6 compact starter
Technical data
3RA68 infeed system for 3RA6 compact starter
 High flexibility for installation and expansion
 Compact design saves space
 Devices are mounted simply by clicking them into place
 No need for complex wiring
 Spring-loaded and screw terminal connections
 Current carrying capacity up to max. 100 A
Component
Maximum rated
operational current in A
Screw-type infeed 50/70 mm2
100
Screw-type infeed 25/35 mm2
63
Spring-loaded infeed 25/35 mm2
63
Expansion plug
63
For further information, go to www.siemens.de/sirius
© Siemens AG 2012. All rights reserved.
Industry Sector
3RA68 Infeed System for 3RA6 Compact Starter
Approvals
3RA68 infeed system for 3RA6 compact starter
 Approval according to UL 508 for the installation of:
 Self-protected combination motor controller type E
 Manual motor controller
 Group application
 Suitable for tap conductor protection
 Approval according to CAN/CSA-C22.2 No. 0.4-04
 Bonding of electrical equipment
 Approval according to CSA-C22.2 No. 14-10
 Industrial control equipment
See UL report (UL File No. E148698) for further information
© Siemens AG 2012. All rights reserved.
Industry Sector
3RA2 load feeder on busbar with infeed
3RA2 load feeder
(3RV2 motor starter protector + 3RT2
contactor) on busbar with infeed
© Siemens AG 2012. All rights reserved.
Industry Sector
3RA2 load feeder on busbar with infeed
3RA2 load feeder
on 8US busbar
with 8US19 infeed
© Siemens AG 2012. All rights reserved.
Industry Sector
8US19 infeed
Device selection
8US19 infeed
© Siemens AG 2012. All rights reserved.
Industry Sector
3RA2 load feeder with 8US busbar adapter
3RA2 load feeder with
8US busbar adapter
© Siemens AG 2012. All rights reserved.
Industry Sector
3RA2 load feeder
3RA2 load feeder
3RV2 circuit breaker + 3RT2 contactor
© Siemens AG 2012. All rights reserved.
Industry Sector
3RV20 circuit breaker
Technical data
Approvals
Device selection
3RV20 circuit breaker
as motor circuit breaker
© Siemens AG 2012. All rights reserved.
Industry Sector
3RV20 Circuit Breaker as Motor Circuit Breaker
Technical Data
3RV20 circuit breaker as motor circuit breaker
 Rated current up to 40 A (depending on the size)
Up to 32 A: Assembly as feeder with connecting module
and contactor or available as 3RA2 feeder
 Rated operational voltage up to max. 690 V AC (IEC)
 Rated operational voltage up to max. 600 V AC (UL, CSA)
 Short-circuit strength up to 100 kA (depending on the voltage)
 Screw-type connection system (up to 40 A), spring-loaded connection
system and ring cable lug connection system (up to 32 A)
For UL applications:
3RV29 28-1H terminal block
 Support of practical conductor cross-sections :
Size S00 max. 4 mm2 / size S0 max. 10 mm2
For further information, see www.siemens.com/sirius
© Siemens AG 2012. All rights reserved.
Industry Sector
3RV20 circuit breaker as motor circuit breaker
Approvals
3RV20 circuit breaker as motor circuit breaker
 Approval to IEC 60947-1, IEC 60947-2 and IEC 60947-4-1 as:
 Short-circuit and motor protection
 System and transformer protection
 Main and emergency off protection
 Approval to CSA C22.2 No. 14
 Approval to UL 508
For UL applications:
3RV29 28-1H terminal block
 „Manual Motor Controller“
 "Self Protected Combination Motor Controller"
when using 3RV29 28-1H terminal block
or 3RV29 28-1K phase barriers
See UL report (UL File No. E47705) for further information
© Siemens AG 2012. All rights reserved.
Industry Sector
8US busbar adapter
Device selection
8US busbar adapter
© Siemens AG 2012. All rights reserved.
Industry Sector
3RW44 soft starter
3RW44 soft starter
© Siemens AG 2012. All rights reserved.
Industry Sector
3RW44 soft starter
Technical data
Approvals
Device selection
3RW44 soft starter
© Siemens AG 2012. All rights reserved.
Industry Sector
3RW44 soft starter
Technical data
3RW44 soft starter
 The soft starter for High Feature applications
 Rated operational current up to 1,214 A
(depending on the size and temperature)
 Rated operational voltage up to 690 V AC
 Rated frequency 50 to 60 Hz
 Screw terminal and spring-loaded connections
 Inside-delta circuit to reduce size and device
costs (smaller size for higher power possible)
 Easy to install and integrate in motor feeders
 Numerous additional functions
For further information, go to www.siemens.de/sirius
© Siemens AG 2012. All rights reserved.
Industry Sector
3RW44 soft starter
Approvals
3RW44 soft starter
 Approval to IEC 60947- 4 - 2
 Approval to UL 508
 Approval to CSA C22.2 No. 14
See UL report (UL File No. E143112) for further information
© Siemens AG 2012. All rights reserved.
Industry Sector
SITOR semiconductor fuse
SITOR semiconductor fuse
© Siemens AG 2012. All rights reserved.
Industry Sector
SITOR semiconductor fuse
Technical data
Approvals
Device selection
SITOR semiconductor fuse
© Siemens AG 2012. All rights reserved.
Industry Sector
SITOR semiconductor fuse
Technical data
SITOR semiconductor fuse
 Fuses to protect power semiconductors against the
effects of a short circuit
 High-speed switch-off characteristic
 Available with various types of connection and in different designs:
LV HRC, cylindrical fuse, and SILIZED
Cylindrical fuse design
 Rated current up to 100 A (depending on the size)
 Rated voltage up to max. 690 V AC
 Rated conditional short-circuit current at 400 V up to 100 kA
(depending on the size)
 Conductor cross-section up to 50 mm²/ AWG 1/0
(depending on the size)
For further information, go to www.siemens.de/sirius
© Siemens AG 2012. All rights reserved.
Industry Sector
SITOR semiconductor fuse
Approvals
SITOR semiconductor fuse
Cylindrical fuse design
 Cylindrical fuse links:
 Approval to IEC 60269-4
 Approval to UL 248-13 and CSA C22.2 No. 248.13
 Cylindrical fuse holders:
 Approval to IEC 60269-2 and IEC 60947-3
 Approval to UL 512 and CSA C22.2 No. 39-M
 Cylindrical fuse bases:
 Approval to IEC 60269-2 and IEC 60947-3
 Approval to UL 512 and CSA C22.2 No. 39-M
See UL report (UL File No. E167357) for further information
© Siemens AG 2012. All rights reserved.
Industry Sector
Class CC fuse system
Class CC
fuse system
© Siemens AG 2012. All rights reserved.
Industry Sector
Class CC fuse system
Technical data
Approvals
Device selection
Class CC
fuse system
© Siemens AG 2012. All rights reserved.
Industry Sector
Class CC fuse system
Technical data
Class CC fuse system
 Class CC fuse system for use as
branch circuit protection
 Rated operational current up to 30 A
 In uninterrupted duty, only 80% of the rated current
is permitted (acc. to NEC 210.20(A))
 Rated operational voltage 600 V AC
(fuse holder and fuse links)
 Conductor cross-sections up to 25 mm²/AWG 4
 Rated breaking capacity 200 kA (fuse links)
For further information, go to www.siemens.de/lowvoltage
© Siemens AG 2012. All rights reserved.
Industry Sector
Class CC fuse system
Approvals
Class CC fuse system
 Approval to UL 512 (fuse holders)
 Approval to UL 248-4 (fuse links)
 Approval to CSA C22.2 No. 14
 No IEC approval!!
See UL report (UL File No. E258218) for further information
© Siemens AG 2012. All rights reserved.
Industry Sector
Distributed IO ET 200S motor starter
Distributed IO
ET 200S motor starter
© Siemens AG 2012. All rights reserved.
Industry Sector
Distributed IO ET 200S motor starter
Technical data
Approvals
Device selection
Distributed IO
ET 200S motor starter
© Siemens AG 2012. All rights reserved.
Industry Sector
Distributed IO ET 200S motor starter
Technical data
Distributed IO ET 200S motor starter
 Multifunctional motor starter for distributed drive solutions
 Functional scope depends on the motor version:
 Standard motor starter
 High Feature motor starter
 Fail-safe motor starter
 Interface modules (IM) are used to connect to
PROFINET and PROFIBUS DP bus systems
 Rated operational current for terminal modules TM-D up to 50 A
 Rated operational current for motor starter up to 16 A
 Rated operational voltage up to 500 V (IEC)
 Rated operational voltage up to 600 V (UL/CSA)
 Rated breaking capacity at 400 V up to 50 kA
 Power of three-phase motors at 500 V up to 7.5 kW
 Conductor cross-sections up to 10 mm²/AWG 10
For further information, go to www.siemens.de/ET200S
© Siemens AG 2012. All rights reserved.
Industry Sector
Distributed IO ET 200S motor starter
Approvals
Distributed IO ET 200S motor starter
 Approval to IEC 60947-4-2 and IEC 60947-4-1
 SIL 3 to IEC 62061 (ET 200S fail-safe version)
 Approval to UL 508
 Approval to CSA C22.2 No. 14
See UL report (UL File No. E31519) for further information
© Siemens AG 2012. All rights reserved.
Industry Sector
NEOZED fuse system (comfort base)
NEOZED fuse system
(comfort base)
© Siemens AG 2012. All rights reserved.
Industry Sector
NEOZED fuse system (comfort base)
Technical data
Approvals
Device selection
NEOZED fuse system
(comfort base)
© Siemens AG 2012. All rights reserved.
Industry Sector
NEOZED fuse system (comfort base)
Technical data
NEOZED fuse system (comfort base)
 Fuse system for use in distribution systems and in industrial
switchboards
 Compact design saving space in the Panel
 Rated operational current up to 100 A (fuse links)
 Rated operational current up to 63 A (comfort base)
 Rated operational voltage 400 V AC/250 V DC
 Rated breaking capacity 50 kA AC/8 kA DC
 Operating class gG
 Conductor cross-sections up to 35 mm²
 1- and 3-pole device versions
For further information, go to www.siemens.de/lowvoltage
© Siemens AG 2012. All rights reserved.
Industry Sector
NEOZED fuse system (comfort base)
Approvals
NEOZED fuse system (comfort base)
 Fuse links:
 Approval to IEC 60269-3
 Approval to DIN VDE 0636-3
 Comfort base:
 Approval to IEC 60269-3
 Approval to DIN VDE 0636-3
 No UL/CSA approval!
© Siemens AG 2012. All rights reserved.
Industry Sector
3TK28 safety relay
3TK28 safety relay
© Siemens AG 2012. All rights reserved.
Industry Sector
3TK28 safety relay
Technical data
Approvals
Device selection
3TK28 safety relay
© Siemens AG 2012. All rights reserved.
Industry Sector
3TK28 safety relay
Technical data
3TK28 safety relay
 Safety relay with solid-state, relay or contactor relay
enabling circuit plus special functions
 Evaluation unit of an end-to-end safety chain
(sensing, evaluating, switching off)
 Can be used in all safety applications thanks to compliance with
the most exacting safety requirements
 Compact and space-saving SIRIUS design
 Highly flexible where connection and expansion are concerned,
making subsequent modification easy
 Screw terminal and spring-loaded connections
For further information, go to www.siemens.de/sicherheitsschaltgeraete
© Siemens AG 2012. All rights reserved.
Industry Sector
3TK28 safety relay
Approvals
3TK28 safety relay
 Meets the most exacting safety requirements
 Approval to EN ISO 13849-1
 Performance Level (PL) e
 Approval to IEC 61508
 Safety Integrity Level (SIL) 3
 Approval to UL/CSA
See UL report (UL File No. E44653) for further information
© Siemens AG 2012. All rights reserved.
Industry Sector
3RK3 modular safety system
Modular
safety system 3RK3
© Siemens AG 2012. All rights reserved.
Industry Sector
3RK3 modular safety system
Technical data
Approvals
Device selection
3RK3 modular safety system
© Siemens AG 2012. All rights reserved.
Industry Sector
3RK3 Modular Safety System
Technical Data
3RK3 modular safety system
 The MSS 3RK3 is a freely parameterizable modular
safety relay comprising:
 Central unit (in Basic or Advanced design)
 Expansion module (I/O module)
 Interface module (PROFIBUS DP interface)
 Operating and monitoring module (diagnostics module)
 High flexibility and reliability in terms of planning
thanks to modular design
 Compact and space-saving SIRIUS design
 Screw-type and spring-loaded connection system
 Direct-data exchange between multiple MSS units
 Distribution of sensors and actuators possible via AS-Interface
For further information, see www.siemens.com/sirius-mms
© Siemens AG 2012. All rights reserved.
Industry Sector
3TK28 safety relay
Approvals
3RK3 modular safety system
 Meets the most exacting safety requirements
 Approval to ISO 13849-1
 Performance Level (PL) e
 Approval to IEC 61508
 Safety Integrity Level (SIL) 3
 Approval to UL/CSA
See UL report (UL File No. .?????) for further information
© Siemens AG 2012. All rights reserved.
Industry Sector
SIMOCODE motor management system
with current/voltage measuring module
SIMOCODE motor management
system with
current/voltage measuring module
© Siemens AG 2012. All rights reserved.
Industry Sector
SIMOCODE 3UF7 motor management system
Technical data
Approvals
Device selection
SIMOCODE 3UF7 motor management system
© Siemens AG 2012. All rights reserved.
Industry Sector
SIMOCODE 3UF7 Motor Management System
Technical Data
SIMOCODE 3UF7 motor management system
 Modular motor management system for fixed-speed motors
 Multifunctional and electronic full motor protection,
independent of the automation system
 Integrated control functions for motor control (instead of hardware)
 Detailed diagnostic, service and operating data
 Comprehensive communication via PROFIBUS or PROFINET / OPC UA / web server
For further information, see www.siemens.com/simocode
© Siemens AG 2012. All rights reserved.
Industry Sector
SIMOCODE 3UF7 motor management system
Approvals
SIMOCODE 3UF7 motor management system
 Meets the most exacting safety requirements
 Performance Level (PL) e to ISO
 Safety Integrity Level (SIL) 3 to IEC
 Approval to EN 13849-1
 Approval to IEC 61508
 Approval to CSA C22.2 No. 14
 Approval to UL 508
See UL report (UL File No. E44653) for further information
© Siemens AG 2012. All rights reserved.
Industry Sector
SIMOCODE motor management system
with current/voltage measuring module
Device selection
Current/voltage measuring module for
SIMOCODE motor management system
© Siemens AG 2012. All rights reserved.
Industry Sector
3NP1 LV HRC fuse switch disconnector
3NP1 LV HRC fuse
switch disconnector
© Siemens AG 2012. All rights reserved.
Industry Sector
3NP1 LV HRC fuse switch disconnector
Technical data
Approvals
Device selection
3NP1 LV HRC fuse switch disconnector
© Siemens AG 2012. All rights reserved.
Industry Sector
3NP1 LV HRC fuse switch disconnector
Technical data
3NP1 LV HRC fuse switch disconnector
 Fuse switch disconnector for the protection and switching of
many different types of load including:
 Combination motor controllers
 In conjunction with SITOR fuses for the protection of
frequency converters and soft starters
 Protection of communication modules
 Group protection of small loads
 Rated operational current up to 630 A
 Rated operational voltage up to 690 V AC
 Rated frequency 50/60 Hz
 Short-circuit strength at 690 V up to 120 kA
For further information, go to www.siemens.de/lowvoltage
© Siemens AG 2012. All rights reserved.
Industry Sector
3NP1 LV HRC fuse switch disconnector 3NP1
Approvals
3NP1 LV HRC fuse switch disconnector
 Approval to IEC 60947-1 and IEC 60947-1
 Approval to EN 60947-1 and EN 60947-3
 Approval to CSA C22.2 No. 39-M
 Approval to UL 512
See UL report (UL File No. .?????) for further information
© Siemens AG 2012. All rights reserved.
Industry Sector
3RF solid-state switching device
3RF solid-state
switching device
© Siemens AG 2012. All rights reserved.
Industry Sector
3RF solid-state switching device
Technical data
Approvals
Device selection
3RF solid-state switching
device
© Siemens AG 2012. All rights reserved.
Industry Sector
3RF solid-state switching device
Technical data
3RF solid-state switching device
 Solid-state switching device used for the frequent switching
of motors, small drives, and valves
 Long service life: More than 100 million operating cycles
 Wear-free and noiseless switching for high system availability
 Rated operational current up to 16 A
 Rated operational voltage 48 to 600 V AC
 Rated control voltage 24 V DC/110 V AC up to 230 AC
 Rated frequency 50/60 Hz ± 10%
 Screw terminal and spring-loaded connections
 Conductor cross-sections up to 10 mm²/AWG 10
For further information, go to www.siemens.de/halbleiterschaltgeraete
© Siemens AG 2012. All rights reserved.
Industry Sector
3RF solid-state switching device
Approvals
3RF solid-state switching device
 Approval to IEC 60947-4-2
 Approval to CSA C22.2 No. 14
 Approval to UL 508
See UL report (UL File No. E143112) for further information
© Siemens AG 2012. All rights reserved.
Industry Sector
3RB3 overload relay
3RB3 overload relay
© Siemens AG 2012. All rights reserved.
Industry Sector
3RB3 overload relay
Technical data
Approvals
Device selection
3RB3 overload relay
© Siemens AG 2012. All rights reserved.
Industry Sector
3RB3 overload relay
Technical data
3RB3 overload relay
 Solid-state overload relay for inverse-time delayed
overload protection of three-phase motors
 Not suitable for protecting single-phase
AC or DC loads
 Rated operational current from 0.4 to 40 A
 Rated operational voltage up to 690 V AC
 Available in sizes S00 and S0
 Optional direct mounting on contactor or stand-alone assembly
 Large wide setting range of 1:4
 Spring-loaded and screw terminal connections
 Conductor cross-sections up to 10 mm²/AWG 6
For further information, go to www.siemens.de/lowvoltage
© Siemens AG 2012. All rights reserved.
Industry Sector
3RB3 overload relay
Approvals
3RB3 overload relay
 Approval to IEC 60947-4-1, IEC 60947-5-1
 Approval to CSA C22.2 No. 14
 Approval to UL 508
See UL report (UL File No. E44653) for further information
© Siemens AG 2012. All rights reserved.
Industry Sector
3RR2 monitoring relay
3RR2 monitoring relay
© Siemens AG 2012. All rights reserved.
Industry Sector
3RR2 monitoring relay
Technical data
Approvals
Device selection
3RR2 monitoring relay
© Siemens AG 2012. All rights reserved.
Industry Sector
3RR2 Monitoring Relay
Technical Data
3RR2 monitoring relay
 Monitoring relay for optimum protection of machines and systems
 One device for overload and underload monitoring
 Direct mounting on RT2 contactor
 Display for indication of values
 Rated operational current from 1.6 to 40 A
 Rated operational voltage up to 690 V AC
 Rated control supply voltage from 24 to 240 V AC/DC
 Screw-type and spring-loaded connection system
 Short-circuit strength up to 100 kA with 690 V
(in combination with suitable protective device)
For further information, see link
© Siemens AG 2012. All rights reserved.
Industry Sector
3RR2 monitoring relay
Approvals
3RR2 monitoring relay
 Approval to IEC 60947-4-1
 Approval to CSA C22.2 No.14
 Approval to UL 508
See UL report (UL File No. E44653) for further information
© Siemens AG 2012. All rights reserved.
Industry Sector
NEOZED bus-mounting base
NEOZED
bus-mounting base
© Siemens AG 2012. All rights reserved.
Industry Sector
NEOZED bus-mounting base
Technical data
Approvals
Device selection
NEOZED
bus-mounting base
© Siemens AG 2012. All rights reserved.
Industry Sector
NEOZED bus-mounting base
Technical data
NEOZED bus-mounting base
 NEOZED bus-mounting base for 3-pole 60 mm busbar systems
 Available in sizes D01 and D02
 Rated operational current up to 63 A
 Rated operational voltage 400 V AC/250 V DC
 Rated operating frequency 50 Hz
 Conditional short-circuit current 50 kA AC/8 kA DC
For further information, go to www.siemens.de/sentron
© Siemens AG 2012. All rights reserved.
Industry Sector
NEOZED bus-mounting base
Approvals
NEOZED bus-mounting base
 Approval to IEC 60269-3
 No CSA or UL approval!!
© Siemens AG 2012. All rights reserved.
Industry Sector
DIAZED bus-mounting base
DIAZED
bus-mounting base
© Siemens AG 2012. All rights reserved.
Industry Sector
DIAZED bus-mounting base
Technical data
Approvals
Device selection
DIAZED
bus-mounting base
© Siemens AG 2012. All rights reserved.
Industry Sector
DIAZED bus-mounting base
Technical data
DIAZED bus-mounting base
 DIAZED bus-mounting base for 3-pole 60 mm busbar systems
 Suitable for the use of DIAZED adapter rings and DIAZED adapter screws
 Available in sizes DII and DIII
 Rated operational current up to 63 A
 Rated operational voltage 500 V AC/DC (size DII),
690 V AC/600 V DC (size DIII)
 Rated frequency 50 Hz
 Conditional short-circuit current 50 kA AC/8 kA DC
For further information, go to www.siemens.de/lowvoltage
© Siemens AG 2012. All rights reserved.
Industry Sector
DIAZED bus-mounting base
Approvals
DIAZED bus-mounting base
 Approval to IEC 60269-3
 No CSA or UL approval!!
© Siemens AG 2012. All rights reserved.
Industry Sector
SIRIUS 3SE5 position switch
SIRIUS 3SE5
position switch
© Siemens AG 2012. All rights reserved.
Industry Sector
SIRIUS 3SE5 position switch
Technical data
Approvals
Device selection
SIRIUS 3SE5 position switch
© Siemens AG 2012. All rights reserved.
Industry Sector
SIRIUS 3SE5 position switch
Technical data
SIRIUS 3SE5 position switch
 Position switch with tumbler to prevent protective doors opening
at random or accidentally when there might still be a
prevailing risk due to the operating status of the machine or system
 Plastic and metal enclosure
 Wide range of actuators
 Devices with ASIsafe electronics integrated in the enclosure
 Rated operational voltage 50/60 Hz 230 V AC/24 V DC
 Rated operational current up to 50/60 Hz 6 A AC/3 A DC
For further information, go to www.siemens.de/sirius-erfassen
© Siemens AG 2012. All rights reserved.
Industry Sector
3SE5 SIRIUS position switch
Approvals
SIRIUS 3SE5 position switch
 Approval to IEC 60947-1 and IEC 60947-5-1
 Approval to CSA C22.2 No. 14
 UL 508, UL 50, and UL 746-C approval
See UL report (UL File No. E44653) for further information
© Siemens AG 2012. All rights reserved.
Industry Sector
SITOP power supply
SITOP power supply
© Siemens AG 2012. All rights reserved.
Industry Sector
SITOP power supply
Technical data
Approvals
Device selection
SITOP power supply
© Siemens AG 2012. All rights reserved.
Industry Sector
SITOP power supply
Technical data
SITOP power supply
 Primary switched-mode power supplies convert 1-, 2-, or 3-phase
line voltages and direct voltages into
stabilized 24 V voltages (SITOP smart)
 Versions for other output voltages including 5, 12, and 48 V DC
are available (SITOP compact, modular, etc.)
 High overload capability
 Rated output current from 2 to 40 A
 Rated output voltage 24 V DC (±3%)
 Rated input voltage up to 550 V AC
For further information, go to www.siemens.de/sirius-versorgen
© Siemens AG 2012. All rights reserved.
Industry Sector
SITOP power supply
Approvals
SITOP power supply
 Approval to IEC 60950-1
 Approval to CSA C22.2 No. 60950-1-3
 Approval to UL 508
 Certified in accordance with ATEX guidelines
See UL report (UL File No. E197259) for further information
© Siemens AG 2012. All rights reserved.
Industry Sector
7KM PAC measuring instrument
7KM PAC measuring
instrument
© Siemens AG 2012. All rights reserved.
Industry Sector
7KM PAC measuring instrument
Technical data
Approvals
Device selection
7KM PAC measuring instrument
© Siemens AG 2012. All rights reserved.
Industry Sector
7KM PAC measuring instrument
Technical data
7KM PAC measuring instrument
 7KM PAC measuring instrument for measuring and displaying all relevant
line system parameters in low-voltage power distribution
 Can be used to take measurements in 3- and 4-wire systems (TN, TT, IT)
 Can be used in 50/60 Hz systems with up to 690/400 V
 Integrated communications interfaces
 Optional expansion module for additional interfaces
 Front mounting or standard rail mounting
For further information, go to www.siemens.de/lowvoltage
© Siemens AG 2012. All rights reserved.
Industry Sector
7KM PAC measuring instrument
Approvals
7KM PAC measuring instrument
 Approval to IEC 61010-1
 Approval to CSA C22.2 No. 61010.1
 Approval to UL 61010-1
 Enclosure Type 5 acc. to UL 50
See UL report (UL File No. E314880) for further information
© Siemens AG 2012. All rights reserved.
Industry Sector
EMERGENCY STOP PUSHBUTTON (3SB3 commanding and signaling device)
EMERGENCY STOP PUSHBUTTON
(3SB3 commanding and signaling device)
© Siemens AG 2012. All rights reserved.
Industry Sector
EMERGENCY STOP PUSHBUTTON (3SB3 commanding and signaling device)
Technical data
Approvals
Device selection
EMERGENCY STOP PUSHBUTTON
(3SB3 commanding and signaling device)
© Siemens AG 2012. All rights reserved.
Industry Sector
EMERGENCY STOP PUSHBUTTON (3SB3 commanding and signaling device)
Technical data
EMERGENCY STOP PUSHBUTTON (3SB3 commanding and signaling device)
 Modular design commanding and signaling device range for
front panel mounting and rear conductor connection
 Modern industrial design and quick mounting
 Supplied in plastic or metal enclosure
 Spring-loaded, solder pin, and screw terminal connections
IEC ratings
 Rated operational current up to 10 A
 Rated operational voltage up to 400 V AC/230 V DC
UL/CSA ratings
 Rated operational current up to 10 A
 Rated operational voltage up to 300 V AC
For further information, go to www.siemens.de/sirius
© Siemens AG 2012. All rights reserved.
Industry Sector
EMERGENCY STOP PUSHBUTTON (3SB3 commanding and signaling device)
Approvals
EMERGENCY STOP PUSHBUTTON (3SB3 commanding and signaling device)
 Approval to IEC 60947-5-1 and IEC 60947-5-5
 Approval to CSA C22.2 No. 14
 Approval to UL 508
See UL report (UL File No. E44653) for further information
© Siemens AG 2012. All rights reserved.
Industry Sector
Main and emergency off switch
Main and emergency off switch
© Siemens AG 2012. All rights reserved.
Industry Sector
Main and emergency off switch
Main and emergency off switch
8UC7 rotary operating mechanism
with 3VL circuit breaker
8UC7 rotary operating mechanism
with 3VL circuit breaker and
8UC94 00 interlocking module
© Siemens AG 2012. All rights reserved.
Industry Sector
Main switch
(3VL circuit breaker)
Main switch
(3VL circuit breaker)
© Siemens AG 2012. All rights reserved.
Industry Sector
8UC7 rotary operating mechanism
8UC7 rotary operating mechanism
with 3VL circuit breaker
8UC7 rotary operating mechanism
with 3VL circuit breaker and
8UC94 00 interlocking module
© Siemens AG 2012. All rights reserved.
Industry Sector
8UC7 rotary operating mechanism
Technical data
Approvals
Device selection
8UC7 rotary operating
mechanism
EMERGENCY OFF version
STANDARD version
© Siemens AG 2012. All rights reserved.
Industry Sector
8UC7 rotary operating mechanism
Technical data
8UC7 rotary operating mechanism
 Rotary actuators for operating switchgear with
panel doors closed
 Available in STANDARD and EMERGENCY OFF versions
 Can be connected to circuit breakers and switch disconnectors
with or without fuses
 Rated operational current up to 1,600 A
 Available in various sizes
EMERGENCY OFF version
 Degree of protection IP 65 when mounted
 For compliance with UL, must always be used in
conjunction with 8UC94 00 interlocking module
 For compliance with UL, the rotary operating mechanism and the
interlocking module remain on the circuit breaker even when the door is open
For further information, go to www.siemens.de/lowvoltage
STANDARD version
© Siemens AG 2012. All rights reserved.
Industry Sector
8UC7 rotary operating mechanism
Approvals
8UC7 rotary operating mechanism
 Approval to IEC 60204-1, IEC 30439-1, and 60947-3
 Approval to CSA
 Approval to UL
 8UC94 00 interlocking module must be used to meet the
door interlocking requirement set out in UL 508A Art. 65-67!!
EMERGENCY OFF version
STANDARD version
© Siemens AG 2012. All rights reserved.
Industry Sector
Lines/cables
Lines/cables
© Siemens AG 2012. All rights reserved.
Industry Sector
NOTE:
Applications consulting from Siemens AG is a free-of-charge service for our customers.
Information, recommendations or instructions (hereinafter referred to as "information") from Siemens AG
are intended to assist the customer and represent descriptions of performance or performance features
of the respective products. Customers are themselves responsible for proper operation of the products within
the scope of the applicable regulations.