HydroRanger 200 HMI Catalog Specification Sheet

© Siemens AG 2015
Level Measurement
Continuous level measurement - Ultrasonic controllers
HydroRanger 200 HMI
■ Overview
■ Application
For water authorities, municipal water, and wastewater plants,
HydroRanger 200 HMI is an economical, low-maintenance solution delivering control efficiency and productivity needed to
meet today’s exacting standards. It offers single point monitoring
with all models, and optional dual-point monitoring with 6 relay
model. As well, it has digital communications with built-in Modbus RTU via RS 485.
The standard 6 relay HydroRanger 200 HMI will monitor open
channel flow and features advanced relay alarming and pump
control functions as well as volume conversion. It is compatible
with SIMATIC PDM, allowing for PC configuration and set-up.
Sonic Intelligence advanced echo-processing software provides increased reading reliability.
4
HydroRanger 200 HMI is an ultrasonic level controller for up to
six pumps and provides control, differential control, and open
channel flow monitoring.
■ Benefits
• Easy to use HMI display with local four-button programming,
menu-driven parameters, and Wizard support for key
applications
• English, German, French, Spanish, Chinese, Italian, Portuguese, and Russian texts on the HMI
• Removable terminal blocks for ease of wiring
• Monitors wet wells, weirs and flumes
• Digital communications with built-in Modbus RTU via RS 485
• Compatible with SmartLinx system and SIMATIC PDM configuration software
• Single or dual point level monitoring
• 6 relays
• Auto False-Echo Suppression for fixed obstruction avoidance
• Anti-grease ring/tide mark build-up
• Differential amplifier transceiver for common mode noise
rejection and improved signal-to-noise ratio
• Wall and panel mounting options
4/1
Siemens FI 01 · News 10/2015
HydroRanger 200 HMI uses proven continuous ultrasonic echo
ranging technology to monitor water and wastewater of any consistency up to 15 m (50 ft) in depth. Achievable resolution is
0.1 % with accuracy to 0.25 % of range. Unlike contacting
devices, HydroRanger 200 HMI is immune to problems caused
by suspended solids, harsh corrosives, grease or silt in the effluent, reducing downtime.
• Key Applications: wet wells, flumes/weirs, bar screen control
© Siemens AG 2015
Level Measurement
Continuous level measurement - Ultrasonic controllers
HydroRanger 200 HMI
■ Technical specifications
Mode of Operation
Design
Measuring principle
Ultrasonic level measurement
Measuring range
0.3 ... 15 m (1 ... 50 ft), transducer
dependent
Weight
• Wall mount
• Panel mount
1.37 kg (3.02 lb)
1.50 kg (3.31 lb)
Measuring points
1 or 2
Material (enclosure)
Polycarbonate
Degree of protection (enclosure)
• Wall mount
• Panel mount
IP65/Type 4X/NEMA 4X
IP54/Type 3/NEMA 3
Input
Analog
0 ... 20 mA or 4 ... 20 mA, from
alternate device, scalable
(6 relay model)
Discrete
10 ... 50 V DC switching level
Logical 0  0.5 V DC
Logical 1 = 10 ... 50 V DC
Max. 3 mA
Output
EchoMax transducer
44 kHz
Ultrasonic transducer
Compatible transducers: ST-H and
EchoMax series XPS-10, XPS-15/15F,
and XRS-5
1)
Relays
• Model with 6 relays
Rating 5 A at 250 V AC, non-inductive
4 SPST Form A/2 SPDT Form C
mA output
• Max. load
• Resolution
0 ... 20 mA or 4 ... 20 mA
750 , isolated
0.1 % of range
Cable
• Transducer and mA output signal
2-core copper conductor, twisted,
shielded, 300 Vrms, 0.82 mm²
(18 AWG), Belden 8 760 or equivalent
is acceptable
• Max. separation between transducer 365 m (1 200 ft)
and transceiver
Displays and controls
Power supply
60 x 40 mm (2.36 x 1.57 inch) LCD
240 x 160 pixels resolution
3)
AC version
100 ... 230 V AC ± 15 %,
50/60 Hz, 36 VA (17 W)
DC version
12 ... 30 V DC (20 W)
Certificates and approvals
• CE, RCM4)
• FM, CSAUS/C, UL listed
• CSAUS/C Class I, Div. 2, Groups A,
B, C and D, Class II, Div. 2,
Groups F and G, Class III
(wall mount only)
• MCERTS Class 2 approved for
Open Channel Flow
• RS 232 with Modbus RTU or ASCII
via RJ-11 connector
• RS 485 with Modbus RTU or ASCII
via terminal blocks
• Optional: SmartLinx cards for
- PROFIBUS DPV1
- DeviceNet
Accuracy
Error in measurement
0.25 % of range or 6 mm (0.24 inch),
whichever is greater
Resolution
0.1 % of measuring range or 2 mm
(0.08 inch), whichever is greater2)
Communication
Temperature compensation
• -50 ... +150 °C (-58 ... +302 °F)
• Integral temperature sensor in
transducer
• External TS-3 temperature sensor
(optional)
• Programmable fixed temperature
values
1)
All relays certified for use with equipment that fails in a state at or under the
rated maximums of the relays.
2)
Program range is defined as the empty distance to the face of the transducer plus any range extension.
3)
Maximum power consumption is listed.
4)
EMC performance available upon request.
Rated operating conditions
Installation conditions
• Location
• Installation category
• Pollution degree
Indoor / outdoor
II
4
Ambient conditions
• Ambient temperature (enclosure)
-20 ... +50 °C (-4 ... +122 °F)
Siemens FI 01 · News 10/2015
4/2
4
© Siemens AG 2015
Level Measurement
Continuous level measurement - Ultrasonic controllers
HydroRanger 200 HMI
Selection and Ordering data
Article No.
Selection and Ordering data
Siemens HydroRanger 200 HMI
Ultrasonic level controller for up to six pumps that
provides control, differential control and open
channel flow monitoring. The HydroRanger 200
HMI is also available as a level measurement controller only. Select option from number of measurement points options below.
7ML5034-
Further designs
777 77
Please add "-Z" to Article No. and specify Order
code(s).
Click on the Article No. for the online configuration in the PIA Life Cycle Portal.
Mounting
4 button HMI, Wall mount, standard enclosure
4 button HMI, Wall mount, 4 entries, 4 M20 cable
glands included
4 button HMI, Panel Mount
4
Input voltage
100 ... 230 V AC
12 ... 30 V DC
Number of measurement points
Single point model, 6 relays
Dual point model, 6 relays
4
5
6
Stainless steel tag [69 x 50 mm (2.71 x 1.97 inch)]:
Measuring-point number/identification
(max. 27 characters), specify in plain text
Y15
Test Certificate: Manufacturer's test certificate M
to DIN 55350, Part 18 and to ISO 9000
C11
Operating Instructions
Article No.
English
A5E36281317
German
A5E36281391
Note: The Operating Instructions should be
ordered as a separate item on the order.
A
B
This device is shipped with the Siemens Milltronics
manual DVD containing the ATEX Quick Start and
Operating Instructions library.
Other Operating Instructions
A
B
Communication (SmartLinx)
Without module
SmartLinx PROFIBUS DP V0 module
0
2
SmartLinx DeviceNet module
3
SmartLinx PROFIBUS DP V1 module
See SmartLinx product page for more information
4
Approvals
General Purpose CE, FM, CSAUS/C, UL listed, RCM
CSA Class I, Div. 2, Groups A, B, C, and D;
Class II, Div. 2, Groups F and G; Class III
Order code
1
2
SmartLinx PROFIBUS DPV1, English
A5E36197302
SmartLinx PROFIBUS DPV1, German
A5E36197305
SmartLinx PROFIBUS DP, English
7ML1998-1AQ03
SmartLinx PROFIBUS DP, German
7ML1998-1AQ33
SmartLinx PROFIBUS DP, French
7ML1998-1AQ13
SmartLinx DeviceNet, English
7ML1998-1BH02
Note: The appropriate SmartLinx Operating
Instructions should be ordered as a separate line
on the order.
Accessories
Tag, stainless steel, 12 x 45 mm (0.47 x 1.77 inch),
one text line, suitable for enclosure
7ML1930-1AC
Sunshield kit, 304 stainless steel
7ML1930-1GA
SITRANS RD100, loop powered display see Chapter 7
7ML5741-...
SITRANS RD200, universal input display with
Modbus conversion - see Chapter 7
7ML5740-...
SITRANS RD300, dual line display with totalizer
and linearization curve and Modbus conversion see Chapter 7
7ML5744-...
SITRANS RD500 web, universal remote monitoring
solution for instrumentation - see Chapter 7
7ML5750-...
Spare parts
4/3
Siemens FI 01 · News 10/2015
Power Supply Board (100 ... 230 V AC)
7ML1830-1MD
Power Supply Board (12 ... 30 V DC)
7ML1830-1ME
Replacement lid with 4 button HMI
A5E35778738
SmartLinx PROFIBUS DP V1 module
A5E35778741
© Siemens AG 2015
Level Measurement
Continuous level measurement - Ultrasonic controllers
HydroRanger 200 HMI
■ Dimensional drawings
Panel mount dimensions
198 (7.8)
94
(3.7)
278 (10.9)
31
(1.2)
4
Wall mount dimensions
15
(0.6)
161 (6.3)
87 (3.4)
15
(0.6)
131 (5.2)
6
(0.2)
228 (9.0)
240 (9.4)
Lid screws
(6)
Cable entry
location
Enclosure
lid
Cable Enclosure
entry
base
Ø4.3 (0.17),
four mounting holes
HydroRanger 200 HMI, dimensions in mm (inch)
Siemens FI 01 · News 10/2015
4/4
© Siemens AG 2015
Level Measurement
Continuous level measurement - Ultrasonic controllers
HydroRanger 200 HMI
■ Schematics
TB1
Or
See note 1
TB1
TB2
L2/N L1
+
-
- +
2
TB3
12 ... 30 V
SYNC
1
DC version
+
mA INPUT
+
SHIELD
Relay 1
1
4 ... 20 mA
OUTPUTS
Relay 2
4
+
2
+
+
Relay 3
TS-3
SHIELD
1
Relay 4
Relay 5
DISCRETE
INPUTS
2
COM
Relay 6
Relays shown in released
state
RS 485
A
B
Note:
1. Use 2-core copper wire, twisted, with shield, for expansion up to
365 m (1 200 ft). Route cable in grounded metal conduit, separate
from other cables.
2. Verify that all system components are installed in accordance with
instructions.
3. Connect all cable shields to the MultiRanger shield connections.
Avoid differential ground potentials by not connecting cable shields
to ground (earth) anywhere else.
4. Keep exposed conductors on shielded cables as short as possible
to reduce noise on the line caused by stray transmissions and noise
pickup.
HydroRanger 200 HMI connections
4/5