© Siemens AG 2015 Level Measurement Continuous level measurement - Ultrasonic controllers HydroRanger 200 HMI ■ Overview ■ Application For water authorities, municipal water, and wastewater plants, HydroRanger 200 HMI is an economical, low-maintenance solution delivering control efficiency and productivity needed to meet today’s exacting standards. It offers single point monitoring with all models, and optional dual-point monitoring with 6 relay model. As well, it has digital communications with built-in Modbus RTU via RS 485. The standard 6 relay HydroRanger 200 HMI will monitor open channel flow and features advanced relay alarming and pump control functions as well as volume conversion. It is compatible with SIMATIC PDM, allowing for PC configuration and set-up. Sonic Intelligence advanced echo-processing software provides increased reading reliability. 4 HydroRanger 200 HMI is an ultrasonic level controller for up to six pumps and provides control, differential control, and open channel flow monitoring. ■ Benefits • Easy to use HMI display with local four-button programming, menu-driven parameters, and Wizard support for key applications • English, German, French, Spanish, Chinese, Italian, Portuguese, and Russian texts on the HMI • Removable terminal blocks for ease of wiring • Monitors wet wells, weirs and flumes • Digital communications with built-in Modbus RTU via RS 485 • Compatible with SmartLinx system and SIMATIC PDM configuration software • Single or dual point level monitoring • 6 relays • Auto False-Echo Suppression for fixed obstruction avoidance • Anti-grease ring/tide mark build-up • Differential amplifier transceiver for common mode noise rejection and improved signal-to-noise ratio • Wall and panel mounting options 4/1 Siemens FI 01 · News 10/2015 HydroRanger 200 HMI uses proven continuous ultrasonic echo ranging technology to monitor water and wastewater of any consistency up to 15 m (50 ft) in depth. Achievable resolution is 0.1 % with accuracy to 0.25 % of range. Unlike contacting devices, HydroRanger 200 HMI is immune to problems caused by suspended solids, harsh corrosives, grease or silt in the effluent, reducing downtime. • Key Applications: wet wells, flumes/weirs, bar screen control © Siemens AG 2015 Level Measurement Continuous level measurement - Ultrasonic controllers HydroRanger 200 HMI ■ Technical specifications Mode of Operation Design Measuring principle Ultrasonic level measurement Measuring range 0.3 ... 15 m (1 ... 50 ft), transducer dependent Weight • Wall mount • Panel mount 1.37 kg (3.02 lb) 1.50 kg (3.31 lb) Measuring points 1 or 2 Material (enclosure) Polycarbonate Degree of protection (enclosure) • Wall mount • Panel mount IP65/Type 4X/NEMA 4X IP54/Type 3/NEMA 3 Input Analog 0 ... 20 mA or 4 ... 20 mA, from alternate device, scalable (6 relay model) Discrete 10 ... 50 V DC switching level Logical 0 0.5 V DC Logical 1 = 10 ... 50 V DC Max. 3 mA Output EchoMax transducer 44 kHz Ultrasonic transducer Compatible transducers: ST-H and EchoMax series XPS-10, XPS-15/15F, and XRS-5 1) Relays • Model with 6 relays Rating 5 A at 250 V AC, non-inductive 4 SPST Form A/2 SPDT Form C mA output • Max. load • Resolution 0 ... 20 mA or 4 ... 20 mA 750 , isolated 0.1 % of range Cable • Transducer and mA output signal 2-core copper conductor, twisted, shielded, 300 Vrms, 0.82 mm² (18 AWG), Belden 8 760 or equivalent is acceptable • Max. separation between transducer 365 m (1 200 ft) and transceiver Displays and controls Power supply 60 x 40 mm (2.36 x 1.57 inch) LCD 240 x 160 pixels resolution 3) AC version 100 ... 230 V AC ± 15 %, 50/60 Hz, 36 VA (17 W) DC version 12 ... 30 V DC (20 W) Certificates and approvals • CE, RCM4) • FM, CSAUS/C, UL listed • CSAUS/C Class I, Div. 2, Groups A, B, C and D, Class II, Div. 2, Groups F and G, Class III (wall mount only) • MCERTS Class 2 approved for Open Channel Flow • RS 232 with Modbus RTU or ASCII via RJ-11 connector • RS 485 with Modbus RTU or ASCII via terminal blocks • Optional: SmartLinx cards for - PROFIBUS DPV1 - DeviceNet Accuracy Error in measurement 0.25 % of range or 6 mm (0.24 inch), whichever is greater Resolution 0.1 % of measuring range or 2 mm (0.08 inch), whichever is greater2) Communication Temperature compensation • -50 ... +150 °C (-58 ... +302 °F) • Integral temperature sensor in transducer • External TS-3 temperature sensor (optional) • Programmable fixed temperature values 1) All relays certified for use with equipment that fails in a state at or under the rated maximums of the relays. 2) Program range is defined as the empty distance to the face of the transducer plus any range extension. 3) Maximum power consumption is listed. 4) EMC performance available upon request. Rated operating conditions Installation conditions • Location • Installation category • Pollution degree Indoor / outdoor II 4 Ambient conditions • Ambient temperature (enclosure) -20 ... +50 °C (-4 ... +122 °F) Siemens FI 01 · News 10/2015 4/2 4 © Siemens AG 2015 Level Measurement Continuous level measurement - Ultrasonic controllers HydroRanger 200 HMI Selection and Ordering data Article No. Selection and Ordering data Siemens HydroRanger 200 HMI Ultrasonic level controller for up to six pumps that provides control, differential control and open channel flow monitoring. The HydroRanger 200 HMI is also available as a level measurement controller only. Select option from number of measurement points options below. 7ML5034- Further designs 777 77 Please add "-Z" to Article No. and specify Order code(s). Click on the Article No. for the online configuration in the PIA Life Cycle Portal. Mounting 4 button HMI, Wall mount, standard enclosure 4 button HMI, Wall mount, 4 entries, 4 M20 cable glands included 4 button HMI, Panel Mount 4 Input voltage 100 ... 230 V AC 12 ... 30 V DC Number of measurement points Single point model, 6 relays Dual point model, 6 relays 4 5 6 Stainless steel tag [69 x 50 mm (2.71 x 1.97 inch)]: Measuring-point number/identification (max. 27 characters), specify in plain text Y15 Test Certificate: Manufacturer's test certificate M to DIN 55350, Part 18 and to ISO 9000 C11 Operating Instructions Article No. English A5E36281317 German A5E36281391 Note: The Operating Instructions should be ordered as a separate item on the order. A B This device is shipped with the Siemens Milltronics manual DVD containing the ATEX Quick Start and Operating Instructions library. Other Operating Instructions A B Communication (SmartLinx) Without module SmartLinx PROFIBUS DP V0 module 0 2 SmartLinx DeviceNet module 3 SmartLinx PROFIBUS DP V1 module See SmartLinx product page for more information 4 Approvals General Purpose CE, FM, CSAUS/C, UL listed, RCM CSA Class I, Div. 2, Groups A, B, C, and D; Class II, Div. 2, Groups F and G; Class III Order code 1 2 SmartLinx PROFIBUS DPV1, English A5E36197302 SmartLinx PROFIBUS DPV1, German A5E36197305 SmartLinx PROFIBUS DP, English 7ML1998-1AQ03 SmartLinx PROFIBUS DP, German 7ML1998-1AQ33 SmartLinx PROFIBUS DP, French 7ML1998-1AQ13 SmartLinx DeviceNet, English 7ML1998-1BH02 Note: The appropriate SmartLinx Operating Instructions should be ordered as a separate line on the order. Accessories Tag, stainless steel, 12 x 45 mm (0.47 x 1.77 inch), one text line, suitable for enclosure 7ML1930-1AC Sunshield kit, 304 stainless steel 7ML1930-1GA SITRANS RD100, loop powered display see Chapter 7 7ML5741-... SITRANS RD200, universal input display with Modbus conversion - see Chapter 7 7ML5740-... SITRANS RD300, dual line display with totalizer and linearization curve and Modbus conversion see Chapter 7 7ML5744-... SITRANS RD500 web, universal remote monitoring solution for instrumentation - see Chapter 7 7ML5750-... Spare parts 4/3 Siemens FI 01 · News 10/2015 Power Supply Board (100 ... 230 V AC) 7ML1830-1MD Power Supply Board (12 ... 30 V DC) 7ML1830-1ME Replacement lid with 4 button HMI A5E35778738 SmartLinx PROFIBUS DP V1 module A5E35778741 © Siemens AG 2015 Level Measurement Continuous level measurement - Ultrasonic controllers HydroRanger 200 HMI ■ Dimensional drawings Panel mount dimensions 198 (7.8) 94 (3.7) 278 (10.9) 31 (1.2) 4 Wall mount dimensions 15 (0.6) 161 (6.3) 87 (3.4) 15 (0.6) 131 (5.2) 6 (0.2) 228 (9.0) 240 (9.4) Lid screws (6) Cable entry location Enclosure lid Cable Enclosure entry base Ø4.3 (0.17), four mounting holes HydroRanger 200 HMI, dimensions in mm (inch) Siemens FI 01 · News 10/2015 4/4 © Siemens AG 2015 Level Measurement Continuous level measurement - Ultrasonic controllers HydroRanger 200 HMI ■ Schematics TB1 Or See note 1 TB1 TB2 L2/N L1 + - - + 2 TB3 12 ... 30 V SYNC 1 DC version + mA INPUT + SHIELD Relay 1 1 4 ... 20 mA OUTPUTS Relay 2 4 + 2 + + Relay 3 TS-3 SHIELD 1 Relay 4 Relay 5 DISCRETE INPUTS 2 COM Relay 6 Relays shown in released state RS 485 A B Note: 1. Use 2-core copper wire, twisted, with shield, for expansion up to 365 m (1 200 ft). Route cable in grounded metal conduit, separate from other cables. 2. Verify that all system components are installed in accordance with instructions. 3. Connect all cable shields to the MultiRanger shield connections. Avoid differential ground potentials by not connecting cable shields to ground (earth) anywhere else. 4. Keep exposed conductors on shielded cables as short as possible to reduce noise on the line caused by stray transmissions and noise pickup. HydroRanger 200 HMI connections 4/5 Siemens FI 01 · News 10/2015