HydroRanger Plus Catalog Specification Sheet

© Siemens AG 2011
Level Measurement
Continuous level measurement — Ultrasonic controllers
HydroRanger Plus
■ Overview
■ Benefits
• Outputs for alarms, chart recorders, controllers and integration of existing systems
• Monitors wet wells, weirs and flumes
• Energy-saving function with built-in real-time clock
• Special control mode to reduce grease rings and other
deposits
• Integral temperature compensation
• Pump performance monitoring
• System monitoring and network analysis
■ Application
The system is effective in wet wells, weirs, and flumes where
foam and turbulence are typical operating conditions. It can be
customized to meet your specific application needs – from measuring flow rate in a narrow flume to volume in a ferric chloride
storage bank.
The system consists of the electronics housed in a wall-mounted
enclosure and a hermetically sealed, corrosion-resistant Echomax transducer. These components can be separated by up to
365 m (1200 ft).
5
HydroRanger Plus is an ultrasonic level controller for control of
wet wells and reservoir pump operations, differential control, and
open channel flow monitoring, using energy-saving algorithms.
5/154
Siemens FI 01 · 2012
Optional submergence shields ensure consistent operation in
wet wells where the transducer may be submerged during flooding from rainfall or a power outage. Siemens patented detection
software can differentiate between a submerged condition and
a high level.
• Key Applications: wet wells, weirs, flumes
© Siemens AG 2011
Level Measurement
Continuous level measurement — Ultrasonic controllers
HydroRanger Plus
■ Technical specifications
Mode of operation
Measuring principle
Ultrasonic level measurement
Measuring range
0.3 ... 15 m (1 ... 50 ft)
Measuring points
1 or 2
Power supply
100/115/200/230 V AC, ±15%,
50/60 Hz, 15 VA and/or
9 ... 30 V DC, 8 W
Ultrasonic transducer
Compatible transducers: ST-H
and Echomax series XPS-10/10F,
XPS 15/15F, XCT-8, XCT-12 and
XRS-5
Output
Ultrasonic transducer
44 kHz
Displays and controls
Relays
5 alarm/control relays, 1 SPDT
Form C per relay, rated 5 A at
250 V AC, resistive load
Rack and panel mount
75 x 20 mm (3 x 0.8") LCD
(selectable backlighting)
mA output
0/4 ... 20 mA, optically isolated
Wall mount
100 x 40 mm (4 x 1.5") multifield
LCD, backlit
• Max. load
1 kΩ
Programming
• Resolution
0.1 % of 20 mA
Removable programmer or
optional Dolphin Plus
Memory
EEPROM (non-volatile), no
backup battery required
Certificates and approvals
CE2), FM, CSAUS/C, C-TICK
Accuracy
Error in measurement
0.25% of range or 6 mm (0.24"),
whichever is greater
Resolution
0.1% of measuring range or
2 mm (0.08"), whichever is
greater1)
Temperature compensation
-50 ... +150 °C (-58 ... +302 °F)
• Integral temperature sensor
• External TS-3 temperature
sensor (optional)
• Programmable fixed temperature
1)
The measuring range corresponds to the distance from the zero point to the
sensor face, plus any range extension.
2) EMC certificate available on request
5
Rated operating conditions
Ambient conditions
• Ambient temperature for enclosure
-20 ... +50 °C (-4 ... +122 °F)
Design
Rack mount
DIN 3 HU/14 pitch, 4 rail plug-in
unit suitable for standard
84 pitch (19") rack
Panel mount
Suitable for standard panel
cutout DIN 43700, 72 x 144 mm,
100 mm center height
Degree of protection (wall mount)
IP65/NEMA 4X/Type 4X
Weight (rack and panel mount)
0.87 kg (1.9 lbs)
Weight (wall mount)
1.5 kg (3.3 lbs)
Material (enclosure)
Polyester/polycarbonate alloy
Electrical connection
Commercially available copper
conductor according to local
requirements, rated 250 V/5 A
Ultrasonic transducer cable
extension
RG 62-A/U coaxial cable with
low capacitance
mA output signal
2-core copper conductor,
twisted, shielded,
0.5 ... 0.75 mm² (22 ... 18 AWG),
Belden 8760 or equivalent is
acceptable
Siemens FI 01 · 2012
5/155
© Siemens AG 2011
Level Measurement
Continuous level measurement — Ultrasonic controllers
HydroRanger Plus
Selection and Ordering data
Order No.
L) 7ML1028HydroRanger Plus, wall mount
Non-contacting ultrasonic echo ranging technology
7A7 7 0
monitor that comes standard with a backlit display
Measuring range: 0.3 m to 15 m (1 ... 50 ft)
Mounting/device version
Version for 19" rack
(requires terminal block; see accessories)
Version for panel
Input voltage
100 V AC, 9 ... 30 V DC
115 V AC, 9 ... 30 V DC
1
2
200 V AC, 9 ... 30 V DC
230 V AC, 9 ... 30 V DC
3
4
Approvals
CE (EN 61326), CSAUS/C, FM, C-TICK
1
2
C
Input voltage
100 V AC, 9 ... 30 V DC
115 V AC, 9 ... 30 V DC
A
B
200 V AC, 9 ... 30 V DC
230 V AC, 9 ... 30 V DC
C
D
Selection and Ordering data
Order code
Stainless steel tag [69 x 50 mm (2.71 x 1.97")]:
Measuring-point number/identification
(max. 16 characters) specify in plain text
Operating Instructions
Approvals
CE; FM General Purpose; CSA Class I, Div. 2,
C-TICK
C
Mounting/enclosure version
Standard enclosure (NEMA 4X)
Standard enclosure prepared for five M20 cable
glands
1
3
C) Subject to export regulations AL: N, ECCN: EAR99.
L) Subject to export regulations AL: N, ECCN: 3A991X.
Further designs
Please add "-Z" to Order No. and specify Order
code(s).
5
Order No.
Selection and Ordering data
L) 7ML1025HydroRanger Plus, rack and panel mount
Non-contacting ultrasonic echo ranging technology
777 0 1
monitor that comes standard with a backlit display
Measuring range: 0.3 m to 15 m (1 ... 50 ft)
K) Subject to export regulations AL: N, ECCN: 5A991X.
Order code
Selection and Ordering data
Y15
Order No.
English
C) 7ML1998-1AC02
French
C) 7ML1998-1AC12
C) 7ML1998-1AC32
German
Note: The Operating Instructions should be ordered
as a separate item on the order.
This device is shipped with the Siemens Milltronics
manual CD containing the complete ATEX Quick Start
and Operating Instructions library.
Further designs
Please add "-Z" to Order No. and specify Order
code(s).
Stainless steel tag [69 x 50 mm (2.71 x 1.97")]:
Measuring-point number/identification
(max. 16 characters) specify in plain text
Y15
Order No.
Operating Instructions
English
C) 7ML1998-1AC02
French
C) 7ML1998-1AC12
SmartLinx Allen-Bradley Remote I/O, English
C) 7ML1998-1AP03
SmartLinx PROFIBUS DP, English
C) 7ML1998-1AQ03
C) 7ML1998-1AC32
German
Note: The Operating Instructions should be ordered
as a separate item on the order.
This device is shipped with the Siemens Milltronics
manual CD containing the complete ATEX Quick Start
and Operating Instructions library.
SmartLinx PROFIBUS DP, German
C) 7ML1998-1AQ33
Accessories
Other Operating Instructions
C) 7ML1998-1BH02
SmartLinx DeviceNet, English
Note: The appropriate SmartLinx Operating Instructions should be ordered as a separate line on the
order.
Accessories
Handheld programmer
7ML1830-2AC
Tag, stainless steel, 12 x 45 mm (0.47 x 1.77"),
one text line, suitable for enclosure
7ML1930-1AC
Terminal block for rack mount
7ML1830-1JL
Handheld programmer
7ML1830-2AC
Tag, stainless steel, 12 x 45 mm (0.47 x 1.77"), one
text line, suitable for enclosure
7ML1930-1AC
M20 cable gland kit (6 M20 cable glands,
6 M20 nuts, 3 stop plugs)
7ML1830-1GM
M20 cable gland kit (4 M20 cable glands,
4 M20 nuts, 4 washers)
7ML1930-1FV
Sunshield kit, 304 SS
7ML1930-1GA
SITRANS RD100 Remote display - see Chapter 8
SITRANS RD100 Remote display - see Chapter 8
SITRANS RD200 Remote display - see Chapter 8
SITRANS RD200 Remote display - see Chapter 8
K) 7ML5750SITRANS RD500 web, datalogging, alarming,
ethernet, and modem support for instrumentation 1AA00-0
see Chapter 8
K) 7ML5750SITRANS RD500 web, datalogging, alarming,
ethernet, and modem support for instrumentation 1AA00-0
see Chapter 8
Spare parts
Spare parts
Card, mother main
C) 7ML1830-1LV
Card, Analog HydroRanger Plus Rack/Panel
C) 7ML1830-1LR
Card, daughter
C) 7ML1830-1LW
Card, daughter
C) 7ML1830-1LS
Card, display
C) 7ML1830-1LU
Card, display, backlit
C) 7ML1830-1LX
C) Subject to export regulations AL: N, ECCN: EAR99.
K) Subject to export regulations AL: N, ECCN: 5A991X.
5/156
Siemens FI 01 · 2012
© Siemens AG 2011
Level Measurement
Continuous level measurement — Ultrasonic controllers
HydroRanger Plus
■ Dimensional drawings
■ Schematics
Rack Mount
DIN 3U/14HP, 4 rail plug-in unit suitable for standard 84 HP (19")
subrack. (Terminal is customer supplied or available as optional
accessory.)
mA In
mA In
+ C2
A2
–
black C4
A4
+
white C6
A6
–
shield C8
A8
sync
black C10
A10 +
9 - 30
white/shield C12
See Note 2
com C14
A12 –
V
TS-3
mA Out
See
Note 1
Sensor
n.o. C18
A18 n.c.
white/shield C20
A20 n.o.
com C22
A22 com
n.c. C24
A24 n.c.
n.o. C26
A26 n.o.
com C28
A28
n.c. C30
A30 L2 / N
n.o. C32
A32 L1
Panel Mount
201 (7.9)
16 (0.6)
144 (5.7)
150 (5.9)
Relay 4
Relay 3
Slip on mounting bracket top and
bottom screws to be tightened to no
more than 5.9 Nm (1 inch/lb) torque.
See
Note 4
2. Use RG-62 A/U coaxial (or equivalent) for extensions up to
365 m (1200 ft). Run in grounded metal conduit, separate from
other wiring.
77
(3.0)
102 (4.0)
180 (7.1)
20 (0.8)
5
Relay 1
1. Required only if mounted adjacent to other Siemens Milltronics
equipment. Interconnect all ‘SYNC’ terminals with a single
18 AWG (0.5 mm 2) wire.
195 (7.7)
168 (6.6)
See
Relay 2 Note 3
Notes
Wall Mount
13 (0.5)
Shield
A16 com
Relay 5
72 (2.9)
A14
n.c. C16
3. Each relay has 1 set of Form ‘C’ (SPDT) contacts relay rated at
5 A 250 V AC, non-inductive, when equal or lower rated limiting
fuses are installed. Relay de-energized when in alarm conditions
and energized for pump control.
4. Before applying AC power (mains), ensure the correct voltage is
selected. Never operate the HydroRanger Plus with the ground
(earth) wire disconnected.
Voltage Selection
Suitable location for conduit
entrances. Use watertight
conduit hubs to maintain
enclosure rating.
HydroRanger Plus, dimensions in mm (inch)
mounting holes,
Ø4.5 mm (0.18"),
4 places
Voltage Selection
Switches
HydroRanger Plus connections, rack and panel mount
Siemens FI 01 · 2012
5/157
© Siemens AG 2011
Level Measurement
Continuous level measurement — Ultrasonic controllers
HydroRanger Plus
See
Note 1
TEMP
Notes
RL5
RL4
See
Note 3
TRANS
See Note 2
RL3
RL2
RL1
Scope
Clock
connection module
–
Power
L1
+
L2/N
10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
GND
9
shield
8
white/shield
7
shield
6
white/shield
5
–
black
4
+
sync
mA Out
3
mA In
2
–
shield
1
+
see
Note 4
EPROM
1. Required only if mounted adjacent to other Siemens Milltronics equipment.
Interconnect all ‘SYNC’ terminals with a single 18 AWG (0.5 mm 2) wire.
Voltage
Selection
Switch
2. Use RG-62 A/U coaxial (or equivalent) for extensions up to 365 m (1200 ft).
Run in grounded metal conduit, separate from other wiring.
3. Each relay has 1 set of Form ‘C’ (SPDT) contacts relay rated at 5 A 250 V AC,
non-inductive, when equal or lower rated limiting fuses are installed. Relay
de-energized when in alarm conditions and energized for pump control.
4. Before applying AC power (mains), ensure the correct voltage is selected.
Never operate the HydroRanger Plus with the ground (earth) wire disconnected.
5
HydroRanger Plus connections, wall mount
5/158
Siemens FI 01 · 2012
Terminal block