LU AO Catalog Specification Sheet

© Siemens AG 2015
Level Measurement
Continuous level measurement - Ultrasonic controllers
SITRANS LU AO
■ Overview
■ Technical specifications
Mode of operation
Input
Communications
Data from SITRANS LU10
Transmission rate
4 800 bits/s
Voltage
± 20 mA bipolar current loop
Polarization
Non-polarized
Max. load
1 receiving unit
Output
Analog outputs
10 analog outputs, programmable
from SITRANS LU10
0 or 4 ... 20 mA, isolated
± 20 mA bipolar current loop
• Max. load
• Resolution
4
Input and transmission
750 Ω
0.1 %
Rated operating conditions
The SITRANS LU AO Analog Output Module provides remote
analog output for the measurement points of the SITRANS LU10
level monitor.
■ Benefits
• Analog outputs can be up to 1 500 m (5 000 ft) from the
SITRANS LU 10
• Analog outputs can be per transducer and/or average of 2 or
more
Ambient conditions
• Ambient temperature for enclosure
• Location
• Installation category
• Pollution degree
Design
Weight
2 kg (4.4 lb)
Material (enclosure)
Polycarbonate
Degree of protection
• Cable connection
Type 4X/NEMA 4X/IP65
2 copper conductors, twisted, with
foil shield/drain wire, 300 V
0.5 ... 0.75 mm² (22 ... 18 AWG)
Copper conductor according to local
requirements, rated 250 V 5 A
■ Application
The operation of the SITRANS LU AO is programmed via the
SITRANS LU10. The only on-board settings are for bank selection and output testing.
The SITRANS LU AO can provide up to 10 analog outputs (each
sharing a common negative bus which is electrically isolated
from ground).
-20 ... +50 °C (-5 ... +122 °F)
Indoor/outdoor
II
4
• Electrical connection and relay
connection
Power supply
100/115/200/230 V AC ± 15 %,
50/60 Hz, 15 VA
Displays and controls
1 LED for display of voltage/
communications state
Certificates and approvals
CE, FM, CSAUS/C , RCM
Selection and Ordering data
Article No.
SITRANS LU AO
Provides remote analog output for the
measurement points of the SITRANS LU10
level monitor.
Approvals: CSAUS/C, FM, CE, RCM
7ML5810-1A
Operating Instructions
English
7ML1998-5CE01
German
Note: Operating Instructions should be
ordered as a separate line item on the order.
7ML1998-5CE31
This device is shipped with the Siemens Milltronics
manual DVD containing the Quick Start and Operating Instructions library.
Accessories
Sun Shield, 304 stainless steel
4/168
Siemens FI 01 · June 2015
7ML1930-1GA
© Siemens AG 2015
Level Measurement
Continuous level measurement - Ultrasonic controllers
SITRANS LU AO
■ Dimensional drawings
209
(8.2)
16
(0.6)
91
(3.6)
Lid screws
(6 places)
172
(6.8)
267
(10.5)
285
(11.2)
4
SITRANS LU AO
Mounting holes
(accessed under lid)
4.3 mm (0.17 inch) diameter
4 places
Lid
Suitable location for
conduit entrances
Enclosure
Mounting screw (by customer)
SITRANS LU AO, dimensions in mm (inch)
■ Schematics
230 V
200 V
OFF
Switch is shown in OFF position.
Select appropriate voltage.
115 V
100 V
See note 1
mA
output
spare
Bi-polar
Receiver
1
2
3
SW3
See note 2
4
+
1_
5
6
7
mA
output
+
2_
8
9
+
3_
+
mA
output
4_
+
5_
mA
output
+
6_
+
7_
mA
output
+
8_
+
9_
+
10_
10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29
L2
/N L1
30 31 32
See note 3
Isolated 0/4 ... 20 mA out,
750 Ω load max. (typical of 10)
100/115/200/230 V AC
50/60 Hz select
voltage via switch
Notes:
1. SITRANS LU AO receiver input is non-polarized.
2. Refer to associated application device instruction manual for wiring detail. Check that the communication parameter P740 (SITRANS LU10) is ON.
3. SITRANS LU AO interconnecting cable shield should be grounded at SITRANS LU10 only. Insulate shields at junctions to prevent inadvertent
grounding. Maximum individual loop length is 3 000 m (10 000 ft).
SITRANS LU AO connections
Siemens FI 01 · June 2015
4/169