SIREC D300 Catalog Sheet

SIREC D Display Recorder
SIREC D300 and SIREC D400
■ Overview
Crystal Clear Display
• Digital Colour LCD (TFT)
• Resolution
- SIREC D300: QVGA Resolution (320 x 240 pixels)
- SIREC D400: SVGA Resolution (800 x 600 pixels)
• Clear and intuitive operation
• Industrial rugged Touch Screen with rapid navigation
• Custom Screens
■ Function
Display
12.1” Colour Active TFT (SIREC D300)/5.5” Colour Active TFT
(SIREC D400)
With more than 256,000 colours makes it easy to interpret process data and take action with the intuitive bar charts, digital values, trends or customised displays. A screen saver function can
be set from 1 to 720 minutes to extend the life of the backlight.
Comprehensive Connectivity
• 10/100 Ethernet (DHCP), Web, Email, OPC Server
• FTP, TCP/IP and RS485 Modbus Protocol
• USB ports for keyboard and mouse
Touch Screen
Data Storage
• On-board non-volatile memory - up to 1850 MByte
• Removable Compact Flash and USB storage
• No moving parts - all solid state data storage
Navigation through the menus and text entry are direct and intuitive:
The heavy duty durable touch screen provides easy data entry
and rapid navigation though the menus. The touch screen operator interface provides fast, easy access to the recorder menus
making set up and data analysis quick and efficient.
Security Stringent - Total Data integrity
• Password Protection - 21CFR Part 11
• ESS - Extended Security System
Plus..
• Health Watch for preventative maintenance
• Remote Access - Advanced Software Data Analysis
• Analysis at your PC
• Independent Chart and Logging speeds
• Global Language Support
• Rapid review and replay of data at recorder
• Approvals - CE, CSA, UL, FM
• NEMA 4X/IP66 (option)
• Up to 50 Hz (20 ms) Logging
• Analog Inputs
- SIREC D300: Up to 16 Analog Inputs
- SIREC D400: Up to 48 Analog Inputs
• Remote Viewing Tool
Example of a recorder menu path from the Main Menu to Pen Scale configuration with clear rapid navigation
Siemens MP 20 News · 2007
13
SIREC D Display Recorder
SIREC D300 and SIREC D400
Standard Screens
Language Support
Up to 20 screens (SIREC D300) respectively 30 screens
(SIREC D400) displaying multiple combinations of Charts, Bars
and Digitals can be configured, 4 respectively 6 (SIREC D300
respectively SIREC D400) examples below.
Standard language prompts for
• English UK & US
• French
• German
• Italian
• Spanish
• Portuguese
• Brazilian
• Polish
• Slovakian
• Czech
• Turkish
• Romanian
• Hungarian
• Russian
Communications
The recorder supports FTP, Modbus TCP/IP (slave mode), Web
and Email over Ethernet (DHCP standard) communications port
and Modbus RTU (slave mode) via an RS485 port. USB ports allow the use of an ASCII barcode reader. Email sent to your network connected PC triggered by an Alarm or an Event.
Ethernet Connectivity
The Ethernet (DHCP standard) connection, with support for various protocols, provides unlimited connectivity to local area networks (LANs). The standard Ethernet interface makes networking of the recorder to a LAN or the world wide web fast and
convenient. Dynamic Host Configuration Protocol (DHCP) automatically acquires the settings (IP address) for network communications from a DHCP server.
RS485 Modbus
The RS485 connection allows process data to be transferred to
other devices, or to record data received in MODBUS RTU protocol (slave mode only).
Simple Network Time Protocol (SNTP)
The recorder can be synchronised over the ethernet network via
a SNTP client or synchronise other recorders via a Server.
Help Files
A complete contextual help system can be accessed and visualised on the screen of the recorder.
Logarithmic Scales
All displayed scales can be set as linear or logarithmic.
Replay with Zoom
Select replay mode and zoom-in on a specific area on the
screen. The data can easily be replayed at the recorder with the
ability to “zoom”. The touch screen makes it fast to review and
analyse historical data. A "Jump" function allows you to go from
any message list directly to the trend showing the occurence of
the alarm.
Web Server
With the recorder connected to a LAN, all process variables,
alarm and messages can be viewed from an internet browser
with automatic refresh.
USB Ports
Front and rear USB host ports for data and setup transfers or remote screen through this port. Front USB port is standard and
the rear USB port is available with the Communications card option. Use these ports to attach external devices (keyboard or
mouse), for direct interfacing with the recorder.
Common Relay Output
A separate relay alarm output at the rear of the unit can be set
up as an alarm output.
Remote Viewer
Extends the user interface of the recorder onto the desktop PC.
Providing remote viewing of the unit launched from a web
browser. Full remote control is available as an option. Compatible with Microsoft™ Internet explorer 6 and higher.
14
Siemens MP 20 News · 2007
SIREC D Display Recorder
SIREC D300 and SIREC D400
Data Storage
Data Security
Internal Data Storage
Total Data Integrity
70MB to 400MB expandable internal non-volatile flash memory
is available for data storage and chart history.
Data is stored in secure encrypted files making it easy to retrieve
the data dependent on process information. Data is automatically recognised without having to remember file names.
Pens 70 MByte
180 MByte 400 MByte 890 MByte 1850 MByte
16
12 Days
30,5 Days
68,5 Days
32
6 Days
15 Days
34 Days
48
4
10 Days
22 Days
96
2
5 Days
11 Days
25 Days
51 Days
311 Days
Password Protection
75 Days
155 Days
50 Days
103 Days
Up to 4 levels of password protection with up to 50 different users are available. Multiple level of password protection and an
audit trail of actions enhance the security of the data.
750 Days
Internal memory (Logging rate = 1 s) - SIREC D400
Extended Security System (option)
8
24 Days
61 Days
137 Days
301 Days
622 Days
ESS provides extended features including entry of unique User
ID’s and associate passwords, time-out of password entry, password expiration, and traceability of user actions. ESS is compatible with the requirements of 21CFR part 11.
16
12 Days
30,5 Days
68,5 Days
750 Days
311 Days
Safety Standards
32
6 Days
15 Days
34 Days
75 Days
155 Days
CE Mark
Pens 70 MByte
180 MByte 400 MByte 890 MByte 1850 MByte
Internal memory (Logging rate = 1 s) - SIREC D300
Data Export
Conformity with 73/23/EEC, Low Voltage Directive and
89/336/EEC EMC Directive.
Removable compact flash and USB flash storage device provides multiple data storage alternatives. Data is stored in a secure binary encrypted format, with the recorder’s configurations,
providing added security of the data files. Removable Compact
flash and USB flash storage devices.
Enclosure rating
Events
"Wire seal provision” that provides added security to seal the
front door and rear wiring when using optional rear cover to prevent undetected entry to these areas of the recorder.
Certain conditions or operations can be set up and logged according to the time and date of the occurrence. Subsequently
events can be reviewed in a list or represented on a graph.
Standard NEMA 3/IP54 type front face protection. NEMA 4X/IP66
available as an option.
Security tag
Batch
Batch enhances the management of data collected in non-continuous process, known as batch processing, used in thermal
treatment, sterilisation, food processing and chemical reactions.
Soft Alarms
6 "software" alarms per pen are easily set up to display and
record selected out-of-limit conditions. These can be tied to the
relay or digital outputs to activate the user’s external equipment.
Independent Display Chart Speeds and Logging rates
Logging rates can be programmed completely separate from
the chart display speed, allowing the data to be displayed and
stored at the rates that best suits the application.
Fuzzy Logging
This standard feature provides a unique method to increase the
storage capacity of the recorder. The data is monitored to determine changes in process data; if no changes are observed data
is logged periodically. If data is changing rapidly, it is recorded
normally at the programmed rate. By not logging data that is
static, data compression of up to 100:1 or more can be achieved
saving valuable memory.
Pulse Inputs
The 8 Digital I/O option card has 4 channels that can be set as
pulse inputs (first 4 channels). The operating frequency for pulse
inputs on the Digital I/O card is 1kHz max.
Siemens MP 20 News · 2007
15
SIREC D Display Recorder
SIREC D300 and SIREC D400
■ Technical specifications
Standard Screens and Custom
Screens
Design Attributes
Display size and Type
Diagonal, Digital Colour LCD
(TFT) with Touch Screen Industrial
grade with brightness adjustment
and wide viewing angle
• SIREC D300
5.5“ (14 cm) diagonal, color
• SIREC D400
12.1“ (30.7 cm) diagonal, color
Resolution
• SIREC D300
QVGA (320 x 240 pixels)
• SIREC D400
SVGA (800 x 600 pixels)
Screen Saver
Set in minutes from 1 … 720, can
be set to dim the screen or to
switch off
Brightness adjustment
Adjustable between 10 and
100%, default set to 80% brightness.
Backlight life time
• SIREC D300
• SIREC D400
55,000 hours to half brightness
when used at 100% (86,000 h if
used at 80%).
Maximum luminosity 400 cd/m²
Data Storage
• Removable Media
43,000 hours to half brightness
when used at 100%
(67,000 h if used at 80%).
Maximum luminosity 400 cd/m²
Compact Flash card, supports up
to 1850 MByte
• Local Mass Storage Options
• USB memory key - up to
2 GByte
• USB hard drive - up to
120 GByte
• Internal Data Buffer
Non-volatile, 70 MByte (16 million
acquisition values) upwards to
1,850 MByte (400 Million points)
• Setup and screens
Stored internally on non-volatile
memory
• Manual Saving
Data saving by inserting compact
flash card or USB memory stick
• Data Saving Period
Related to log rate, number of
pens, totals and alarms.
Each pen is capable of its own
independent storage rate
(20 ms … 60 h)
Display Update Rate
Display values updated every
second
Status Display
A status bar, at the top of the
recorder’s screen, displays the
real-time icons of the recorder
status, such as Recording Time
left and alarm active
Communications
Mathematics
Ethernet 10/100 base -T with
RJ45 connector supporting
Modbus/TCP, FTP, Internet, DHCP
or fixed IP address.
RS485 Modbus RTU (up to
115200 Baud Rate)
Basic Maths include Add, Subtract, Multiply, Divide, Modulo and
power. Full Maths and Scripting
(option) support up to 100 character free form math expression
for each pen. For example SINE,
COS, TAN, Log, Parenthesis (eg.
A1 + A2), comm variables, free
memory, and access to any data
item variable (A1, P1, D1 etc.).
Front and Rear USB Ports
Fully programmable display values in engineering units. Time &
date stamp on every division.
Sets of Standard screens are
available to display data on a
chart, digital reading, bargraphs
or numerous combinations
thereof. Screen properties can be
modified on the recorder and customised to suit. Custom screens
created in the Screen Designer
software can be imported into the
recorder for specialist applications. Custom Screen firmware
option is required.
Digital values displayed include
• alarms on bars,
• engineering units,
• pen name,
• Measuring point number
• tag, time and date,
• 20 character description and
• totalised values.
USB host ports front and rear for
data and setup transfers through
these ports. External devices
(keyboard or mouse), Barcode
reader, or external mass storage
device. (USB 1.1 compliant)
• Data Format
Binary encoded format
• Recycling Mode
Internal memory has FIFO (First In
First Out) capability where the
newest data over-writes the oldest
data
Power Requirements
• Voltage (VRMS)
100 V AC … 250 V AC (auto
select)
• Frequency
50/60 Hz
• Power Consumption
- SIREC D300
< 40 W
- SIREC D400
< 60 W
• Optional instrument power Voltage
- SIREC D300
20 … 55 V DC / 20 … 30 V AC
Power Consumption: < 40 W
- SIREC D400
20 … 55 V DC / 20 … 30 V AC
Power Consumption: < 60 W
Common Relay Output (SPNC)
16
Siemens MP 20 News · 2007
• NC common alarm relay
2 contacts, normally open when
the recorder is powered (no
active alarms), rating 24 V, 1 A
Battery
Battery backed up for clock, Lithium battery Type 6032, 3.0 V –
10 years life (Recorder powered), 4 years life, typical
(Recorder unpowered)
SIREC D Display Recorder
SIREC D300 and SIREC D400
Password Protection
Multiple Administrator control of
password setup and management with 4 levels of password
protection for – Engineer, Supervisor, Technician, and Operator.
Up to 50 different users are available.
Password protection restricts user
entry to the recorder set up and
specific screens.
• Engineer
Highest access to all levels,
Supervisor, Technician and
Operator
• Supervisor
2nd highest level including Technician and Operator access
• Technician
3rd level including Operator
access
• Operator
4th and lowest level of access
Languages
• English UK & US
• French
• German
• Italian
• Spanish
• Portuguese
• Brazilian
• Polish
• Slovakian
• Czech
• Turkish
• Romanian
• Hungarian
• Russian
Temperature Units
°C, °F oder K (Kelvin)
Recorder Identification
Status bar: Alternately displays
Recorder ID and Recorder
Screen Name. Displays Time and
Date.
Clock
Alarm Set Points
• Alarm triggers
Accuracy: ± 29 ppm
(± 1 minute/month) at 25°C.
Summer/Winter manual or automatic time adjustment or via communications. SNTP Client and/or
Server included for synchronising over Ethernet.
6 per pen integral “soft” alarm set
points easily set by user to
announce selected out of limit
conditions; user can select if an
alarm triggers a change in the
screen background colour
Alarm triggers can be set for Hi,
Lo, Deviation (latched or
unlatched) for alarm acknowledgement
• Alarm Damping
1 s … 24 h
• Hysteresis
± 100% of pen scale
• Common relay output
1 A , 24 V; can be activated on
any alarm
Data Replay Mode
Data replay facility on chart displays at normal, fast or slow
speeds with zoom and cursor
Display Chart Speeds
• Chart rates
• 1 mm/h
• 5 mm/h
• 10 mm/h
• 20 mm/h
• 30 mm/h
• 60 mm/h
• 120 mm/h
• 600 mm/h
• 1200 mm/h
• 6000 mm/h
Combinations of rates can be
mixed and chart speeds can be
set independently for each chart.
Display speeds are independent
of logging rate.
Messages Screen
The message screen displays
system information and records
any setup activity that has been
changed. It also provides warning
and error message updates, lists
alarm activity and will display
user defined marks on a chart.
CE Conformity (CE Mark)
This product conforms with the
protection requirements of the following European Council Directives: 73/23/EEC, the Low Voltage
Directive, and 89/336/EEC, the
EMC Directive.
Conformity of this product with
any other “CE Mark” Directive(s)
shall not be assumed.
Immunity Product Classification
Complies with EN 61326 Class I:
Cord Connected, Panel Mounted
Industrial Control Equipment with
protective earthing (grounding),
EN 61010-1
Enclosure Rating
Front panel designed to
NEMA3/IP54
(Optional NEMA 4X/IP66)
Installation Requirements
Category II:
Overvoltage (EN 61010-1)
Pollution Degree 2
EMC Standards
Emissions - EN 61326 Class B
Immunity - EN 61326 Industrial
Levels
Safety
Complies with EN 61010-1: 2001
Panel Mounted Equipment, Terminals must be enclosed within the
panel
Analog Inputs
Number of Inputs
• SIREC D300
4, 6, 8, 12 or 16 input channels
• SIREC D400
4, 6, 8, 12, 16, 24, 32, 40 or 48
input channels
Input Types
mV, V, mA with external shunt
(provided as standard), Thermocouple, RTD and ohms
Minimum Input Span
Range is fully configurable with
span limitation of the operating
range selected with 4% under
range to 4% over-range capability
(50 V Range 2%)
Burnout (T/C)
Active (High or Low), Passive and
Health watch/maintenance
(option).
Cold Junction Compensation
Internal compensation with the
ability to manually adjust values,
External Input for compensation,
External CJC value specified
Siemens MP 20 News · 2007
17
SIREC D Display Recorder
SIREC D300 and SIREC D400
Input Resolution
0.0015% (16 Bit ADC)
•L
-200 ... 0 °C (-328 ... 32 °F)
0 ... 900 °C (32 ... 1652 °F)
10 Ω, use ± 0.1% external resistor,
Volts > 1 MΩ, all other > 10 MΩ
• G (W_W26)
0 ... 100 °C (32 ... 212 °F)
100 ... 316 °C (212 ... 601 °F)
316 ... 2315 °C (601 ... 4199 °F)
• C (W5, W26)
0 ... 180 °C (32 ... 356 °F)
180 ... 1220 °C (356 ... 2228 °F)
1220 ... 2315 °C
(2228 ... 4199 °F)
• M (NiMo-NiCo) (NNM90)
-50 ... 370 °C (-58 ... 698 °F)
370 ... 1410 °C (698 ... 2570 °F)
• N (Nicosil Nisil)
-200 ... 100 °C (328 ... 212 °F)
100 ... 1300 °C (212 ... 2372 °F)
Input Impedance
• Current loop resistance
Source Impedance
• T/C and RTD
100 Ω per lead maximum
(Cu10 = 15 Ω)
Square Root Extraction
Available as standard on every
input type
Sensor Compensation
Single point and Dual point
Input Sampling Rate
• SIREC D300
Recorder has 2 available slots
with up to 8 analog inputs each;
the input sampling rate is dependent on actuation type
• SIREC D400
Recorder has 6 available slots
with up to 8 analog inputs each;
the input sampling rate is dependent on actuation type
• All Inputs
100 ms (10 Hz), 200 ms (5 Hz),
500 ms (2 Hz)
• Fast Sampling
20 ms (50 Hz) - mA, mV, Volts and
Ohms only
Linear Scales
• Normal and Scientific notation
• Decimal Point automatic or programmable
• Engineering units, user definable (10 characters)
Logarithmic Scales
Logarithmic Decade limits:
-38 min, to +38 max, (recommend
up to 20 decades on one screen
to ensure clarity)
• Chromel/Copel
-50 ... 600 °C (-58 ... 1112 °F)
• P (Platinel)
0 ... 1390 °C (32 ... 2534 °F)
•D
0 ... 180 °C (32 ... 356 °F)
180 ... 1840 °C (356 ... 3344 °F)
1840 ... 2490 °C
(3344 ... 4515 °F)
Resistance thermometers
Temperatur range
• Pt100 α = 0,00385
-200 ... 850 °C (-328 ... 1562 °F)
• Pt200
-200 ... 850 °C (-328 ... 1562 °F)
• Pt500
-200 ... 850 °C (-328 ... 1562 °F)
• Pt1000
-200 ... 850 °C (-328 ... 1562 °F)
• Nickel, 100 Ω
-60 ... 180 °C (-76 ... 356 °F)
• Nickel, 120 Ω
-80 ... 260 °C (-112 ... 500 °F)
• Cu10
-200 ... 260 °C (-328 ... 500 °F)
• Cu53
0 ... 150 °C (32 ... 302 °F)
Logging
Logging Method
Input Isolation
300 V AC channel-to-channel,
channel-to-ground
Sample, Average, Min/Max - can
be set independently per pen
Logging Types
Continuous, Fuzzy
Noise Rejection
At 50/60Hz ± 2%
Logging Rate
From 200 ms … 60 h per Pen
• Common mode
2 Hz = -120 dB, 5 Hz = -120 dB,
10 Hz = -120 dB
Fuzzy Logging
• Normal Mode
2 Hz = -85 dB, 5 Hz = -80 dB,
10 Hz = -48 dB
A secure data storage technique
which delivers data compression
ratio of 100:1 or more; self teaching, storing the data at a variable
rate to match the process
Input Actuation (Linear)
Range
• mV (DC)
-1000 … +1000
• V (DC)
-50 … +50
Mechanical Design
Enclosure/Bezel
Zinc plated steel case with high
impact resistant polycarbonate
bezel; scratch resistant lens
• Enclosure Rating
• NEMA 3/IP54 protection rating
standard
• Optional NEMA 4X/IP66 (Front
face only)
• mA
4 … 20, 0 … 20
• 200 Ω
0 … 200
• 500 Ω
0 … 500
• 1000 Ω
0 … 1000
• 4000 Ω
0 … 4000
• Colour
Bezel: Grey
Thermocouples
Temperatur range
Mounting Panel
•B
260 ... 538 °C (500 ... 1000 °F)
538 ... 1816 °C (1000 ... 3300 °F)
•E
-270 ... -200 °C (-454 ... -328 °F)
-200 ... -70 °C (-328 ... -94 °F)
-70 ... 1000 °C (-94 ... 1832 °F)
•J
-210 ... 0 °C (-346 ... 32 °F)
0 ... 1200 °C (32 ... 2192 °F)
•K
-270 ... -70 °C (-454 ... -94 °F)
-70 ... 1372 °C (-94 ... 2502 °F)
•R
-50 ... 260 °C (-58 ... 500 °F)
260 ... 1768 °C (500 ... 3214 °F)
•S
-50 ... 260 °C (-58 ... 500 °F)
260 ... 1768 °C (500 ... 3214 °F)
•T
-270 ... -210 °C (-454 ... -346 °F)
-210 ... 400 °C (-346 ... 752 °F)
Unlimited mounting angle
For the best view of the display
the viewing angle should not
exceed:
SIREC D300
• 55° from the left or right,
• 40° looking down and
• 50° looking up at the recorder
display.
SIREC D400
• 70° from the left or right,
• 45° looking down and
• 55° looking up at the recorder
display.
Mounting adjustable for panel
thickness of 2 mm … 20 mm.
Adapter kits available for covering existing panel cutouts.
18
Siemens MP 20 News · 2007
SIREC D Display Recorder
SIREC D300 and SIREC D400
• Number/Type
300 x 300 x 247
(11.34 x 11.34 x 9.72”)
• 4 or 8 relay contacts SPDT,
3 A 240 V AC, 3 A 24 V AC/DC,
0.2A 240 V DC (non-inductive,
internally suppressed)
• 8 I/O or 16 I/O - SPNO,
1 A 24 V DC (non-inductive, internally suppressed)
• Activation
Fully programmable internal
alarm levels. Assignable to any
relay output
• SIREC D300
138 x 138 mm (5.43 x 5.43”)
Digital Input/Output
• SIREC D400
281 x 281 mm (11.06 x 11.06”)
• Quantity
• 8 I/O or 16 I/O
All channels may be selected
freely as either digital inputs or
outputs. The Digital I/O card also
has 4 channels that can be set as
pulse inputs (channels 1 … 4).
The operating frequency for pulse
inputs on the Digital I/O card is
1kHz max.
• Relay Outputs
• 4 relay outputs
All four channels are relay outputs
only
• Relays/DI card
• 8 relays/ 2 DI card
2 outputs can be configured for
use as digital inputs: A digital
input is provided by a volt free
contact between the normally
open (NO) and the common (C)
terminals of an output relay. If the
2 Digital inputs are used only 6
relay outputs are available.
Closed < 500 Ω, Open > 300 kΩ.
Custom Screens
Provides the capability in the
recorder to accept custom screen
designs from the Screen
Designer.
Email
Setup email accounts to send the
following:
When an Alarm is triggered or an
Email can be sent as a part of an
Event occurring, such as: Alarms
- In/Out/Ack, Totaliser – Start,
Stop or Reset, Digital Inputs – On,
Off or State change, TC Burnout –
on a specific Analog Input channel, Scheduled Events – Once,
Interval, Specific days, Month
End
OPC Server
OPC 3.0 DA and AE compliant.
Totalisers and up to 96 pens can
be transmitted via OPC server,
max poll rate 1/s
Event marker
User defined process events are
recorded and can be set to cause
particular recorder actions.
Events can consist of recording
start/stop, digital inputs, alarms,
totalising actions, timers, barcode, etc. Once an event has
been caused it can produce a
definable set of effects on the
recorder which can include, mark
on chart, relay outputs, recording
control, acknowledge alarm, trigger an Event, set/clear Relay,
Screen change, E-mail a message and Reset max/mins. Each
event marker can be recorded for
analysis using the SIREC D application software.
Analog Outputs
(Re-transmission Outputs)
Re-transmission outputs available; a pen drives each output.
Analog inputs, totalised values or
any mathematical result can be
re-transmitted.
Dimensions (W x H x D) in mm
Additional 80 mm (3.15”) clearance recommended for a straight
type power cable and signal connectors
• SIREC D300
144 x 144 x 200
(5.67 x 5.67 x 7.87”)
• SIREC D400
Cutout (W x H) in mm
Weight
• SIREC D300
Max. 3.5 kg (7.7lb)
• SIREC D400
Max. 10 kg (22 lb)
Wiring Connections
IEC Power Plug. Removable terminal strip for input and alarm
connections
Environmental and Operating
Conditions
Ambient Temperature
0 °C … 50 °C (32 °F ... 122 °F)
Relative Humidity (%RH)
10 ... 90
Vibration
• Frequency (Hz)
0 ... 70
• Acceleration (g)
0.1
Mechanical Shock
• Acceleration (g)
1
• Duration (ms)
30
Mounting Position from Vertical
• Tilted Forward
40°
• Tilted Backward
65°
• Tilted to Side (±)
65°
Power Requirements
• Mains Voltage (Vrms)
100 … 250
• Low Voltage AC (Vrms)
20 … 30
• DC Voltages
20 … 55
• Frequency (Hz)
47 … 63
Power Consumption
• SIREC D300
AC: < 40 W (max),
DC: < 40 W (max). Typical 20 W
• SIREC D400
AC: < 60 W (max),
DC: < 60 W (max) . Typical 30 W
Warm Up
30 minutes minimum
Seismic Qualification
Complies with IEEE 323-1974
and/or 1983 and IEEE 344-1975
and/or 1987 (optional)
Options
Pulse Input
• Quantity
4 isolated inputs per board
• Frequency
1 Hz … 25 kHz, updated once
per second
• Input
Low < 1V, High > 4 V … < 50 V or
Volt free input: Low = short circuit,
High = open circuit.
Alarm Outputs
Programmable alarm set points
(6 per pen) can be configured to
activate up to 16 (SIREC D300)
respectively 48 outputs
(SIREC D400)
• Update rate
200 ms for all alarms
Modification 03/2008
Siemens MP 20 News · 2007
19
SIREC D Display Recorder
SIREC D300 and SIREC D400
• Quantity
- SIREC D300
2 or 4 re-transmission outputs
- SIREC D400
2, 4, 6 or 8 re-transmission outputs
• Update Rate
250 ms all channels
• Accuracy
± 0.1% (0 … 500 Ω load),
± 0.25% (500 Ω, 1 kΩ load)
• Type
0 … 20 mA, 4 … 20 mA
• Maximum Load Resistance
1 kΩ
• Resolution
0,002%
• Isolation
300 V AC
Health Watch/Maintenance Capability
The recorder keeps track of
important “life actions” for
improved diagnostics and preventative maintenance notification.
Including
• Powered On
• Last powered On
• Time On since power up
• Total On time
• Total Off time
• Longest Off time
• Hardware/Firmware updates
• Lithium cell life
• Backlight life left at 100% brightness
• Compact Flash insertions,
• Hi/Lo CJC value (Hi & Lo temps),
• Analog In last factory/user calibration
• Relay operations
Totaliser/Sterilisation
One totaliser per input. Totaliser
value must be assigned to a pen
for display and storage.
Multiple totalisations (Maths
option) are possible with the use
of extra pens (option). Reset may
be manual or programmed. Totalisation values are 10 digits plus
exponent.
Each pen can be totalised
according to the Fo or Po sterilisation function at 121.11°C
(250 °F).
The Standard Reference Temperature and Thermal Resistance (Z
Value) are fully adjustable values
of X, Y, W and V. Start temp, Reference temp and Z factor are all
user defined, allowing support for
many different types of sterilisation applications.
Specification table for Sterilisation
The definition of Fo/Po is the sterilisation/pasteurisation time in
minutes required to destroy a
stated number of organisms with
a known z at temperature T.
Batch
The Batch function allows the
user to segment portions of data
for further analysis.
Batch controls include
• Start,
• Stop,
• Pause,
• for viewing,
• Resume and Abort.
Print Support
Network printing from status,
message and replay screens.
Plus screen capture facility of process screens instantly using a
basic USB standard PCL printer.
Math Algorithms
All analog input channels have a
math expression block. This is a
fully user programmable 100
character free form math expression for each pen. Math calculations available on all pens, one
per input plus 16 extra pens for
the SIREC D300 and 48 extra
pens for the SIREC D400
recorder. Scripting maths
includes conditions and multi-line
scripting in pen maths expressions. Allow functions, permanent variables and constants,
timers. 500 characters maximum
per pen.
Miscellaneous
Optional customer ID Tagging (3
lines of up to 22 characters each
line)
Agency Approval
• CSA
CSA22.2-No.1010.1-2004 Certificate Number L211230
• UL
ANSI/UL61010-1-2004 File #
201698
FM Class 1 Division 2 (optional)
Transmitter Power (optional)
• SIREC D300
200 mA at 24 V DC ± 3 V DC
• SIREC D400
1 A at 24 V DC ± 3 V DC
Extended Security System (ESS)
Provides full support for 21 CFR
Part 11.
Includes features for entry of
unique User ID’s and associated
passwords:
• Timeout on inactivity
(1 … 10 min)
• Password expiration
(1 … 365 days)
• Up to 50 users
• Password re-entry lock out for incorrect entry of password more
than 3 times, no re-use of passwords (programmable
4 … 12 times)
• Traceability by user name
20
Siemens MP 20 News · 2007
SIREC D Display Recorder
SIREC D300 and SIREC D400
Firmware Credit System
The credits system is a flexible way of adding to the recorder features without having to upgrade the firmware. Simply purchase
a number of credits to cover your current and possibly future requirements and the recorder will be delivered with the credits
loaded. The credit value in each recorder is displayed in the
Factory menu.
• Select the Options button and by activating and de-activating
the options in the credit list, the recorder will change its functionality. Any greyed out options on the list will mean there are
not enough credits available for that feature on the recorder.
Credits can be applied as desired to the Firmware functions until
the total number of credits purchased has been used up. Additional credits can be purchased later if new features are to be activated and not enough credits are available to support these additional functions.
Firmware option
Credit value
Description
Full Maths
4
Full Math - this can handle math expressions that can consist of expressions up to 100 characters
in length. (Note 1)
Full Maths with Scripting
6
A powerful multi-line scripting ability available to solve complex state based applications.
Eg.: “If .. X happens, then Y will happen, else.. Z will occur. (Note 1)
Events
6
Events are certain conditions or operations that can be set up and logged according to the time
and date of an occurrence. Subsequently events can be reviewed or displayed on a graph.
Events can produce the following actions: Mark on Chart, start/stop Logging, Start/stop/reset Totalisers, Set/clear Relay (Digital), Acknowledge alarm, trigger an Event, Screen change, E-mail a
message and Reset max/mins. (Note 3)
Fast Scanning mode
5
For fast processes, the scan rate and recording of the data can be set for up to 50 times per second (20 ms) for
• SIREC D300: up to 8 inputs
• SIREC D400: up to 16 inputs
Totalisers/ Sterilisation calcu- 4
lation
Each pen can be associated with a totaliser. Using extra pens, the totalised values can be displayed and recorded; multiple totals can be calculated out of the same variable (weekly, monthly,
etc.). The totaliser function can handle Fo and Po sterilisation calculation. (Note 1)
Custom Screens
4
Import custom built screens that have been created in SIREC D-Designer. (Note 2)
Health Watch/ Maintenance
2
The recorder keeps track of important “life actions” for improved diagnostics and preventative
mainte-nance notification. Including Powered On, Last powered On, Time On since power up,
Total On time, Total Off time, Longest Off time, Lithium cell life, Backlight life left at 100% brightness, Compact Flash insertions, Hi/Lo CJC value (Hi & Lo temps), Analog In last factory/user cal,
Relay operations
Print Support
2
Enables the printer option to print text from various screens using a basic USB standard PCL
printer.
Batch
3
The Batch function allows the user to segment portions of data for further analysis. Batch controls
include Start, Stop, Pause, for viewing, Resume and Abort.
Groups
2
Groups of Pens can be specified and named with a Group number to display on the recorder.
Remote Viewer
3
Extends the user interface of the recorder onto the desktop PC. Providing full remote control of the
unit launched from a web browser.
Email
3
Setup email accounts to send the following: When an Alarm is triggered or an Email can be sent as
a part of an Event occurring, such as:
Alarms - In/Out/Ack, Totaliser – Start, Stop or Reset, Digital Inputs – On, Off or State change, TC
Burnout – on a specific Analog Input channel, Scheduled Events – Once, Interval, Specific days,
Month End.
OPC Server
8
OPC (OLE for Process Control) -Software application for realtime interfacing between servers and
cli-ents. OPC is a software standard that defines common interfaces for data exchange between
devices such as recorders, controllers, PLC’s and Microsoft Windows™ based applications
Extra Pens (4)
2
4 extra pens to store and display totalised values, results of calculations, etc.
• SIREC D300: Maximum is up to 16 extra pens
• SIREC D400: Maximum is up to 48 extra pens
Notes
• (1) Additional pens (“Extra Pens”) can be used to display and
store the results of calculations, totalisers, variables imported
via communications, or to store values.
• (2) Screens from Screen Designer for SIREC D300 and SIREC
D400 cannot be imported.
• (3) Event markers are required to automatically reset the totalisers, for example on a periodic basis or on an external condition. (Not necessary if the totalisers are reset manually).
Additional information is available in the Internet under:
http://www.siemens.com/sirec
Siemens MP 20 News · 2007
21
SIREC D Display Recorder
SIREC D300 and SIREC D400
■ Selection and Ordering Data
Order No.
■ Selection and Ordering Data
Order No.
SIREC D300 display recorder 1)
7ND4421-
SIREC D300 display recorder 1)
7ND4421-
Front dimensions:
144 mm x 144 mm, for all applications,
Cycle time: 200 ms for mA,V,mV/500 ms
for TC/RTD/R
Rear side: Ethernet interface; RS485;
USB
Front face: slot for CF card;
USB interface
7 7 A 7 7 - 7 7 7 7
Front dimensions:
144 mm x 144 mm, for all applications,
Cycle time: 200 ms for mA,V,mV/500 ms
for TC/RTD/R
Rear side: Ethernet interface; RS485;
USB
Front face: slot for CF card;
USB interface
7 7 A 7 7 - 7 7 7 7
Power supply
Firmware options
(see table below " Firmware options and
required credits")
50 or 60 Hz, 90 ... 240 V AC
• without transmitter power supply
} 1
• 24 V DC max. 200 mA transmitter power
supply
None
2
}
A
10 credits
B
20 credits
C
30 credits
D
Analog inputs/ Pulse inputs
40 credits
E
8 analog inputs
50 credits
F
A
60 credits
G
• 2 analog outputs
B
Protection rating standard (front face)
• 4 analog outputs
C
IP54
14 analog inputs, without analog outputs
D
• without earthquake-proof version
16 analog inputs, without analog outputs
E
IP66 (NEMA 4X)
24/48 V DC / 24 V AC, 50/60 Hz, without
transmitter power supply
• without analog outputs
4
}
4 pulse inputs
}
A
• without earthquake-proof version
D
• without analog outputs
H
• Earthquake-proof version
E
• 2 analog outputs
J
Documentation
• 4 analog outputs
K
Manual in German
• 8 analog inputs, without analog outputs
L
Manual in English
8 pulse inputs, without analog outputs
M
1)
}
0
4 relays (240 V)
1
8 relays, of which 2 can be optionally
configured as binary input (240 V)
2
8 binary outputs and inputs
(24 V relay/freely-configurable)
3
16 binary outputs and inputs
(24 V relay/freely-configurable)
4
}
1
180 Mbyte
2
400 Mbyte
3
890 Mbyte
4
1850 Mbyte
5
Extended Security System (ESS)
}
None
With
22
1
2
Siemens MP 20 News · 2007
2
Subject to export regulations AL:N, ECCN: EAR99
Scope of delivery:
Recorder, CD-ROM with manual in German or English, SIREC D software
(SIREC D-Viewer).
Note: CF card is included in the scope of delivery.
Internal data storage
70 Mbyte (standard)
1
} Available ex stock
Switching outputs and inputs
None
}
SIREC D Display Recorder
SIREC D300 and SIREC D400
■ Selection and Ordering Data
■ Selection and Ordering Data
Order No.
SIREC D400 display recorder 1)
Front dimensions:
300 mm x 300 mm, for all applications
7ND44617 7 7 7 7 - 7 7 7 7
Order No.
SIREC D400 display recorder 1)
Front dimensions:
300 mm x 300 mm, for all applications
Power supply
Internal data storage
50 or 60 Hz, 90 ... 240 V AC
70 Mbyte (standard)
7ND44617 7 7 7 7 - 7 7 7 7
}
1
} 1
180 Mbyte
2
• 24 V DC max. 200 mA transmitter power
supply
2
400 Mbyte
3
890 Mbyte
4
24/48 V DC / 24 V AC, 50/60 Hz,
without transmitter power supply
4
1850 Mbyte
5
• without transmitter power supply
Analog inputs (slot allocation 1 … 4)
Extended Security System (ESS)
16 analog inputs
None
1
• without pulse inputs
A
With
2
• 4 pulse inputs
B
• 8 pulse inputs
C
Firmware options
(see table "Firmware options and
required credits")
}
24 analog inputs
}
None
A
• without pulse inputs
D
10 credits
B
• 4 pulse inputs
E
20 credits
C
32 analog inputs, without pulse inputs
F
30 credits
D
40 credits
E
without analog inputs
• 4 pulse inputs
G
50 credits
F
• 8 pulse inputs
H
60 credits
G
• 12 pulse inputs
J
70 credits
H
• 16 pulse inputs
K
Protection rating standard (front face)
IP54
Analog inputs/Pulse inputs
(slot allocation 5 and 6)
• without earthquake-proof version
without analog inputs
• without analog outputs
A
IP66 (NEMA 4X)
}
A
• 2 analog outputs
B
• 4 analog outputs
C
• without earthquake-proof version
D
• Earthquake-proof version
E
Documentation
8 analog inputs
Manual in German
• without analog outputs
D
• 2 analog outputs
F
16 analog inputs, without analog outputs
G
}
}
1
Manual in English
2
} Available ex stock
1)
Switching outputs and inputs
(distributed on 3 slots)
None
}
0
4 relays (240 V)
1
8 relays, of which 2 can be optionally
configured as binary input (240 V)
2
16 relays, of which 4 can be optionally
configured as binary input (240 V)
3
24 relays, of which 6 can be optionally
configured as binary input (240 V)
4
8 binary outputs and inputs
(24 V relay/freely-configurable)
5
16 binary outputs and inputs
(24 V relay/freely-configurable/ 1 x 16)
6
24 binary outputs and inputs
(24 V relay/freely-configurable/16 + 8)
7
48 binary outputs and inputs
(24 V relay/freely-configurable/3 x 16)
8
Subject to export regulations AL:N, ECCN: EAR99
Scope of delivery:
Recorder, CD-ROM with manual in German or English, SIREC D software
(SIREC D-Viewer).
Note: CF card is included in the scope of delivery.
Modification 03/2008
Siemens MP 20 News · 2007
23
SIREC D Display Recorder
SIREC D300 and SIREC D400
■ Accessories
Firmware options and required credits
Order No.
SIREC D300
Firmware options for
SIREC D300 and SIREC D400
Code No. of recorder required
Options
10 credits
7ND4 801-8AC
20 credits
7ND4 801-8BC
30 credits
7ND4 801-8CC
40 credits
7ND4 801-8DC
50 credits
7ND4 801-8EC
60 credits
7ND4 801-8FC
70 credits (SIREC D400 only)
7ND4 801-8GC
Options/enabling of SIREC D
software
Code No. of software required
Required credits
Groups/summarize channels
2
Diagnostic functions
2
Print support
2
4 extra pens (virtual channels)
2
8 extra pens (virtual channels)
4
16 extra pens (virtual channels)
8
Counter
2
Remote viewer
3
Batch
3
E-mail function
3
Enabling of SIREC D-Manager
7ND4 800-8BA
Totalisers
4
Enabling of SIREC D-Server
7ND4 800-8CA
Maths (free functions)
4
Enabling of SIREC D-Designer
(only for SIREC D300 and SIREC
D400)
7ND4 801-8DA
Maths and Scripts (free functions)
6
Events (logical connections)
6
Upgrading of SIREC D-Manager
to SIREC D-Server
7ND4 800-8EA
OPC Interface
8
Custom specified screens
4
SIREC D software
Only for subsequent orders; software is included in delivery of
recorder
Evaluation software for
SIREC D200/D300/D400 (on CD)
incl. enabling for SIREC D-Viewer
and manual for the software on
CD in German, English, French
7ND4 800-8AA
Fast scanning
(20 ms/only with mV/V/mA)
5
SIREC D400
Options
Required credits
Groups/summarize channels
2
Diagnostic functions
2
Documentation
Included on CD-ROM in scope of
delivery
Print support
2
4 extra pens (virtual channels)
2
SIREC D300 and SIREC D400
recorder manual
8 extra pens (virtual channels)
4
16 extra pens (virtual channels)
8
32 extra pens (virtual channels)
16
48 extra pens (virtual channels)
24
Counter
2
• French (can only be downloaded from Internet)
Remote Viewer
3
Batch
3
Scope of delivery:
Recorder, CD-ROM with manual in German or English, SIREC D software
(SIREC D-Viewer).
Note: CF card is included in the scope of delivery.
E-mail function
3
Full Maths
4
Maths (free functions)
4
Maths and Scripts (free functions)
6
• German (can also be downloaded from Internet)
A5E01001785
• English (can also be downloaded from Internet)
A5E01001767
24
Siemens MP 20 News · 2007
Events (logical connections)
6
OPC Interface
8
Custom specified screens
4
Fast scanning
(20 ms/only with mV/V/mA)
5
Modification 07/2007
SIREC D Display Recorder
SIREC D300 and SIREC D400
■ Options
Options - Hardware
• Alarm Card
- 4 or 8 outputs relay contacts SPCO 240 V
- 8 Digital I/O or 16 Digital I/O - SPNO 24 V DC
- Programmable alarm set points can be configured to activate up to 16 outputs for the SIREC D300 and 48 outputs for
the SIREC D400.
• Analog Output
- 2 or 4 outputs available per card
- Output type: 0-20 mA or 4-20 mA
• Nema 4X/IP66
- Nema 4X/IP66 protection available as an option.
• Portable Recorders
- Portable cases available as an accessory item.
• Digital Input
Two digital input options are available:
- 2 inputs on 8 channel Alarm card, 8 inputs on 8 Digital I/O
card and 16 inputs on a 16 Digutal I/O card. The digital inputs allow users to initiate, from a remote location via a dry
contact closure, selected recorder functions.
• Pulse Counting
- Up to four counting inputs per board, are available to count
signals up to 25 kHz (SIREC D300: max. 2 cards;
SIREC D400: max. 6 cards).
• Approvals
- CSA, UL and FM CL1 Div 2 approvals
• 24 V AC/DC or 48 V DC Power Supply
- 20 to 55 V DC
- 20 to 30 V AC
• 24 V DC Transmitter Power Supply
- Can supply up to 200 mA (SIREC D300) respectively 1 A
(SIREC D400) to external transmitters.
• Print Support
- Network printing from status, message and replay screens.
Plus screen capture facility of process screens instantly using a basic USB standard PCL printer.
■ Dimensional drawings
156.92 (6.178)
80 (3.150)
200 (7.874)
37 (1.457)
137.5 (5.413)
144,01 (5.670)
144.01 (5.670)
Two mounting brackets are supplied as standard
138.00
(5.43”)
Panel
Cut-out
Panel
Cut-out
+1
-0
138.00
(5.43”)
+1
-0
> 7.00
(0.28”)
> 6.00 (0.237”)
Panel
Cut-out
SIREC D300 Recorder Panel Cut-Out
SIREC D300, dimensions in mm (inch) and panel cut-out
Siemens MP 20 News · 2007
25
SIREC D Display Recorder
SIREC D300 and SIREC D400
200 (7.874)
47 (1.850)
Two mounting brackets are supplied as standard
281.00
(11.06”)
Panel
Cut-Out
Panel
Cut-Out
Panel
Cut-Out
SIREC D400, dimensions mm (inch) and panel cut-out
Siemens MP 20 News · 2007
281
(11.06”)
> 20,00
(0.787”)
> 20.00 (0.787”)
26
80 (3.150)
280 (11.024)
300 (11.811)
300 (11.811)
SIREC D400 Recorder Panel Cut-Out
SIREC D Display Recorder
SIREC D300 and SIREC D400
■ Schematics
CJC
Connector
position
Slot A
Slot B
24 V TX
Power Supply
2-way connector
Analogue Input - Slots A and B
1 2 3 4 5 6 7 8 9 10 11 12
13 14 15 16 17 18 19 20 21 22 23 24
CJC
- +* -+ * - +* - +*
-+* -+ * -+* -+ *
Slot G
4 and 8 Relay Alarm - Slot G
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Analogue Output - Slot B only
1 2 3 4 5 6 7 8 9 10 11 12
NC C NO NC C NO NC C NO NC C NO NC C NO NC C NO NC C NO NC C NO
(Last 2 channels can be Digital Inputs on 8 Alarm Relay card)
+
+
NU
NU
Loop Loop
Loop
Loop
+
+
NU
NU
Loop Loop
Loop Loop
Pulse Input - Slots A & B
(Connector position on right hand side)
8 and 16 Digital Input/Output - Slot G
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
NO C NO C NO C NO C NO C NO C NO C NO C NO C NO C NO C NO C NO C NO C NO C NO C
24 V Transmitter Power Supply
13 14 15 16 17 18 19 20 21 22 23 24
- + NU - + NU - + NU - + NU
This is already fitted to the power supply card within the recorder.
Connection is made via a 2-way connector at rear of unit
Key: NO = Normally Open, C = Common , NC = Normally Closed,
NU = Not Used
SIREC D300 - Terminal assignments and power requirements (rear of unit)
Siemens MP 20 News · 2007
27
SIREC D Display Recorder
SIREC D300 and SIREC D400
Slot A
Slot B
Slot C
Slot D
Slot E
Slot F
24 V TX
Power Supply
CJC
Connector
position
Analogue Input - Slots A to F
1 2 3 4 5 6 7 8 9 10 11 12
13 14 15 16 17 18 19 20 21 22 23 24
CJC
- +* - +* - +* - +*
- +* - +* - +* - +*
Slot G
Slot H
Slot I
Analogue Output - Slots E and F
4 and 8 Relay Alarm - Slots G to I
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
NC C NO NC C NO NC C NO NC C NO NC C NO NC C NO NC C NO NC C NO
1 2 3 4 5 6 7 8 9 10 11 12
(Last 2 channels can be Digital Inputs on the 8 Alarm Relay card)
8 and 16 Digital Input/Output - Slots G to I
+
NU
NU +
Loop
Loop
Loop Loop
+
+
NU
NU
Loop Loop
Loop Loop
Pulse Input - Slots A to F
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
NO C NO C NO C NO C NO C NO C NO C NO C NO C NO C NO C NO C NO C NO C NO C NO C
(Connector position on right hand side)
13 14 15 16 17 18 19 20 21 22 23 24
24 V Transmitter Power Supply
Connection is made via two 10-way connector at rear of unit
Key: NO = Normally Open , C = Common , NC = Normally Closed,
NU = Not Used
- + NU - + NU - + NU - + NU
SIREC D400 - Terminal assignments and power requirements (rear of unit)
■ More information
Additional information is available in the Internet under:
http://www.siemens.com/sirec
28