Download

ACT20X
Manual
Revision History
Version
Date
Change
0.0
02/2009
First Edition
1.0
12/2011
Further products
complemented
2.0
02/2014
Updating of ATEX and
IEC labeling
Further products
complemented
Contact Address
Weidmüller Interface GmbH & Co. KG
PO Box 3030
32720 Detmold
Klingenbergstraße 16
32758 Detmold
Germany
Phone
Fax
E-Mail
Internet
1066540000/02/02.14
+49 (0) 5231 14-0
+49 (0) 5231 14-2083
[email protected]
www.weidmueller.com
3
Contents
Contents
Revision History ............................................................................................................................................... 3
Contact Address ............................................................................................................................................... 3
Contents ............................................................................................................................. 4
1.
Approvals............................................................................................................... 8
1.1
CE........................................................................................................................................................ 8
1.2
EMC..................................................................................................................................................... 8
1.3
LVD ..................................................................................................................................................... 8
1.4
UL ........................................................................................................................................................ 8
1.5
ATEX ................................................................................................................................................... 8
1.6
IECEx .................................................................................................................................................. 8
1.7
cFMus ................................................................................................................................................. 8
1.8
SIL ....................................................................................................................................................... 9
1.9
GOST .................................................................................................................................................. 9
1.10
DNV ..................................................................................................................................................... 9
2.
Warranty Statement ............................................................................................ 10
2.1
36 Months Warranty ........................................................................................................................ 10
3.
Safety Instructions .............................................................................................. 11
3.1
Approved Use .................................................................................................................................. 11
3.2
Qualified Personnel......................................................................................................................... 11
3.3
Accuracy of the Technical Documentation .................................................................................. 11
3.4
Liability ............................................................................................................................................. 11
3.5
Definitions ........................................................................................................................................ 11
3.6
Symbol Identification ...................................................................................................................... 12
3.7
Electrical Precautions ..................................................................................................................... 12
3.8
General Instructions ....................................................................................................................... 12
4.
Introduction ......................................................................................................... 13
4.1
Product Description ........................................................................................................................ 13
5.
4
4.1.1
Product Family ACT20X ......................................................................................................... 13
4.1.2
General Description ................................................................................................................ 15
4.1.3
The Six Basic Module Types in Detail .................................................................................... 16
Installation ........................................................................................................... 17
1066540000/02/02.14
Contents
5.1
General ............................................................................................................................................. 17
5.1.1
Environment ............................................................................................................................ 17
5.2
Unpacking ........................................................................................................................................ 17
5.3
Mounting .......................................................................................................................................... 18
5.4
Marking ............................................................................................................................................. 18
5.5
Electrical Connections.................................................................................................................... 19
5.5.1
EMI Protection......................................................................................................................... 19
5.6
Calibration and Adjustment ........................................................................................................... 19
5.7
Release Lever .................................................................................................................................. 19
5.8
Encoding .......................................................................................................................................... 20
5.9
Configuration ................................................................................................................................... 21
6.
Operation ............................................................................................................. 22
6.1
Normal Operation ............................................................................................................................ 22
6.2
Warm-Up .......................................................................................................................................... 22
6.3
Cleaning ........................................................................................................................................... 22
7.
Product Installation / Operation ......................................................................... 23
7.1
ACT20X-HDI-SDO (NAMUR Pulse Isolator) .................................................................................. 23
7.2
7.3
7.4
7.1.1
Description .............................................................................................................................. 23
7.1.2
Status/Alarm LEDs .................................................................................................................. 24
7.1.3
Electrical Connections ............................................................................................................ 25
7.1.4
Function Description ............................................................................................................... 25
7.1.5
Specifications .......................................................................................................................... 25
ACT20X-HTI-SAO (Temperature/mA Converter) .......................................................................... 30
7.2.1
Description .............................................................................................................................. 30
7.2.2
Status/Alarm LEDs .................................................................................................................. 31
7.2.3
Electrical Connections ............................................................................................................ 32
7.2.4
Specifications .......................................................................................................................... 32
ACT20X-SDI-HDO (Solenoid/Alarm Driver) ................................................................................... 39
7.3.1
Description .............................................................................................................................. 39
7.3.2
Status/Alarm LEDs .................................................................................................................. 40
7.3.3
Electrical Connections ............................................................................................................ 41
7.3.4
Specifications .......................................................................................................................... 41
ACT20X-HUI-SAO (Universal Converter) ...................................................................................... 46
7.4.1
Description .............................................................................................................................. 46
7.4.2
Status/Alarm LEDs .................................................................................................................. 47
1066540000/02/02.14
5
Contents
7.5
7.6
7.7
7.8
7.4.3
Electrical Connections ............................................................................................................ 48
7.4.4
Specifications .......................................................................................................................... 48
ACT20X-HAI-SAO (HART-transparent Repeater) ......................................................................... 56
7.5.1
Description .............................................................................................................................. 56
7.5.2
Status/Alarm LEDs .................................................................................................................. 57
7.5.3
Electrical Connections ............................................................................................................ 58
7.5.4
Specifications .......................................................................................................................... 58
ACT20X-SAI-HAO (HART-transparent Driver) .............................................................................. 63
7.6.1
Description .............................................................................................................................. 63
7.6.2
Status/Alarm LEDs .................................................................................................................. 64
7.6.3
Electrical Connections ............................................................................................................ 65
7.6.4
Specifications .......................................................................................................................... 65
ACT20-FEED-IN-PRO-S ................................................................................................................... 70
7.7.1
Description .............................................................................................................................. 70
7.7.2
Status/Alarm LEDs .................................................................................................................. 71
7.7.3
Electrical connections ............................................................................................................. 72
7.7.4
Specifications .......................................................................................................................... 72
Female Plug BHZ 5.00 ..................................................................................................................... 76
7.8.1
Description .............................................................................................................................. 76
7.8.2
Specifications .......................................................................................................................... 77
Appendix A. Installation Drawings ACT20X-HDI-SDO (NAMUR Pulse Isolator) ......................................79
ATEX Installation Drawing ...................................................................................................................... 79
IECEx Installation Drawing ..................................................................................................................... 83
FM Installation Drawing .......................................................................................................................... 87
Appendix B. Installation Drawings ACT20X-HTI-SAO (Temperature/mA Converter) ..............................91
ATEX Installation Drawing ...................................................................................................................... 91
IECEx Installation Drawing ..................................................................................................................... 97
FM Installation Drawing ........................................................................................................................ 103
Appendix C. Installation Drawings ACT20X-SDI-HDO (Solenoid/Alarm Driver).....................................109
ATEX Installation Drawing .................................................................................................................... 109
IECEx Installation Drawing ................................................................................................................... 115
FM Installation Drawing ........................................................................................................................ 121
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter) ........................................127
ATEX Installation Drawing .................................................................................................................... 127
IECEx Installation Drawing ................................................................................................................... 137
FM Installation Drawing ........................................................................................................................ 147
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater) ...........................157
6
1066540000/02/02.14
Contents
ATEX Installation Drawing .................................................................................................................... 157
IECEx Installation Drawing ................................................................................................................... 167
FM Installation Drawing ........................................................................................................................ 177
Appendix F. Installation Drawings ACT20X-SAI-HAO (HART-transparent Driver) ................................187
ATEX Installation Drawing .................................................................................................................... 187
IECEx Installation Drawing ................................................................................................................... 191
FM Installation Drawing ........................................................................................................................ 195
Appendix G. Installation Drawings ACT20-FEED-IN-PRO-S (Power Feed-In Unit) ................................199
ATEX Installation Drawing .................................................................................................................... 199
IECEx Installation Drawing ................................................................................................................... 203
FM Installation Drawing ........................................................................................................................ 207
1066540000/02/02.14
7
Approvals
1.
Approvals
1.1
CE
These products fulfill the guidelines issued by the
European Union and are therefore entitled to carry
the CE mark.
DEKRA Certification B.V.
II (1) D [Ex ia Da] IIIC
I (M1) [Ex ia Ma] I
1.6
IECEx
In accordance with:
- IEC 60079-0:2011
1.2
EMC
In accordance with:
- IEC 60079-11:2011
- IEC 60079-15:2010
- IEC 60079-26:2007
- EN 61326-1:2006
IECEx marking:
Ex nA nC IIC T4 Gc
1.3
LVD
In accordance with:
- EN 61010-1:2010
1.4
UL
In accordance with:
- UL 61010-1
[Ex ia Ga] IIC/IIB/IIA
[Ex ia Da] IIIC
[Ex ia Ma] I
1.7
cFMus
In accordance with:
Canada
- E60079-0
- CSA 22.2-157
- E60079-11
- CSA 22.2-213
- E60079-15
USA
1.5
ATEX
In accordance with:
- UL 60079-0
- FM3600
- UL 60079-11
- FM3610
- UL 60079-15
- FM3611
- FM3810
- EN 60079-0:2012
- EN 60079-11:2012
- EN 60079-15:2010
- EN 60079-26:2007
cFMus marking:
Install in CL I DIV2 GP A-D T4
Provides IS circuits to CL I-III DIV 1/2 GP A-G or
CL I Zn2 AEx/Ex nA nC [ia] IIC T4.
ATEX marking:
II (1) G [Ex ia Ga] IIC/IIB/IIA
II 3 G Ex nA nC IIC T4 Gc
8
1066540000/02/02.14
Approvals
1.8
SIL
1.9
GOST
1066540000/02/02.14
1.10
DNV
9
Warranty Statement
2.
Warranty Statement
2.1
36 Months Warranty
Weidmüller gives a 36 months warranty on the
product in accordance with the warranty terms as
described in the general business conditions of
the Weidmüller company which has sold the
products to you.
Weidmüller guarantees that defects which have
already existed at the time when the risk passed
will be repaired by Weidmüller free of charge or
Weidmüller will provide a new, functionally
equivalent product to replace the defective one.
The warranty referred to above covers Weidmüller
products. Unless otherwise expressly stated in
this catalogue/product description, Weidmüller
gives no warranty or guarantee as to the
interoperability in specific systems or the fitness
for any particular purpose. To the extent permitted
by law, any claims for damages and
reimbursement of expenses, based on whatever
legal reason, including contract or tort, shall be
excluded.
Unless otherwise expressly stated in this
warranty, the general business conditions and the
expressive liability commitments therein of the
respective Weidmüller company which has sold
the products to you are applicable.
10
1066540000/02/02.14
Safety Instructions
3.
Safety Instructions
3.1
Approved Use
This product is intended for use in applications as
described in the operating instructions only.
Any other utilization is not permitted and can lead
to accidents or destruction of the device.
Using the device in non-approved applications will
immediately void all guarantee and warranty
claims on the part of the operator against the
manufacturer.
3.2
Qualified Personnel
These operating instructions are intended for
trained and qualified personnel that is familiar with
the valid regulations and standards relevant to the
field of application.
3.3
3.4
Liability
To the extent that instructions in this manual are
not strictly observed, the customer cannot
advance a demand against Weidmüller that would
otherwise exist according to the concluded sales
agreement.
3.5
Definitions
• Hazardous voltages have been defined as the
ranges: 75…1500 V DC and 50…1000 V AC.
• Technicians are qualified persons trained to
mount, operate and troubleshoot technically
correct and in accordance with safety
regulations.
• Operators, being familiar with the contents of
this manual, adjust and operate the knobs or
potentiometers during normal operation.
Accuracy of the Technical
Documentation
These manual was written with due care and
attention.
However, unless otherwise required by law, we do
not guarantee that the data, images and drawings
are accurate or complete nor do we accept liability
for their contents.
Weidmüller’s general business conditions apply in
their respective valid form. They are subject to
alteration without notice.
1066540000/02/02.14
11
Safety Instructions
3.6
Symbol Identification
3.7
Electrical Precautions
DANGER
WARNING
Indicates an imminently hazardous
situation which, if not avoided, will result
in death or serious injury.
High voltage!
• Before removing or mounting the unit,
turn off power supply.
Follow ESD installation regulations,
including EMI precautions.
WARNING
Indicates a potentially hazardous
situation which, if not avoided, could
result in death or serious injury.
3.8
General Instructions
• Read and follow all instructions in this manual.
CAUTION
Indicates a potentially hazardous
situation which, if not avoided, may
result in minor or moderate injury.
NOTICE
Indicates a situation that may result in material
damage.
The CE mark proves the compliance of
the module with the essential
requirements of the directives.
• Inform yourself about hazards which can be
caused by the product.
• Observe the safety and accident prevention
regulations.
• Regularly check that all measures to prevent
accidents are being complied with.
• Only operate the product if it is in perfect
technical condition, according to its intended
use, in awareness of safety and risks and in
adherence to the instructions in this manual.
• Keep this manual and all other applicable
documents complete, legible and accessible to
personnel at all times.
• Refrain from any procedures and actions that
would expose personnel or third parties to any
risk.
Ex modules have been approved
according to the ATEX directive for use
in connection with installations in
explosive areas.
This symbol is combined with one of the
signal words DANGER, WARNING or
CAUTION to indicate a hazardous
situation.
The double insulation symbol shows that
the device is protected by double or
reinforced insulation..
12
1066540000/02/02.14
Introduction
4.
Introduction
4.1
Product Description
4.1.1
Product Family ACT20X
Order No.
Type
Description
Function
8965340000
ACT20X-HDI-SDO-RNO-S
NAMUR pulse isolator –
relay NO
NAMUR in (from Ex) to
relay out
8965350000
ACT20X-HDI-SDO-RNC-S
NAMUR pulse isolator –
relay NC
NAMUR in (from Ex) to
relay out
8965360000
ACT20X-HDI-SDO-S
NAMUR pulse isolator
NAMUR in (from Ex) to
digital out
8965370000
ACT20X-2HDI-2SDO-RNO-S
2-channel
NAMUR pulse isolator –
relay NO
2x NAMUR in (from Ex) to
2x relays out
8965380000
ACT20X-2HDI-2SDO-RNC-S
2-channel
NAMUR pulse isolator –
relay NC
2x NAMUR in (from Ex) to
2x relays out
8965390000
ACT20X-2HDI-2SDO-S
2-channel
NAMUR pulse isolator
2x NAMUR in (from Ex) to
2x digital out
8965400000
ACT20X-SDI-HDO-L-S
Solenoid/alarm driver,
L = low current max. 35 mA
digital in to safe digital out
(to Ex IIC)
8965410000
ACT20X-SDI-HDO-H-S
Solenoid/alarm driver,
H = high current max. 60 mA
digital in to safe digital out
(to Ex IIB)
8965420000
ACT20X-2SDI-2HDO-S
2-channel
Solenoid/alarm driver,
L = low current max. 35 mA
2x digital in to 2x safe
digital out (to Ex)
8965430000
ACT20X-HAI-SAO-S
HART-transparent repeater
mA in (from Ex) to mA out
with HART transparency
8965440000
ACT20X-2HAI-2SAO-S
2-channel
HART-transparent repeater
2x mA in (from Ex) to 2x
mA out with HART
transparency
8965450000
ACT20X-SAI-HAO-S
HART-transparent driver
mA in to mA out (to Ex)
with HART transparency
8965460000
ACT20X-2SAI-2HAO-S
2-channel
HART-transparent driver
2x mA in to 2x mA out (to
Ex) with HART
transparency
8965470000
ACT20X-HTI-SAO-S
Temperature/mA converter
temperature in (from Ex)
to mA out
8965480000
ACT20X-2HTI-2SAO-S
2-channel
Temperature/mA converter
2x temperature in (from
Ex) to 2x mA out
1066540000/02/02.14
13
Introduction
8965490000
Table 4-1:
14
ACT20X-HUI-SAO-S
Universal converter
universal analog in (from
Ex) to analog (V / mA) +
trip relay out
Family ACT20X
1066540000/02/02.14
Introduction
4.1.2
General Description
Weidmüller’s ACT20X – new signal converters for
hazardous areas: Universal family of products
covers the entire field of hazardous area
applications with six different basic functions.
With the introduction of its ACT20X modules
Weidmüller is offering a completely new family of
signal converters for hazardous area applications.
With just 11 mm per channel these compactly
designed modules require very little space in the
electrical cabinet. All ACT20X converters can be
configured via a PC utilizing the software "WIManager". This software is based on vendor-neutral
FDT/DTM technology. The innovative modules are
designed to be installed in safe or hazardous areas
of Zone 2. The ACT20X family includes digital and
analogue intrinsically safe converters that both
isolate and convert signals from as well as into
hazardous areas. The innovative signal converters
process 2-wire HART, NAMUR, RTD, thermocouple
or DC signals as well as digital signals with electrical
connection to hazardous area Zone 0. All modules
have 3-way separation and are optionally available
with dual channel functionality. With high levels of
insulation resistance, accuracy and thermal stability
ACT20X modules provide a pure, disturbance free
signal at all times. A relay-based error monitoring
facility simplifies servicing. ACT20X modules can be
utilized in temperatures from -20 °C to +60 °C
without restrictions. They have all relevant
international approvals such as ATEX, IECEx, FM –
in other words, the modules are predestined for use
in applications all over the world.
simple, coded mating. The integrated release lever
ensures the connection can be disconnected without
damage when servicing is required. Devices from
the ACT20X family have been designed to operate
in an ambient temperature range of -20 °C to +60 °C
– in other words in practically all fields of industry.
The hinged and transparent front plate can easily be
opened upwards. It has been designed for simple
accommodation of device markers.
Products from the ACT20X assortment are designed
to be installed in Zone 2 / Division 2 or in nonhazardous areas; international approvals such as
ATEX, IECEx and FM (Class I, Division 1 and 2)
allow processing of signals from Zone 0 / Division 1.
Put succinctly, the modules are suitable for use in
applications across the globe.
Utilizing the "WI-Manager" configuration software
based on FDT technology (Field Device Tool) makes
it possible to adapt all ACT20X products via a PC to
meet different process application requirements. For
this purpose Weidmüller provides the Device Type
Manager (DTM), which can be executed in any FDTbased frame application. As well as fast and errorfree parameterization of individual devices DTMs
make it possible to evaluate measurement and
diagnostic data. In addition, it is possible to
unambiguously identify a connected device via DTM.
ACT20X modules are equipped with a cleverly
designed connection technology that supports
1066540000/02/02.14
15
Introduction
4.1.3
The Six Basic Module Types in
Detail
NAMUR Pulse Isolator
The pulse isolator ACT20X-HDI-SDO is a special
signal isolator/converter for NAMUR sensor signals
from within Ex Zone 0. Transistor or relay outputs
are available on the output side.
For the higher accuracy of thermo couple signals,
the use of special cold junction terminals ACT20XCJC-HTI-S (PRT 11 = 1-channel, PRT 21 = 2channel) recommended
Universal Converter
Solenoid/Alarm Driver
The universal isolator/converter ACT20X-HUI-SAO
is a user configurable temperature and signal
converter for Pt100, thermal and current (mA) inputs
from within Ex Zone 0 as well as an output for nonhazardous area devices.
The ACT20X-SDI-HDO is a solenoid/alarm driver for
the control of solenoids, acoustic alarms and LEDs
mounted in the hazardous area (Ex Zone 0).
The ACT20X-HUI-SAO-S converts and isolates
current, voltage, potentiometer and temperature
sensor signals (mA, V, potentiometer, RTD and TC).
Optionally one or two channel versions available.
For the higher accuracy of thermocouple signals, the
use of special cold junction terminal ACT20X-CJCHTI-S is recommended:
1160640000 ACT20X-CJC-HTI-S PRT 11 (1-chan.)
A dual-channel version is optionally available.
HART-Transparent Repeater
The ACT20X-HAI-SAO-S current supply isolator is a
HART-protocol, transparent isolator for analogue
input signals from Exzone 0. The input may also
operate as an active current loop (the loop current
provided by the device). It provides an 4...20 mA
current signal for the safe zone on the output side.
Features
• Full functionality interfacing with Zone 0 /
Division 1 hazardous area inputs and outputs
It is available in a single-channel or two-channel
version.
• Approvals include use for Zone 0 (IECEx, ATEX),
Class I, Division 1 and 2 (FM).
HART-Transparent Driver
• Analogue and binary signal interfacing with
measurement and control devices.
The ACT20X-SAI-HAO-S is a HART-protocol,
transparent current output isolator. A DC current
input signal from the safe area will be galvanically
separated and drives controlled field devices in Ex
zone 0.
Temperature, DC, resistance and potentiometer
It is available in a single-channel or two-channel
version.
• Dual channel options – minimizes rail space and
installation cost
Temperature/mA Converter
• HART-transparent signaling
The devices of the ACT20X-HTI-SAO family transmit
analog signals galvanic isolated from hazardous
areas to the safe area. The input circuits are
designed intrinsically safe.
• Integral fault alarm
The ACT20X-HTI-SAO converts and isolates current
and temperature sensor signals (mA, RTD and TC).
The two-channel version ACT20X-2HTI-2SAO can
be used as a signal splitter for mA signals.
16
• inputs
• Milliamp and relay/opto outputs
• High quality, 3-port isolation
• -20 to +60 °C ambient temperature
• All modules configurable with FDT/DTM Software
"WI-Manager"
1066540000/02/02.14
Installation
5.
Installation
DANGER
5.2
Risk of explosion!
1 Check on receipt that the product received
corresponds to the one ordered.
• For installation in Zone 2, install the
module in an outer enclosure with IP
protection of at least IP54.
• Protection must be according to type
of protection Ex-n or Ex-e.
WARNING
High voltage!
• Before removing or mounting the unit,
turn off power supply.
NOTICE
Material damage through ESD!
• Only carry out the following procedures under
ESD-safe conditions.
5.1
General
This product should only be installed by technically
qualified personnel with sufficient training in
instrumentation and control engineering.
Unpacking
2 Also make sure that installation instructions have
been supplied.
3 Unpack the product carefully.
• The use of stranded wires is not permitted for
mains wiring except for wires fitted with cable
ends.
• Descriptions of input/output and supply
connections are shown in the block diagram and
on the side label.
• The module is provided with field wiring terminals
and must be supplied from a power supply having
double/reinforced insulation.
• A power switch must be easily accessible and
close to the module.
• The power switch must be marked with a label
telling that it will switch off the voltage to the
module.
• Year of manufacture can be taken from the first
two digits in the serial number.
• Should there be any doubt as to the correct
handling of the module, contact your local
distributor.
VDE 0105 Part 1 / DIN EN 50110-1 defines qualified
personnel as electrically skilled workers,
electronically instructed personnel or personnel
meeting similar local standards.
5.1.1
Environment
This product is designed for use either indoors
(IP20) in a control panel, or in a weather-proof field
enclosure.
• Avoid direct sunlight, dust, high temperatures,
mechanical vibrations and shock as well as rain
and heavy moisture.
• If necessary, heating in excess of the stated limits
for ambient temperatures should be avoided by
ventilation.
• Product must be installed in pollution degree 2,
overvoltage category II as defined in IEC 60664-1.
• Product is designed to be safe at least under an
altitude of up to 2000 m.
1066540000/02/02.14
17
Installation, Mounting
5.3
Mounting
The product is designed to be mounted onto a TS 35
DIN rail.
5.4
Marking
A device marker is located below the upper set of
terminals for costumer identification.
It clips onto the rail via a spring-loaded mounting
foot and can be removed via a spring release on the
edge of the product near the mounting rail.
Illustration 5-3:
Illustration 5-1:
Mounting, Step 1
Illustration 5-2:
Mounting, Step 2
18
Marking
1 Device Marker
1066540000/02/02.14
Installation
5.5
Electrical Connections
See section 7, "Product Installation / Operation” for
further information.
5.6
Calibration and Adjustment
• During calibration and adjustment, carry out the
measuring and connection of external voltages
according to the specifications in this manual.
• Only use tools and instruments that are safe to
use.
5.5.1
EMI Protection
NOTICE
Do not install input, output and power supply
cables close to sources of electrical interference!
5.7
Release Lever
The terminals are released with a release lever.
For example, sources of electrical interference could
include relays, contactors, motors and their controls,
including thyristor drives and the cables which
connect these devices. Avoid installing ACT20X
cables in the same ducting as such cables.
Local electrical installation practices must be
followed.
Illustration 5-4:
Release Lever
1 Release lever
See section 7.8, "Female Plug BHZ 5.00” for further
information.
1066540000/02/02.14
19
Installation, Encoding
5.8
Encoding
NOTICE
Leaving the product connectors uncoded results
in lack of interchanging protection. All connectors
will be identically encoded.
2 Plug encoded connector onto pin header.
Encoding element is transferred from connector
to pin header.
Encoding element remains in the pin header
housing.
• Create connector coding plan prior to first
mating and encode connectors accordingly.
• Perform encoding procedure for each new
module.
The product housing is equipped with an automatic
encoding.
This connector interchanging protection is initially
encoded upon shipping and can be individually
adjusted.
1 Use screw driver to turn adjusting dial of
connector clockwise.
Either dial has 4 encoding positions, resulting in
4² = 16 possible positions.
Connector is encoded.
Illustration 5-5:
Encoding Connector
Illustration 5-6:
Encoding Positions
20
Illustration 5-7:
Transfer Encoding Element
See section 7.8, "Female Plug BHZ 5.00” for further
information.
1066540000/02/02.14
Installation
5.9
Configuration
DANGER
2 Connect the CBX200 USB jack, as shown in the
illustration:
Configuration must be performed in a
safe area!
Configuration is performed via a connector located
behind the front flap.
1 Open the front flap, as shown in the illustration:
Illustration 5-9:
1
2
3
CBX200 USB Connection
Jack connection under front flap
CBX200 with USB connection
PC
3 See "WI-Manager" documentation for further
information.
Illustration 5-8:
Opening Front Flap
1066540000/02/02.14
21
Operation, Normal Operation
6.
Operation
6.1
Normal Operation
Operators are only allowed to adjust and operate
modules that are safely fixed in panels, etc., thus
avoiding the danger of personal injury and damage.
This means there is no electrical shock hazard and
the module is easily accessible.
6.2
6.3
Cleaning
1 Power supply switched off.
2 Clean with cloth moistened with distilled water.
Warm-Up
The product is designed to start-up as soon as
power is supplied. However a warm-up period of 15
minutes is required before it performs to the
specifications above.
When auxiliary power is switched on, for the first
200 ms the product will consume up to 200 mA.
22
1066540000/02/02.14
Product Installation / Operation
7.
Product Installation / Operation
7.1
ACT20X-HDI-SDO (NAMUR Pulse Isolator)
7.1.1
Description
The pulse isolator ACT20X-HDI-SDO is a special signal isolator/converter for NAMUR sensor signals from
within Ex Zone 0. The product is able for an intrinsically safe operation of NAMUR sensors or for contacts
with floating and resistance circuits.
Transistor or relay outputs are available on the output side. A dual-channel version is optionally available.
The following NAMUR pulse isolators are available:
Order No.
Type
Description
8965340000
ACT20X-HDI-SDO-RNO-S
NAMUR pulse isolator – relay NO
8965350000
ACT20X-HDI-SDO-RNC-S
NAMUR pulse isolator – relay NC
8965360000
ACT20X-HDI-SDO-S
NAMUR pulse isolator
8965370000
ACT20X-2HDI-2SDO-RNO-S
2-channel NAMUR pulse isolator – relay NO
8965380000
ACT20X-2HDI-2SDO-RNC-S
2-channel NAMUR pulse isolator – relay NC
8965390000
ACT20X-2HDI-2SDO-S
2-channel NAMUR pulse isolator
1066540000/02/02.14
23
Product Installation / Operation, ACT20X-HDI-SDO (NAMUR Pulse Isolator)
7.1.2
Status/Alarm LEDs
Illustration 7-1:
Status/Alarm LEDs
Condition
LED 1
Channel 1
Channel 2
LED 3
Output
Status
Relay (NC)
LED 2
Output
yellow
ON
energized
OFF
OFF
energized
red
flashing
OFF
de-energized
Channel 2
Channel 1
Device OK
activated
de-activated
green
flashing
wire short/break
activated
de-activated
green
flashing
wire short/break
yellow
ON
energized
OFF
OFF
energized
red
flashing
OFF
de-energized
No supply
OFF
OFF
OFF
OFF
OFF
de-energized
Device failure
OFF
red
OFF
red
OFF
de-energized
Flashing:
Table 7-1:
24
8% ON and 92% OFF
__|¯|_______|¯|_______|¯|_______
Status/Alarm LEDs
1066540000/02/02.14
Product Installation / Operation, ACT20X-HDI-SDO (NAMUR Pulse Isolator)
7.1.3
Electrical Connections
Terminal
Function
11
SW Sense
12
NAMUR −
13
SW Supply
14
Connector
Terminal
Function
41
COM /
42
NO / NC / OPTO –
43
COM /
NAMUR +
44
NO / NC / OPTO –
21
SW Sense
51
GND
22
NAMUR −
52
+24 V DC
23
SW Supply
53
NC
24
NAMUR +
54
COM
Table 7-2:
7.1.4
Ex input
channel 1
Ex input
channel 2
/ OPTO +
/ OPTO +
Connector
output
channel 1
output
channel 2
power supply
status relay
Electrical Connections
Function Description
(1) NAMUR sensor with cable error detection in case of cable disconnection or short circuit.
(2) Mechanical switch with cable error detection in case of cable disconnection or short circuit, when series
resistance (RS) and parallel resistance (RP) are mounted on the switch.
(3) Mechanical switch with cable error detection in case of cable disconnection, when parallel resistance
(RP) is mounted on the switch.
(4) Mechanical switch without cable error detection.
See illustration 7-2 "Functional Block Diagram" for further information.
7.1.5
Specifications
Features
• Configuration and monitoring via FDT/DTM-Software "WI-Manager".
• Selection of direct or inverted function for each channel.
• The device can be mounted in the safe area and in Zone 2 / Class I, Division 2 and receive signals from
Zone 0, 1, 2 and Zone 20, 21 and 22 including M1 / Class I/II/III, Division 1, Group A-G.
• Extended self diagnostic: Monitoring of error events and cable breakage via the individual status relay.
• LED indication for operation status and malfunction.
• 3-way galvanic isolation between input, output and supply.
1066540000/02/02.14
25
Product Installation / Operation, ACT20X-HDI-SDO (NAMUR Pulse Isolator)
Illustration 7-2:
26
Functional Block Diagram
1066540000/02/02.14
Product Installation / Operation, ACT20X-HDI-SDO (NAMUR Pulse Isolator)
Illustration 7-3:
Applications
Input NAMUR / Mechanical Switch with Series and Parallel Resistance
NAMUR sensor, according to
EN 60947-5-6
Mechanical Switch, Series resistance (RS)
nom. 750 Ω
Mechanical Switch, Parallel resistance (RP)
nom. 15 kΩ
Frequency range
0…5 kHz
Min. pulse length
> 0.1 ms
Resistance
nom. 1 kΩ
Trigger level, signal
< 1.2 mA, > 2.1 mA
Trigger level, cable fault
< 0.1 mA, > 6.5 mA
1066540000/02/02.14
27
Product Installation / Operation, ACT20X-HDI-SDO (NAMUR Pulse Isolator)
Status Relay
Safe Area
Zone 2 Installation
Voltage max.
125 V AC / 110 V
32 V AC / 32 V DC
Current max.
0.5 A AC / 0.3 A
0.5 A AC / 1 A DC
Power max.
62.5 VA / 32 W
16 VA / 32 W
Relay Output
Safe Area
Zone 2 Installation
Voltage max.
250 V AC / 30 V
32 V AC / 30 V DC
Current max.
2 A AC / 2 A DC
2 A AC / 2 A DC
Power max.
500 VA / 60 W
16 VA / 60 W
Max. switching frequency
20 Hz
Opto NPN Output
Max. switching frequency
5 kHz
Min. pulse length
60 μs
Max. load, current / voltage
80 mA / 30 V DC
Voltage drop at 80 mA
< 2.5 V DC
Power Supply
Supply voltage
19.2…31.2 V DC
NAMUR supply
8 V DC / 8 mA
Max. consumption (2-channels)
≤3W
Fuse
400 mA / 250 V AC
Isolation Voltages (reinforced insulation), Test/Operation
Inputs / outputs / supply
2.6 kV AC / 300 V AC
Output 1 to output 2
1.5 kV AC / 150 V AC
Status relay to supply
1.5 kV AC / 150 V AC
Environmental Specifications
Specifications range
-20…+60 °C
Storage temperature
-20…+85 °C
Relative humidity (non-condensation)
< 95 %
Calibration temperature
+20…28 °C
28
1066540000/02/02.14
Product Installation / Operation, ACT20X-HDI-SDO (NAMUR Pulse Isolator)
General Specifications
Communications interface,
adapter / configuration software / FDT-DTM
device driver
CBX200 USB / "WI-Manager" / ACT20X DTM
Dimensions (H x W x D)
105.6 x 22.5 x 114.7 mm
Protection degree
IP20
Screw terminal torque
0.5 Nm
Vibration
IEC 60068-2-6, test Fc, 1g, 2…100 Hz
Vibration, continuous
IEC 60068-2-64, test Fh, 1g, 3…100 Hz
Wire size, stranded wire
AWG 26…14 / 0.13…2.08 mm²
Response time for cable fault
< 200 ms
Default Settings
Channel 1 function
direct
Channel 2 function
direct
Short circuit indication
yes
Breakage indication
yes
1066540000/02/02.14
29
Product Installation / Operation, ACT20X-HTI-SAO (Temperature/mA Converter)
7.2
ACT20X-HTI-SAO (Temperature/mA Converter)
7.2.1
Description
The modules of the ACT20X-HTI-SAO family transmit analog signals galvanic isolated from hazardous areas
to the safe area. The input circuits are designed intrinsically safe.
The ACT20X-HTI-SAO converts and isolates current and temperature sensor signals (mA, RTD and TC).
The two-channel version ACT20X-2HTI-2SAO can be used as a signal splitter for mA signals.
For the higher accuracy of thermo couple signals, the use of special cold junction terminals ACT20X-CJCHTI-S recommended:
1160640000 ACT20X-CJC-HTI-S PRT 11 (1-channel)
1160650000 ACT20X-CJC-HTI-S PRT 21 (2-channel)
The following converter types are available:
Order No.
Type
Description
8965470000
ACT20X-HTI-SAO-S
Temperature/mA converter
8965480000
ACT20X-2HTI-2SAO-S
2-channel temperature/mA converter
30
1066540000/02/02.14
Product Installation / Operation, ACT20X-HTI-SAO (Temperature/mA Converter)
7.2.2
Status/Alarm LEDs
Illustration 7-4:
Status/Alarm LEDs
Condition
LED 1
Channel 1
Channel 2
LED 3
Output
Status
Relay (NC)
LED 2
Output
OFF
ON
energized
red
fault state
energized
red
flashing
fault state
de-energized
Channel 2
Channel 1
Device
OK
defective
green
flashing
wire short/break
OK
defective
green
flashing
wire short/break
OFF
ON
energized
red
fault state
energized
red
flashing
fault state
de-energized
No supply
OFF
OFF
OFF
OFF
OFF
de-energized
Device failure
OFF
red
OFF
red
OFF
de-energized
Flashing:
Table 7-3:
8% ON and 92% OFF
__|¯|_______|¯|_______|¯|_______
Status/Alarm LEDs
1066540000/02/02.14
31
Product Installation / Operation, ACT20X-HTI-SAO (Temperature/mA Converter)
7.2.3
Electrical Connections
Function
Terminal
RTD
Connector
mA
2W
11
4W
Sense–
Sense–
+
41
Out −
–
42
Out +
43
Out −
44
Out +
51
GND
52
+24 V DC
53
NC
54
COM
–
R
R–
R–
13
+
R
R+
R+
14
Ex input
channel 1
Sense+
21
Sense–
Sense–
+
–
22
–
R
R–
R–
23
+
R
R+
R+
24
7.2.4
Function
3W
12
Ex input
channel 2
Sense+
Table 7-4:
Terminal
Connector
TC
output
channel 1
output
channel 2
power
supply
status
relay
Electrical Connections
Specifications
Features
• Configuration and monitoring are performed via FDT/DTM Software "WI-Manager".
• The device can be mounted in the safe area and in Zone 2 / Class I, Division 2 and receive signals from
Zone 0, 1, 2 and Zone 20, 21 and 22 including M1 / Class I/II/III, Division 1, Group A-G.
• The passive signal inputs for RTD, TC and mA are made for one or two channels and completely
electrically isolated.
• The two-channel version is suitable to use as a signal splitter.
• 3-way galvanic isolation between input, output and supply.
• Front LEDs indicate operation status and malfunction.
• The cold junction compensation for TC-signal inputs is either the internal cold junction compensation, or for
higher accuracy is an external cold junction compensation terminal available –- 1 channel 1160640000
ACT20X-CJC-HTI-S PRT 11 or 2 channel 1160650000 ACT20X-CJC-HTI-S PRT 21.
• Extended self diagnostic: Monitoring of error events and cable breakage via the individual status relay.
32
1066540000/02/02.14
Product Installation / Operation, ACT20X-HTI-SAO (Temperature/mA Converter)
Illustration 7-5:
Functional Block Diagram
1066540000/02/02.14
33
Product Installation / Operation, ACT20X-HTI-SAO (Temperature/mA Converter)
Illustration 7-6:
Applications
RTD Input
Pt100, according to
-200…+850 °C, IEC 60751
Ni100, according to
-60…+250 °C, DIN 43760
Sensor types
(* = without short circuit detection)
Pt10*, Pt20*, Pt50*, Pt100, Pt250, Pt300, Pt400,
Pt500, Pt1000, Ni50, Ni100, Ni120, Ni1000
Cable resistance per wire (max.)
50 Ω
Sensor current
nom. 0.2 mA
Effect of sensor cable resistance (3/4-wire)
< 0.002 Ω
Sensor error detection (programmable)
ON/OFF
34
1066540000/02/02.14
Product Installation / Operation, ACT20X-HTI-SAO (Temperature/mA Converter)
Sensor error current:
when detecting
else
< 2 μA
0 μA
TC Input, Sensor Types
Temperature Range
Standard
B
0…+1820 °C
IEC 60584-1
E
-100…+1000 °C
IEC 60584-1
J
-100…+1200 °C
IEC 60584-1
K
-180…+1372 °C
IEC 60584-1
L
-200…+900 °C
DIN 43710
N
-180…+1300 °C
IEC 60584-1
R
-50…+1760 °C
IEC 60584-1
S
-50…+1760 °C
IEC 60584-1
T
-200…+400 °C
IEC 60584-1
U
-200…+600 °C
DIN 43710
W3
0…+2300 °C
ASTM E988-90
W5
0…+2300 °C
ASTM E988-90
LR
-200…+800 °C
GOST 3044-84
Accuracy, General Values
Absolute Accuracy
Temperature Coefficient
All
≤ ±0.1 % of span
≤ ±0.01 % of span / °C
Accuracy, Basic Values
Absolute Accuracy
Temperature Coefficient
mA
≤ ±16 μA
≤ ±1.6 μA / °C
Pt100, Pt200, Pt1000
≤ ±0.2 °C
≤ ±0.02 C / °C
Pt500, Ni100, Ni120, Ni1000
≤ ±0.3 °C
≤ ±0.03 C / °C
Pt50, Pt400, Ni50
≤ ±0.4 °C
≤ ±0.04 C / °C
Pt250, Pt300
≤ ±0.6 °C
≤ ±0.06 C / °C
Pt20
≤ ±0.8 °C
≤ ±0.08 C / °C
Pt10
≤ ±1.4 °C
≤ ±0.14 C / °C
TC type: E, J, K, L, N, T, U
≤ ±1 °C
≤ ±0.1 C / °C
TC type: R, S, W3, W5, LR
≤ ±2 °C
≤ ±0.2 C / °C
TC type: B (160…400 °C)
≤ ±4.5 °C
≤ ±0.45 C / °C
TC type: B (400…1820 °C)
≤ ±2 °C
≤ ±0.2 C / °C
1066540000/02/02.14
35
Product Installation / Operation, ACT20X-HTI-SAO (Temperature/mA Converter)
TC Input, Cold Junction Compensation (CJC)
CJC: external with ACT20X-CJC-HTI
(1160640000 or 1160650000)
+20…+28 °C ≤ ±1 °C
-20…+20 °C and +28…+60 °C≤ ±1.6 °C
CJC via internal sensor
∆t = internal temperature – ambient temperature
±(2.0 °C + 0.2 °C * ∆t)
Sensor error detection (programmable, only wire
breakage)
ON/OFF
Sensor error current:
when detecting
else
nom. 2 μA
0 μA
Current Input
Measurement range
0…20 mA
Programmable measurement ranges
0…20 / 4…20 mA
Input resistance
nom. 20 Ω + PTC 50 Ω
Sensor error detection (programmable)
ON/OFF
Current Output
Programmable signal ranges
0…20 mA / 4…20 mA / 20…0 mA / 20…4 mA
Load max.
4 mA / 600 Ω / 12 V DC
Load stability
≤ ±0.01 % of span / 100 Ω
Sensor error detection
0 / 3.5 mA / 23 mA / none
Output limitation:
on 4…20 and 20…4 mA signals
on 0…20 and 20…0 mA signals
3.8…20.5 mA
0…20.5 mA
Current limit
≤ 28 mA
2-wire 4…20 mA Loop Powered Output
Signal range
4…20 mA
Load resistance
≤ (Vsupply – 3.5 V) / 0.023 A [Ω]
Load stability
≤ 0.01 % of span / 100 Ω
Max. external 2-wire supply
3.5…26 V DC
Effect of external 2-wire supply voltage variation
< 0.005 % of span / V
36
1066540000/02/02.14
Product Installation / Operation, ACT20X-HTI-SAO (Temperature/mA Converter)
Status Relay
Safe Area
Zone 2 Installation
Voltage max.
125 V AC / 110 V
32 V AC / 32 V DC
Current max.
0.5 A AC / 0.3 A
0.5 A AC / 1 A DC
Power max.
62.5 VA / 32 W
16 VA / 32 W
Power Supply
Supply voltage
19.2…31.2 V DC
Max. consumption (2-channels)
≤ 3.5 W
Fuse
1.25 A / 250 V AC
Isolation Voltages (reinforced insulation), Test/Operation
Inputs / outputs / supply
2.6 kV AC / 300 V AC
Output 1 to output 2
1.5 kV AC / 150 V AC
Status relay to supply
1.5 kV AC / 150 V AC
Environmental Specifications
Ambient temperature
-20…+60 °C
Storage temperature
-20…+85 °C
Relative humidity (non-condensation)
< 95 %
Calibration temperature
+20…28 °C
General Specifications
Communications interface,
adapter / configuration software / FDT-DTM
device driver
CBX200 USB / "WI-Manager" / ACT20X DTM
Dimensions (H x W x D)
105.6 x 22.5 x 114.7 mm
Protection degree
IP20
Screw terminal torque
0.5 Nm
Vibration
IEC 60068-2-6, test Fc, 1g, 2…100 Hz
Vibration, continuous
IEC 60068-2-64, test Fh, 1g, 3…100 Hz
Wire size, stranded wire
AWG 26…14 / 0.13…2.08 mm²
EMC immunity influence
≤ ±0.5 % of span
Extended EMC immunity:
NAMUR NE 21, A criterion, burst
≤ ±1 % of span
Signal/Noise ratio
min. 60 dB (0…100 kHz)
1066540000/02/02.14
37
Product Installation / Operation, ACT20X-HTI-SAO (Temperature/mA Converter)
Average response time incl. delay:
Temperature input
mA input
≤1s
≤ 0.4 s
Default Settings
Input type
Temperature
Connection type
3-wire
Temperature unit
°C
Temperature sensor type
Pt100
Temperature range
0…150°C
Output current range
0…20 mA
Output current on error
0…23 mA
Analog output response time (1/10 s)
1s
38
1066540000/02/02.14
Product Installation / Operation, ACT20X-SDI-HDO (Solenoid/Alarm Driver)
7.3
ACT20X-SDI-HDO (Solenoid/Alarm Driver)
7.3.1
Description
The ACT20X-SDI-HDO is a solenoid/alarm driver for the control of solenoids, acoustic alarms and LEDs
mounted in the hazardous area (Ex Zone 0).
Optionally one or two channel versions available.
The following solenoid/alarm drivers are available:
Order No.
Type
Description
8965400000
ACT20X-SDI-HDO-L-S
Solenoid/alarm driver,
L = low current max. 35 mA
8965410000
ACT20X-SDI-HDO-H-S
Solenoid/alarm driver,
H = high current max. 60 mA
8965420000
ACT20X-2SDI-2HDO-S
2-channel solenoid/alarm driver,
L = low current max. 35 mA
1066540000/02/02.14
39
Product Installation / Operation, ACT20X-SDI-HDO (Solenoid/Alarm Driver)
7.3.2
Status/Alarm LEDs
Illustration 7-7:
Status/Alarm LEDs
Condition
LED 1
Channel 1
Channel 2
LED 3
Output
Status
Relay (NC)
LED 2
Output
yellow
ON
energized
OFF
OFF
energized
Channel 2
Channel 1
Device OK
activated
green
flashing
de-activated
activated
yellow
ON
energized
OFF
OFF
energized
green
flashing
de-activated
No supply
OFF
OFF
OFF
OFF
OFF
de-energized
Device failure
OFF
red
OFF
red
OFF
de-energized
Flashing:
Table 7-5:
40
8% ON and 92% OFF
__|¯|_______|¯|_______|¯|_______
Status/Alarm LEDs
1066540000/02/02.14
Product Installation / Operation, ACT20X-SDI-HDO (Solenoid/Alarm Driver)
7.3.3
Electrical Connections
Terminal
Function
11
GND
12
Ex 1
13
Ex 2
14
Terminal
Function
41
In −
42
In +
43
In −
Ex 3
44
In +
21
GND
51
GND
22
Ex 1
52
+24 V DC
23
Ex 2
53
COM
24
Ex 3
54
NC
Table 7-6:
7.3.4
Connector
Ex output
channel 1
Ex output
channel 2
Connector
input
channel 1
input
channel 2
power supply
status relay
Electrical Connections
Specifications
Features
• Solenoid/alarm driver for the control of solenoids, acoustic alarms and LEDs installed in the hazardous
area.
• Two hardware versions make it possible to choose either low (35 mA) or high (60 mA) current output with
1-channel or 2-channel versions.
• Configuration and monitoring via FDT/DTM-Software "WI-Manager".
• Selection of direct or inverted function for each channel and the possibility of reducing the output current to
the hazardous area to suit the application.
• The device can be mounted in the safe area and in Zone 2 / Class I, Division 2 and receive signals from
Zone 0, 1, 2 and Zone 20, 21 and 22 including M1 / Class I/II/III, Division 1, Group A-G.
• Extended self diagnostic: Monitoring of error events via the individual status relay.
• LED indication: green and 2 yellow/red front LEDs to indicate operation status and malfunction.
• 3-way galvanic isolation between input, output and supply, 2.6 kV AC.
1066540000/02/02.14
41
Product Installation / Operation, ACT20X-SDI-HDO (Solenoid/Alarm Driver)
Illustration 7-8:
42
Functional Block Diagram
1066540000/02/02.14
Product Installation / Operation, ACT20X-SDI-HDO (Solenoid/Alarm Driver)
Illustration 7-9:
Applications
NPN Input (NPN and mechanical switch)
Trigger level (low)
≤ 2 V DC
Trigger level (high)
≥ 4 V DC
Max. external voltage
28 V DC
Input impedance
3.5 kΩ
PNP Input
Trigger level (low)
≤ 8 V DC
Trigger level (high)
≥ 10 V DC
1066540000/02/02.14
43
Product Installation / Operation, ACT20X-SDI-HDO (Solenoid/Alarm Driver)
Max. external voltage
28 V DC
Input impedance
3.5 kΩ
Output
Output ripple
ACT20X-SDI-HDO-L-S, ACT20X-2SDI-HDO-S,
low current (< 35 mA),
Ex barrier data channel 1
< 40 mV RMS
Vout no load
Vout with load
Iout max.
11–12
min. 24 V
min. 12.5 V
35 mA
11–13
min. 24 V
min. 13.5 V
35 mA
11–14
min. 24 V
min. 14.5 V
35 mA
Vout no load
Vout with load
Iout max.
21–22
min. 24 V
min. 12.5 V
35 mA
21–23
min. 24 V
min. 13.5 V
35 mA
21–24
min. 24 V
min. 14.5 V
35 mA
ACT20X-2SDI-HDO-S,
low current (< 35 mA),
Ex barrier data channel 2
ACT20X-SDI-HDO-H-S,
high current (< 60 mA),
Ex barrier data channel 1
11–12
11–13
11–14
Vout no load
Vout with load
Iout max.
min. 9 V
60 mA
min. 11.5 V
50 mA
min. 10 V
60 mA
min. 12.5 V
50 mA
min. 11 V
60 mA
min. 13.5 V
50 mA
min. 24 V
min. 24 V
min. 24 V
Status Relay
Safe area
Zone 2 Installation
Voltage max.
125 V AC / 110 V DC
32 V AC / 32 V DC
Current max.
0.5 A AC / 0.3 A DC
0.5 AC / 0.1 A DC
Power max.
62.5 VA / 32 W
16 VA / 32 W
44
1066540000/02/02.14
Product Installation / Operation, ACT20X-SDI-HDO (Solenoid/Alarm Driver)
Power Supply
Supply voltage
19.2…31.2 V DC
Max. consumption (2-channels)
≤ 3.5 W
Fuse
1.25 A / 250 V AC
EMC immunity influence
< ±0.5 % of span
Extended EMC immunity:
NAMUR NE 21, A criterion, burst
< ±1 % of span
Isolation Voltages (reinforced insulation), Test/Operation
Inputs / outputs / supply
2.6 kV AC / 300 V AC
Output 1 to output 2
1.5 kV AC / 150 V AC
Status relay to supply
1.5 kV AC / 150 V AC
Environmental Specifications
Ambient temperature
-20…+60 °C
Storage temperature
-20…+85 °C
Relative humidity (non-condensation)
< 95 %
Calibration temperature
+20…28 °C
General Specifications
Communications interface,
adapter / configuration software / FDT-DTM
device driver
CBX200 USB / "WI-Manager" / ACT20X DTM
Dimensions (H x W x D)
105.6 x 22.5 x 114.7 mm
Protection degree
IP20
Screw terminal torque
0.5 Nm
Wire size, stranded wire
AWG 26…14 / 0.13…2.08 mm²
Default Settings
Channel 1 function
Direct
Channel 2 function
Direct
1066540000/02/02.14
45
Product Installation / Operation, ACT20X-HUI-SAO (Universal Converter)
7.4
ACT20X-HUI-SAO (Universal Converter)
7.4.1
Description
The device ACT20X-HUI-SAO-S transmits analog signals from hazardous areas safely galvanically
separated into non or less hazardous areas. The input circuits are designed intrinsically safe.
The ACT20X-HUI-SAO-S converts and isolates current, voltage, potentiometer and temperature sensor
signals (mA, V, potentiometer, RTD and TC).
For the higher accuracy of thermocouple signals, the use of special cold junction terminal ACT20X-CJC-HTIS is recommended:
1160640000 ACT20X-CJC-HTI-S PRT 11 (1-Kanal)
The following converter type is available:
Order No.
Type
Description
8965490000
ACT20X-HUI-SAO-S
Universal converter
46
1066540000/02/02.14
Product Installation / Operation, ACT20X-HUI-SAO (Universal Converter)
7.4.2
Status/Alarm LEDs
Illustration 7-10:
Status/Alarm LEDs
Condition
LED 1
LED 2
Output
Analog
Output
Relay
LED 3
(Error)
Status
Relay (NC)
1)
active
1)
OFF
energized
1)
fault state
1)
red
flashing
energized
1)
fault state
1)
red
flashing
energized
Device/Signal
OK
OK and wire
short/break
de-activated
and wire
short/break
green
flashing
Output relay
activated
green
flashing
yellow
energized
OFF
de-energized
No supply
OFF
OFF
OFF
de-energized
OFF
de-energized
Device failure
OFF
red
OFF
de-energized
red
de-energized
de-activated
Flashing:
8% ON and 92% OFF
1)
depends on configuration
Table 7-7:
__|¯|_______|¯|_______|¯|_______
Status/Alarm LEDs
1066540000/02/02.14
47
Product Installation / Operation, ACT20X-HUI-SAO (Universal Converter)
7.4.3
Electrical Connections
Function
Terminal
Terminal
Function
41
Out −
M3
42
Out +
2W /3W / 4W
M1
43
COM
4W
M2
44
NO
51
+24 V DC
52
GND
53
NC
54
COM
TC
RTD
11
+
3W / 4W
12
– / CJC
2W / 3W / 4W
13
CJC
POT
V
mA
mA
Loop
Connector
output
14
21
–
22
+
23
–
+
24
+
Table 7-8:
7.4.4
–
output
relay
power
supply
status
relay
Electrical Connections
Specifications
Features
• Configuration and monitoring via FDT/DTM-Software "WI-Manager".
• The device can be mounted in the safe area and in Zone 2 / Class I, Division 2 and receive signals from
Zone 0, 1, 2 and Zone 20, 21 and 22 including M1 / Class I/II/III, Division 1, Group A-G.
• The active or passive signal inputs for RTD, TC, potentiometer, V and mA are completely electrically
isolated.
• The device detects automatically whether an active or passive current signal is connected.
• The cold junction compensation for TC-signal inputs is either the internal cold junction compensation, or for
higher accuracy is an external cold junction compensation terminal available –- 1 channel 1160640000
ACT20X-CJC-HTI-S PRT 11.
• Extended self diagnostic: Monitoring of error events (e.g. cable breakage) via status relay.
• Front LEDs indicates operation status and malfunction.
• 3-way galvanic isolation between input, output and power supply.
48
1066540000/02/02.14
Product Installation / Operation, ACT20X-HUI-SAO (Universal Converter)
Illustration 7-11:
Functional Block Diagram
1066540000/02/02.14
49
Product Installation / Operation, ACT20X-HUI-SAO (Universal Converter)
Illustration 7-12:
Applications
RTD, Resistance and Potentiometer Input
Pt100, according to
-200…+850 °C, IEC 60751
Ni100, according to
-60…+250 °C, DIN 43760
Resistance
(without short circuit detection in the range
R = 0…18Ω, appr.)
0…10 kΩ
Potentiometer
10 Ω…10 kΩ
Sensor types
(* = without short circuit detection)
Pt10*, Pt20*, Pt50*, Pt100, Pt250, Pt300, Pt400,
Pt500, Pt1000, Ni50, Ni100, Ni120, Ni1000
Cable resistance per wire (max.)
50 Ω
Sensor current
nom. 0.2 mA
Effect of sensor cable resistance (3/4-wire)
< 0.002 Ω
50
1066540000/02/02.14
Product Installation / Operation, ACT20X-HUI-SAO (Universal Converter)
Sensor error detection (programmable)
ON/OFF
Short circuit detection, RTD
Yes
TC Input, Sensor Types
Temperature Range
Standard
B
0…+1820 °C
IEC 60584-1
E
-100…+1000 °C
IEC 60584-1
J
-100…+1200 °C
IEC 60584-1
K
-180…+1372 °C
IEC 60584-1
L
-200…+900 °C
DIN 43710
N
-180…+1300 °C
IEC 60584-1
R
-50…+1760 °C
IEC 60584-1
S
-50…+1760 °C
IEC 60584-1
T
-200…+400 °C
IEC 60584-1
U
-200…+600 °C
DIN 43710
W3
0…+2300 °C
ASTM E988-90
W5
0…+2300 °C
ASTM E988-90
LR
-200…+800 °C
GOST 3044-84
Accuracy, General Values
Absolute Accuracy
Temperature Coefficient
All
≤ ±0.1 % of span
≤ ±0.01 % of span / °C
Accuracy, Basic Values
Absolute Accuracy
Temperature Coefficient
mA
≤ ±16 μA
≤ ±1.6 μA / °C
Volt
≤ ±20 μV
≤ ±2 μV / °C
Pt100, Pt200, Pt1000
≤ ±0.2 °C
≤ ±0.02 C / °C
Pt500, Ni100, Ni120, Ni1000
≤ ±0.3 °C
≤ ±0.03 C / °C
Pt50, Pt400, Ni50
≤ ±0.4 °C
≤ ±0.04 C / °C
Pt250, Pt300
≤ ±0.6 °C
≤ ±0.06 C / °C
Pt20
≤ ±0.8 °C
≤ ±0.08 C / °C
Pt10
≤ ±1.4 °C
≤ ±0.14 C / °C
TC type: E, J, K, L, N, T, U
≤ ±1 °C
≤ ±0.1 C / °C
TC type: R, S, W3, W5, LR
≤ ±2 °C
≤ ±0.2 C / °C
TC type: B (160…400 °C)
≤ ±4.5 °C
≤ ±0.45 C / °C
TC type: B (400…1820 °C)
≤ ±2 °C
≤ ±0.2 C / °C
1066540000/02/02.14
51
Product Installation / Operation, ACT20X-HUI-SAO (Universal Converter)
TC Input, Cold Junction Compensation (CJC)
CJC: external with ACT20X-CJC-HTI
(1160640000)
+20…+28 °C ≤ ±1 °C
-20…+20 °C and +28…+60 °C ≤ ±1.6 °C
CJC via internal sensor
∆t = internal temperature – ambient temperature
±(2.0 °C + 0.4 °C * ∆t)
Sensor error detection (programmable, only wire
breakage)
ON/OFF
Sensor error current:
when detecting
else
nom. 2 μA
0 μA
Current Input
Measurement range
0…20 mA
Programmable measurement ranges
0…20 and 4…20 mA
Input resistance
nom. 20 Ω + PTC 50 Ω
Sensor error detection:
loop break (only when input is selected as
4…20 mA)
Yes
Voltage Input
Measurement range
0…12 V DC
Programmable measurement ranges
0…1 V / 0.2…1 V / 0…5 V / 1…5 V / 0…10 V /
2…10 V
Input resistance
nom. > 10 MΩ
Current Output
Signal range (span)
0…23 mA
Programmable signal ranges
0…20 mA / 4…20 mA / 20…0 mA / 20…4 mA
Load max.
4 mA / 600 Ω / 12 V DC
Load stability
≤ 0.01 % of span / 100 Ω
Sensor error detection
0 / 3.5 mA / 23 mA / none
NAMUR NE 43, Upscale / Downscale
23 mA / 3.5 mA
Output limitation:
on 4…20 and 20…4 mA signals
on 0…20 and 20…0 mA signals
3.8…20.5 mA
0…20.5 mA
Current limit
≤ 28 mA
52
1066540000/02/02.14
Product Installation / Operation, ACT20X-HUI-SAO (Universal Converter)
2-wire 4…20 mA Output
Signal range
4…20 mA
Load resistance
≤ (Vsupply – 3.5 V) / 0.023 A [Ω]
Load stability
≤ 0.01 % of span / 100 Ω
Max. external 2-wire supply
3.5…26 V DC
Effect of external 2-wire supply voltage variation
< 0.005 % of span / V
Relay Output
Safe Area
Zone 2 Installation
Voltage max.
250 V AC / 30 V DC
32 V AC / 30 V DC
Current max.
2 A AC / 2 A DC
2 A AC / 2 A DC
Power max.
500 VA / 60 W
64 VA / 60 W
Relay functions
Setpoint, Window, Sensor error, Power and Off
Hysteresis in % / display counts
0.1…25 % / 1…2999
On and Off delay
0…3600 s
Sensor error detection
Break / Make / Hold
Status Relay
Safe Area
Zone 2 Installation
Voltage max.
125 V AC / 110 V DC
32 V AC / 32 V DC
Current max.
0.5 A AC / 0.3 A DC
0,5 A AC / 1 A DC
Power max.
62.5 VA / 32 W
16 VA / 32 W
Power Supply
Supply voltage
19.2…31.2 V DC
Max. consumption
≤ 3.5 W
Fuse
1.25 A / 250 V AC
Isolation Voltages (reinforced insulation), Test/Operation
Inputs / outputs / supply
2.6 kV AC / 300 V AC
Status relay to supply
1.5 kV AC / 150 V AC
Environmental Specifications
Ambient temperature
-20…+60 °C
Storage temperature
-20…+85 °C
Relative humidity (non-condensation)
< 95 %
1066540000/02/02.14
53
Product Installation / Operation, ACT20X-HUI-SAO (Universal Converter)
Calibration temperature
+20…28 °C
General Specifications
Communications interface,
adapter / configuration software / FDT-DTM
device driver
CBX200 USB / "WI-Manager" / ACT20X DTM
Dimensions (H x W x D)
105.6 x 22.5 x 114.7 mm
Protection degree
IP20
Screw terminal torque
0.5 Nm
Vibration
IEC 60068-2-6, test Fc, 1g, 2…100 Hz
Vibration, continuous
IEC 60068-2-64, test Fh, 1g, 3…100 Hz
Wire size, stranded wire
AWG 26…14 / 0.13…2.08 mm²
EMC immunity influence
≤ ±0.5 % of span
Extended EMC immunity:
NAMUR NE 21, A criterion, burst
≤ ±1 % of span
Signal/Noise ratio
min. 60 dB (0…100 kHz)
Response time (0…90 %, 100…10 %):
Temperature input, programmable
mA / V input, programmable
1…60 s
0.4…60 s
Default Settings
Input type
Temperature
Connection type
3-wire
Temperature unit
°C
Temperature sensor type
Pt100
Temperature range
0…150 °C
Output current range
0…20 mA
Output current on error
23 mA
Analog output response time (1/10 s)
1s
Relay Software Parameters / Default Settings
Function
SETPOINT
Contact function
Normally Open (NO)
Setpoint
50 °C (input type temperature) / 50 %
Activation direction
Increasing
Hysteresis
1 °C (input type temperature) / 1 %
54
1066540000/02/02.14
Product Installation / Operation, ACT20X-HUI-SAO (Universal Converter)
Action on error
Relay OPEN
Activation delay
0s
Deactivation delay
0s
Illustration 7-13:
Graphic depiction of window
Illustration 7-14:
Graphic depiction of setpoint
1066540000/02/02.14
55
Product Installation / Operation, ACT20X-HAI-SAO (HART-transparent Repeater)
7.5
ACT20X-HAI-SAO (HART-transparent Repeater)
7.5.1
Description
The ACT20X-HAI-SAO-S current supply isolator is a HART-protocol, transparent isolator for analogue input
signals from Ex Zone 0. The input may also operate as an active current loop (the loop current provided by
the device). It provides an 4...20 mA current signal for the safe zone on the output side.
It is available in a single-channel or two-channel version.
The following HART-transparent repeaters are available:
Order No.
Type
Description
8965430000
ACT20X-HAI-SAO-S
HART-transparent repeater
8965440000
ACT20X-2HAI-2SAO-S
2-channel HART-transparent repeater
56
1066540000/02/02.14
Product Installation / Operation, ACT20X-HAI-SAO (HART-transparent Repeater)
7.5.2
Status/Alarm LEDs
Illustration 7-15:
Status/Alarm LEDs
Condition
LED 1
Channel 1
Channel 2
LED 3
Output
Status
Relay (NC)
LED 2
Output
activated
OFF
active
energized
defective
red
inactive
de-energized
red
flashing
inactive
de-energized
red
blinking
inactive
de-energized
Channel 1
Device OK
signal limit
exceeded
green
flashing
Channel 2
fixed loop break
limit exceeded
activated
OFF
active
energized
defective
red
inactive
de-energized
red
flashing
inactive
de-energized
red
blinking
inactive
de-energized
signal limit
exceeded
green
flashing
fixed loop break
limit exceeded
No supply
OFF
OFF
OFF
OFF
OFF
de-energized
Device failure
OFF
red
OFF
red
OFF
de-energized
Blinking:
50% ON and 50% OFF
__|¯¯¯¯|____|¯¯¯¯|____|¯¯¯¯|____
Flashing:
8% ON and 92% OFF
__|¯|_______|¯|_______|¯|_______
Table 7-9:
Status/Alarm LEDs
1066540000/02/02.14
57
Product Installation / Operation, ACT20X-HAI-SAO (HART-transparent Repeater)
7.5.3
Electrical Connections
Terminal
Function
11
I Passive −
12
I Passive +
13
I Active Return
14
Terminal
Function
41
Out −
42
Out +
43
Out −
I Active Supply
44
Out +
21
I Passive −
51
GND
22
I Passive +
52
+24 V DC
23
I Active Return
53
NC
24
I Active Supply
54
COM
Table 7-10:
7.5.4
Connector
Ex input
channel 1
Ex input
channel 2
Connector
output
channel 1
output
channel 2
power supply
status relay
Electrical Connections
Specifications
Features
• HART-compatible for 0.5...2.5 kHz
• Configuration and monitoring via FDT/DTM-Software "WI-Manager".
• The device can be mounted in the safe area and in Zone 2 / Class I, Division 2 and receive signals from
Zone 0, 1, 2 and Zone 20, 21 and 22 including M1 / Class I/II/III, Division 1, Group A-G.
• The active or passive mA current signal inputs are completely electrically isolated.
• The device detects automatically whether an active or passive current signal is connected.
• The two-channel device can be used as a signal splitter.
• Extended self diagnostic: Monitoring of error events (e.g. cable breakage) via status relay.
• Front LEDs indicates operation status and malfunction.
• 3-way galvanic isolation between input, output and power supply.
58
1066540000/02/02.14
Product Installation / Operation, ACT20X-HAI-SAO (HART-transparent Repeater)
Illustration 7-16:
Functional Block Diagram
1066540000/02/02.14
59
Product Installation / Operation, ACT20X-HAI-SAO (HART-transparent Repeater)
Illustration 7-17:
Applications
Current Input
Measurement range
3.5…23 mA
Alarm setpoint, low/high limit (programmable)
0…28 mA
Sensor error detection
< 1 mA
Current Output
Signal range (programmable)
3.5…23 mA
Load max.
20 mA / 600 Ω / 12 V DC
Load stability
≤ 0.01 % of span /100 Ω
Sensor error detection (programmable)
3.5 mA / 23 mA / none
60
1066540000/02/02.14
Product Installation / Operation, ACT20X-HAI-SAO (HART-transparent Repeater)
Current limit
≤ 28 mA
Effect of supply voltage change
< ±10 μA
2-wire 4…20 mA Current Loop Output
Signal range
3.5...23 mA
Load resistance
≤ (Vsupply – 3.5 V) / 0.023 A [Ω]
Load stability
≤ 0.01 % of span/100 Ω
External 2-wire supply voltage
3.5…26 V DC
Effect of external 2-wire supply voltage change
< 0.005 % of span / V
Accuracy
Absolute Accuracy
Temperature Coefficient
General values
≤ ±0.1 % of span
≤ ±0.01 % of span / °C
Basic values
≤ ±16 µA
≤ ±1.6 µA / °C
Status Relay
Safe Area
Zone 2 Installation
Voltage max.
125 V AC / 110 V
32 V AC / 32 V DC
Current max.
0.5 A AC / 0.3 A
0.5 A AC / 1 A DC
Power max.
62.5 VA / 32 W
16 VA / 32 W
Power Supply
Supply voltage
19.2…31.2 V DC
Max. consumption (2-channels)
≤3W
Fuse
1.25 A / 250 V AC
Isolation Voltages (reinforced insulation), Test/Operation
Inputs / outputs / supply
2.6 kV AC / 300 V AC
Output 1 to output 2
1.5 kV AC / 150 V AC
Status relay to supply
1.5 kV AC / 150 V AC
Environmental Specifications
Specifications range
-20…+60 °C
Storage temperature
-20…+85 °C
Relative humidity (non-condensation)
< 95 %
Calibration temperature
+20…28 °C
1066540000/02/02.14
61
Product Installation / Operation, ACT20X-HAI-SAO (HART-transparent Repeater)
General Specifications
Communications interface,
adapter / configuration software / FDT-DTM
device driver
CBX200 USB / "WI-Manager" / ACT20X DTM
Dimensions (H x W x D)
105.6 x 22.5 x 114.7 mm
Protection degree
IP20
Screw terminal torque
0.5 Nm
Vibration
IEC 60068-2-6, test Fc, 1g, 2…100 Hz
Vibration, continuous
IEC 60068-2-64, test Fh, 1g, 3…100 Hz
Wire size, stranded wire
AWG 26…14 / 0.13…2.08 mm²
EMC immunity influence
≤ ±0.5 % of span
Extended EMC immunity:
NAMUR NE 21, A criterion, burst
≤ ±1 % of span
Response time for cable fault
< 200 ms
HART Communication
Frequency range
0.5…2.5 kHz
Signal / noise ratio
min. 60 dB (0.5…10 kHz)
Response time (0…90 %, 100…10 %)
< 5 ms
Default Settings
Low/high limit
62
3.8 mA / 20.5 mA
1066540000/02/02.14
Product Installation / Operation, ACT20X-SAI-HAO (HART-transparent Driver)
7.6
ACT20X-SAI-HAO (HART-transparent Driver)
7.6.1
Description
The ACT20X-SAI-HAO-S is a HART-protocol, transparent current output isolator. A DC current input signal
from the safe area will be galvanically separated and drives controlled field devices in Ex Zone 0.
It is available in a single-channel or two-channel version.
The following HART-transparent drivers are available:
Order No.
Type
Description
8965450000
ACT20X-SAI-HAO-S
HART-transparent driver
8965460000
ACT20X-2SAI-2HAO-S
2-channel HART-transparent driver
1066540000/02/02.14
63
Product Installation / Operation, ACT20X-SAI-HAO (HART-transparent Driver)
7.6.2
Status/Alarm LEDs
Illustration 7-18:
Status/Alarm LEDs
Condition
LED 1
Channel 1
Channel 2
LED 3
Output
Status
Relay (NC)
LED 2
Output
OK
OFF
ON
energized
defective
red
fault state
de-energized
red
flashing
fault state
de-energized
red
blinking
fault state
de-energized
Channel 1
Device
signal limit
exceeded
green
flashing
Channel 2
fixed loop break
limit exceeded
OK
OFF
ON
energized
defective
red
fault state
de-energized
red
flashing
fault state
de-energized
red
blinking
fault state
de-energized
signal limit
exceeded
green
flashing
fixed loop break
limit exceeded
No supply
OFF
OFF
OFF
OFF
OFF
de-energized
Device failure
OFF
red
OFF
red
OFF
de-energized
Blinking:
50% ON and 50% OFF
__|¯¯¯¯|____|¯¯¯¯|____|¯¯¯¯|____
Flashing:
8% ON and 92% OFF
__|¯|_______|¯|_______|¯|_______
Table 7-11:
64
Status/Alarm LEDs
1066540000/02/02.14
Product Installation / Operation, ACT20X-SAI-HAO (HART-transparent Driver)
7.6.3
Electrical Connections
Terminal
Function
11
Out −
12
Out +
13
Connector
Terminal
Function
Connector
41
In –
42
In +
input
channel 1
43
In –
44
In +
51
GND
52
+24 V DC
53
NC
54
COM
Ex output
channel 1
14
21
Out −
22
Out +
23
Ex output
channel 2
24
Table 7-12:
7.6.4
input
channel 2
power supply
status relay
Electrical Connections
Specifications
Features
• HART-compatible for 0.5...2.5 kHz
• Configuration and monitoring via FDT/DTM-Software "WI-Manager".
• The device can be mounted in the safe area and in Zone 2 / Class I, Division 2 and receive signals from
Zone 0, 1, 2 and Zone 20, 21 and 22 including M1 / Class I/II/III, Division 1, Group A-G.
• The mA current signal inputs are completely electrically isolated.
• The device detects automatically whether an active or passive current signal is connected.
• Extended self diagnostic: Monitoring of error events (e.g. cable breakage) via status relay.
• Front LEDs indicates operation status and malfunction.
• 3-way galvanic isolation between input, output and power supply.
1066540000/02/02.14
65
Product Installation / Operation, ACT20X-SAI-HAO (HART-transparent Driver)
Illustration 7-19:
66
Functional Block Diagram
1066540000/02/02.14
Product Installation / Operation, ACT20X-SAI-HAO (HART-transparent Driver)
Illustration 7-20:
Applications
Current Input
Measurement range
3.5…23 mA
Input resistance
nom. 20 Ω + PTC 50 Ω
Alarm setpoint, low/high limit (programmable)
0…28 mA
Sensor error detection
< 1 mA
Current Output
Signal range (programmable)
3.5…23 mA
Load max.
20 mA / 725 Ω / 14.5 V DC
Load stability
≤ 0.01 % of span / 100 Ω
1066540000/02/02.14
67
Product Installation / Operation, ACT20X-SAI-HAO (HART-transparent Driver)
Sensor error detection (programmable)
3.5 mA / 23 mA / none
Current limit
≤ 28 mA
Accuracy
Absolute Accuracy
Temperature Coefficient
General values
≤ ±0.1 % of span
≤ ±0.01 % of span / °C
Basic values
≤ ±16 µA
≤ ±1.6 µA / °C
Status Relay
Safe Area
Zone 2 Installation
Voltage max.
125 V AC / 110 V
32 V AC / 32 V DC
Current max.
0.5 A AC / 0.3 A
0.5 A AC / 1 A DC
Power max.
62.5 V AC / 32 W
16 VA / 32 W
Power Supply
Supply voltage
19.2…31.2 V DC
Max. consumption (2-channels)
≤ 3.5 W
Fuse
1.25 A / 250 V AC
Isolation Voltages (reinforced insulation), Test/Operation
Inputs / outputs / supply
2.6 kV AC / 300 V AC
Input 1 to input 2
1.5 kV AC / 150 V AC
Status relay to supply
1.5 kV AC / 150 V AC
Environmental Specifications
Ambient temperature
-20…+60 °C
Storage temperature
-20…+85 °C
Relative humidity (non-condensation)
< 95 %
Calibration temperature
+20…28 °C
General Specifications
Communications interface,
adapter / configuration software / FDT-DTM
device driver
CBX200 USB / "WI-Manager" / ACT20X DTM
Dimensions (H x W x D)
105.6 x 22.5 x 114.7 mm
Protection degree
IP20
Screw terminal torque
0.5 Nm
68
1066540000/02/02.14
Product Installation / Operation, ACT20X-SAI-HAO (HART-transparent Driver)
Vibration
IEC 60068-2-6, test Fc, 1g, 2…100 Hz
Vibration, continuous
IEC 60068-2-64, test Fh, 1g, 3…100 Hz
Wire size, stranded wire
AWG 26…14 / 0.13…2.08 mm²
EMC immunity influence
≤ ±0.5 % of span
Extended EMC immunity:
NAMUR NE 21, A criterion, burst
≤ ±1 % of span
HART Communication
Frequency range
0.5…2.5 kHz
Signal / noise ratio
min. 60 dB (0.5…10 kHz)
Response time (0…90 %, 100…10 %)
< 5 ms
Default Settings
Low/high limit
1066540000/02/02.14
3.8 mA / 20.5 mA
69
Product Installation / Operation, ACT20-FEED-IN-PRO-S
7.7
ACT20-FEED-IN-PRO-S
7.7.1
Description
The power feed-in unit ACT20-FEED-IN-PRO-S supplies the devices on the CH20M DIN rail bus with
24 V DC. At the same time, the ACT20-FEED-IN-PRO-S device reads the group error contact – optionally
provided by the installed devices – from the CH20M rail bus and sends a message through the status relay
to the external controller. Optionally, two power supplies can be connected for the primary and secondary
supplies (backup). An installation in Zone 2 / Division 2 is also possible. Three LEDs show the status of the
power supply and the error status.
The ACT20-FEED-IN-PRO-S can supply a maximum of 4 A to feed up to 120 devices mounted on a CH20M
rail bus. Quick identification of errors on the DIN rail bus is through the internal status relay. The ACT20FEED-IN-PRO-S device immediately recognises and displays when a power supply has failed. The supply is
then switched automatically to the redundant power supply.
The following Power Feed-In Unit is available:
Order No.
Type
Description
8965500000
ACT20-FEED-IN-PRO-S
Power Feed-In Unit
70
1066540000/02/02.14
Product Installation / Operation, ACT20-FEED-IN-PRO-S
7.7.2
Status/Alarm LEDs
Illustration 7-21:
Status/Alarm LEDs
LED 1
(PWR)
LED 2
(PWR BACKUP)
LED 3
(Alarm)
No power supply
OFF
OFF
OFF
de-energized de-energized
Primary supply voltage
green
OFF
red
de-energized de-energized
Secondary supply
voltage
OFF
green
red
de-energized de-energized
Primary and secondary
supply voltage
green
green
OFF
Condition
Status
Relay (NC)
1)
Status
Relay (NO)
1)
Collective error message
active
red
de-energized de-energized
inactive
OFF
energized 2) energized 2)
1)
depends on collective error message
2)
if the primary and/or secondary power supply is applied
Table 7-13:
Status/Alarm LEDs
1066540000/02/02.14
71
Product Installation / Operation, ACT20-FEED-IN-PRO-S
7.7.3
Electrical connections
Terminal
Function
41
NO
42
COM
43
NC
Connector
status relay
44
51
GND
52
+24 V DC
53
+24 V DC
54
GND
81
collective error contact
82
+24 V DC
83
GND
power supply
backup power supply
Weidmüller DIN rail bus CH20M
84
85
Table 7-14:
7.7.4
Electrical connections
Specifications
Features
• The power feed-in unit ACT20-FEED-IN-PRO-S detects errors from any of the devices mounted on the
Weidmüller DIN rail bus CH20M and transmits a collective alarm to an external control system via the
internal status relay.
• Optional connection of two power supplies - a primary power supply and a backup power supply.
• Redundant power supply can be obtained by mounting two feed-in units connected to two separate power
supplies.
• The status relay will be energised when the following conditions are met:
- The power supply is present on terminal 51 and 52.
- The backup power supply is present on terminal 53 and 54.
If the backup power supply is not required, the included jumper must be employed between terminal 52
and 53.
- There are no error signals from the devices connected to the Weidmüller DIN rail bus.
• The device can be mounted in the safe area (non-hazardous) and in zone 2 / division 2.
• The status of the power supply and the backup power supply is indicated by two green LEDs.
• A malfunction is indicated by a red LED.
72
1066540000/02/02.14
Product Installation / Operation, ACT20-FEED-IN-PRO-S
Illustration 7-22:
Functional Block Diagram
1066540000/02/02.14
73
Product Installation / Operation, ACT20-FEED-IN-PRO-S
*
If the backup power supply is not required, the included jumper must be employed between terminal 52 and 53.
Illustration 7-23:
Applications
Input Supply Voltage
Supply voltage
21.6…26.4 V DC
Backup supply voltage
21.6…26.4 V DC
Trigger level for collective alarm on DIN rail bus
< 21 V DC
Efficiency
> 97.9 %
Internal consumption max.
2W
74
1066540000/02/02.14
Product Installation / Operation, ACT20-FEED-IN-PRO-S
Output Power Supply
Output voltage at 4 A
Vinput power supply – 0.5 V DC
Output current max.
4 A DC
Output power max.
96 W
Status Relay (Alarm),Safe Area
Voltage max.
250 V AC / 30 V DC
Current max.
2 A AC / 2 A DC
Power max.
500 VA / 60 W
Environmental Specifications
Ambient temperature
-20…+60 °C
Storage temperature
-20…+85 °C
Relative humidity (non-condensation)
< 95 %
General Specifications
Dimensions L x W x H
109.2 x 22.5 x 113.6 mm
Protection degree
IP 20
Screw terminal torque
0.5 Nm
Wire size (stranded wire)
AWG 26…14 / 0.13…2.08 mm
Isolation test voltage
2.6 kV AC
1066540000/02/02.14
2
75
Product Installation / Operation, Female Plug BHZ 5.00
7.8
Female Plug BHZ 5.00
7.8.1
Description
Among other things, the following female plug is available:
Order No.
Type
Description
1069380000
BHZ 5.00/04/90LH BK/BL
Female plug
Features
• Simple, component-friendly unplugging of the female plug using the integrated release lever.
• Together with the captive, unique "Auto-Set" encoding, the uniquely detectable markers on the plug
connection and in the front ensure misconnection-proof assignment of the connections. Both markers can
be printed as cards in a PrintJet and then permanently snapped on.
• Quick and easy operation by means of an integrated colour-coded release lever with grip tab and including
a screwdriver pocket.
• Touch protection for the male and female header on both sides.
• During the installation: the quick all-purpose "Multi-Tool" screw head ensures a secure contact, userfriendly operation and less complexity. Additional features, such as the "Wire ready" technology, enable
you to minimize wiring costs and increase customer satisfaction.
76
1066540000/02/02.14
Product Installation / Operation, Female Plug BHZ 5.00
7.8.2
Specifications
General Specifications
Product family
OMNIMATE Housing - series CH20M
Wire connection method
Clamping yoke connection
Conductor outlet direction
90°
Pitch
5 mm / 0.197 inch
Number of poles
4
Screwdriver blade DIN 5264
0.6 x 3.5
Tightening torque
0.4...0.6 Nm
Clamping screw
M 2.5
Stripping length
8 mm
Dimensions L x W x H
14.6 x 22.4 x 29 mm
Connectable Wires
Clamping range
0.13...3.31 mm
Solid, H05(07) V-U
0.2...2.5 mm
2
Flexible, H05(07) V-K
0.2...2.5 mm
2
With wire end ferrule, DIN 46228/1
0.25...2.5 mm
2
With wire end ferrule and plastic collar, DIN 46228/4
0.25...2.5 mm
2
2
Rated Data according to UL 1059 and CSA
Rated voltage / Rated current (use group B)
300 V / 10 A
Rated voltage / Rated current (use group C)
50 V / 10 A
Rated voltage / Rated current (use group D)
300 V / 10 A
Wire cross-section
AWG 26...12
Rated Data according to DIN IEC
Rated current, max. number of poles
10 A @ Tu = 20 °C, 9 A @ Tu = 40 °C
Rated voltage / overvoltage category / pollution degree
400 V / II / 2
320 V / /II / 2
250 V / /II / 3
Rated impulse voltage / overvoltage category /
pollution degree
4 kV / II / 2
4 kV / /II / 2
4 kV / /II / 3
1066540000/02/02.14
77
Product Installation / Operation, Female Plug BHZ 5.00
Material Data
UL 94 flammability rating
V-0
Isulating material
PA 66 GV30
Colour
black
78
1066540000/02/02.14
Appendix A. Installation Drawings ACT20X-HDI-SDO (NAMUR Pulse Isolator)
Appendix A. Installation Drawings ACT20X-HDI-SDO (NAMUR Pulse Isolator)
ATEX Installation Drawing
The module is available in the following variants:
Order No.
Installation Drawing
Type
8965340000
4 50102 Sheet 1-2
ACT20X-HDI-SDO-RNO-S
8965350000
4 50102 Sheet 1-2
ACT20X-HDI-SDO-RNC-S
8965360000
4 50588 Sheet 1-2
ACT20X-HDI-SDO-S
8965370000
4 50589 Sheet 1-2
ACT20X-2HDI-2SDO-RNO-S
8965380000
4 50589 Sheet 1-2
ACT20X-2HDI-2SDO-RNC-S
8965390000
4 50590 Sheet 1-2
ACT20X-2HDI-2SDO-S
DANGER
For safe installation of ACT20X-(2)HDI-(2)SDO-(RNO/RNC)-S the following must be observed:
The module may only be installed by qualified personnel familiar with the national and
international laws, directives and standards that apply to this region.
DANGER
To prevent ignition of explosive atmospheres, disconnect power before servicing and do not
separate connectors when energized and an explosive gas mixture is present.
For installation in Zone 2, the module must be installed in an outer enclosure having an IP protection of at
least IP54 according to type of protection Ex-n or Ex-e.
In type of protection “intrinsic safety for group IIIC” the parameters for intrinsic safety for gas group IIB are
applicable.
If the sensor circuits have been installed in a type of protection other than “intrinsic safety”, the module must
not be re-installed in type of protection ”intrinsic safety”.
The module must be installed in pollution degree 2, overvoltage category II as defined in EN 60664-1.
Do not separate connectors when energized and an explosive gas mixture is present.
The wiring of unused terminals is not allowed.
The year of manufacture can be taken from the first two digits in the serial number.
2
Wire cross-section:
AWG 26...12 / 0.13...3.31 mm
Number of wires per terminal:
1 wire or 2 wires in a common ferrule
Tightening torque per terminal, max.:
0.6 Nm
1066540000/02/02.14
79
Appendix A. Installation Drawings ACT20X-HDI-SDO (NAMUR Pulse Isolator)
CBX200 – "WI-Manager" Software
For installation in Zone 2 / Division 2 the following must be observed:
- The CBX200 is an interface cable for configuration via PC.
- Configuration must be performed only in a safe area.
ATEX Certificate
KEMA 09ATEX 0168 X
Marking
II (1) G [Ex ia Ga] IIC/IIB/IIA
II 3 G Ex nA nC IIC T4 Gc
II (1) D [Ex ia Da] IIIC
I (M1) [Ex ia Ma] I
Standards
EN 60079-0:2012, EN 60079-11:2012, EN 60079-15:2010,
EN 60079-26:2007
80
1066540000/02/02.14
Appendix A. Installation Drawings ACT20X-HDI-SDO (NAMUR Pulse Isolator)
Illustration 7-24:
ATEX Installation Drawing, (450102 Sheet 1-2, 450588 Sheet 1-2, 450589 Sheet 1-2,
450590 Sheet 1-2)
Terminal CH1 (11, 12, 13, 14), CH2 (21, 22, 23, 24)
Ex Input
Uo
10.6 V DC
Io
12 mA DC
Po
32 mW
Lo/Ro
1150 µH/Ω
Group
Co
Lo
IIC
2 µF
260 mH
IIB
6 µF
780 mH
IIA
18 µF
1000 mH
I
90 µF
1000 mH
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um
1066540000/02/02.14
253 V, max. 400 Hz
81
Appendix A. Installation Drawings ACT20X-HDI-SDO (NAMUR Pulse Isolator)
Terminal (51, 52)
Supply
Voltage
19.2…31.2 V DC
Power max.
3W
Terminal (53, 54)
Status Relay
Non Hazardous
Location
Zone 2 Installation
Voltage max.
125 V AC / 110 V DC
32 V AC / 32 V DC
Current max.
0.5 A AC / 0.3 A DC
0.5 A AC / 1 A DC
Power max.
62.5 VA / 32 W
16 VA / 32 W
Terminal CH1 (41, 42) and CH2 (43, 44)
Digital Output, NPN Output
Voltage max.
30 V DC
Current max.
80 mA
Terminal CH1 (41, 42) and CH2 (43, 44)
Relay Output
Non Hazardous
Location
Zone 2 Installation
Voltage max.
250 V AC / 30 V DC
32 V AC / 30 V DC
Current max.
2 A AC / 2 A DC
2 A AC / 2 A DC
Power max.
500 VA / 60 W
64 VA / 60 W
82
1066540000/02/02.14
Appendix A. Installation Drawings ACT20X-HDI-SDO (NAMUR Pulse Isolator)
IECEx Installation Drawing
The module is available in the following variants:
Order No.
Installation Drawing
Type
8965340000
4 50102 Sheet 3-4
ACT20X-HDI-SDO-RNO-S
8965350000
4 50102 Sheet 3-4
ACT20X-HDI-SDO-RNC-S
8965360000
4 50588 Sheet 3-4
ACT20X-HDI-SDO-S
8965370000
4 50589 Sheet 3-4
ACT20X-2HDI-2SDO-RNO-S
8965380000
4 50589 Sheet 3-4
ACT20X-2HDI-2SDO-RNC-S
8965390000
4 50590 Sheet 3-4
ACT20X-2HDI-2SDO-S
DANGER
For safe installation of ACT20X-(2)HDI-(2)SDO-(RNO/RNC)-S the following must be observed:
The module may only be installed by qualified personnel familiar with the national and
international laws, directives and standards that apply to this region.
DANGER
To prevent ignition of explosive atmospheres, disconnect power before servicing and do not
separate connectors when energized and an explosive gas mixture is present.
For installation in Zone 2, the module must be installed in an outer enclosure having an IP protection of at
least IP54 according to type of protection Ex-n or Ex-e.
In type of protection “intrinsic safety for group IIIC” the parameters for intrinsic safety for gas group IIB are
applicable.
If the sensor circuits have been installed in a type of protection other than “intrinsic safety”, the module must
not be re-installed in type of protection ”intrinsic safety”.
The module must be installed in pollution degree 2, overvoltage category II as defined in IEC 60664-1.
Do not separate connectors when energized and an explosive gas mixture is present.
The wiring of unused terminals is not allowed.
The year of manufacture can be taken from the first two digits in the serial number.
2
Wire cross-section:
AWG 26...12 / 0.13...3.31 mm
Number of wires per terminal:
1 wire or 2 wires in a common ferrule
Tightening torque per terminal, max.:
0.6 Nm
1066540000/02/02.14
83
Appendix A. Installation Drawings ACT20X-HDI-SDO (NAMUR Pulse Isolator)
CBX200 – "WI-Manager" Software
For installation in Zone 2 / Division 2 the following must be observed:
- The CBX200 is an interface cable for configuration via PC.
- Configuration must be performed only in a safe area.
IECEx Certificate
KEM 09.0072 X
Marking
Ex nA nC IIC T4 Gc
[Ex ia Ga] IIC/IIB/IIA
[Ex ia Da] IIIC
[Ex ia Ma] I
Standards
IEC 60079-0:2011, IEC 60079-11:2011, IEC 60079-15:2010,
IEC 60079-26:2007
84
1066540000/02/02.14
Appendix A. Installation Drawings ACT20X-HDI-SDO (NAMUR Pulse Isolator)
Illustration 7-25:
IECEx Installation Drawing, (450102 Sheet 3-4, 450588 Sheet 3-4, 450589 Sheet 3-4,
450590 Sheet 3-4)
Terminal CH1 (11, 12, 13, 14), CH2 (21, 22, 23, 24)
Ex Input
Uo
10.6 V DC
Io
12 mA DC
Po
32 mW
Lo/Ro
1150 µH/Ω
Group
Co
Lo
IIC
2 µF
260 mH
IIB
6 µF
780 mH
IIA
18 µF
1000 mH
I
90 µF
1000 mH
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um
1066540000/02/02.14
253 V, max. 400 Hz
85
Appendix A. Installation Drawings ACT20X-HDI-SDO (NAMUR Pulse Isolator)
Terminal (51, 52)
Supply
Voltage
19.2…31.2 V DC
Power max.
3W
Terminal (53, 54)
Status Relay
Non Hazardous
Location
Zone 2 Installation
Voltage max.
125 V AC / 110 V DC
32 V AC / 32 V DC
Current max.
0.5 A AC / 0.3 A DC
0.5 A AC / 1 A DC
Power max.
62.5 VA / 32 W
16 VA / 32 W
Terminal CH1 (41, 42) and CH2 (43, 44)
Digital Output, NPN Output
Voltage max.
30 V DC
Current max.
80 mA
Terminal CH1 (41, 42) and CH2 (43, 44)
Relay Output
Non Hazardous
Location
Zone 2 Installation
Voltage max.
250 V AC / 30 V DC
32 V AC / 30 V DC
Current max.
2 A AC / 2 A DC
2 A AC / 2 A DC
Power max.
500 VA / 60 W
64 VA / 60 W
86
1066540000/02/02.14
Appendix A. Installation Drawings ACT20X-HDI-SDO (NAMUR Pulse Isolator)
FM Installation Drawing
The module is available in the following variants:
Order No.
Installation Drawing
Type
8965340000
4 50102 Sheet 5-6
ACT20X-HDI-SDO-RNO-S
8965350000
4 50102 Sheet 5-6
ACT20X-HDI-SDO-RNC-S
8965360000
4 50588 Sheet 5-6
ACT20X-HDI-SDO-S
8965370000
4 50589 Sheet 5-6
ACT20X-2HDI-2SDO-RNO-S
8965380000
4 50589 Sheet 5-6
ACT20X-2HDI-2SDO-RNC-S
8965390000
4 50590 Sheet 5-6
ACT20X-2HDI-2SDO-S
DANGER
For safe installation of ACT20X-(2)HDI-(2)SDO-(RNO/RNC)-S the following must be observed:
The module may only be installed by qualified personnel familiar with the national and
international laws, directives and standards that apply to this region.
DANGER
To prevent ignition of explosive atmospheres, disconnect power before servicing and do not
separate connectors when energized and an explosive gas mixture is present.
WARNING
Substitution of components may impair intrinsic safety and/or suitability for Division 2 / Zone 2.
The installation and wiring must be in accordance with the Canadian Electrical Code for Canada and
National Electrical Code NFPA 70, Article 500 or 505 for installation in USA.
The module must be supplied from a Power Supply having double or reinforced insulation.
The use of stranded wires is not permitted for mains wiring except when wires are fitted with cable ends.
The module must be installed in pollution degree 2, overvoltage category II as defined in IEC 60664-1.
The module must be installed in an enclosure suitable for the environment where it is used.
For installation in Zone 2 or Division 2, the module must be installed in a suitable outer enclosure according
to the regulations in the CEC for Canada or NEC for USA.
The module is galvanically isolated and does not require grounding.
Use 60/75 °C copper conductors in the wire size AWG 26-14.
The year of manufacture can be taken from the first two digits in the serial number.
1066540000/02/02.14
87
Appendix A. Installation Drawings ACT20X-HDI-SDO (NAMUR Pulse Isolator)
CBX200 – "WI-Manager" Software
For installation in Zone 2 / Division 2 the following must be observed:
- The CBX200 is an interface cable for configuration via PC.
- Configuration must be performed only in a safe area.
c-FM-us Certificate
3038275C / 3038275
Marking
Install in CL I DIV2 GP A-D T4
Provides IS Circuits to
CL I-III DIV 1/2 GP A-G or
CL I Zn2 AEx/Ex nA nC [ia] IIC T4
Standards
Canada
Zones:
Divisions:
USA
Zones:
Divisions:
88
E60079-0, E60079-11, E60079-15
CSA 22.2-157, CSA 22.2-213
UL 60079-0, UL 60079-11, UL 60079-15
FM3600, FM3610, FM3611, FM3810
1066540000/02/02.14
Appendix A. Installation Drawings ACT20X-HDI-SDO (NAMUR Pulse Isolator)
Illustration 7-26:
FM Installation Drawing, (450102 Sheet 5-6, 450588 Sheet 5-6, 450589 Sheet 5-6,
450590 Sheet 5-6)
Terminal CH1 (11, 12, 13, 14), CH2 (21, 22, 23, 24)
Ex Input
Uo, Vt
10.6 V DC
Io, Isc
12 mA DC
Po, Pt
32 mW
Lo/Ro, La/Ra
1150 µH/Ω
Group
C o, C a
L o, L a
IIC or A, B
2 µF
260 mH
IIB or C, E, F
6 µF
780 mH
IIA or D, G
18 µF
1000 mH
1066540000/02/02.14
89
Appendix A. Installation Drawings ACT20X-HDI-SDO (NAMUR Pulse Isolator)
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um
253 V, max. 400 Hz
Terminal (51, 52)
Supply
Voltage
19.2…31.2 V DC
Power max.
3W
Terminal (53, 54)
Status Relay
Non Hazardous
Location
Zone 2 Installation
Voltage max.
125 V AC / 110 V DC
32 V AC / 32 V DC
Current max.
0.5 A AC / 0.3 A DC
0.5 A AC / 1 A DC
Power max.
62.5 VA / 32 W
16 VA / 32 W
Terminal CH1 (41, 42) and CH2 (43, 44)
Digital Output, NPN Output
Voltage max.
30 V DC
Current max.
80 mA
Terminal CH1 (41, 42) and CH2 (43, 44)
Relay Output
Non Hazardous
Location
Zone 2 Installation
Voltage max.
250 V AC / 30 V DC
32 V AC / 30 V DC
Current max.
2 A AC / 2 A DC
2 A AC / 2 A DC
Power max.
500 VA / 60 W
64 VA / 60 W
90
1066540000/02/02.14
Appendix B. Installation Drawings ACT20X-HTI-SAO (Temperature/mA Converter)
Appendix B. Installation Drawings ACT20X-HTI-SAO (Temperature/mA Converter)
ATEX Installation Drawing
The module is available in the following variants:
Order No.
Installation Drawing
Type
8965470000
4 50594 Sheet 1-2
ACT20X-HTI-SAO-S
8965480000
4 50595 Sheet 1-2
ACT20X-2HTI-2SAO-S
DANGER
For safe installation of the Temperature and mA Converter ACT20X-(2)HTI-(2)SAO-S the
following must be observed: The module may only be installed by qualified personnel familiar
with the national and international laws, directives and standards that apply to this region.
DANGER
To prevent ignition of explosive atmospheres, disconnect power before servicing and do not
separate connectors when energized and an explosive gas mixture is present.
For installation in Zone 2, the module must be installed in an outer enclosure having an IP protection of at
least IP54 according to type of protection Ex-n or Ex-e.
In type of protection “intrinsic safety for group IIIC” the parameters for intrinsic safety for gas group IIB are
applicable.
If the sensor circuits (Terminals 11…14, 21…24) have been installed in a type of protection other than
“intrinsic safety”, the module must not be re-installed in type of protection ”intrinsic safety”.
The module must be installed in pollution degree 2, overvoltage category II as defined in EN 60664-1.
Do not separate connectors when energized and an explosive gas mixture is present.
The wiring of unused terminals is not allowed.
The year of manufacture can be taken from the first two digits in the serial number.
2
Wire cross-section:
AWG 26...12 / 0.13...3.31 mm
Number of wires per terminal:
1 wire or 2 wires in a common ferrule
Tightening torque per terminal, max.:
0.6 Nm
1066540000/02/02.14
91
Appendix B. Installation Drawings ACT20X-HTI-SAO (Temperature/mA Converter)
CBX200 – "WI-Manager" Software
For installation in Zone 2 / Division 2 the following must be observed:
- The CBX200 is an interface cable for configuration via PC.
- Configuration must be performed only in a safe area.
ATEX Certificate
KEMA 10ATEX 0020 X
Marking
II (1) G [Ex ia Ga] IIC/IIB/IIA
II 3 G Ex nA nC IIC T4 Gc
II (1) D [Ex ia Da] IIIC
I (M1) [Ex ia Ma] I
Standards
EN 60079-0:2012, EN 60079-11:2012, EN 60079-15:2010,
EN 60079-26:2007
92
1066540000/02/02.14
Appendix B. Installation Drawings ACT20X-HTI-SAO (Temperature/mA Converter)
Illustration 7-27:
ATEX Installation Drawing (1), (450594 Sheet 1-2, 450595 Sheet 1-2)
Terminal CH1 (11, 12, 13, 14), CH2 (21, 22, 23, 24)
Ex Input
Uo
8.7 V
Io
18.4 mA
Po
40 mW
Lo/Ro
892 µH/Ω
Ui
10 V
Ii
30 mA
Ci
30 nF
Li
820 nH
Group
Co
Lo
IIC
5 µF
100 mH
IIB
50 µF
300 mH
IIA or I
1000 µF
700 mH
1066540000/02/02.14
93
Appendix B. Installation Drawings ACT20X-HTI-SAO (Temperature/mA Converter)
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um
253 V, max. 400 Hz
Terminal (51, 52)
Supply
Voltage
19.2…31.2 V DC
Terminal (53, 54)
Status Relay
Non Hazardous
Location
Zone 2 Installation
Voltage max.
125 V AC / 110 V DC
32 V AC / 32 V DC
Current max.
0.5 A AC / 0.3 A DC
0.5 A AC / 1 A DC
Power max.
62.5 VA / 32 W
16 VA / 32 W
94
1066540000/02/02.14
Appendix B. Installation Drawings ACT20X-HTI-SAO (Temperature/mA Converter)
Illustration 7-28:
ATEX Installation Drawing (2), (450594 Sheet 1-2, 450595 Sheet 1-2)
Terminal CH1 (13), CH2 (22)
Ex Input
Uo
17.4 V
Io
18.4 mA
Po
80 mW
Lo/Ro
445 µH/Ω
Ui
10 V
Ii
30 mA
Ci
15 nF
Li
1.7 µH
Group
Co
Lo
IIC
0.3 µF
80 mH
IIB
1.6 µF
250 mH
IIA or I
8 µF
600 mH
1066540000/02/02.14
95
Appendix B. Installation Drawings ACT20X-HTI-SAO (Temperature/mA Converter)
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um
253 V, max. 400 Hz
Terminal (51, 52)
Supply
Voltage
19.2…31.2 V DC
Terminal (53, 54)
Status Relay
Non Hazardous
Location
Zone 2 Installation
Voltage max.
125 V AC / 110 V DC
32 V AC / 32 V DC
Current max.
0.5 A AC / 0.3 A DC
0.5 A AC / 1 A DC
Power max.
62.5 VA / 32 W
16 VA / 32 W
96
1066540000/02/02.14
Appendix B. Installation Drawings ACT20X-HTI-SAO (Temperature/mA Converter)
IECEx Installation Drawing
The module is available in the following variants:
Order No.
Installation Drawing
Type
8965470000
4 50594 Sheet 3-4
ACT20X-HTI-SAO-S
8965480000
4 50595 Sheet 4-6
ACT20X-2HTI-2SAO-S
DANGER
For safe installation of the Temperature and mA Converter ACT20X-(2)HTI-(2)SAO-S the
following must be observed: The module may only be installed by qualified personnel familiar
with the national and international laws, directives and standards that apply to this region.
DANGER
To prevent ignition of explosive atmospheres, disconnect power before servicing and do not
separate connectors when energized and an explosive gas mixture is present.
For installation in Zone 2, the module must be installed in an outer enclosure having an IP protection of at
least IP54 according to type of protection Ex-n or Ex-e.
In type of protection “intrinsic safety for group IIIC” the parameters for intrinsic safety for gas group IIB are
applicable.
If the sensor circuits (Terminals 11…14, 21…24) have been installed in a type of protection other than
“intrinsic safety”, the module must not be reinstalled in type of protection ”intrinsic safety”.
The module must be installed in pollution degree 2, overvoltage category II as defined in IEC 60664-1.
Do not separate connectors when energized and an explosive gas mixture is present.
The wiring of unused terminals is not allowed.
The year of manufacture can be taken from the first two digits in the serial number.
2
Wire cross-section:
AWG 26...12 / 0.13...3.31 mm
Number of wires per terminal:
1 wire or 2 wires in a common ferrule
Tightening torque per terminal, max.:
0.6 Nm
1066540000/02/02.14
97
Appendix B. Installation Drawings ACT20X-HTI-SAO (Temperature/mA Converter)
CBX200 – "WI-Manager" Software
For installation in Zone 2 / Division 2 the following must be observed:
- The CBX200 is an interface cable for configuration via PC.
- Configuration must be performed only in a safe area.
IECEx Certificate
KEM 09.0092 X
Marking
Ex nA nC IIC T4 Gc
[Ex ia Ga] IIC/IIB/IIA
[Ex ia Da] IIIC
[Ex ia Ma] I
Standards
IEC 60079-0:2011, IEC 60079-11:2011, IEC 60079-15:2010,
IEC 60079-26:2007
98
1066540000/02/02.14
Appendix B. Installation Drawings ACT20X-HTI-SAO (Temperature/mA Converter)
Illustration 7-29:
IECEx Installation Drawing (1), (450594 Sheet 3-4, 450595 Sheet 4-6)
Terminal CH1 (11, 12, 13, 14), CH2 (21, 22, 23, 24)
Ex Input
Uo
8.7 V
Io
18.4 mA
Po
40 mW
Lo/Ro
892 µH/Ω
Ui
10 V
Ii
30 mA
Ci
30 nF
Li
820 nH
Group
Co
Lo
IIC
5 µF
100 mH
IIB
50 µF
300 mH
IIA or I
1000 µF
700 mH
1066540000/02/02.14
99
Appendix B. Installation Drawings ACT20X-HTI-SAO (Temperature/mA Converter)
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um
253 V, max. 400 Hz
Terminal (51, 52)
Supply
Voltage
19.2…31.2 V DC
Terminal (53, 54)
Status Relay
Non Hazardous
Location
Zone 2 Installation
Voltage max.
125 V AC / 110 V DC
32 V AC / 32 V DC
Current max.
0.5 A AC / 0.3 A DC
0.5 A AC / 1 A DC
Power max.
62.5 VA / 32 W
16 VA / 32 W
100
1066540000/02/02.14
Appendix B. Installation Drawings ACT20X-HTI-SAO (Temperature/mA Converter)
Illustration 7-30:
IECEx Installation Drawing (2), (450594 Sheet 3-4, 450595 Sheet 4-6)
Terminal CH1 (13), CH2 (22)
Ex Input
Uo
17.4 V
Io
18.4 mA
Po
80 mW
Lo/Ro
445 µH/Ω
Ui
10 V
Ii
30 mA
Ci
15 nF
Li
1.7 µH
Group
Co
Lo
IIC
0.3 µF
80 mH
IIB
1.6 µF
250 mH
IIA or I
8 µF
600 mH
1066540000/02/02.14
101
Appendix B. Installation Drawings ACT20X-HTI-SAO (Temperature/mA Converter)
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um
253 V, max. 400 Hz
Terminal (51, 52)
Supply
Voltage
19.2…31.2 V DC
Terminal (53, 54)
Status Relay
Non Hazardous
Location
Zone 2 Installation
Voltage max.
125 V AC / 110 V DC
32 V AC / 32 V DC
Current max.
0.5 A AC / 0.3 A DC
0.5 A AC / 1 A DC
Power max.
62.5 VA / 32 W
16 VA / 32 W
102
1066540000/02/02.14
Appendix B. Installation Drawings ACT20X-HTI-SAO (Temperature/mA Converter)
FM Installation Drawing
The module is available in the following variants:
Order No.
Installation Drawing
Type
8965470000
4 50594 Sheet 5-6
ACT20X-HTI-SAO-S
8965480000
4 50595 Sheet 7-9
ACT20X-2HTI-2SAO-S
DANGER
For safe installation of the Temperature and mA Converter ACT20X-(2)HTI-(2)SAO-S the
following must be observed: The module may only be installed by qualified personnel familiar
with the national and international laws, directives and standards that apply to this region.
DANGER
To prevent ignition of explosive atmospheres, disconnect power before servicing and do not
separate connectors when energized and an explosive gas mixture is present.
WARNING
Substitution of components may impair intrinsic safety and/or suitability for Division 2 / Zone 2.
The installation and wiring must be in accordance with the Canadian Electrical Code for Canada and
National Electrical Code NFPA 70, Article 500 or 505 for installation in USA.
The module must be supplied from a Power Supply having double or reinforced insulation.
The use of stranded wires is not permitted for mains wiring except when wires are fitted with cable ends.
The module must be installed in pollution degree 2, overvoltage category II as defined in IEC 60664-1.
The module must be installed in an enclosure suitable for the environment where it is used.
For installation in Zone 2 or Division 2, the module must be installed in a suitable outer enclosure according
to the regulations in the CEC for Canada or NEC for USA.
The module is galvanically isolated and does not require grounding.
Use 60/75 °C copper conductors in the wire size AWG 26-14.
The year of manufacture can be taken from the first two digits in the serial number.
1066540000/02/02.14
103
Appendix B. Installation Drawings ACT20X-HTI-SAO (Temperature/mA Converter)
CBX200 – "WI-Manager" Software
For installation in Zone 2 / Division 2 the following must be observed:
- The CBX200 is an interface cable for configuration via PC.
- Configuration must be performed only in a safe area.
c-FM-us Certificate
3038275C / 308275
Marking
Install in CL I DIV2 GP A-D T4
Provides IS Circuits to
CL I-III DIV 1/2 GP A-G or
CL I Zn2 AEx/Ex nA nC [ia] IIC T4
Standards
Canada
Zones:
Divisions:
USA
Zones:
Divisions:
104
E60079-0, E60079-11, E60079-15
CSA 22.2-157, CSA 22.2-213
UL 60079-0, UL 60079-11, UL 60079-15
FM3600, FM3610, FM3611, FM3810
1066540000/02/02.14
Appendix B. Installation Drawings ACT20X-HTI-SAO (Temperature/mA Converter)
Illustration 7-31:
FM Installation Drawing (1), (450594 Sheet 5-6, 450595 Sheet 7-9)
Terminal CH1 (11, 12, 13, 14), CH2 (21, 22, 23, 24)
Ex Input
Uo, Vt
8.7 V
Io, It
18.4 mA
Po
40 mW
Lo/Ro
892 µH/Ω
Ui
10 V
Ii
30 mA
Ci
30 nF
Li
820 nH
Group
C o, C a
L o, L a
IIC Group A, B
5 µF
100 mH
IIB Group C, E, F
50 µF
300 mH
IIA Group D, G
1000 µF
700 mH
1066540000/02/02.14
105
Appendix B. Installation Drawings ACT20X-HTI-SAO (Temperature/mA Converter)
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um
253 V, max. 400 Hz
Terminal (51, 52)
Supply
Voltage
19.2…31.2 V DC
Terminal (53, 54)
Status Relay
Non Hazardous
Location
Zone 2 Installation
Voltage max.
125 V AC / 110 V DC
32 V AC / 32 V DC
Current max.
0.5 A AC / 0.3 A DC
0.5 A AC / 1 A DC
Power max.
62.5 VA / 32 W
16 VA / 32 W
106
1066540000/02/02.14
Appendix B. Installation Drawings ACT20X-HTI-SAO (Temperature/mA Converter)
Illustration 7-32:
FM Installation Drawing (2), (450594 Sheet 5-6, 450595 Sheet 7-9)
Terminal CH1 (13), CH2 (22)
Ex Input
Uo, Vt
17.4 V
Io, It
18.4 mA
Po
80 mW
Lo/Ro
445 µH/Ω
Ui
10 V
Ii
30 mA
Ci
15 nF
Li
1.7 µH
1066540000/02/02.14
107
Appendix B. Installation Drawings ACT20X-HTI-SAO (Temperature/mA Converter)
Group
C o, C a
L o, L a
IIC or Group A, B
0.3 µF
80 mH
IIB or Group C, E, F
1.6 µF
250 mH
IIA or Group D, G
8 µF
600 mH
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um
253 V, max. 400 Hz
Terminal (51, 52)
Supply
Voltage
19.2…31.2 V DC
Terminal (53, 54)
Status Relay
Non Hazardous
Location
Zone 2 Installation
Voltage max.
125 V AC / 110 V DC
32 V AC / 32 V DC
Current max.
0.5 A AC / 0.3 A DC
0.5 A AC / 1 A DC
Power max.
62.5 VA / 32 W
16 VA / 32 W
108
1066540000/02/02.14
Appendix C. Installation Drawings ACT20X-SDI-HDO (Solenoid/Alarm Driver)
Appendix C. Installation Drawings ACT20X-SDI-HDO (Solenoid/Alarm Driver)
ATEX Installation Drawing
The module is available in the following variants:
Order No.
Installation Drawing
Type
8965400000
4 51478 Sheet 1-2
ACT20X-SDI-HDO-L-S
8965410000
4 51478 Sheet 1-2
ACT20X-SDI-HDO-H-S
8965420000
4 51478 Sheet 1-2
ACT20X-2SDI-2HDO-S
DANGER
For safe installation of ACT20X-(2)SDI-(2)HDO-(L/H)-S the following must be observed: The
module may only be installed by qualified personnel familiar with the national and international
laws, directives and standards that apply to this region.
DANGER
To prevent ignition of explosive atmospheres, disconnect power before servicing and do not
separate connectors when energized and an explosive gas mixture is present.
For installation in Zone 2, the module must be installed in an outer enclosure having an IP protection of at
least IP54 according to type of protection Ex-n or Ex-e.
In type of protection “intrinsic safety for group IIIC” the parameters for intrinsic safety for gas group IIB are
applicable.
If the sensor circuits have been installed in a type of protection other than “intrinsic safety”, the module must
not be re-installed in type of protection ”intrinsic safety”.
The module must be installed in pollution degree 2, overvoltage category II as defined in EN 60664-1.
Do not separate connectors when energized and an explosive gas mixture is present.
The wiring of unused terminals is not allowed.
The year of manufacture can be taken from the first two digits in the serial number.
2
Wire cross-section:
AWG 26...12 / 0.13...3.31 mm
Number of wires per terminal:
1 wire or 2 wires in a common ferrule
Tightening torque per terminal, max.:
0.6 Nm
1066540000/02/02.14
109
Appendix C. Installation Drawings ACT20X-SDI-HDO (Solenoid/Alarm Driver)
CBX200 – "WI-Manager" Software
For installation in Zone 2 / Division 2 the following must be observed:
- The CBX200 is an interface cable for configuration via PC.
- Configuration must be performed only in a safe area.
ATEX Certificate
KEMA 10ATEX 0019 X
Marking
II (1) G [Ex ia Ga] IIC/IIB/IIA
II 3 G Ex nA nC IIC T4 Gc
II (1) D [Ex ia Da] IIIC
I (M1) [Ex ia Ma] I
Standards
EN 60079-0:2012, EN 60079-11:2012, EN 60079-15:2010,
EN 60079-26:2007
110
1066540000/02/02.14
Appendix C. Installation Drawings ACT20X-SDI-HDO (Solenoid/Alarm Driver)
Illustration 7-33:
ATEX Installation Drawing, (451478 Sheet 1-2)
Terminal CH1 (41, 42) and CH2 (43, 44)
Input
Voltage max
28 V DC
Trigger: NPN
Low < 2 V, High > 4 V
Trigger: PNP
Low < 8 V, High > 10 V
Terminal (11–12, 21–22)
Ex Output
8965400000 (ACT20X-SDI-HDO-L-S)
8965420000 (ACT20X-2SDI-2HDO-S)
Group
Co
Lo
Lo/Ro
Uo
28 V
IIC
80 nF
4.2 mH
54 µH/Ω
Io
93 mA
IIB
640 nF
16.8 mH
218 µH/Ω
Po
0.65 W
IIA
2.1 µF
32.6 mH
436 µH/Ω
I
3.76 µF
47 mH
717 µH/Ω
1066540000/02/02.14
111
Appendix C. Installation Drawings ACT20X-SDI-HDO (Solenoid/Alarm Driver)
Terminal (11–13, 21–23)
Ex Output
8965400000 (ACT20X-SDI-HDO-L-S)
8965420000 (ACT20X-2SDI-2HDO-S)
Group
Co
Lo
Lo/Ro
Uo
28 V
IIC
80 nF
3.5 mH
50 µH/Ω
Io
100 mA
IIB
640 nF
14.2 mH
201 µH/Ω
Po
0.70 W
IIA
2.1 µF
27.6 mH
402 µH/Ω
I
3.76 µF
46 mH
667 µH/Ω
Ex Output
8965400000 (ACT20X-SDI-HDO-L-S)
8965420000 (ACT20X-2SDI-2HDO-S)
Group
Co
Lo
Lo/Ro
Uo
28 V
IIC
80 nF
2.9 mH
46 µH/Ω
Io
110 mA
IIB
640 nF
11.8 mH
184 µH/Ω
Po
0.77 W
IIA
2.1 µF
22.8 mH
369 µH/Ω
I
3.76 µF
38 mH
607 µH/Ω
Ex Output
8965410000 (ACT20X-SDI-HDO-H-S
Group
Co
Lo
Lo/Ro
Uo
28 V
IIC
80 nF
2.69 mH
44 µH/Ω
Io
115 mA
IIB
640 nF
10.8 mH
176 µH/Ω
Po
0.81 W
IIA
2.1 µF
20.8 mH
353 µH/Ω
I
3.76 µF
33 mH
578 µH/Ω
Ex Output
8965410000 (ACT20X-SDI-HDO-H-S)
Group
Co
Lo
Lo/Ro
Uo
28 V
IIC
–
–
–
Io
125 mA
IIB
640 nF
9.1 mH
163 µH/Ω
Po
0.88 W
IIA
2.1 µF
17.6 mH
327 µH/Ω
I
3.76 µF
28 mH
533 µH/Ω
Terminal (11–14, 21–24)
Terminal (11–12)
Terminal (11–13)
112
1066540000/02/02.14
Appendix C. Installation Drawings ACT20X-SDI-HDO (Solenoid/Alarm Driver)
Terminal (11–14)
Ex Output
8965410000 (ACT20X-SDI-HDO-H-S)
Group
Co
Lo
Lo/Ro
Uo
28 V
IIC
80 nF
–
–
Io
135 mA
IIB
640 nF
7.8 mH
150 µH/Ω
Po
0.95 W
IIA
2.1 µF
15.1 mH
301 µH/Ω
I
3.76 µF
24 mH
493 µH/Ω
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Input
Um
253 V, max. 400 Hz
Terminal (51, 52)
Supply
Voltage
19.2…31.2 V DC
Power max
3.5 W
Terminal (53, 54)
Status Relay
Non Hazardous
Location
Zone 2 Installation
Voltage max.
125 V AC / 110 V DC
32 V AC / 32 V DC
Current max.
0.5 A AC / 0.3 A DC
0.5 A AC / 1 A DC
Power max.
62.5 VA / 32 W
16 VA / 32 W
1066540000/02/02.14
113
Appendix C. Installation Drawings ACT20X-SDI-HDO (Solenoid/Alarm Driver)
114
1066540000/02/02.14
Appendix C. Installation Drawings ACT20X-SDI-HDO (Solenoid/Alarm Driver)
IECEx Installation Drawing
The module is available in the following variants:
Order No.
Installation Drawing
Type
8965400000
4 51478 Sheet 3-4
ACT20X-SDI-HDO-L-S
8965410000
4 51478 Sheet 3-4
ACT20X-SDI-HDO-H-S
8965420000
4 51478 Sheet 3-4
ACT20X-2SDI-2HDO-S
DANGER
For safe installation of ACT20X-(2)SDI-(2)HDO-(L/H)-S the following must be observed: The
module may only be installed by qualified personnel familiar with the national and international
laws, directives and standards that apply to this region.
DANGER
To prevent ignition of explosive atmospheres, disconnect power before servicing and do not
separate connectors when energized and an explosive gas mixture is present.
For installation in Zone 2, the module must be installed in an outer enclosure having an IP protection of at
least IP54 according to type of protection Ex-n or Ex-e.
In type of protection “intrinsic safety for group IIIC” the parameters for intrinsic safety for gas group IIB are
applicable.
If the sensor circuits have been installed in a type of protection other than “intrinsic safety”, the module must
not be re-installed in type of protection ”intrinsic safety”.
The module must be installed in pollution degree 2, overvoltage category II as defined in IEC 60664-1.
Do not separate connectors when energized and an explosive gas mixture is present.
The wiring of unused terminals is not allowed.
The year of manufacture can be taken from the first two digits in the serial number.
2
Wire cross-section:
AWG 26...12 / 0.13...3.31 mm
Number of wires per terminal:
1 wire or 2 wires in a common ferrule
Tightening torque per terminal, max.:
0.6 Nm
1066540000/02/02.14
115
Appendix C. Installation Drawings ACT20X-SDI-HDO (Solenoid/Alarm Driver)
CBX200 – "WI-Manager" Software
For installation in Zone 2 / Division 2 the following must be observed:
- The CBX200 is an interface cable for configuration via PC.
- Configuration must be performed only in a safe area.
IECEx Certificate
KEM 09.0071 X
Marking
Ex nA nC IIC T4 Gc
[Ex ia Ga] IIC/IIB/IIA
[Ex ia Da] IIIC
[Ex ia Ma] I
Standards
IEC 60079-0:2011, IEC 60079-11:2011, IEC 60079-15:2010,
IEC 60079-26:2007
116
1066540000/02/02.14
Appendix C. Installation Drawings ACT20X-SDI-HDO (Solenoid/Alarm Driver)
Illustration 7-34:
IECEx Installation Drawing, (451478 Sheet 3-4)
Terminal CH1 (41, 42) and CH2 (43, 44)
Input
Voltage max
28 V DC
Trigger: NPN
Low < 2 V, High > 4 V
Trigger: PNP
Low < 8 V, High > 10 V
Terminal (11–12, 21–22)
Ex Output
8965400000 (ACT20X-SDI-HDO-L-S)
8965420000 (ACT20X-2SDI-2HDO-S)
Group
Co
Lo
Lo/Ro
Uo
28 V
IIC
80 nF
4.2 mH
54 µH/Ω
Io
93 mA
IIB
640 nF
16.8 mH
218 µH/Ω
Po
0.65 W
IIA
2.1 µF
32.6 mH
436 µH/Ω
I
3.76 µF
32.6 mH
436 µH/Ω
1066540000/02/02.14
117
Appendix C. Installation Drawings ACT20X-SDI-HDO (Solenoid/Alarm Driver)
Terminal (11–13, 21–23)
Ex Output
8965400000 (ACT20X-SDI-HDO-L-S)
8965420000 (ACT20X-2SDI-2HDO-S)
Group
Co
Lo
Lo/Ro
Uo
28 V
IIC
80 nF
3.5 mH
50 µH/Ω
Io
100 mA
IIB
640 nF
14.2 mH
201 µH/Ω
Po
0.70 W
IIA
2.1 µF
27.6 mH
402 µH/Ω
I
3.76 µF
46 mH
667 µH/Ω
Ex Output
8965400000 (ACT20X-SDI-HDO-L-S)
8965420000 (ACT20X-2SDI-2HDO-S)
Group
Co
Lo
Lo/Ro
Uo
28 V
IIC
80 nF
2.9 mH
46 µH/Ω
Io
100 mA
IIB
640 nF
12.8 mH
184 µH/Ω
Po
0.70 W
IIA
2.1 µF
22.8 mH
369 µH/Ω
I
3.76 µF
38 mH
607 µH/Ω
Ex Output
8965410000 (ACT20X-SDI-HDO-H-S
Group
Co
Lo
Lo/Ro
Uo
28 V
IIC
80 nF
2.69 mH
44 µH/Ω
Io
115 mA
IIB
640 nF
10.8 mH
176 µH/Ω
Po
0.81 W
IIA
2.1 µF
20.8 mH
353 µH/Ω
I
3.76 µF
33 mH
578 µH/Ω
Ex Output
8965410000 (ACT20X-SDI-HDO-H-S)
Group
Co
Lo
Lo/Ro
Uo
28 V
IIC
–
–
–
Io
125 mA
IIB
640 nF
9.1 mH
162 µH/Ω
Po
0.88 W
IIA
2.1 µF
17.6 mH
325 µH/Ω
I
3.76 µF
28 mH
533 µH/Ω
Terminal (11–14, 21–24)
Terminal (11–12)
Terminal (11–13)
118
1066540000/02/02.14
Appendix C. Installation Drawings ACT20X-SDI-HDO (Solenoid/Alarm Driver)
Terminal (11–14)
Ex Output
8965410000 (ACT20X-SDI-HDO-H-S)
Group
Co
Lo
Lo/Ro
Uo
28 V
IIC
–
–
–
Io
135 mA
IIB
640 nF
7.8 mH
150 µH/Ω
Po
0.95 W
IIA
2.1 µF
15.1 mH
301 µH/Ω
I
3.76 µF
24 mH
493 µH/Ω
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Input
Um
253 V, max. 400 Hz
Terminal (51, 52)
Supply
Voltage
19.2…31.2 V DC
Power max
3.5 W
Terminal (53, 54)
Status Relay
Non Hazardous
Location
Zone 2 Installation
Voltage max.
125 V AC / 110 V DC
32 V AC / 32 V DC
Current max.
0.5 A AC / 0.3 A DC
0.5 A AC / 1 A DC
Power max.
62.5 VA / 32 W
16 VA / 32 W
1066540000/02/02.14
119
Appendix C. Installation Drawings ACT20X-SDI-HDO (Solenoid/Alarm Driver)
120
1066540000/02/02.14
Appendix C. Installation Drawings ACT20X-SDI-HDO (Solenoid/Alarm Driver)
FM Installation Drawing
The module is available in the following variants:
Order No.
Installation Drawing
Type
8965400000
4 51478 Sheet 5-6
ACT20X-SDI-HDO-L-S
8965410000
4 51478 Sheet 5-6
ACT20X-SDI-HDO-H-S
8965420000
4 51478 Sheet 5-6
ACT20X-2SDI-2HDO-S
DANGER
For safe installation of ACT20X-(2)SDI-(2)HDO-(L/H)-S the following must be observed: The
module may only be installed by qualified personnel familiar with the national and international
laws, directives and standards that apply to this region.
DANGER
To prevent ignition of explosive atmospheres, disconnect power before servicing and do not
separate connectors when energized and an explosive gas mixture is present.
WARNING
Substitution of components may impair intrinsic safety and/or suitability for Division 2 / Zone 2.
The installation and wiring shall be in accordance with the Canadian Electrical Code for Canada and
National Electrical Code NFPA 70, Article 500 or 505 for installation in USA.
The module must be supplied from a Power Supply having double or reinforced insulation.
The use of stranded wires is not permitted for mains wiring except when wires are fitted with cable ends.
The module must be installed in pollution degree 2, overvoltage category II as defined in IEC 60664-1.
The module must be installed in an enclosure suitable for the environment where it is used.
For installation in Zone 2 or Division 2, the module must be installed in a suitable outer enclosure according
to the regulations in the CEC for Canada or NEC for USA.
The module is galvanically isolated and does not require grounding.
Use 60/75 °C copper conductors in the wire size AWG 26-14.
The year of manufacture can be taken from the first two digits in the serial number.
1066540000/02/02.14
121
Appendix C. Installation Drawings ACT20X-SDI-HDO (Solenoid/Alarm Driver)
CBX200 – "WI-Manager" Software
For installation in Zone 2 / Division 2 the following must be observed:
- The CBX200 is an interface cable for configuration via PC.
- Configuration must be performed only in a safe area.
c-FM-us Certificate
3038275C / 3038275
Marking
Install in CL I DIV2 GP A-D T4
Provides IS Circuits to
CL I-III DIV 1/2 GP A-G or
CL I Zn2 AEx/Ex nA nC [ia] IIC T4
Standards
Canada
Zones:
Divisions:
USA
Zones:
Divisions:
122
E60079-0, E60079-11, E60079-15
CSA 22.2-157, CSA 22.2-213
UL 60079-0, UL 60079-11, UL 60079-15
FM3600, FM3610, FM3611, FM3810
1066540000/02/02.14
Appendix C. Installation Drawings ACT20X-SDI-HDO (Solenoid/Alarm Driver)
Illustration 7-35:
FM Installation Drawing, (451478 Sheet 5-6)
Terminal CH1 (41, 42) and CH2 (43, 44)
Input
Voltage max
28 V DC
Trigger: NPN
Low < 2 V, High > 4 V
Trigger: PNP
Low < 8 V, High > 10 V
Terminal (11–12, 21–22)
Ex Output
8965400000 (ACT20X-SDI-HDO-L-S)
8965420000 (ACT20X-2SDI-2HDO-S)
Group
Co
Lo
Lo/Ro
Uo
28 V
IIC
80 nF
4.2 mH
54 µH/Ω
Io
93 mA
IIB
640 nF
16.8 mH
218 µH/Ω
Po
0.65 W
IIA
2.1 µF
32.6 mH
436 µH/Ω
1066540000/02/02.14
123
Appendix C. Installation Drawings ACT20X-SDI-HDO (Solenoid/Alarm Driver)
Terminal (11–13, 21–23)
Ex Output
8965400000 (ACT20X-SDI-HDO-L-S)
8965420000 (ACT20X-2SDI-2HDO-S)
Group
Co
Lo
Lo/Ro
Uo
28 V
IIC
80 nF
3.5 mH
50 µH/Ω
Io
100 mA
IIB
640 nF
14.2 mH
201 µH/Ω
Po
0.70 W
IIA
2.1 µF
27.6 mH
402 µH/Ω
Ex Output
8965400000 (ACT20X-SDI-HDO-L-S)
8965420000 (ACT20X-2SDI-2HDO-S)
Group
Co
Lo
Lo/Ro
Uo
28 V
IIC
80 nF
2.9 mH
46 µH/Ω
Io
100 mA
IIB
640 nF
12.8 mH
184 µH/Ω
Po
0.70 W
IIA
2.1 µF
22.8 mH
369 µH/Ω
Ex Output
8965410000 (ACT20X-SDI-HDO-H-S
Group
Co
Lo
Lo/Ro
Uo
28 V
IIC
80 nF
2.69 mH
44 µH/Ω
Io
115 mA
IIB
640 nF
10.8 mH
176 µH/Ω
Po
0.81 W
IIA
2.1 µF
20.8 mH
353 µH/Ω
Ex Output
8965410000 (ACT20X-SDI-HDO-H-S)
Group
Co
Lo
Lo/Ro
Uo
28 V
IIC
–
–
–
Io
125 mA
IIB
640 nF
9.1 mH
162 µH/Ω
Po
0.88 W
IIA
2.1 µF
17.6 mH
325 µH/Ω
Ex Output
8965410000 (ACT20X-SDI-HDO-H-S)
Group
Co
Lo
Lo/Ro
Uo
28 V
IIC
–
–
–
Io
135 mA
IIB
640 nF
7.8 mH
150 µH/Ω
Po
0.95 W
IIA
2.1 µF
15.1 mH
301 µH/Ω
Terminal (11–14, 21–24)
Terminal (11–12)
Terminal (11–13)
Terminal (11–14)
124
1066540000/02/02.14
Appendix C. Installation Drawings ACT20X-SDI-HDO (Solenoid/Alarm Driver)
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Input
Um
253 V, max. 400 Hz
Terminal (51, 52)
Supply
Voltage
19.2…31.2 V DC
Power max
3.5 W
Terminal (53, 54)
Status Relay
Non Hazardous
Location
Zone 2 Installation
Voltage max.
125 V AC / 110 V DC
32 V AC / 32 V DC
Current max.
0.5 A AC / 0.3 A DC
0.5 A AC / 1 A DC
Power max.
62.5 VA / 32 W
16 VA / 32 W
1066540000/02/02.14
125
Appendix C. Installation Drawings ACT20X-SDI-HDO (Solenoid/Alarm Driver)
126
1066540000/02/02.14
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
ATEX Installation Drawing
The module is available in the following variants:
Order No.
Installation Drawing
Type
8965490000
4 51481 Sheet 1-4
ACT20X-HUI-SAO-S
DANGER
For safe installation of the Universal Converter ACT20X-HUI-SAO-S the following must be
observed: The module may only be installed by qualified personnel familiar with the national and
international laws, directives and standards that apply to this region.
DANGER
To prevent ignition of explosive atmospheres, disconnect power before servicing and do not
separate connectors when energized and an explosive gas mixture is present.
For installation in Zone 2, the module must be installed in an outer enclosure in type of protection Ex-n or
Ex-e, providing an IP protection of at least IP54. Cable entry devices and blanking elements shall fulfil the
same requirements.
In type of protection “intrinsic safety for group IIIC” the parameters for intrinsic safety for gas group IIB are
applicable.
The module must be installed in pollution degree 2, overvoltage category II as defined in EN 60664-1.
Do not separate connectors when energized and an explosive gas mixture is present.
The wiring of unused terminals is not allowed.
The year of manufacture can be taken from the first two digits in the serial number.
2
Wire cross-section:
AWG 26...12 / 0.13...3.31 mm
Number of wires per terminal:
1 wire or 2 wires in a common ferrule
Tightening torque per terminal, max.:
0.6 Nm
1066540000/02/02.14
127
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
CBX200 – "WI-Manager" Software
For installation in Zone 2 / Division 2 the following must be observed:
- The CBX200 is an interface cable for configuration via PC.
- Configuration must be performed only in a safe area.
ATEX Certificate
KEMA 10ATEX 0071 X
Marking
II (1) G [Ex ia Ga] IIC/IIB/IIA
II 3 G Ex nA nC IIC T4 Gc
II (1) D [Ex ia Da] IIIC
I (M1) [Ex ia Ma] I
Standards
EN 60079-0:2012, EN 60079-11:2012, EN 60079-15:2010,
EN 60079-26:2007
128
1066540000/02/02.14
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
Illustration 7-36:
ATEX Installation Drawing (1), (451481 Sheet 1-4)
Terminal (21, 22) and (21, 23)
Input
Ui
30 V
Ii
120 mA
Pi
900 mW
Ci
3 nF
Li
1 µH
1066540000/02/02.14
129
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
Terminal (21–24, 22–24)
Input
Group
Co
Lo
Lo/Ro
Uo
28 V
IIC
80 nF
4 mH
54 µH/Ω
Io
93 mA
IIB
640 nF
16 mH
218 µH/Ω
Po
0.65 W
IIA or I
2.1 µF
32 mH
436 µH/Ω
Group
Co
Lo
Lo/Ro
Terminal (21–23)
Input
Uo
28 V
IIC
80 nF
1000 mH
4 mH/Ω
Io
1.1 mA
IIB
640 nF
1000 mH
17 mH/Ω
Po
8 mW
IIA or I
2.1 µF
1000 mH
35 mH/Ω
Group
Co
Lo
Lo/Ro
Terminal (21–22)
Input
Uo
8.3 V
IIC
7 µF
1000 mH
100 mH/Ω
Io
0.2 mA
IIB
73 µF
1000 mH
400 mH/Ω
Po
0.4 mW
IIA or I
1000 µF
1000 mH
800 mH/Ω
Group
Co
Lo
Lo/Ro
Terminal (11, 12, 13, 14)
Input
Uo
8.3 V
IIC
7 µF
207 mH
1 mH/Ω
Io
13.1 mA
IIB
73 µF
828 mH
5 mH/Ω
Po
27.3 mW
IIA or I
1000 µF
1000 mH
10 mH/Ω
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um
253 V, max. 400 Hz
Terminal (51, 52)
Supply
Voltage
19.2…31.2 V DC
Terminal (41, 42)
Output
Current
130
0/4…20 mA
1066540000/02/02.14
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
Terminal (43, 44)
Relay Output
Non Hazardous
Location
Zone 2 Installation
Voltage max.
250 V AC / 30 V DC
32 V AC / 30 V DC
Current max.
2 A AC / 2 A DC
2 A AC / 2 A DC
Power max.
500 VA / 60 W
64 VA / 60 W
Status Relay
Non Hazardous
Location
Zone 2 Installation
Voltage max.
125 V AC / 110 V DC
32 V AC / 32 V DC
Current max.
0.5 A AC / 0.3 A DC
0.5 A AC / 1 A DC
Power max.
62.5 VA / 32 W
16 VA / 32 W
Terminal (53, 54)
1066540000/02/02.14
131
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
Illustration 7-37:
ATEX Installation Drawing (2), (451481 Sheet 1-4)
Terminal (24-22)
Input
Ui
30 V
Ii
120 mA
Pi
900 mW
Ci
3 nF
Li
2 µH
132
1066540000/02/02.14
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
Terminal (24–22, 22–21)
Input
Group
Co
Lo
Lo/Ro
Uo
28 V
IIC
80 nF
4.2 mH
54 µH/Ω
Io
93 mA
IIB
640 nF
16 mH
218 µH/Ω
Po
0.65 W
IIA or I
2.1 µF
32 mH
436 µH/Ω
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um
253 V, max. 400 Hz
Terminal (51, 52)
Supply
Voltage
19.2…31.2 V DC
Terminal (43, 44)
Relay Output
Non Hazardous
Location
Zone 2 Installation
Voltage max.
250 V AC / 30 V DC
32 V AC / 30 V DC
Current max.
2 A AC / 2 A DC
2 A AC / 2 A DC
Power max.
500 VA / 60 W
64 VA / 60 W
Status Relay
Non Hazardous
Location
Zone 2 Installation
Voltage max.
125 V AC / 110 V DC
32 V AC / 32 V DC
Current max.
0.5 A AC / 0.3 A DC
0.5 A AC / 1 A DC
Power max.
62.5 VA / 32 W
16 VA / 32 W
Terminal (53, 54)
1066540000/02/02.14
133
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
Illustration 7-38:
ATEX Installation Drawing (3), (451481 Sheet 1-4)
Terminal (21-22)
Input
Ui
30 V
Ii
120 mA
Pi
900 mW
Ci
3 nF
Li
1 µH
134
1066540000/02/02.14
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
Terminal (22–21, 21–22)
Input
Group
Co
Lo
Lo/Ro
Uo
16.6 V
IIC
0.4 µF
1000 mH
25 mH/Ω
Io
0.2 mA
IIB
2.3 µF
1000 mH
100 mH/Ω
Po
0.8 mW
IIA or I
9.5 µF
1000 mH
200 mH/Ω
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um
253 V, max. 400 Hz
Terminal (51, 52)
Supply
Voltage
19.2…31.2 V DC
Terminal (43, 44)
Relay Output
Non Hazardous
Location
Zone 2 Installation
Voltage max.
250 V AC / 30 V DC
32 V AC / 30 V DC
Current max.
2 A AC / 2 A DC
2 A AC / 2 A DC
Power max.
500 VA / 60 W
64 VA / 60 W
Status Relay
Non Hazardous
Location
Zone 2 Installation
Voltage max.
125 V AC / 110 V DC
32 V AC / 32 V DC
Current max.
0.5 A AC / 0.3 A DC
0.5 A AC / 1 A DC
Power max.
62.5 VA / 32 W
16 VA / 32 W
Terminal (53, 54)
1066540000/02/02.14
135
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
136
1066540000/02/02.14
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
IECEx Installation Drawing
The module is available in the following variants:
Order No.
Installation Drawing
Type
8965490000
4 51481 Sheet 5-8
ACT20X-HUI-SAO-S
DANGER
For safe installation of the Universal Converter ACT20X-HUI-SAO-S the following must be
observed: The module may only be installed by qualified personnel familiar with the national and
international laws, directives and standards that apply to this region.
DANGER
To prevent ignition of explosive atmospheres, disconnect power before servicing and do not
separate connectors when energized and an explosive gas mixture is present.
For installation in Zone 2, the module must be installed in an outer enclosure having an IP protection of at
least IP54 according to type of protection Ex-n or Ex-e.
In type of protection “intrinsic safety for group IIIC” the parameters for intrinsic safety for gas group IIB are
applicable.
The module must be installed in pollution degree 2, overvoltage category II as defined in IEC 60664-1.
Do not separate connectors when energized and an explosive gas mixture is present.
The wiring of unused terminals is not allowed.
The year of manufacture can be taken from the first two digits in the serial number.
For group I (mining), the parameters for group IIA apply.
2
Wire cross-section:
AWG 26...12 / 0.13...3.31 mm
Number of wires per terminal:
1 wire or 2 wires in a common ferrule
Tightening torque per terminal, max.:
0.6 Nm
1066540000/02/02.14
137
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
CBX200 – "WI-Manager" Software
For installation in Zone 2 / Division 2 the following must be observed:
- The CBX200 is an interface cable for configuration via PC.
- Configuration must be performed only in a safe area.
IECEx Certificate
KEM 10.0034 X
Marking
Ex nA nC IIC T4 Gc
[Ex ia Ga] IIC/IIB/IIA
[Ex ia Da] IIIC
[Ex ia Ma] I
Standards
IEC 60079-0:2011, IEC 60079-11:2011, IEC 60079-15:2010,
IEC 60079-26:2007
138
1066540000/02/02.14
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
Illustration 7-39:
IECEx Installation Drawing (1), (451481 Sheet 5-8)
Terminal (21, 22) and (21, 23)
Input
Ui
30 V
Ii
120 mA
Pi
900 mW
Ci
3 nF
Li
1 µH
1066540000/02/02.14
139
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
Terminal (21–24, 22–24)
Input
Group
Co
Lo
Lo/Ro
Uo
28 V
IIC
80 nF
4 mH
54 µH/Ω
Io
93 mA
IIB
640 nF
16 mH
218 µH/Ω
Po
0.65 W
IIA or I
2.1 µF
32 mH
436 µH/Ω
Group
Co
Lo
Lo/Ro
Terminal (21–23)
Input
Uo
28 V
IIC
80 nF
1000 mH
4 mH/Ω
Io
1.1 mA
IIB
640 nF
1000 mH
17 mH/Ω
Po
8 mW
IIA or I
2.1 µF
1000 mH
35 mH/Ω
Group
Co
Lo
Lo/Ro
Terminal (21–22)
Input
Uo
8.3 V
IIC
7 µF
1000 mH
100 mH/Ω
Io
0.2 mA
IIB
73 µF
1000 mH
400 mH/Ω
Po
0.4 mW
IIA or I
1000 µF
1000 mH
800 mH/Ω
Group
Co
Lo
Lo/Ro
Terminal (11, 12, 13, 14)
Input
Uo
8.3 V
IIC
7 µF
207 mH
1 mH/Ω
Io
13.1 mA
IIB
73 µF
828 mH
5 mH/Ω
Po
27.3 mW
IIA or I
1000 µF
1000 mH
10 mH/Ω
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um
253 V, max. 400 Hz
Terminal (51, 52)
Supply
Voltage
19.2…31.2 V DC
Terminal (41, 42)
Output
Current
140
0/4…20 mA
1066540000/02/02.14
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
Terminal (43, 44)
Relay Output
Non Hazardous
Location
Zone 2 Installation
Voltage max.
250 V AC / 30 V DC
32 V AC / 30 V DC
Current max.
2 A AC / 2 A DC
2 A AC / 2 A DC
Power max.
500 VA / 60 W
64 VA / 60 W
Status Relay
Non Hazardous
Location
Zone 2 Installation
Voltage max.
125 V AC / 110 V DC
32 V AC / 32 V DC
Current max.
0.5 A AC / 0.3 A DC
0.5 A AC / 1 A DC
Power max.
62.5 VA / 32 W
16 VA / 32 W
Terminal (53, 54)
1066540000/02/02.14
141
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
Illustration 7-40:
IECEx Installation Drawing (2), (451481 Sheet 5-8)
Terminal (24-22)
Input
Ui
30 V
Ii
120 mA
Pi
900 mW
Ci
3 nF
Li
2 µH
142
1066540000/02/02.14
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
Terminal (24–22, 22–21)
Input
Group
Co
Lo
Lo/Ro
Uo
28 V
IIC
80 nF
4.2 mH
54 µH/Ω
Io
93 mA
IIB
640 nF
16 mH
218 µH/Ω
Po
0.65 W
IIA or I
2.1 µF
32 mH
436 µH/Ω
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um
253 V, max. 400 Hz
Terminal (51, 52)
Supply
Voltage
19.2…31.2 V DC
Terminal (43, 44)
Relay Output
Non Hazardous
Location
Zone 2 Installation
Voltage max.
250 V AC / 30 V DC
32 V AC / 30 V DC
Current max.
2 A AC / 2 A DC
2 A AC / 2 A DC
Power max.
500 VA / 60 W
64 VA / 60 W
Status Relay
Non Hazardous
Location
Zone 2 Installation
Voltage max.
125 V AC / 110 V DC
32 V AC / 32 V DC
Current max.
0.5 A AC / 0.3 A DC
0.5 A AC / 1 A DC
Power max.
62.5 VA / 32 W
16 VA / 32 W
Terminal (53, 54)
1066540000/02/02.14
143
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
Illustration 7-41:
IECEx Installation Drawing (3), (451481 Sheet 5-8)
Terminal (21-22)
Input
Ui
30 V
Ii
120 mA
Pi
900 mW
Ci
3 nF
Li
2 µH
144
1066540000/02/02.14
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
Terminal (22–21, 21–22)
Input
Group
Co
Lo
Lo/Ro
Uo
16.6 V
IIC
0.4 µF
1000 mH
25 mH/Ω
Io
0.2 mA
IIB
2.3 µF
1000 mH
100 mH/Ω
Po
0.8 mW
IIA or I
9.5 µF
1000 mH
200 mH/Ω
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um
253 V, max. 400 Hz
Terminal (51, 52)
Supply
Voltage
19.2…31.2 V DC
Terminal (43, 44)
Relay Output
Non Hazardous
Location
Zone 2 Installation
Voltage max.
250 V AC / 30 V DC
32 V AC / 30 V DC
Current max.
2 A AC / 2 A DC
2 A AC / 2 A DC
Power max.
500 VA / 60 W
64 VA / 60 W
Status Relay
Non Hazardous
Location
Zone 2 Installation
Voltage max.
125 V AC / 110 V DC
32 V AC / 32 V DC
Current max.
0.5 A AC / 0.3 A DC
0.5 A AC / 1 A DC
Power max.
62.5 VA / 32 W
16 VA / 32 W
Terminal (53, 54)
1066540000/02/02.14
145
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
146
1066540000/02/02.14
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
FM Installation Drawing
The module is available in the following variants:
Order No.
Installation Drawing
Type
8965490000
4 51481 Sheet 9-12
ACT20X-HUI-SAO-S
DANGER
For safe installation of the Universal Converter ACT20X-HUI-SAO-S the following must be
observed: The module may only be installed by qualified personnel familiar with the national and
international laws, directives and standards that apply to this region.
DANGER
To prevent ignition of explosive atmospheres, disconnect power before servicing and do not
separate connectors when energized and an explosive gas mixture is present.
WARNING
Substitution of components may impair intrinsic safety and/or suitability for Division 2 / Zone 2.
The installation and wiring must be in accordance with the Canadian Electrical Code for Canada and
National Electrical Code NFPA 70, Article 500 or 505 for installation in USA.
The module must be installed in pollution degree 2, overvoltage category II as defined in IEC 60664-1.
For installation in Zone 2 or Division 2, the module must be installed in a suitable outer enclosure having an
IP protection of at least IP54.
The module is galvanically isolated and does not require grounding.
Use 60/75 °C copper conductors in the wire size AWG 26-14.
In type of protection “intrinsic safety for group IIIC” the parameters for intrinsic safety for gas group IIB are
applicable.
The year of manufacture can be taken from the first two digits in the serial number.
1066540000/02/02.14
147
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
CBX200 – "WI-Manager" Software
For installation in Zone 2 / Division 2 the following must be observed:
- The CBX200 is an interface cable for configuration via PC.
- Configuration must be performed only in a safe area.
c-FM-us Certificate
3038275C / 3038275
Marking
Install in CL I DIV2 GP A-D T4
Provides IS Circuits to
CL I-III DIV 1/2 GP A-G or
CL I Zn2 AEx/Ex nA nC [ia] IIC T4
Standards
Canada
Zones:
Divisions:
USA
Zones:
Divisions:
148
E60079-0, E60079-11, E60079-15
CSA 22.2-157, CSA 22.2-213
UL 60079-0, UL 60079-11, UL 60079-15
FM3600, FM3610, FM3611, FM3810
1066540000/02/02.14
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
Illustration 7-42:
FM Installation Drawing (1), (451481 Sheet 9-12)
Terminal (21-22) and (21-23)
Input
Ui, Vmax
30 V
Ii, Imax
120 mA
Pi
900 mW
Ci
3 nF
Li
1 µH
1066540000/02/02.14
149
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
Terminal (21–24, 22–24)
Input
Group
Co
Lo
Lo/Ro
Uo, VOC
28 V
IIC or A, B
80 nF
4 mH
54 µH/Ω
Io, ISC
93 mA
IIB or C, E, F
640 nF
16 mH
218 µH/Ω
Po
0.65 W
IIA or D, G
2.1 µF
32 mH
436 µH/Ω
Group
Co
Lo
Lo/Ro
Terminal (21–23)
Input
Uo, VOC
28 V
IIC or A, B
80 nF
1000 mH
4 mH/Ω
Io, ISC
1.1 mA
IIB or C, E, F
640 nF
1000 mH
17 mH/Ω
Po
8 mW
IIA or D, G
2.1 µF
1000 mH
35 mH/Ω
Group
Co
Lo
Lo/Ro
Terminal (21–22)
Input
Uo, VOC
8.3 V
IIC or A, B
7 µF
1000 mH
100 mH/Ω
Io, ISC
0.2 mA
IIB or C, E, F
73 µF
1000 mH
400 mH/Ω
Po
0.4 mW
IIA or D, G
1000 µF
1000 mH
800 mH/Ω
Group
Co
Lo
Lo/Ro
Terminal (11, 12, 13, 14)
Input
Uo, VOC
8.3 V
IIC or A, B
7 µF
207 mH
1 mH/Ω
Io, ISC
13.1 mA
IIB or C, E, F
73 µF
828 mH
5 mH/Ω
Po
27.3 mW
IIA or D, G
1000 µF
1000 mH
10 mH/Ω
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um
253 V, max. 400 Hz
Terminal (51, 52)
Supply
Voltage
19.2…31.2 V DC
Terminal (41, 42)
Output
Current
150
0/4…20 mA
1066540000/02/02.14
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
Terminal (43, 44)
Relay Output
Non Hazardous
Location
Zone 2 Installation
Voltage max.
250 V AC / 30 V DC
32 V AC / 30 V DC
Current max.
2 A AC / 2 A DC
2 A AC / 2 A DC
Power max.
500 VA / 60 W
64 VA / 60 W
Status Relay
Non Hazardous
Location
Zone 2 Installation
Voltage max.
125 V AC / 110 V DC
32 V AC / 32 V DC
Current max.
0.5 A AC / 0.3 A DC
0.5 A AC / 1 A DC
Power max.
62.5 VA / 32 W
16 VA / 32 W
Terminal (53, 54)
1066540000/02/02.14
151
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
Illustration 7-43:
152
FM Installation Drawing (2), (451481 Sheet 9-12)
1066540000/02/02.14
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
Terminal (24-22)
Input
Ui
30 V
Ii
120 mA
Pi
900 mW
Ci
3 nF
Li
2 µH
Terminal (24–22, 22–21)
Input
Group
Co
Lo
Lo/Ro
Uo
28 V
IIC or A, B
80 nF
4 mH
54 µH/Ω
Io
93 mA
IIB or C, E, F
640 nF
16 mH
218 µH/Ω
Po
0.65 W
IIA or D, G
2.1 µF
32 mH
436 µH/Ω
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um
253 V, max. 400 Hz
Terminal (51, 52)
Supply
Voltage
19.2…31.2 V DC
Terminal (43, 44)
Relay Output
Non Hazardous
Location
Zone 2 Installation
Voltage max.
250 V AC / 30 V DC
32 V AC / 30 V DC
Current max.
2 A AC / 2 A DC
2 A AC / 2 A DC
Power max.
500 VA / 60 W
64 VA / 60 W
Status Relay
Non Hazardous
Location
Zone 2 Installation
Voltage max.
125 V AC / 110 V DC
32 V AC / 32 V DC
Current max.
0.5 A AC / 0.3 A DC
0.5 A AC / 1 A DC
Power max.
62.5 VA / 32 W
16 VA / 32 W
Terminal (53, 54)
1066540000/02/02.14
153
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
Illustration 7-44:
154
FM Installation Drawing (3), (451481 Sheet 9-12)
1066540000/02/02.14
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
Terminal (21-22)
Input
Ui, Vmax
30 V
Ii, Imax
120 mA
Pi
900 mW
Ci
3 nF
Li
2 µH
Terminal (22–21, 21–22)
Input
Group
Co
Lo
Lo/Ro
Uo, VOC
16.6 V
IIC or A, B
0.4 µF
1000 mH
25 mH/Ω
Io, ISC
0.2 mA
IIB or C, E, F
2.3 µF
1000 mH
100 mH/Ω
Po
0.8 mW
IIA or D, G
9.5 µF
1000 mH
200 mH/Ω
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um
253 V, max. 400 Hz
Terminal (51, 52)
Supply
Voltage
19.2…31.2 V DC
Terminal (43, 44)
Relay Output
Non Hazardous
Location
Zone 2 Installation
Voltage max.
250 V AC / 30 V DC
32 V AC / 30 V DC
Current max.
2 A AC / 2 A DC
2 A AC / 2 A DC
Power max.
500 VA / 60 W
64 VA / 60 W
Status Relay
Non Hazardous
Location
Zone 2 Installation
Voltage max.
125 V AC / 110 V DC
32 V AC / 32 V DC
Current max.
0.5 A AC / 0.3 A DC
0.5 A AC / 1 A DC
Power max.
62.5 VA / 32 W
16 VA / 32 W
Terminal (53, 54)
1066540000/02/02.14
155
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
156
1066540000/02/02.14
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
ATEX Installation Drawing
The module is available in the following variants:
Order No.
Installation Drawing
Type
8965430000
4 53449 Sheet 1-4
ACT20X-HAI-SAO-S
8965440000
4 53449 Sheet 1-4
ACT20X-2HAI-2SAO-S
DANGER
For safe installation of ACT20X-(2)HAI-(2)SAO-S the following must be observed: The module
may only be installed by qualified personnel familiar with the national and international laws,
directives and standards that apply to this region.
DANGER
To prevent ignition of explosive atmospheres, disconnect power before servicing and do not
separate connectors when energized and an explosive gas mixture is present.
For installation in Zone 2, the module must be installed in an outer enclosure in type of protection Ex-n or
Ex-e, providing an IP protection of at least IP54. Cable entry devices and blanking elements shall fulfil the
same requirements.
In type of protection “intrinsic safety ia IIIC” the parameters for intrinsic safety for gas group IIB are
applicable.
The module must be installed in pollution degree 2, overvoltage category II as defined in EN 60664-1.
The Loop Supply and Current Input terminals for the same channel shall not be applied at the same time.
The wiring of unused terminals is not allowed.
Do not separate connectors when energized and an explosive gas mixture is present.
The wiring of unused terminals is not allowed.
The year of manufacture can be taken from the first two digits in the serial number.
2
Wire cross-section:
AWG 26...12 / 0.13...3.31 mm
Number of wires per terminal:
1 wire or 2 wires in a common ferrule
Tightening torque per terminal, max.:
0.6 Nm
1066540000/02/02.14
157
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
CBX200 – "WI-Manager" Software
For installation in Zone 2 / Division 2 the following must be observed:
- The CBX200 is an interface cable for configuration via PC.
- Configuration must be performed only in a safe area.
ATEX Certificate
DEKRA 11ATEX 0131 X
Marking
II (1) G [Ex ia Ga] IIC/IIB/IIA
II 3 G Ex nA nC IIC T4 Gc
II (1) D [Ex ia Da] IIIC
I (M1) [Ex ia Ma] I
Standards
EN 60079-0:2012, EN 60079-11:2012, EN 60079-15:2010,
EN 60079-26:2007
158
1066540000/02/02.14
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
Illustration 7-45:
ATEX Installation Drawing (1), (453449 Sheet 1-4)
Terminal CH1 (13, 14), CH2 (23, 24)
Ex Input (Loop Current Source)
Uo
28 V
Io
93 mA
Po
0.65 W
Group
Co
Lo
IIC
0.08 µF
3 mH
IIB
0.6 µF
12 mH
IIA
2.15 µF
25 mH
I
3.76 µF
30 mH
1066540000/02/02.14
159
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um
253 V, max. 400 Hz
Terminal (51, 52)
Supply
Voltage
19.2…31.2 V DC
Terminal (53, 54)
Status Relay
Non Hazardous
Location
Zone 2 Installation
Voltage max.
125 V AC / 110 V DC
32 V AC / 32 V DC
Current max.
0.5 A AC / 0.3 A DC
0.5 A AC / 1 A DC
Power max.
62.5 VA / 32 W
16 VA / 32 W
160
1066540000/02/02.14
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
Illustration 7-46:
ATEX Installation Drawing (2), (453449 Sheet 1-4)
Terminal CH1 (11, 12), CH2 (21, 22)
Ex Input (External Current Source)
Uo
0V
Io
0 mA
Po
0 mW
Ui
30 V
Ii
120 mA
Pi
0.85 W
Ci
2 nF
Li
0 µH
1066540000/02/02.14
161
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
Group
Co
Lo
IIC
0.08 µF
3 mH
IIB
0.6 µF
12 mH
IIA
2.15 µF
25 mH
I
3.76 µF
30 mH
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um
253 V AC, max. 400 Hz
Terminal (51, 52)
Supply
Voltage
19.2…31.2 V DC
Terminal (53, 54)
Status Relay
Non Hazardous
Location
Zone 2 Installation
Voltage max.
125 V AC / 110 V DC
32 V AC / 32 V DC
Current max.
0.5 A AC / 0.3 A DC
0.5 A AC / 1 A DC
Power max.
62.5 VA / 32 W
16 VA / 32 W
162
1066540000/02/02.14
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
Illustration 7-47:
ATEX Installation Drawing (3), (453449 Sheet 1-4)
Terminal CH1 (14), CH2 (22)
Ex Input (Loop Current Source Channel 1 to Channel 2)
Uo
28 V
Io
93 mA
Po
0.65 W
Group
Co
Lo
IIC
0.08 µF
3 mH
IIB
0.6 µF
12 mH
IIA
2.15 µF
25 mH
I
3.76 µF
30 mH
1066540000/02/02.14
163
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um
253 V, max. 400 Hz
Terminal (51, 52)
Supply
Voltage
19.2…31.2 V DC
Terminal (53, 54)
Status Relay
Non Hazardous
Location
Zone 2 Installation
Voltage max.
125 V AC / 110 V DC
32 V AC / 32 V DC
Current max.
0.5 A AC / 0.3 A DC
0.5 A AC / 1 A DC
Power max.
62.5 VA / 32 W
16 VA / 32 W
164
1066540000/02/02.14
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
Illustration 7-48:
ATEX Installation Drawing (4), (453449 Sheet 1-4)
Terminal CH1 (12), CH2 (21)
Ex Input (External Current Source Channel 1 to Channel 2)
Uo
0V
Io
0 mA
Po
0 mW
Ui
30 V
Ii
120 mA
Pi
0.85 W
Ci
4 nF
Li
0 µH
1066540000/02/02.14
165
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
Group
Co
Lo
IIC
0.08 µF
3 mH
IIB
0.6 µF
12 mH
IIA
2.15 µF
25 mH
I
3.76 µF
30 mH
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um
253 V, max. 400 Hz
Terminal (51, 52)
Supply
Voltage
19.2…31.2 V DC
Terminal (53, 54)
Status Relay
Non Hazardous
Location
Zone 2 Installation
Voltage max.
125 V AC / 110 V DC
32 V AC / 32 V DC
Current max.
0.5 A AC / 0.3 A DC
0.5 A AC / 1 A DC
Power max.
62.5 VA / 32 W
16 VA / 32 W
166
1066540000/02/02.14
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
IECEx Installation Drawing
The module is available in the following variants:
Order No.
Installation Drawing
Type
8965430000
4 53449 Sheet 5-8
ACT20X-HAI-SAO-S
8965440000
4 53449 Sheet 5-8
ACT20X-2HAI-2SAO-S
DANGER
For safe installation of ACT20X-(2)HAI-(2)SAO-S the following must be observed: The module
may only be installed by qualified personnel familiar with the national and international laws,
directives and standards that apply to this region.
DANGER
To prevent ignition of explosive atmospheres, disconnect power before servicing and do not
separate connectors when energized and an explosive gas mixture is present.
For installation in Zone 2, the module must be installed in an outer enclosure having an IP protection of at
least IP54 according to type of protection Ex-n or Ex-e.
In type of protection “intrinsic safety ia IIIC” the parameters for intrinsic safety for gas group IIB are
applicable.
The module must be installed in pollution degree 2, overvoltage category II as defined in IEC 60664-1.
The Loop Supply and Current Input terminals for the same channel shall not be applied at the same time.
The wiring of unused terminals is not allowed.
Do not separate connectors when energized and an explosive gas mixture is present.
The wiring of unused terminals is not allowed.
The year of manufacture can be taken from the first two digits in the serial number.
2
Wire cross-section:
AWG 26...12 / 0.13...3.31 mm
Number of wires per terminal:
1 wire or 2 wires in a common ferrule
Tightening torque per terminal, max.:
0.6 Nm
1066540000/02/02.14
167
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
CBX200 – "WI-Manager" Software
For installation in Zone 2 / Division 2 the following must be observed:
- The CBX200 is an interface cable for configuration via PC.
- Configuration must be performed only in a safe area.
IECEx Certificate
DEK 11.0050 X
Marking
Ex nA nC IIC T4 Gc
[Ex ia Ga] IIC/IIB/IIA
[Ex ia Da] IIIC
[Ex ia Ma] I
Standards
IEC 60079-0:2011, IEC 60079-11:2011, IEC 60079-15:2010,
IEC 60079-26:2007
168
1066540000/02/02.14
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
Illustration 7-49:
IECEx Installation Drawing (1), (453449 Sheet 5-8)
Terminal CH1 (13, 14), CH2 (23, 24)
Ex Input (Loop Current Source)
Uo
28 V
Io
93 mA
Po
0.65 W
Group
Co
Lo
IIC
0.08 µF
3 mH
IIB
0.6 µF
12 mH
IIA
2.15 µF
25 mH
I
3.76 µF
30 mH
1066540000/02/02.14
169
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um
253 V, max. 400 Hz
Terminal (51, 52)
Supply
Voltage
19.2…31.2 V DC
Terminal (53, 54)
Status Relay
Non Hazardous
Location
Zone 2 Installation
Voltage max.
125 V AC / 110 V DC
32 V AC / 32 V DC
Current max.
0.5 A AC / 0.3 A DC
0.5 A AC / 1 A DC
Power max.
62.5 VA / 32 W
16 VA / 32 W
170
1066540000/02/02.14
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
Illustration 7-50:
IECEx Installation Drawing (2), (453449 Sheet 5-8)
Terminal CH1 (11, 12), CH2 (21, 22)
Ex Input (External Current Source)
Uo
0V
Io
0 mA
Po
0 mW
Ui
30 V
Ii
120 mA
Pi
0.85 W
Ci
2 nF
Li
0 µH
1066540000/02/02.14
171
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
Group
Co
Lo
IIC
0.08 µF
3 mH
IIB
0.6 µF
12 mH
IIA
2.15 µF
25 mH
I
3.76 µF
30 mH
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um
253 V AC, max. 400 Hz
Terminal (51, 52)
Supply
Voltage
19.2…31.2 V DC
Terminal (53, 54)
Status Relay
Non Hazardous
Location
Zone 2 Installation
Voltage max.
125 V AC / 110 V DC
32 V AC / 32 V DC
Current max.
0.5 A AC / 0.3 A DC
0.5 A AC / 1 A DC
Power max.
62.5 VA / 32 W
16 VA / 32 W
172
1066540000/02/02.14
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
Illustration 7-51:
IECEx Installation Drawing (3), (453449 Sheet 5-8)
Terminal CH1 (14), CH2 (22)
Ex Input (Loop Current Source Channel 1 to Channel 2)
Uo
28 V
Io
93 mA
Po
0.65 W
Group
Co
Lo
IIC
0.08 µF
3 mH
IIB
0.6 µF
12 mH
IIA
2.15 µF
25 mH
I
3.76 µF
30 mH
1066540000/02/02.14
173
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um
253 V, max. 400 Hz
Terminal (51, 52)
Supply
Voltage
19.2…31.2 V DC
Terminal (53, 54)
Status Relay
Non Hazardous
Location
Zone 2 Installation
Voltage max.
125 V AC / 110 V DC
32 V AC / 32 V DC
Current max.
0.5 A AC / 0.3 A DC
0.5 A AC / 1 A DC
Power max.
62.5 VA / 32 W
16 VA / 32 W
174
1066540000/02/02.14
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
Illustration 7-52:
IECEx Installation Drawing (4), (453449 Sheet 5-8)
Terminal CH1 (12), CH2 (21)
Ex Input (External Current Source Channel 1 to Channel 2)
Uo
0V
Io
0 mA
Po
0 mW
Ui
30 V
Ii
120 mA
Pi
0.85 W
Ci
4 nF
Li
0 µH
1066540000/02/02.14
175
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
Group
Co
Lo
IIC
0.08 µF
3 mH
IIB
0.6 µF
12 mH
IIA
2.15 µF
25 mH
I
3.76 µF
30 mH
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um
253 V, max. 400 Hz
Terminal (51, 52)
Supply
Voltage
19.2…31.2 V DC
Terminal (53, 54)
Status Relay
Non Hazardous
Location
Zone 2 Installation
Voltage max.
125 V AC / 110 V DC
32 V AC / 32 V DC
Current max.
0.5 A AC / 0.3 A DC
0.5 A AC / 1 A DC
Power max.
62.5 VA / 32 W
16 VA / 32 W
176
1066540000/02/02.14
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
FM Installation Drawing
The module is available in the following variants:
Order No.
Installation Drawing
Type
8965430000
4 53449 Sheet 9-13
ACT20X-HAI-SAO-S
8965440000
4 53449 Sheet 9-13
ACT20X-2HAI-2SAO-S
DANGER
For safe installation of ACT20X-(2)HAI-(2)SAO-S the following must be observed: The module
may only be installed by qualified personnel familiar with the national and international laws,
directives and standards that apply to this region.
DANGER
To prevent ignition of explosive atmospheres, disconnect power before servicing and do not
separate connectors when energized and an explosive gas mixture is present.
WARNING
Substitution of components may impair intrinsic safety and/or suitability for Division 2 / Zone 2.
In Class I, Division 2 installations, the subject equipment shall be mounted within a tool-secured enclosure
which is capable of accepting one or more of the Class I, Division 2 wiring methods specified in the National
Electrical Code (ANSI/NFPA 70) or Canadian Electrical Code (C22.1).
The module must be installed in pollution degree 2, overvoltage category II as defined in IEC 60664-1.
For installation in Zone 2 or Division 2, the module must be installed in a suitable outer enclosure having an
IP protection of at least IP54.
The module is galvanically isolated and does not require grounding.
Use 60/75 °C copper conductors in the wire size AWG 26-14.
The Loop Supply and Current Input terminals for the same channel shall not be applied at the same time.
The wiring of unused terminals is not allowed.
The year of manufacture can be taken from the first two digits in the serial number.
1066540000/02/02.14
177
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
CBX200 – "WI-Manager" Software
For installation in Zone 2 / Division 2 the following must be observed:
- The CBX200 is an interface cable for configuration via PC.
- Configuration must be performed only in a safe area.
c-FM-us certificate
3038275
Marking
Install in CL I DIV2 GP A-D T4
Provides IS Circuits to
CL I-III DIV 1/2 GP A-G or
CL I Zn2 AEx/Ex nA nC [ia] IIC T4
178
1066540000/02/02.14
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
Illustration 7-53:
FM Installation Drawing (1), (453449 Sheet 9-13)
Terminal CH1 (13, 14), CH2 (23, 24)
Ex Input (Loop Current Source)
Uo, VOC
28 V
Io, ISC
93 mA
Po
0.65 W
1066540000/02/02.14
179
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
Group
Co
Lo
IIC or A, B
0.08 µF
3 mH
IIB or C, E, F
0.6 µF
12 mH
IIA or D, G
2.15 µF
25 mH
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um
253 V, max. 400 Hz
Terminal (51, 52)
Supply
Voltage
19.2…31.2 V DC
Terminal (53, 54)
Status Relay
Non Hazardous
Location
Zone 2 Installation
Voltage max.
125 V AC / 110 V DC
32 V AC / 32 V DC
Current max.
0.5 A AC / 0.3 A DC
0.5 A AC / 1 A DC
Power max.
62.5 VA / 32 W
16 VA / 32 W
180
1066540000/02/02.14
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
Illustration 7-54:
FM Installation Drawing (2), (453449 Sheet 9-13)
Terminal CH1 (11, 12), CH2 (21, 22)
Ex Input (External Current Source)
Uo, VOC
0V
Io, ISC
0 mA
Po
0 mW
Ui, Vmax
30 V
Ii, Imax
120 mA
Pi
0.85 W
Ci
2 nF
Li
0 µH
1066540000/02/02.14
181
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
Group
Co
Lo
IIC or A, B
0.08 µF
3 mH
IIB or C, E, F
0.6 µF
12 mH
IIA or D, G
2.15 µF
25 mH
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um
253 V, max. 400 Hz
Terminal (51, 52)
Supply
Voltage
19.2…31.2 V DC
Terminal (53, 54)
Status Relay
Non Hazardous
Location
Zone 2 Installation
Voltage max.
125 V AC / 110 V DC
32 V AC / 32 V DC
Current max.
0.5 A AC / 0.3 A DC
0.5 A AC / 1 A DC
Power max.
62.5 VA / 32 W
16 VA / 32 W
182
1066540000/02/02.14
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
Illustration 7-55:
FM Installation Drawing (3), (453449 Sheet 9-13)
Terminal CH1 (14), CH2 (22)
Ex Input (Loop Current Source Channel 1 to Channel 2)
Uo, Voc
28 V
Io, Isc
93 mA
Po
0.65 W
Group
Co
Lo
IIC or A, B
0.08 µF
3 mH
IIB or C, E, F
0.6 µF
12 mH
IIA or D, G
2.15 µF
25 mH
1066540000/02/02.14
183
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um
253 V, max. 400 Hz
Terminal (51, 52)
Supply
Voltage
19.2…31.2 V DC
Terminal (53, 54)
Status Relay
Non Hazardous
Location
Zone 2 Installation
Voltage max.
125 V AC / 110 V DC
32 V AC / 32 V DC
Current max.
0.5 A AC / 0.3 A DC
0.5 A AC / 1 A DC
Power max.
62.5 VA / 32 W
16 VA / 32 W
184
1066540000/02/02.14
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
Illustration 7-56:
FM Installation Drawing (4), (453449 Sheet 9-13)
Terminal CH1 (12), CH2 (21)
Ex Input (External Current Source Channel 1 to Channel 2)
Uo
0V
Io
0 mA
Po
0 mW
Ui, Vmax
30 V
Ii, Imax
120 mA
Pi
0.85 W
Ci
4 nF
Li
0 µH
1066540000/02/02.14
185
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
Group
Co
Lo
IIC or A, B
0.08 µF
3 mH
IIB or C, E, F
0.6 µF
12 mH
IIA or D, G
2.15 µF
25 mH
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um
253 V, max. 400 Hz
Terminal (51, 52)
Supply
Voltage
19.2…31.2 V DC
Terminal (53, 54)
Status Relay
Non Hazardous
Location
Zone 2 Installation
Voltage max.
125 V AC / 110 V DC
32 V AC / 32 V DC
Current max.
0.5 A AC / 0.3 A DC
0.5 A AC / 1 A DC
Power max.
62.5 VA / 32 W
16 VA / 32 W
186
1066540000/02/02.14
Appendix F. Installation Drawings ACT20X-SAI-HAO (HART-transparent Driver)
Appendix F. Installation Drawings ACT20X-SAI-HAO (HART-transparent Driver)
ATEX Installation Drawing
The module is available in the following variants:
Order No.
Installation Drawing
Type
8965450000
4 53448 Sheet 1-2
ACT20X-SAI-HAO-S
8965460000
4 53448 Sheet 1-2
ACT20X-2SAI-2HAO-S
DANGER
For safe installation of ACT20X-(2)SAI-(2)HAO-S the following must be observed: The module
may only be installed by qualified personnel familiar with the national and international laws,
directives and standards that apply to this region.
DANGER
To prevent ignition of explosive atmospheres, disconnect power before servicing and do not
separate connectors when energized and an explosive gas mixture is present.
For installation in Zone 2, the module must be installed in an outer enclosure having an IP protection of at
least IP54 according to type of protection Ex-n or Ex-e.
In type of protection “Ex ia Da” the parameters for intrinsic safety for gas group IIB are applicable.
The module must be installed in pollution degree 2, overvoltage category II as defined in EN 60664-1.
Do not separate connectors when energized and an explosive gas mixture is present.
The wiring of unused terminals is not allowed.
The year of manufacture can be taken from the first two digits in the serial number.
2
Wire cross-section:
AWG 26...12 / 0.13...3.31 mm
Number of wires per terminal:
1 wire or 2 wires in a common ferrule
Tightening torque per terminal, max.:
0.6 Nm
1066540000/02/02.14
187
Appendix F. Installation Drawings ACT20X-SAI-HAO (HART-transparent Driver)
CBX200 – "WI-Manager" Software
For installation in Zone 2 / Division 2 the following must be observed:
- The CBX200 is an interface cable for configuration via PC.
- Configuration must be performed only in a safe area.
ATEX Certificate
DEKRA 11ATEX 0164 X
Marking
II (1) G [Ex ia Ga] IIC/IIB/IIA
II 3 G Ex nA nC IIC T4 Gc
II (1) D [Ex ia Da] IIIC
I (M1) [Ex ia Ma] I
Standards
EN 60079-0:2012, EN 60079-11:2012, EN 60079-15:2010,
EN 60079-26:2007
188
1066540000/02/02.14
Appendix F. Installation Drawings ACT20X-SAI-HAO (HART-transparent Driver)
Illustration 7-57:
ATEX Installation Drawing, (453448 Sheet 1-2)
Terminal CH1 (11, 12), CH2 (21, 22)
Ex Output
Uo
28 V
Io
93 mA
Po
0.65 W
Group
Co
Lo
IIC
0.08 µF
4 mH
IIB
0.65 µF
16 mH
IIA
2.15 µF
32 mH
I
3.76 µF
46 mH
1066540000/02/02.14
189
Appendix F. Installation Drawings ACT20X-SAI-HAO (HART-transparent Driver)
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Current Input
Um
253 V, max. 400 Hz
Terminal (51, 52)
Supply
Voltage
19.2…31.2 V DC
Terminal (53, 54)
Status Relay
Non Hazardous
Location
Zone 2 Installation
Voltage max.
125 V AC / 110 V DC
32 V AC / 32 V DC
Current max.
0.5 A AC / 0.3 A DC
0.5 A AC / 1 A DC
Power max.
62.5 VA / 32 W
16 VA / 32 W
190
1066540000/02/02.14
Appendix F. Installation Drawings ACT20X-SAI-HAO (HART-transparent Driver)
IECEx Installation Drawing
The module is available in the following variants:
Order No.
Installation Drawing
Type
8965450000
4 53448 Sheet 3-4
ACT20X-SAI-HAO-S
8965460000
4 53448 Sheet 3-4
ACT20X-2SAI-2HAO-S
DANGER
For safe installation of ACT20X-(2)SAI-(2)HAO-S the following must be observed: The module
may only be installed by qualified personnel familiar with the national and international laws,
directives and standards that apply to this region.
DANGER
To prevent ignition of explosive atmospheres, disconnect power before servicing and do not
separate connectors when energized and an explosive gas mixture is present.
For installation in Zone 2, the module must be installed in an outer enclosure having an IP protection of at
least IP54 according to type of protection Ex-n or Ex-e.
In type of protection “Ex ia Da” the parameters for intrinsic safety for gas group IIB are applicable.
The module must be installed in pollution degree 2, overvoltage category II as defined in IEC 60664-1.
Do not separate connectors when energized and an explosive gas mixture is present.
The wiring of unused terminals is not allowed.
The year of manufacture can be taken from the first two digits in the serial number.
2
Wire cross-section:
AWG 26...12 / 0.13...3.31 mm
Number of wires per terminal:
1 wire or 2 wires in a common ferrule
Tightening torque per terminal, max.:
0.6 Nm
1066540000/02/02.14
191
Appendix F. Installation Drawings ACT20X-SAI-HAO (HART-transparent Driver)
CBX200 – "WI-Manager" Software
For installation in Zone 2 / Division 2 the following must be observed:
- The CBX200 is an interface cable for configuration via PC.
- Configuration must be performed only in a safe area.
IECEx Certificate
DEK 11.0059 X
Marking
Ex nA nC IIC T4 Gc
[Ex ia Ga] IIC/IIB/IIA
[Ex ia Da] IIIC
[Ex ia Ma] I
Standards
IEC 60079-0:2011, IEC 60079-11:2011, IEC 60079-15:2010,
IEC 60079-26:2007
192
1066540000/02/02.14
Appendix F. Installation Drawings ACT20X-SAI-HAO (HART-transparent Driver)
Illustration 7-58:
IECEx Installation Drawing, (453448 Sheet 3-4)
Terminal CH1 (11, 12), CH2 (21, 22)
Ex Output
Uo
28 V
Io
93 mA
Po
0.65 W
Group
Co
Lo
IIC
0.08 µF
4 mH
IIB
0.65 µF
16 mH
IIA
2.15 µF
32 mH
I
3.76 µF
25 mH
1066540000/02/02.14
193
Appendix F. Installation Drawings ACT20X-SAI-HAO (HART-transparent Driver)
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Current Input
Um
253 V, max. 400 Hz
Terminal (51, 52)
Supply
Voltage
19.2…31.2 V DC
Terminal (53, 54)
Status Relay
Non Hazardous
Location
Zone 2 Installation
Voltage max.
125 V AC / 110 V DC
32 V AC / 32 V DC
Current max.
0.5 A AC / 0.3 A DC
0.5 A AC / 1 A DC
Power max.
62.5 VA / 32 W
16 VA / 32 W
194
1066540000/02/02.14
Appendix F. Installation Drawings ACT20X-SAI-HAO (HART-transparent Driver)
FM Installation Drawing
The module is available in the following variants:
Order No.
Installation Drawing
Type
8965450000
4 53448 Sheet 5-6
ACT20X-SAI-HAO-S
8965460000
4 53448 Sheet 5-6
ACT20X-2SAI-2HAO-S
DANGER
For safe installation of ACT20X-(2)SAI-(2)HAO-S the following must be observed: The module
may only be installed by qualified personnel familiar with the national and international laws,
directives and standards that apply to this region.
DANGER
To prevent ignition of explosive atmospheres, disconnect power before servicing and do not
separate connectors when energized and an explosive gas mixture is present.
WARNING
Substitution of components may impair intrinsic safety and/or suitability for Division 2 / Zone 2.
In Class I, Division 2 or Zone 2 installations, the subject equipment shall be mounted within a tool-secured
enclosure which is capable of accepting one or more of Class I, Division 2 wiring methodes specified in the
National Electrical Code (ANSI/NFPA 70) or the Canadian Electrical code (C22.1).
The module must be installed in pollution degree 2, overvoltage category II as defined in IEC 60664-1.
For installation in Zone 2 or Division 2, the module must be installed in a suitable outer enclosure having an
IP protection of at least IP54.
The module is galvanically isolated and does not require grounding.
Use 60/75 °C copper conductors in the wire size AWG (26-14).
The year of manufacture can be taken from the first two digits in the serial number.
1066540000/02/02.14
195
Appendix F. Installation Drawings ACT20X-SAI-HAO (HART-transparent Driver)
CBX200 – "WI-Manager" Software
For installation in Zone 2 / Division 2 the following must be observed:
- The CBX200 is an interface cable for configuration via PC.
- Configuration must be performed only in a safe area.
c-FM-us Certificate
3038275
Marking
Install in CL I DIV2 GP A-D T4
Provides IS Circuits to
CL I-III DIV 1/2 GP A-G or
CL I Zn2 AEx/Ex nA nC [ia] IIC T4
Standards
Canada
Zones:
CAN/CSA-C22.2 E60079-0,
CAN/CSA-C22.2 E60079-11,
CAN/CSA-C22.2 E60079-15
Divisions: CSA 22.2-157, CSA 22.2-213
USA
Zones:
ANSI/ISA 60079-0, ANSI/ISA 60079-11,
ANSI/ISA 60079-15
Divisions: FM3600, FM3610, FM3611, FM3810
196
1066540000/02/02.14
Appendix F. Installation Drawings ACT20X-SAI-HAO (HART-transparent Driver)
Illustration 7-59:
FM Installation Drawing, (453448 Sheet 5-6)
Terminal CH1 (11, 12), CH2 (21, 22)
Ex Output
Uo
28 V
Io
93 mA
Po
0.65 W
Group
Co
Lo
IIC
0.08 µF
4 mH
IIB
0.65 µF
16 mH
IIA
2.15 µF
32 mH
1066540000/02/02.14
197
Appendix F. Installation Drawings ACT20X-SAI-HAO (HART-transparent Driver)
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Current Input
Um
253 V, max. 400 Hz
Terminal (51, 52)
Supply
Voltage
19.2…31.2 V DC
Terminal (53, 54)
Status Relay
Non Hazardous
Location
Zone 2 Installation
Voltage max.
125 V AC / 110 V DC
32 V AC / 32 V DC
Current max.
0.5 A AC / 0.3 A DC
0.5 A AC / 1 A DC
Power max.
62.5 VA / 32 W
16 VA / 32 W
198
1066540000/02/02.14
Appendix G. Installation Drawings ACT20-FEED-IN-PRO-S (Power Feed-In Unit)
Appendix G. Installation Drawings ACT20-FEED-IN-PRO-S (Power Feed-In Unit)
ATEX Installation Drawing
The module is available in the following variants:
Order No.
Installation Drawing
Type
8965500000
4 52691 Sheet 1-2
ACT20-FEED-IN-PRO-S
DANGER
For safe installation of ACT20-FEED-IN-PRO-S the following must be observed: The module
may only be installed by qualified personnel familiar with the national and international laws,
directives and standards that apply to this region.
DANGER
To prevent ignition of explosive atmospheres, disconnect power before servicing and do not
separate connectors when energized and an explosive gas mixture is present.
DANGER
Do not install or remove modules from the Power Rail unless area is known to be nonhazardous.
The ACT20-FEED-IN-PRO-S must be supplied from a power source with double or reinforced insulation to
mains.
For installation in Zone 2, the module must be installed in an outer enclosure having an IP protection of at
least IP54 according to type of protection Ex-n or Ex-e.
Cable entry devices and blanking elements shall fulfil the same requirements.
Transients are suppressed by an internal transient protection device, which is set to a level not exeeding
40% of the rated voltage.
The year of manufacture can be taken from the first two digits in the serial number.
2
Wire cross-section:
AWG 26...12 / 0.13...3.31 mm
Number of wires per terminal:
1 wire or 2 wires in a common ferrule
Tightening torque per terminal, max.:
0.6 Nm
ATEX Certificate
DEKRA 11ATEX 0129 X
Marking
II 3 G Ex nA nC IIC T4 Gc
Standards
1066540000/02/02.14
EN 60079-0:2012, EN 60079-15:2010
199
Appendix G. Installation Drawings ACT20-FEED-IN-PRO-S (Power Feed-In Unit)
Illustration 7-60:
ATEX Installation Drawing, (452691 Sheet 1-2)
Terminal (51, 52)
Supply
Voltage
21.6…26.6 V DC
Current
4 A DC
Terminal (53, 54)
Backup Supply
Voltage
21.6…26.6 V DC
Current
4 A DC
Terminal (41, 42, 43)
Power Rail Status Relay
Non Hazardous
Location
Zone 2 Installation
Voltage max.
250 V AC / 30 V DC
32 V AC / 30 V DC
Current max.
2 A AC / 2 A DC
2 A AC / 2 A DC
Power max.
500 VA / 60 W
64 VA / 60 W
200
1066540000/02/02.14
Appendix G. Installation Drawings ACT20-FEED-IN-PRO-S (Power Feed-In Unit)
ACT20-FEED-IN-PRO-S Power unit with backup.
ACT20-FEED-IN-PRO-S shall only be used with the CH20M-BUS supplied by Weidmüller.
Use CH20M BUS-AP (Bus End Plate) to prevent the mounting rail from being short circuited by the outer
enclosure.
Use CH20M BUS-ADP (Bus Cover) to prevent the open mounting rail from being accidentally short circuited.
Redundant ACT20-FEED-IN-PRO-S Power unit with backup.
ACT20-FEED-IN-PRO-S shall only be used with the CH20M-BUS supplied by Weidmüller.
Use CH20M BUS-AP (Bus End Plate) to prevent the mounting rail from being short circuited by the outer
enclosure.
Power is supplied to the Power Rail from two ACT20-FEED-IN-PRO-S modules. Both modules have
connections for normal supply and backup supply.
1066540000/02/02.14
201
Appendix G. Installation Drawings ACT20-FEED-IN-PRO-S (Power Feed-In Unit)
202
1066540000/02/02.14
Appendix G. Installation Drawings ACT20-FEED-IN-PRO-S (Power Feed-In Unit)
IECEx Installation Drawing
The module is available in the following variants:
Order No.
Installation Drawing
Type
8965500000
4 52691 Sheet 3-4
ACT20-FEED-IN-PRO-S
DANGER
For safe installation of ACT20-FEED-IN-PRO-S the following must be observed: The module
may only be installed by qualified personnel familiar with the national and international laws,
directives and standards that apply to this region.
DANGER
To prevent ignition of explosive atmospheres, disconnect power before servicing and do not
separate connectors when energized and an explosive gas mixture is present.
DANGER
Do not install or remove modules from the Power Rail unless area is known to be nonhazardous.
The ACT20-FEED-IN-PRO-S must be supplied from a power source with double or reinforced insulation to
mains.
For installation in Zone 2, the module must be installed in an outer enclosure having an IP protection of at
least IP54 according to type of protection Ex-n or Ex-e.
Cable entry devices and blanking elements shall fulfil the same requirements.
Transients are suppressed by an internal transient protection device, which is set to a level not exeeding
40% of the rated voltage.
The year of manufacture can be taken from the first two digits in the serial number.
2
Wire cross-section:
AWG 26...12 / 0.13...3.31 mm
Number of wires per terminal:
1 wire or 2 wires in a common ferrule
Tightening torque per terminal, max.:
0.6 Nm
IECEx Certificate
DEK 11.0048 X
Marking
Ex nA nC IIC T4 Gc
Standards
IEC 60079-0:2011, IEC 60079-15:2010
1066540000/02/02.14
203
Appendix G. Installation Drawings ACT20-FEED-IN-PRO-S (Power Feed-In Unit)
Illustration 7-61:
IECEx Installation Drawing, (452691 Sheet 3-4)
Terminal (51, 52)
Supply
Voltage
21.6…26.6 V DC
Current
4 A DC
Terminal (53, 54)
Backup Supply
Voltage
21.6…26.6 V DC
Current
4 A DC
Terminal (41, 42, 43)
Power Rail Status Relay
Non Hazardous
Location
Zone 2 Installation
Voltage max.
250 V AC / 30 V DC
32 V AC / 30 V DC
Current max.
2 A AC / 2 A DC
2 A AC / 2 A DC
Power max.
500 VA / 60 W
64 VA / 60 W
204
1066540000/02/02.14
Appendix G. Installation Drawings ACT20-FEED-IN-PRO-S (Power Feed-In Unit)
ACT20-FEED-IN-PRO-S Power unit with backup.
ACT20-FEED-IN-PRO-S shall only be used with the CH20M-BUS supplied by Weidmüller.
Use CH20M BUS-AP (Bus End Plate) to prevent the mounting rail from being short circuited by the outer
enclosure.
Use CH20M BUS-ADP (Bus Cover) to prevent the open mounting rail from being accidentally short circuited.
Redundant ACT20-FEED-IN-PRO-S Power unit with backup.
ACT20-FEED-IN-PRO-S shall only be used with the CH20M-BUS supplied by Weidmüller.
Use CH20M BUS-AP (Bus End Plate) to prevent the mounting rail from being short circuited by the outer
enclosure.
Power is supplied to the Power Rail from two ACT20-FEED-IN-PRO-S modules. Both modules have
connections for normal supply and backup supply.
1066540000/02/02.14
205
Appendix G. Installation Drawings ACT20-FEED-IN-PRO-S (Power Feed-In Unit)
206
1066540000/02/02.14
Appendix G. Installation Drawings ACT20-FEED-IN-PRO-S (Power Feed-In Unit)
FM Installation Drawing
The module is available in the following variants:
Order No.
Installation Drawing
Type
8965500000
4 52691 Sheet 5-6
ACT20-FEED-IN-PRO-S
DANGER
For safe installation of ACT20-FEED-IN-PRO-S the following must be observed: The module
may only be installed by qualified personnel familiar with the national and international laws,
directives and standards that apply to this region.
DANGER
To prevent ignition of explosive atmospheres, disconnect power before servicing and do not
separate connectors when energized and an explosive gas mixture is present.
DANGER
Do not install or remove modules from the Power Rail unless area is known to be nonhazardous.
WARNING
Substitution of components may impair intrinsic safety and/or suitability for Division 2 / Zone 2.
The installation and wiring must be in accordance with the Canadian Electrical Code for Canada and
National Electrical Code NFPA 70, Article 500 or 505 for installation in USA.
The module must be installed in pollution degree 2 or better.
The module must be supplied from a Power Supply having double or reinforced insulation.
The use of stranded wires is not permitted for mains wiring except when wires are fitted with cable ends.
For installation in Zone 2 or Division 2, the module must be installed in a suitable outer enclosure
according to the regulations in the CEC for Canada or NEC for USA.
The year of manufacture can be taken from the first two digits in the serial number.
c-FM-us Certificate
3043148
Marking
CL I DIV2 GP A-D T4
CL I Zn2 AEx/Ex nA nC IIC T4
Standards
Class 3600, Class 3611, Class 3810, ANSI/ISA 12.00.01, ANSI/ISA
12.12.02, ISA 60079-15:2002, CSA-E79-15, CSA-C22.2-213
1066540000/02/02.14
207
Appendix G. Installation Drawings ACT20-FEED-IN-PRO-S (Power Feed-In Unit)
Illustration 7-62:
FM Installation Drawing, (452691 Sheet 5-6)
Terminal (51, 52)
Supply
Voltage
21.6…26.6 V DC
Current
4 A DC
Terminal (53, 54)
Backup Supply
Voltage
21.6…26.6 V DC
Current
4 A DC
Terminal (41, 42, 43)
Power Rail Status Relay
Non Hazardous
Location
Zone 2 Installation
Voltage max.
250 V AC / 30 V DC
32 V AC / 30 V DC
Current max.
2 A AC / 2 A DC
2 A AC / 2 A DC
Power max.
500 VA / 60 W
64 VA / 60 W
208
1066540000/02/02.14
Appendix G. Installation Drawings ACT20-FEED-IN-PRO-S (Power Feed-In Unit)
ACT20-FEED-IN-PRO-S Power unit with backup.
ACT20-FEED-IN-PRO-S shall only be used with the CH20M-BUS supplied by Weidmüller.
Use CH20M BUS-AP (Bus End Plate) to prevent the mounting rail from being short circuited by the outer
enclosure.
Use CH20M BUS-ADP (Bus Cover) to prevent the open mounting rail from being accidentally short circuited.
Redundant ACT20-FEED-IN-PRO-S Power unit with backup.
ACT20-FEED-IN-PRO-S shall only be used with the CH20M-BUS supplied by Weidmüller.
Use CH20M BUS-AP (Bus End Plate) to prevent the mounting rail from being short circuited by the outer
enclosure.
Power is supplied to the Power Rail from two ACT20-FEED-IN-PRO-S modules. Both modules have
connections for normal supply and backup supply.
1066540000/02/02.14
209
Appendix G. Installation Drawings ACT20-FEED-IN-PRO-S (Power Feed-In Unit)
210
1066540000/02/02.14
Weidmüller Interface GmbH & Co. KG
P.O. Box 3030
32720 Detmold
Klingenbergstraße 16
32758 Detmold
Germany
Phone
+49 (0) 5231 14-0
Fax
+49 (0) 5231 14-2083
E-Mail
[email protected]
Order number:
Internet
www.weidmueller.com