Download

Intrinsically safe signal conditioners
for hazardous area applications
Contents
Intrinsically safe signal conditioners
for hazardous area applications
Intrinsically safe signal conditioners
for hazardous area applications
2028820000
Intrinsically safe signal conditioners for hazardous area applications – Overview
B.2
ACT20X – Overview
B.4
Current supply isolator
B.6
Current output isolator
B.8
Temperature transducer
B.10
Universal measurement and signal isolator-converter
B.12
NAMUR isolating switching amplifier
B.16
Valve control module
B.20
B
B.1
Intrinsically safe signal conditioners
for hazardous area applications
Intrinsically safe signal conditioners for hazardous area applications – Overview
Intrinsically safe signal conditioners
for hazardous area applications
ACT20X signal converters
The ACT20X is a completely new line of signal converter
products for the Ex zone. These compact modules require
only 11 mm per channel and take up very little space in
the electrical cabinet. Weidmüller has specifically designed
the ACT20X line for process automation applications in Ex
and non-Ex zones. The 17 different variants can process all
standard input signals (such as 2-wire, HART®-, NAMUR-,
RTD, thermocouple or DC signals) from Ex zone 0. They
can also handle digital or analogue signals from Ex-zone
field devices to the controller. The integrated relay output
issues an alert in the event of a malfunction; this makes
troubleshooting easier and reduces facility down times.
The WI-Manager configuration software is based on FDT
(Field Device Tool) technology. The software allows you to
configure all ACT20X products with your PC so that they
can be custom-fit to a wide variety of process applications.
Weidmüller provides a device type manager (DTM) for
the ACT20X modules that can be used in any FDT-based
frame. The DTMs allow you to configure different devices
quickly and accurately. They also enable you to analyse
measurements and diagnostics data. The DTM can also be
used to clearly identify the connected device. The FDT frame
application “WI Manager“ and the device-specific DTMs
are available from Weidmüller free of charge. The ACT20X
modules can be used in a temperature range from –20 °C
to +60 °C without limitations. The modules can be installed
in the safe zone or in the explosion risk area of Zone 2. The
ACT20Xs always deliver a pure, interference-free signal
B
B.2
thanks to their accuracy, temperature stability and high
insulation strength. They can easily be used around the
globe since they already have all the necessary international
approvals, including ATEX, ICEEX, GOST and FM.
The newest member of the ACT20X family is the ACT20XHUI-SAO-LP. This offers an intrinsically safe input for 0/4 to
20 mA, 0 to10 V, temperature and resistance signals, and
separates the Ex zone from the safe zone. The narrow
12.5 mm module is supplied via the 4 to 20 mA output.
Features
•International approvals for Zone 0, 1 and 2 (IECEx, ATEX)
and Class 1 Division 1 and 2 (FM)
•Analogue and binary signal interface to Zone 0/Div.1 for
explosion-risk inputs and outputs
•All standard input signals (4 to 20 mA HART®-, NAMUR-,
RTD- or thermocouple signals) out of Ex zone 0, 1 or 2
•Two-channel type saves space in the electrical cabinet
and reduces installation costs
•HART® transparent signal isolator
• Integrated alarm contact
•Configuration over FDT/DTM standard with the frame
application “WI Manager“
2028820000
Intrinsically safe signal conditioners
for hazardous area applications
Intrinsically safe signal conditioners for hazardous area applications – Overview
B
ACT20X
2028820000
B.3
Intrinsically safe signal conditioners
for hazardous area applications
ACT20X – Overview
ACT20X – intrinsic safety signal conditioners for hazardous areas
PC-configurable conditioners family for hazardous
areas in the new Weidmüller electronics housing for
installation in safe or hazardous areas.
B
ACT20X meets the arduous requirements of the process
industry where potentially explosive fluids are controlled. The
range connects to sensors and actuators in the hazardous
area, isolates their signals and limits the energy passed to
them. On the input side ACT20X models can process d.c.,
B.4
temperature, Namur and volt-free contact signals. On the
output side field devices in the Ex area are controlled via
the ACT20X with analogue or digital signals. All ACT20X
products are characterised by insulation, accuracy and high
temperature stability.
The digital 2-channel versions with width of 22.5 mm
are available with either transistor or relay output. Due to
this high component density, the space requirements and
installation costs are reduced accordingly.
2028820000
Intrinsically safe signal conditioners
for hazardous area applications
ACT20X – Overview
Configuration via FDT
All modules can be quickly and
conveniently configured with
manufacturer-independent FDT/DTM
software.
\
;
"
Worldwide application
Fulfils the strict standards and requirements of the process industry. Can be
used worldwide due to international and
local approvals ATEX, IECEX,
CULUS, FM, GOST and DNV.
Intelligent connection system
Pluggable, coded, with release lever.
The release lever simplifies
maintenance and allows disconnection
without damaging the cables.
Alarm function
No laborious troubleshooting. Alarm
function integrated for cable or sensor
errors. In case of failures, a diagnostic
signal is sent to the control system.
+60 °C
to
–20 °C
SIL
61508
2028820000
B
Current supply isolator,
HART® Transparent
Current output isolator,
HART® Transparent
Temperature transducer
Robust
Wide ambient temperature range from
– 20 °C … + 60 °C.
Universal measurement and signal
isolator/converter
SIL certification according 61508
NAMUR disconnect-switch
amplifier
Available for safety functions, e.g.
switching aggregates
on/off, monitoring actuators or
temperature/pressure.
Valve control component
B.5
Intrinsically safe signal conditioners
for hazardous area applications
ACT20X
Current supply isolator, HART® Transparent
The ACT20X-HAI-SAO current supply isolator is a HART®-protocol transparent signal isolator for analogue
input signals from Ex zone 0. It provides an analogue signal for the safe zone on the output side. It is available
in a single-channel or double-channel version.
EX area Zone 0, 1, 2, 20, 21, 22
Safe area Zone 2 / FM Class 1, Division 2
Input Signals
Output Signals
B
Removable
terminals
(black)
LED Channel 1
red = inactive,
flashing = fault
LED green
= supply
Analogue, 4...20 mA
+
44
14
42
+
-
43
13
41
–
42
12
44
+
43
–
mA
Channel 1:
Tx
+
2-wire supply –
4...20 mA
mA
Current
-
2-wire supply +
2-wire supply –
4...20 mA
mA
41
11
active or passive sensor
Marker
–
mA
–
2-wire supply +
active or passive output
Power Supply and
Module Status
+
24
51
-
23
52
22
53
21
54
Channel 2:
Tx
+
Current
-
active or passive sensor
Ex label (excerpt)
ATEX
II 3 G Ex nA nC IIC T4 Gc
II (1) G [Ex ia Ga] IIC/IIB/IIA
II (1) D [Ex ia Da] IIIC
IECEx
Ex nA nC IIC T4 Gc
[Ex ia Ga] IIC/IIB/IIA
FM
Installation in CL I DIV2 GP A-D T4
Kl. I-III ABT 1/2 GP A-G or
Kl. I Zn2 AEx/Ex nA nC [ia] IIC T4
Example:
ATEX version,
Ex input, External Current Source:
(More details in ATEX certificate)
Gnd. Supply +19,2...31,2 V DC
Module status
N.C.
Module status
Uo/Ui
Io/li
Po/Pi
Li
Ci
IIC
IIB
IIA
0 V / 30 V
0 mA / 120 mA
0 mW / 0,85 W
0 µH
2 nF
Co = 0,08 µF, Lo= 3 mH
Co = 0,6 µF, Lo= 12 mH
Co = 2,15 µF, Lo= 25 mH
Removable
terminals
(blue)
%
LED Channel 2
red = inactive,
flashing = fault
\
SIL
SUITABLE
61508
Application example:
Measuring temperature with a head transmitter, signal transmission with HART®
(;=RQH
$&VXSSO\
&RQWUROV\VWHP
9'&
=RQH
ZLUH+$57Š
KHDGWUDQVPLWWHU
IRUWHPSHUDWXUH
9
P$+$57Š
LQSXW
P$+$57Š
RXWSXW
7RRWKHULVRODWRUV
3DVVLYH
LQSXW
FKDQQHO
$&7;+$,6$2
7DQN
B.6
2028820000
Current supply isolator
Intrinsically safe signal conditioners
for hazardous area applications
ACT20X
ACT20X-HAI-SAO-S / 2HAI-2SAO-S
• Converts analogue signals from Ex zone 0 into
analogue output signals for safe zones.
• Active and passive current inputs/outputs
• HART® - transparent
• PC configuration with FDT/DTM software, download
link at www.weidmueller.com
• Relay output for failure alarm
• 2-channel module, can also be used as a signal splitter
B
I
I
PS
Technical data
Input
Input current
Sensor supply
Residual ripple (current loop)
Output analogue
Output current
Output signal limit
load impedance current
2-wire supply
Accuracy
Temperature coefficient
Step response time
Cut-off frequency (-3 dB)
Alarm output
Type
Nominal switching voltage
4...20 mA
≤ 28 V DC
< 7.5 mVeff
4...20 mA
< 28 mA
≤ 600 Ω
≤ 26 V DC
< 0.1% span
< 0.01% of span/°C (TU)
≤ 5 ms
0.5…2.5 kHz @ 3.5…23 mA bi-directional HART® signal
Relay, 1 NC (voltage-free)
≤ 125 V AC / 110 V DC (safe area)
≤ 32 V AC / 32 V DC (Zone 2)
≤ 0.5 A AC / 0.3 A DC (safe zone), ≤ 0.5 A AC / 1 A DC ( Zone 2)
Continuous current
≤ 62.5 VA / 32 W (safe area)
≤ 16 VA / 32 W (Zone 2)
Power rating
General data
Supply voltage
Power consumption
Ambient temperature / Storage temperature
Approvals
Approvals
19.2 – 31.2 V DC
≤ 3 W (2 channels)
/ -20 °C...60 °C / -20 °C...85 °C
cULus; DEKRAATEX; DETNORVER; EAC; FMEX; GOSTEX; GOSTME25;
IECEXDEK
Insulation coordination
Insulation voltage
Rated voltage
EMC standards
2.6 kV (input / output)
300 V
DIN EN 61326, NE 21
Ordering data
Type
1-channel version
ACT20X-HAI-SAO-S
2-channel version
ACT20X-2HAI-2SAO-S
Dimensions
Clamping range (nominal / min. / max.)
Depth x width x height
Note
2028820000
mm²
mm
Qty.
Order No.
1
8965430000
1
8965440000
Screw connection, Removable terminal block
2.5/0.5/2.5
113.6/22.5/117.2
CBX200 USB configuration adapter - 8978580000
B.7
Intrinsically safe signal conditioners
for hazardous area applications
ACT20X
Current output isolator, HART® Transparent
The ACT20X-SAI-HAO current output isolator is HART®-transparent. The input is connected to the safe area
controller or PLC, and the output is connected to an analog actuator in a hazardous area, e.g. Zone 0. It is
available in a single-channel or double-channel version.
EX area Zone 0, 1, 2, 20, 21, 22
Safe area Zone 2 / FM Class 1, Division 2
Ex Output signals
B
Input signals
Removable
terminals
(black)
LED Channel 1
red = defective,
flashing = fault
LED green
= supply
41
42
12
44
-
41
11
43
+
passive valve
Marker
Ch1
43
13
Ch 2
42
+
Load
4...20 mA
44
14
-
Channel 1:
Analogue, 4...20 mA
active input
Channel 2:
Power Supply and
Module Status
Load
4...20 mA
24
51
23
52
22
53
21
54
passive valve
Ex label (excerpt)
ATEX
II 3 G Ex nA nC IIC T4 Gc
II (1) G [Ex ia Ga] IIC/IIB/IIA
II (1) D [Ex ia Da] IIIC
IECEx
Ex nA nC IIC T4 Gc
[Ex ia Ga] IIC/IIB/IIA
[Ex ia Da] IIIC
FM
Installation in CL I DIV2 GP A-D T4
Kl. I-III ABT 1/2 GP A-G or
Kl. I Zn2 AEx/Ex nA nC [ia] IIC T4
Example:
ATEX version,
Ex output,
(More details in ATEX certificate)
Uo
Io
Po
IIC
IIB
IIA
Gnd. Supply +19,2...31,2 V DC
Module status
N.C.
Module status
28 V
93 mA
0.65 W
Co = 0.08 µF, Lo= 4 mH
Co = 0.65 µF, Lo= 16 mH
Co = 2.15 µF, Lo= 32 mH
Removable
terminals
(blue)
%
LED Channel 2
red = inactive,
flashing = fault
\
SIL
SUITABLE
61508
Application example: controlling an actuator in the Ex zone.
&RQWURO
V\VWHP
(;=RQH
$&VXSSO\
9'&
9
+$57YDOYH
$FWXDWRU
9'&
P$+$57LQSXW
2XWSXW²
&RQWUROV\VWHP
$FWXDWRU
P$+$57RXWSXW
3RVLWLRQ
WUDQVPLWWHU
$&7;6$,+$2
&RQWUROYDOYH
B.8
2028820000
Current output isolator
Intrinsically safe signal conditioners
for hazardous area applications
ACT20X
ACT20X-SAI-HAO-S / 2SAI-2HAO-S
• For controlling field devices located in explosion risk
zones
• HART® Transparent
• Relay output for error alarm
• PC configuration with FDT/DTM software, download at
www.weidmueller.com
• 1 or 2 channels in one module
B
I
I
PS
Technical data
Input
Input current
Voltage drop
Output analogue
Output current
Output signal limit
load impedance current
2-wire supply
Residual ripple (current loop)
Accuracy
Temperature coefficient
Step response time
Cut-off frequency (-3 dB)
Alarm output
Type
Nominal switching voltage
4…20mA
<2V
4…20 mA (max. 23 mA)
< 28 mA
≤ 725 Ω
> 14.5 V @ 20 mA
< 7.5 mVeff
< 0.1% span
< 0.01% of span/°C (TU)
≤ 5 ms
0.5…2.5 kHz @ 3.5…23 mA bi-directional HART® signal
Relay, 1 NC (voltage-free)
≤ 125 V AC / 110 V DC (safe area)
≤ 32 V AC / 32 V DC (Zone 2)
≤ 0.5 A AC / 0.3 A DC (safe zone), ≤ 0.5 A AC / 1 A DC ( Zone 2)
Continuous current
≤ 62.5 VA / 32 W (safe area)
≤ 16 VA / 32 W (Zone 2)
Power rating
General data
Supply voltage
Power consumption
Ambient temperature / Storage temperature
Approvals
Approvals
19.2 – 31.2 V DC
≤ 3 W (2 channels)
/ -20 °C...60 °C / -20 °C...85 °C
cULus; DEKRAATEX; DETNORVER; EAC; FMEX; GOSTEX; GOSTME25;
IECEXDEK
Insulation coordination
Insulation voltage
Rated voltage
EMC standards
2.6 kV (input / output)
300 V
DIN EN 61326, NE 21
Ordering data
Type
1-channel version
ACT20X-SAI-HAO-S
2-channel version
ACT20X-2SAI-2HAO-S
Dimensions
Clamping range (nominal / min. / max.)
Depth x width x height
Note
2028820000
mm²
mm
Qty.
Order No.
1
8965450000
1
8965460000
Screw connection, Removable terminal block
2.5/0.5/2.5
113.6/22.5/117.2
CBX200 USB configuration adapter - 8978580000
B.9
Intrinsically safe signal conditioners
for hazardous area applications
ACT20X
Temperature transducer
The ACT20X-HTI-SAO temperature transducer processes temperature signals from PT100 sensors and
thermocouples originating in the Ex zone. A current signal (mA) can also be connected as the input signal. The
input is part of an intrinsically safe circuit (Zone 0). The isolated milliamp analogue output is the input to the
receiver or controller in the safe area. It is available in a single-channel or double-channel version.
EX area Zone 0, 1, 2, 20, 21, 22
Safe area Zone 2 / FM Class 1, Division 2
,QSXWVLJQDOV
B
57'
&RQQHFWLRQ
ZLUHV
&KDQQHO
&XUUHQW
2XWSXWVLJQDOV
²
²
P$
P$
DFWLYHVHQVRU
SDVVLYHVHQVRU
57'
&RQQHFWLRQ
ZLUHV
&KDQQHO
&XUUHQW
DFWLYHVHQVRU
SDVVLYHVHQVRU
Ex label (excerp)
ATEX
II 3 G Ex nA nC IIC T4
II (1) G [Ex ia] IIC/IIB/IIA
II (1) D [Ex iaD]
IECEx
Ex nA nC IIC T4 Gc
[Ex ia Ga] IIC/IIB/IIA
LED Channel 1
red = defective,
flashing = fault
LED green
= supply
$QDORJXHP$
7&
Removable
terminals
(black)
SDVVLYHVHQVRU
ZLUHVXSSO\²
P$
P$
²
ZLUHVXSSO\
ZLUHVXSSO\²
P$
P$
²
Marker
&KDQQHO
&KDQQHO
ZLUHVXSSO\
DFWLYHRUSDVVLYHRXWSXW
6XSSO\DQGPRGXOHVWDWXV
7&
6XSSO\²
6XSSO\9'&
0RGXOHVWDWXV
1&
0RGXOHVWDWXV
SDVVLYHVHQVRU
FM
Installation in CL I DIV2 GP A-D T4
Kl. I-III ABT 1/2 GP A-G or
Kl. I Zn2 AEx/Ex nA nC [ia] IIC T4
Example:
ATEX version,
Ex input Temperature,
(More details in ATEX certificate)
Uo/Ui
Io/li
Po
Lo/Ro/L i
Ci
IIC
IIB
IIA
8.7 V / 10 V
18.4 mA / 30 mA
400 mW
892 µH/Ω / 820 nH
30 nF
Co = 5 µF,
Lo= 100 mH
Co = 50 µF, Lo= 300 mH
Co = 1000 µF, Lo= 700 mH
Removable
terminals
(blue)
LED Channel 2
red = defective,
flashing = fault
\%
SIL
SUITABLE
61508
Application example: temperature measurements in the Ex zone
(;=RQH
$&VXSSO\
9
5HVLVWDQFH
WHPSHUDWXUHVHQVRU
&RQWUROV\VWHP
,QSXWP$
$FWLYHSDVVLYH
=RQH
7DQN
B.10
Accuracy / temperature coefficients
ACT20X-HTI-SAO
Input
Accuracy
Input mA
Input RTD
Pt100
Ni100
Input TC
Type B
Type E, J, K, L, N, T, U
Type R, S, W3, W5, LR
Note
≤ ±4 μA
Temperature
coefficient
≤ ±4 μA / °C
≤ ±0.2 °C
≤ ±0.3 °C
≤ ±0.02 °C / °C
≤ ±0.03 °C / °C
≤ ±4.5 °C
≤ ±1 °C
≤ ±2 °C
≤ ±0.45 °C / °C
≤ ±0.1 °C / °C
≤ ±0.2 °C / °C
2028820000
Temperature transducer
Intrinsically safe signal conditioners
for hazardous area applications
ACT20X
ACT20X-HTI-SAO-S / 2HTI-2SAO-S
8VDEOHDV
‡6DIHW\EDUULHULQVXODWRU
‡6LJQDOFRQYHUVLRQ
‡ZLUHPHDVXULQJWUDQVGXFHU
‡$PSOLILHUUHSHDWHU
• Converts intrinsically safe RTD, thermocouple and mA
signals into analogue signals for safe zones.
• PC configuration with FDT/DTM software, download
link at www.weidmueller.com
• Relay output for failure alarm
• 1 or 2 channels in one module
• 2-channel module, can also be used as a signal splitter
B
J, I,U
I
PS
Technical data
Input
Type
Sensor supply
Temperature input range
Line resistance in measuring circuit
Input current
Input resistance, current
Output
Output current
intrinsically safe circuit, RTD, TC, DC (mA)
Configurable
≤ 50 Ω
0...20 mA, 4…20mA
20 Ω + PTC 50 Ω
0…23 mA, configurable: 0…20 / 4…20 / 20…0 / 20…4 mA,
configurable downscale (3.5 mA) ⁄ upscale (23 mA) @ error
3.8…20.5 mA / 0…20.5 mA (dependent on range)
≤ 600 Ω
≤ 0.01% of span / 100 Ω
Output signal limit
load impedance current
Influence of load resistance
Current loop output
Output current (current loop)
Load resistance
Influence of load resistance
2-wire supply
Alarm output
Type
Nominal switching voltage
4…20 mA
(UB - 3.5) / 0.023 A
≤ 0.01% of span / 100 Ω
3.5…26 V DC
Relay, 1 NC (voltage-free)
≤ 125 V AC / 110 V DC (safe area)
≤ 32 V AC / 32 V DC (Zone 2)
≤ 0.5 A AC / 0.3 A DC (safe zone), ≤ 0.5 A AC / 1 A DC ( Zone 2)
Continuous current
≤ 62.5 VA / 32 W (safe area)
≤ 16 VA / 32 W (Zone 2)
Power rating
General data
Supply voltage
Power consumption
Tightening torque, min. / Tightening torque, max.
Ambient temperature / Storage temperature
Approvals
Approvals
19.2 – 31.2 V DC
≤ 3 W (2 channels)
0.4 Nm / 0.6 Nm
/ -20 °C...60 °C / -20 °C...85 °C
cULus; DETNORVER; EAC; FMEX; GOSTEX; GOSTME25; IECEXKEM;
KEMAATEX
Insulation coordination
Insulation voltage
Rated voltage
EMC standards
7\SH
7HPSHUDWXUH $FFXUDF\
UDQJH
0HWDO37&
3W
«ƒ&
“[7&ODVV$
3W
«ƒ&
“ƒ&[7&ODVV%
3W
«ƒ&
1L
1L
«ƒ& “[7
1L
«ƒ& “[7
1L
7&7\SHDFFRUGLQJWR,(&
%
«ƒ& “.
«ƒ& “.
«ƒ& “.
(
«ƒ& “.
«ƒ& “.
-
«ƒ& “.
«ƒ& “.
.
«ƒ& “.
«ƒ& “.
«ƒ& “.
1
«ƒ& “.
«ƒ& “.
5
«ƒ& “.
ƒ& “.
6
«ƒ& “.
«ƒ& “.
7
«ƒ& “.
«ƒ& “.
DFFRUGLQJWR',1
8
«ƒ& “ƒ&
/
«ƒ& “ƒ&
2.6 kV (input / output)
300 V
DIN EN 61326, NE 21
Ordering data
Type
1-channel version
ACT20X-HTI-SAO-S
2-channel version
ACT20X-2HTI-2SAO-S
Dimensions
Clamping range (nominal / min. / max.)
Length x width x height
Note
2028820000
mm²
mm
Qty.
Order No.
1
8965470000
1
8965480000
Screw connection, Removable terminal block
2.5/0.5/2.5
22.5/117.2
CBX200 USB configuration adapter - 8978580000
B.11
Intrinsically safe signal conditioners
for hazardous area applications
ACT20X
Universal measurement and signal isolator-converter
The ACT20X-HUI-SAO-S is a universal input signal isolator/converter. This model processes temperature
signals from PT100 sensors and thermocouples as well as DC voltage and current signals (mA) from the
hazardous area. On the output side, an isolated milliamp signal is passed to the receiver or controller in the
safe area. This model also has a relay output which can be used for a process alarm or trip.
EX area Zone 0, 1, 2, 20, 21, 22
2XWSXWVLJQDOV
B
57'DQGOLQ5
FRQQHFWLRQ
FDEOHV
SDVVLYHVHQVRU SDVVLYHVHQVRU
&XUUHQW
&KDQQHO
DFWLYHSDVVLYHVHQVRU
Ex label (excerpt)
ATEX
II 3 G Ex nA nC IIC T4
II (1) G [Ex ia] IIC/IIB/IIA
II (1) D [Ex iaD]
IECEx
Ex nA nC IIC T4 Gc
[Ex ia Ga] IIC/IIB/IIA
[Ex ia a] IIIC
LED Channel 1
configurable
LED green
= supply
ZLUHVXSSO\
P$
P$
P$
²
Marker
²
ZLUHVXSSO\
5HOD\
12
5HOD\
DFWLYHRUSDVVLYHRXWSXW
6XSSO\DQGPRGXOHVWDWXV
9ROWDJH
²
Removable
terminals
(black)
$QDORJXHP$DQGUHOD\
DFWLYHVHQVRU
7[
,QSXWVLJQDOV
7&
&KDQQHO
3RWHQWLR
PHWHU
Safe area Zone 2 / FM Class 1, Division 2
DFWLYHVHQVRU
FM
Installation in CL I DIV2 GP A-D T4
Kl. I-III ABT 1/2 GP A-G or
Kl. I Zn2 AEx/Ex nA nC [ia] IIC T4
Example:
ATEX version,
Ex input External Current Source
(More details in ATEX certificate)
Ui / Uo
Ii / Io
Pi /Po
Ci
Li
IIC
IIB IIA 0DVV²
6XSSO\9'&
0RGXOHVWDWXV
1&
0RGXOHVWDWXV
30 V / 8.3 V
120 mA / 0.2 mA
900 mW / 0.4 mW
3 nF
1 μH
Lo=1000 mH
Co= 7 μF Lo=1000 mH
Co= 73 μF Co= 1000 μF Lo=1000 mH
Removable
terminals
(blue)
%
LED Channel 2
red = inactive,
flashing = fault
\
SIL
SUITABLE
61508
Application example: position measurement of an actuator
(;=RQH
$&VXSSO\
&RQWUROV\VWHP
9'&
9
2WKHUGHYLFHV
P$RXWSXW
3RVLWLRQDO
SRWHQWLRPHWHU
$&7;+8,6$2
9DOYH
B.12
3DVVLYH
LQSXW
FKDQQHO
Accuracy / temperature coefficients
ACT20X-HUI-SAO
Input
Accuracy
Input mA
Input Volt
Input RTD
Pt100
Ni100
Input TC
Type B
Type E, J, K, L, N, T, U
Type R, S, W3, W5, LR
Note
≤ ±4 μA
≤ ±20 μV
Temperature
coefficient
≤ ±4 μA / °C
≤ ±2 μV / °C
≤ ±0.2 °C
≤ ±0.3 °C
≤ ±0.02 °C / °C
≤ ±0.03 °C / °C
≤ ±4.5 °C
≤ ±1 °C
≤ ±2 °C
≤ ±0.45 °C / °C
≤ ±0.1 °C / °C
≤ ±0.2 °C / °C
2028820000
Universal signal converter
Intrinsically safe signal conditioners
for hazardous area applications
ACT20X
ACT20X-HUI-SAO-S
8VDEOHDV
‡6DIHW\EDUULHULQVXODWRU
‡6LJQDOFRQYHUVLRQ
‡ZLUHPHDVXULQJWUDQVGXFHU
‡$PSOLILHUUHSHDWHU
• Universal isolator for intrinsically safe RTD signals,
thermal sensor signals, resistor signals, potentiometer
signals and DC signals (mA,V)
• PC configuration with FDT/DTM software, download at
www.weidmueller.com
• Digital relay output adjustable as threshold switch
• Relay output for error alarm
B
J, I, U
I
PS
Technical data
Input
Type
intrinsically safe circuit, active (as current source) or passive (as
current sink)
28...16.5 V DC/0…20 mA
Adjustable from -200...+800°C
≤ 50 Ω
0...20 mA, 4…20mA, ± 25 mA
0…12 V DC, configurable: 0..1 / 0.2…1 / 0…5 / 0…10 and 2…10 V DC
Sensor supply
Temperature input range
Line resistance in measuring circuit
Input current
Input voltage
10 Ω…10 kΩ
> 10 MΩ @ 600 mV, 2 MΩ @ 28 V / 20 Ω + PTC 50 Ω
Potentiometer
Input resistance, voltage/current
Output analogue
Output current
0…23 mA, configurable: 0…20 / 4…20 / 20…0 / 20…4 mA,
configurable downscale (3.5 mA) ⁄ upscale (23 mA) @ error
3.8…20.5 mA / 0…20.5 mA (dependent on range)
≤ 600 Ω
≤ 0.01% of span / 100 Ω
Output signal limit
load impedance current
Influence of load resistance
Current loop output
Output current (current loop)
Load resistance
Influence of load resistance
2-wire supply
Output digital
Type
Function
Nominal switching voltage
4…20 mA
≤ (Vs - 10) / 20 mA (current loop)
≤ 0.01% of span / 100 Ω
≤ 26 V DC
Relay, 1 NO / NC contact
Configurable switching thresholds, Sensor error, Window function
≤ 250 V AC / 30 V DC (safe area)
≤ 32 V AC / 32 V DC (Zone 2)
≤ 2 A AC/DC (safe area, Zone 2 area)
Continuous current
Alarm output
Type
Nominal switching voltage
Relay, 1 NC (voltage-free)
≤ 125 V AC / 110 V DC (safe area)
≤ 32 V AC / 32 V DC (Zone 2)
≤ 0.5 A AC / 0.3 A DC (safe zone), ≤ 0.5 A AC / 1 A DC ( Zone 2)
Continuous current
General data
Supply voltage
Power consumption
Tightening torque, min. / Tightening torque, max.
Ambient temperature / Storage temperature
Approvals
Approvals
19.2 – 31.2 V DC
≤ 3.5 W
0.4 Nm / 0.6 Nm
/ -20 °C...60 °C / -20 °C...85 °C
cULus; DETNORVER; EAC; FMEX; GOSTEX; GOSTME25; IECEXKEM;
KEMAATEX
Insulation coordination
Insulation voltage / Rated voltage
EMC standards
Dimensions
Clamping range (nominal / min. / max.)
Length x width x height
Note
2028820000
7\SH
7HPSHUDWXUH $FFXUDF\
UDQJH
0HWDO37&
3W
«ƒ&
“[7&ODVV$
3W
«ƒ&
“ƒ&[7&ODVV%
3W
«ƒ&
1L
1L
«ƒ& “[7
1L
«ƒ& “[7
1L
7&7\SHDFFRUGLQJWR,(&
%
«ƒ& “.
«ƒ& “.
«ƒ& “.
(
«ƒ& “.
«ƒ& “.
-
«ƒ& “.
«ƒ& “.
.
«ƒ& “.
«ƒ& “.
«ƒ& “.
1
«ƒ& “.
«ƒ& “.
5
«ƒ& “.
ƒ& “.
6
«ƒ& “.
«ƒ& “.
7
«ƒ& “.
«ƒ& “.
DFFRUGLQJWR',1
8
«ƒ& “ƒ&
/
«ƒ& “ƒ&
2.6 kV (input / output) / 300 V
DIN EN 61326, NE 21
mm²
mm
Ordering data
Type
1-channel version
ACT20X-HUI-SAO-S
Qty.
1
Order No.
8965490000
Screw connection, Removable terminal block
2.5/0.5/2.5
22.5/117.2
CBX200 USB configuration adapter - 8978580000
B.13
Intrinsically safe signal conditioners
for hazardous area applications
ACT20X
Output loop powered universal measurement and signal isolating converter
The ACT20X-HUI-SAO-LP is a universal input, isolating signal converter. This model processes temperature
signals from PT100 sensors and thermocouples as well as DC voltage and current signals (mA) from the
hazardous area. The 12.5 mm wide module is powered through it‘s 4-20 mA output.
EX area Zone 0, 1, 2, 20, 21, 22
B
Safe area Zone 2 / FM Class 1, Division 2
Input signals
Removable
terminals
(black)
Output signals
Marker
RTD/RES
POT
2-wire
3-wire
TC
mV
mA
+
+
Volt
11
-
41
12
42
- Loop Powered (4-20 mA)
+Loop Powered (4-20 mA)
21
+
22
-20 ≤ Ta ≤ +60 °C
Zone 2 / FM Cl. 1, div. 2,
gr. A-D or safe area
Zone 0, 1, 2, 20, 21, 22 /
Cl. I/II/III, div. 1 gr. A-G
Ex label
ATEX
II 3 G Ex nA nC IIC T4
II (1) G [Ex ia] IIC/IIB/IIA
II (1) D [Ex iaD]
IECEx
Ex nA IIC T4 Gc
[Ex ia Ma Ga] I/IIC [Ex ia Da] IIIC
Example:
IECEx version
(More details in IECEx certificate)
Uo
Io
Po
Ci
Li
Removable
terminals
(blue)
5.88 V
3.1 mA
4.6 mW
0.001 μF
negligible
%
\
Application example: Temperature measurement in the EX-zone
(;=RQH
6DIH=RQH
&RQWURO
V\VWHP
5HVLVWDQFH
WHPSHUDWXUHVHQVRU
P$2XWSXW
=RQH
7DQN
B.14
$&7;+8,6$2
,QSXW
FKDQQHO
DFWLYH
Accuracy / temperature coefficients
ACT20X-HUI-SAO-LP
Input
Accuracy
Input mA
Input Volt
Input RTD
Pt100
Ni100
Input TC
Type B
Type E, J, K, L, N, T, U
Type R , S, W3, W5, LR
Note
≤ ±4 μA
≤ ±20 μV
Temperature
coefficient
≤ ±4 μA / °C
≤ ±2 μV / °C
≤ ±0.2 °C
≤ ±0.3 °C
≤ ±0.02 °C / °C
≤ ±0.03 °C / °C
≤ ±4.5 °C
≤ ±1 °C
≤ ±2 °C
≤ ±0.45 °C / °C
≤ ±0.1 °C / °C
≤ ±0.2 °C / °C
2028820000
Universal measurement and signal isolatorconverter
Output-loop powered
Intrinsically safe signal conditioners
for hazardous area applications
ACT20X
ACT20X-HUI-SAO-LP-S
• Universal isolator for intrinsically safe RTD signals,
thermal sensor signals, resistor signals, potentiometer
signals and DC signals (mA,V)
• Supply via output loop
• 12.5 mm thin housing
• PC configuration with FDT/DTM software, download at
www.weidmueller.com
B
J, I, U
I
Technical data
Potentiometer
Input resistance, voltage/current
Output analogue
Output current
load impedance current
Residual ripple (current loop)
Accuracy
Temperature coefficient
Step response time
Cut-off frequency (-3 dB)
General data
Supply voltage
Tightening torque, min. / Tightening torque, max.
Ambient temperature / Storage temperature
Approvals
Approvals
4…20 mA (max. 23 mA)
≤ 700 Ω
≤ 10 mVss
< 0.1 % of end value
< 0.02 °C of measuring range / °C
< 400 ms (10…90 %)
100 Hz
via output current loop, 11…28 V DC (loop powered)
0.4 Nm / 0.6 Nm
/ 0 °C...60 °C / -20 °C...70 °C
CE; EAC; GOSTEX
Insulation coordination
Insulation voltage / Rated voltage
Rated voltage
Standards
3.51 kV between input and output / 300 Veff
300 Veff
DIN EN 61326-1, IEC 61010-1, IEC 61010-2-030, IEC 60079-0, IEC
60079-11, IEC 60079-15, IEC 60079-26
4 kV (1.2/50 µs)
III
2
Impulse withstand voltage
Overvoltage category
Pollution degree
Inputs
Type
Thermocouples (TC), RTD, mA,
Volt, mV, resistor, potentiometer
Type Standard
Lower
Upper
Min.
limit
limit
area
B
100 °C
1820 °C
400 °C
E
-270 °C
1000 °C
IEC584
J
-270 °C
1200 °C
80 °C
K
-270 °C
1372 °C
L
DIN43710 -100 °C
900 °C
N
-180 °C
1300 °C
100 °C
R, S
IEC584
-50 °C
1768 °C
300 °C
T
-270 °C
400 °C
80 °C
U
DIN43710 -200 °C
600 °C
100 °C
User-defined Input
Up to 101 values
Error detection
Upper error signalling value:
23 mA,
Lower error signalling value:
3,5 mA
mA
±25 mA @ 70 Ω
4 mA
±28 V @ 2 MΩ
2,0 V
Volt
±12 V @ 2 MΩ
1,0 V
±600 mV @ >10 MΩ
50 mV
mV
±150 mV @ >10 MΩ
15 mV
Type Standard
Lower
Upper
Min.
limit
limit
area
Pt100,
Pt200
-200 °C
850 °C
-20 °C
Pt1000 DIN43710
Ni120
-80 °C
320 °C
15 °C
Cu10
-100 °C
260 °C
100 °C
User-defined Input
Up to 101 values
Resistance
0 to12 kΩ
500 Ω
0 to15 kΩ
100 Ω
0 to 750 Ω
50 Ω
Potentiometer
1.2 kΩ to 500 kΩ
Thermocouple inputs
intrinsically safe circuit
Adjustable from -200...+800°C
configurable, ± 25 mA, 0...20 mA, 4…20mA
configurable, ± 12 V DC (min. measurement range 1 V), ± 28 V DC
(min. measurement range 2 V), ± 600 mV DC (min. measurement
range 50 mV), ± 150 mV DC (min. measurement range 15 mV)
10 Ω…10 kΩ
> 10 MΩ @ 600 mV, 2 MΩ @ 28 V / 70 Ω
2-, 3-, 4-wire RTD
Input
Type
Temperature input range
Input current
Input voltage
Ordering data
Type
1-channel version
ACT20X-HUI-SAO-LP-S
Dimensions
Clamping range (nominal / min. / max.)
Depth/Width/Height
Note
2028820000
mm²
Qty.
1
Order No.
1318220000
Screw connection, Removable terminal block
2.5/0.5/2.5
113.6/12.5/117.2117.2
CBX200 USB configuration adapter - 8978580000
B.15
Intrinsically safe signal conditioners
for hazardous area applications
ACT20X
NAMUR isolating switching amplifier: with relay output
The ACT20X-HDI-SDO-RNO (NC) isolating switching amplifier is a specialised signal isolating converter
for Namur sensor signals or for volt-free contacts from a Zone 0 hazardous area. A single relay, available
optionally as NC or NO, provides the output signal in the safe zone. Single-channel or double-channel versions
are also available.
EX area Zone 0, 1, 2, 20, 21, 22
Safe area Zone 2 / FM Class 1, Division 2
Input signals
B
NAMUR
Mechanical
switch
+
Channel 1:
Output signals
Rs
Rp
–
Rp
44
14
44
43
13
43
42
12
42
41
11
41
LED Channel 1
yellow = active
flashing red
= fault
Removable
terminals
(black)
LED green
= supply
Relay
Channel 2:
N.O. or N.C.
Marker
Relay
Relay
Channel 1:
N.O. or N.C.
Relay
Power supply
NAMUR
Mechanical
switch
Channel 2:
+
Rs
Rp
–
Ex label (excerpt)
ATEX
II 3 G Ex nA nC IIC T4
II (1) G [Ex ia Ga] IIC/IIB/IIA
II (1) D [Ex iaD]
IECEx
Ex nA nC IIC T4 Gc
[Ex ia Ga] IIC/IIB/IIA
[Ex ia Da] IIIC
Rp
24
51
23
52
22
53
21
54
FM
Installation in CL I DIV2 GP A-D T4
Kl. I-III ABT 1/2 GP A-G oder
Kl. I Zn2 AEx/Ex nA nC [ia] IIC T4
Example:
ATEX version,
Ex input
(More details in ATEX certificate)
Gnd. –
Supply +19,2...31,2 V DC
Module status
N.C.
Module status
Uo
Io
Po
Lo / Ro IIC
IIB
IIA
10.6 V
12 mA
32 mW
1150 µH/Ω
Co = 2 µF,
Co = 6 µF,
Co = 18 µF,
LED Channel 2
yellow = active
flashing red
= fault
Removable
terminals
(blue)
Lo= 260 mH
Lo= 780 mH
Lo= 1000 mH
%
\
SIL
SUITABLE
61508
Application: monitoring of fill level with the ACT20X HDI-SDO-RNO (relay output)
(;=RQH
$&VXSSO\
&RQWURO
9'&
9
/HYHOLQGLFDWRU
&KDQQHOGLJLWDOLQSXW
2WKHUFRQYHUWHU
&KDQQHOGLJLWDORXWSXW
=RQH
$&7;+',6'2512
7DQN
B.16
2028820000
Intrinsically safe signal conditioners
for hazardous area applications
ACT20X
ACT20X-HDI-SDO-RNO-S / RNC-S
ACT20X-2HDI-2SDO-RNO-S / RNC-S
NAMUR isolating switching amplifier
• Converts intrinsically safe digital signals (NAMUR /
switching contact) from EX Zone 0 into digital output
signals (relay output) for the safe zone
• PC configuration with FDT/DTM software, download at
www.weidmueller.com
• Relay output for error alarm, cable break, short-circuit
• 1 or 2 channels in one module
B
PS
Technical data
Input
Sensor
Sensor supply
Resistance
Input frequency
Pulse duration
Input resistance
Trigger level low / Trigger level high
Output signal in case of wire break
Output
Type
NAMUR sensor, according to EN60947, switch with or without RS, RP
8 V DC / 8 mA
RP = 750 Ω / RS = 15kΩ
0...5 kHz
> 0.1 ms
1 kΩ
< 1.2 mA / > 2.1 mA
< 0.1 mA, > 6.5 mA (in case of wire break)
Relay, 2 NC (voltage-free), Switching frequency 20 Hz, digital, output =
input, direct or inverse (configurable)
≤ 250 V AC / 30 V DC (safe area)
≤ 32 V AC / 32 V DC (Zone 2)
≤ 2 A AC/DC (safe area, Zone 2 area)
≤ 500 VA / 60 W (safe area)
≤ 16 VA / 32 W (Zone 2)
Rated switching voltage
Continuous current
Power rating
Alarm output
Type
Nominal switching voltage
Relay, 1 NC (voltage-free)
≤ 125 V AC / 110 V DC (safe area)
≤ 32 V AC / 32 V DC (Zone 2)
≤ 0.5 A AC / 0.3 A DC (safe zone), ≤ 0.5 A AC / 1 A DC ( Zone 2)
Continuous current
≤ 62.5 VA / 32 W (safe area)
≤ 16 VA / 32 W (Zone 2)
Power rating
General data
Supply voltage
NAMUR supply
Power consumption
Tightening torque, min. / Tightening torque, max.
Ambient temperature / Storage temperature
Approvals
Approvals
19.2 – 31.2 V DC
8 V DC / 8 mA
≤ 3 W (2 channels)
0.4 Nm / 0.6 Nm
/ -20 °C...60 °C / -20 °C...85 °C
cULus; DETNORVER; EAC; FMEX; GOSTEX; GOSTME25; IECEXKEM;
KEMAATEX
Insulation coordination
Insulation voltage
Rated voltage
EMC standards
2.6 kV (input / output)
300 V
DIN EN 61326, NE 21
Ordering data
Dimensions
Clamping range (nominal / min. / max.)
Length x width x height
Note
2028820000
mm²
mm
Screw connection, Removable terminal block
2.5/0.5/2.5
22.5/117.2
Type
1-channel version, NC
ACT20X-HDI-SDO-RNC-S
1-channel version, NO
ACT20X-HDI-SDO-RNO-S
2-channel version, NC
ACT20X-2HDI-2SDO-RNC-S
2-channel version, NO
ACT20X-2HDI-2SDO-RNO-S
Qty.
Order No.
1
8965350000
1
8965340000
1
8965380000
1
8965370000
CBX200 USB configuration adapter - 8978580000
B.17
Intrinsically safe signal conditioners
for hazardous area applications
ACT20X
Pulse Isolator, with NPN transistor output.
The ACT20X-HDI-SDO isolating switching amplifier is a digital pulse signal isolator for Namur sensors or
volt-free contacts from a Zone 0 hazardous area. A transistor (NPN) output is provided for the receiver or
controller in the safe area. Single-channel or double-channel versions are also available.
EX area Zone 0, 1, 2, 20, 21, 22
Safe area Zone 2 / FM Class 1, Division 2
Input signals
Output signals
B
NAMUR
Mechanical
switch
Channel 1:
+
Rs
Rp
–
Rp
44
14
44
43
13
43
42
12
42
41
11
41
LED Channel 1
yellow = active
flashing red
= fault
Removable
terminals
(black)
LED green
= supply
Opto +
Marker
Channel 2:
Opto –
Opto +
Channel 1:
Opto –
Power Supply
NAMUR
Mechanical
switch
Channel 2:
+
Rs
Rp
–
Ex label (excerpt)
ATEX
II 3 G Ex nA nC IIC T4
II (1) G [Ex ia Ga] IIC/IIB/IIA
II (1) D [Ex iaD]
IECEx
Ex nA nC IIC T4 Gc
[Ex ia Ga] IIC/IIB/IIA
[Ex ia Da] IIIC
Rp
24
51
23
52
22
53
21
54
FM
Installation in CL I DIV2 GP A-D T4
Kl. I-III ABT 1/2 GP A-G oder
Kl. I Zn2 AEx/Ex nA nC [ia] IIC T4
Example:
ATEX version
Ex input
(More details in ATEX certificate)
Gnd –
Supply +19,2...31,2 V DC
Module status
N.C.
Module status
Uo
Io
Po
Lo / Ro IIC
IIB
IIA
10.6 V
12 mA
32 mW
1150 µH/Ω
Co = 2 µF,
Co = 6 µF,
Co = 18 µF,
Removable
terminals
(blue)
Lo= 260 mH
Lo= 780 mH
Lo= 1000 mH
%
LED Channel 2
yellow = active
flashing red
= fault
\
SIL
SUITABLE
61508
Application: monitoring the fill level with isolating switching amplifier
(;=RQH
$&VXSSO\
&RQWURO
9'&
9
/HYHOLQGLFDWRU
&KDQQHOGLJLWDOLQSXW
2WKHUFRQYHUWHU
&KDQQHOGLJLWDORXWSXW
=RQH
$&7;+',6'2512
7DQN
B.18
2028820000
NAMUR isolating switching amplifier
Intrinsically safe signal conditioners
for hazardous area applications
ACT20X
ACT20X-HDI-SDO-S / 2HDI-2SDO-S
• Converts intrinsically safe signals (NAMUR / switching
contact) from EX Zone 0 into digital output signals
(relay output) for the safe zone
• PC configuration with FDT/DTM software, download at
www.weidmueller.com
• Relay output for error alarm
• 1 or 2 channels in one module
B
PS
Technical data
Input
Sensor
Sensor supply
Resistance
Input frequency
Pulse duration
Input resistance
Trigger level low / Trigger level high
Output signal in case of wire break
Output
Type
NAMUR sensor, according to EN60947, switch with or without RS, RP
8 V DC / 8 mA
Parallel resistor 15kΩ, Series resistor 750Ω
0...5 kHz
> 0.1 ms
1 kΩ
< 1.2 mA / > 2.1 mA
< 0.1 mA, > 6.5 mA (in case of wire break)
NPN transistor output, digital, output = input, direct or inverse
(configurable)
5 kHz
> 0.1 ms
≤ 30 V DC
≤ 80 mA / ≤ 2.4 W
< 2.5 V DC
Switching frequency
Pulse duration
Rated switching voltage
Power rating
Voltage drop at max. load
Alarm output
Type
Nominal switching voltage
Relay, 1 NC (voltage-free)
≤ 125 V AC / 110 V DC (safe area)
≤ 32 V AC / 32 V DC (Zone 2)
≤ 0.5 A AC / 0.3 A DC (safe zone), ≤ 0.5 A AC / 1 A DC ( Zone 2)
Continuous current
≤ 62.5 VA / 32 W (safe area)
≤ 16 VA / 32 W (Zone 2)
Power rating
General data
Power consumption
Supply voltage
NAMUR supply
Power consumption
Tightening torque, min. / Tightening torque, max.
Ambient temperature / Storage temperature
Approvals
Approvals
≤ 3 W (2 channels)
19.2 – 31.2 V DC
8 V DC / 8 mA
≤ 3 W (2 channels)
0.4 Nm / 0.6 Nm
/ -20 °C...60 °C / -20 °C...85 °C
cULus; DETNORVER; EAC; FMEX; GOSTEX; GOSTME25; IECEXKEM;
KEMAATEX
Insulation coordination
Insulation voltage
Rated voltage
EMC standards
2.6 kV (input / output)
300 V
DIN EN 61326, NE 21
Ordering data
Type
1-channel version
ACT20X-HDI-SDO-S
2-channel version
ACT20X-2HDI-2SDO-S
Dimensions
Clamping range (nominal / min. / max.)
Length x width x height
Note
2028820000
mm²
mm
Qty.
Order No.
1
8965360000
1
8965390000
Screw connection, Removable terminal block
2.5/0.5/2.5
22.5/117.2
CBX200 USB configuration adapter - 8978580000
B.19
Intrinsically safe signal conditioners
for hazardous area applications
ACT20X
Valve control component for gas group IIC, 35 mA
The ACT20X-SDI-HAO-S solenoid/actuator driver takes a switched input from e.g. a safe area controller and
delivers an corresponding output to operate an actuator in a hazardous area, e.g. Zone 0. It is available in a
single-channel or double-channel version.
EX area Zone 0, 1, 2, 20, 21, 22
Save area Zone 2 /FM Kl. 1 Abt. 2
Ex-Output Signals
B
Solenoid
Channel 1:
Alarm
Input signals
44
14
42
43
13
41
42
12
44
41
11
43
Removable
terminals
(black)
LED Channel 1
yellow = active
red = fault
LED green
= supply
+V
+V
Marker
+V
+V
Power Supply
Solenoid
Channel 2:
Alarm
Ex label (excerpt)
ATEX
II 3 G Ex nA nC IIC T4
II (1) G [Ex ia Ga] IIC/IIB/IIA
II (1) D [Ex iaD]
IECEx
Ex nA nC IIC T4 Gc
[Ex ia Ga] IIC/IIB/IIA
[Ex ia Da] IIIC
24
51
23
52
22
53
21
54
FM
Installation in CL I DIV2 GP A-D T4
Kl. I-III ABT 1/2 GP A-G oder
Kl. I Zn2 AEx/Ex nA nC [ia] IIC T4
Example:
ATEX version
Ex Output Terminal (11-14)
(More details in ATEX certificate)
Gnd –
Supply +19,2...31,2 V DC
Module status
N.C.
Module status
Uo
Io
Po
IIC
IIB
IIA
28 V
100 mA
0.70 mW
Co = 0.08 µF, Lo= 2.9 mH
Co = 0.64 µF, Lo= 12.8 mH
Co = 2.1 µF, Lo= 22.8 mH
Removable
terminals
(blue)
%
LED Channel 2
yellow = active
red = fault
\
SIL
SUITABLE
61508
Application: Inflow control in Ex zone with gas group IIC
&RQWURO
V\VWHP
(;=RQH
,JQLWLRQSURWHFWLRQJURXS,,&
$&VXSSO\
Output data For gas group IIC (≤ 35 mA)
([DODUPVLUHQ
9'&
Connection terminal
Channel 1
U without load
11-12
Min. 24 V
11-13
Min. 24 V
11-14
Min. 24 V
Note
$ODUPVLJQDO
&KDQQHOGLJLWDOLQSXW
&KDQQHOGLJLWDORXWSXW
&KDQQHOGLJLWDOLQSXW
&KDQQHOGLJLWDORXWSXW
=RQH
$&7;6',+'2
9DOYHRSHQ
FORVHGVLJQDO
B.20
6ROHQRLGYDOYH
7DQN
U with load
Min. 12.5 V
Min. 13.5 V
Min. 14.5 V
I max
35 mA
35 mA
35 mA
For gas group IIC (≤ 35 mA)
Connection terminal
Channel 2
U without load
21-22
Min. 24 V
21-23
Min. 24 V
21-24
Min. 24 V
Note
U with load
Min. 12.5 V
Min. 13.5 V
Min. 14.5 V
I max
35 mA
35 mA
35 mA
2028820000
Valve control module
Intrinsically safe signal conditioners
for hazardous area applications
ACT20X
ACT20X-SDI-HDO / 2SDI-2HDO
• Valve control component for control of intrinsically safe
valves, LEDs, acoustic alarms, etc.
• PC configuration with FDT/DTM software, download at
www.weidmueller.com
• Output current is limited to 35 mA for ignition group IIC
• 1 or 2 channels in one module
• Relay output for error alarm
B
PS
Technical data
Input
Type
Input voltage
Input resistance, voltage
Trigger level low
Trigger level high
Alarm output
Type
Nominal switching voltage
NPN, PNP switching signal
≤ 28 V DC
3.5 kΩ
≤ 2.0 V DC (NPN), ≤ 8.0 V DC (PNP)
≥ 4.0 V DC (NPN), ≥ 10V DC (PNP)
Relay, 1 NC (voltage-free)
≤ 125 V AC / 110 V DC (safe area)
≤ 32 V AC / 32 V DC (Zone 2)
≤ 0.5 A AC / 0.3 A DC (safe zone), ≤ 0.5 A AC / 1 A DC ( Zone 2)
Continuous current
≤ 62.5 VA / 32 W (safe area)
≤ 16 VA / 32 W (Zone 2)
Power rating
General data
Supply voltage
Power consumption
Tightening torque, min. / Tightening torque, max.
Ambient temperature / Storage temperature
Approvals
Approvals
19.2 – 31.2 V DC
≤ 3.5 W (with 2 channels)
0.4 Nm / 0.6 Nm
/ -20 °C...60 °C / -20 °C...85 °C
cULus; DETNORVER; EAC; FMEX; GOSTEX; GOSTME25; IECEXKEM;
KEMAATEX
Insulation coordination
Insulation voltage
Rated voltage
EMC standards
2.6 kV (input / output)
300 V
DIN EN 61326, NE 21
Ordering data
Type
1-channel version
ACT20X-SDI-HDO-L-S
2-channel version
ACT20X-2SDI-2HDO-S
Dimensions
Clamping range (nominal / min. / max.)
Length x width x height
Note
2028820000
mm²
mm
Qty.
Order No.
1
8965400000
1
8965420000
Screw connection, Removable terminal block
2.5/0.5/2.5
22.5/117.2
CBX200 USB configuration adapter - 8978580000
B.21
Intrinsically safe signal conditioners
for hazardous area applications
ACT20X
Valve control component for gas group IIB, 60 mA
The ACT20X-SDI-HAO-S solenoid/actuator driver takes a switched input from e.g. a safe area controller and
delivers an corresponding output to operate an actuator in a hazardous area, e.g. Zone.
This driver is suitable for switching solenoid valves or alarm devices.
EX area Zone 0, 1, 2, 20, 21, 22
Safe area Zone 2 / FM Class 1, Division 2
Ex Output Signals
B
Alarm
Input Signals
Channel 1:
Solenoid
44
14
42
43
13
41
42
12
44
41
11
43
Removable
terminals
(black)
LED
LED green
= supply
+V
+V
Marker
+V
+V
Power supply
51
52
53
54
Ex label (excerpt)
ATEX
II 3 G Ex nA nC IIC T4
II (1) G [Ex ia Ga] IIC/IIB/IIA
II (1) D [Ex iaD]
IECEx
Ex nA nC IIC T4 Gc
[Ex ia Ga] IIC/IIB/IIA
[Ex ia Da] IIIC
FM
Installation in CL I DIV2 GP A-D T4
Kl. I-III ABT 1/2 GP A-G oder
Kl. I Zn2 AEx/Ex nA nC [ia] IIC T4
Example:
ATEX version,
Ex Output Terminal (11-14)
(More details in ATEX certificate)
Gnd –
+19,2...31.2 V DC
Module status
N.C.
Module status
Uo
Io
Po
IIC
IIB
IIA
28 V
135 mA
0.95 W
Co = –,
L o= –
Co = 0.64 µF, Lo= 7.8 mH
Co = 2.1 µF, Lo= 15.1 mH
Removable
terminals
(blue)
%
\
SIL
SUITABLE
61508
Application: Inflow control in Ex zone with gas group IIB
&RQWURO
V\VWHP
(;=RQH
,JQLWLRQSURWHFWLRQJURXS,,&
$&VXSSO\
9'&
Output data For gas group IIB (≤ 60 mA)
&KDQQHOGLJLWDO2XWSXW
&KDQQHOGLJLWDO,QSXW
$&7;6',+'2
B.22
9DOYHRSHQ
FORVHGVLJQDO
6ROHQRLGYDOYH
=RQH
7DQN
Connection terminal
Channel 1
U without load U with load
Min. 9 V
11-12
Min. 24 V
Min. 11.5 V
Min. 12.5 V
11-13
Min. 24 V
Min. 10 V
Min. 11 V
11-14
Min. 24 V
Min. 13 V
Note
I max
60 mA
50 mA
60 mA
50 mA
60 mA
50 mA
2028820000
Valve control component
Intrinsically safe signal conditioners
for hazardous area applications
ACT20X
ACT20X-SDI-HDO-H-S
• Valve control component for control of intrinsically safe
valves, LEDs, acoustic alarms, etc.
• PC configuration with FDT/DTM software, download at
www.weidmueller.com
• Output current is limited to 35 mA for ignition group IIC
• 1 or 2 channels in one module
• Relay output for error alarm
B
PS
Technical data
Input
Type
Input voltage
Input resistance, voltage
Trigger level low
Trigger level high
Alarm output
Type
Nominal switching voltage
NPN, PNP switching signal
≤ 28 V DC
3.5 kΩ
≤ 2.0 V DC (NPN), ≤ 8.0 V DC (PNP)
≥ 4.0 V DC (NPN), ≥ 10V DC (PNP)
Relay, 1 NC (voltage-free)
≤ 125 V AC / 110 V DC (safe area)
≤ 32 V AC / 32 V DC (Zone 2)
≤ 0.5 A AC / 0.3 A DC (safe zone), ≤ 0.5 A AC / 1 A DC ( Zone 2)
Continuous current
≤ 62.5 VA / 32 W (safe area)
≤ 16 VA / 32 W (Zone 2)
Power rating
General data
Supply voltage
Power consumption
Tightening torque, min. / Tightening torque, max.
Ambient temperature / Storage temperature
Approvals
Approvals
19.2 – 31.2 V DC
<2W
0.4 Nm / 0.6 Nm
/ -20 °C...60 °C / -20 °C...85 °C
cULus; DETNORVER; EAC; FMEX; GOSTEX; GOSTME25; IECEXKEM;
KEMAATEX
Insulation coordination
Insulation voltage
Rated voltage
EMC standards
2.6 kV (input / output)
300 V
DIN EN 61326, NE 21
Ordering data
Type
1-channel version
ACT20X-SDI-HDO-H-S
Dimensions
Clamping range (nominal / min. / max.)
Length x width x height
Note
2028820000
mm²
mm
Qty.
1
Order No.
8965410000
Screw connection, Removable terminal block
2.5/0.5/2.5
22.5/117.2
CBX200 USB configuration adapter - 8978580000
B.23
B
B.24
2028820000
Intrinsically safe signal conditioners
for hazardous area applications