Specifications

3RHP Series AC Control
te
• 100K-cycle UL508 Endurance Rating for Enhanced Reliability
• 40 and 50A output
• Voltage ratings to 600 VAC
• Lifetime 2 million operations at full load
• LED input status indicator
• Wire, lug or quick connect termination
• Industry Standard DP contactor mounting
PRODUCT SELECTION (by control voltage and output rating)
20-26 VAC
100-130 VAC
208-240 VAC
40A 280 VAC
50A 280 VAC
40A 600 VAC
50A 600 VAC
3RHP2840E
3RHP2840F
3RHP2840G
3RHP2850E
3RHP2850F
3RHP2850G
3RHP6040E
3RHP6040F
3RHP6040G
3RHP6050E
3RHP6050F
3RHP6050G
ol
e
Control Voltage
OUTPUT SPECIFICATIONS (voltage)
Description
Operating Voltage (47-63Hz) [Vrms]
Maximum Off-State Leakage Current per channel
280 VAC
600 VAC
24-280
0.05 mA @ 240 VAC
48-600
0.06 mA @ 480 VAC
OUTPUT SPECIFICATIONS (current)
Description
40A
50A
Maximum Load Current per phase @ 40°C [Arms] (1)
40A Resistive
Power terminals
1/4" Quick Connect and 10x32 binder
head screws
Wire Size
8-14 AWG
50A Resistive
1/4" Quick Connect and box lugs
6-14 AWG
bs
INPUT SPECIFICATIONS
Description
Coil Voltage [50/60 Hz]
Min. Turn-On Voltage
Min. Turn-Off Voltage
Coil Power Consumption, inrush.
Coil Power Consumption, sealed.
SUFIX E
SUFIX F
SUFIX G
20-26 VAC
20 VAC
12 VAC
56 VA @ 24 VAC
6.6 VA @ 24 VAC
100-130 VAC
100 VAC
24 VAC
56 VA @ 120 VAC
6.6 VA @ 120 VAC
208-240 VAC
208 VAC
48 VAC
56 VA @ 220 VAC
6.6 VA @ 220 VAC
GENERAL SPECIFICATIONS
Description
O
Dielectric Strength, Input to Output
Dielectric Strength, Input/Output to ground
Contacts (2)
Ambient Operating Temperature Range (3)
Ambient Storage Temperature Range
Max. Turn-On Time 50/60 Hz
Max. Turn-Off Time 50/60Hz
Maximum Number of Operations
Lifetime Number of Operations @ Rated Current (4)
Weight (typical)
Screw Torque (input/Output) 40A
Screw Torque (input/Output) 50A
Parameters
4000 Vrms
2500 Vrms
Three Normally Open
-20 to 65 °C
-40 to 100 °C
20 ms / 16.6 ms
40 ms / 32 ms
30 per Minute
> 2 Million
1.19 lbs (540 g)
4.4-5 in lb (0.5-0.6 Nm) / 15-18 in lb (1.7-2.1 Nm)
4.4-5 in lb (0.5-0.6 Nm) / 20-25 in lb (2.2-2.9 Nm)
GENERAL NOTES
(1)
(2)
(3)
(4)
See Derating curves for additional operating conditions.
The RHP includes a Solid State Relay, therefore electrical isolation is not provided.
The RHP includes over temperature protection for the solid state relay.
40°C ambient temperature, 30 operations/min, maximum voltage control.
ol
e
te
MECHANICAL SPECIFICATIONS
O
bs
THERMAL DERATE INFORMATION
bs
ol
e
te
TYPICAL ELECTRICAL CONNECTIONS
O
AGENCY APPROVALS
UL/cUL UL508, E116950
EN60950-1-2006
Rev.063011
O
bs
ol
e
te
ACCESSORIES
O
te
ol
e
bs
O
bs
ol
e
te
ANNEX - ENVIROMENTAL INFORMATION