3RHP Series AC Control te • 100K-cycle UL508 Endurance Rating for Enhanced Reliability • 40 and 50A output • Voltage ratings to 600 VAC • Lifetime 2 million operations at full load • LED input status indicator • Wire, lug or quick connect termination • Industry Standard DP contactor mounting PRODUCT SELECTION (by control voltage and output rating) 20-26 VAC 100-130 VAC 208-240 VAC 40A 280 VAC 50A 280 VAC 40A 600 VAC 50A 600 VAC 3RHP2840E 3RHP2840F 3RHP2840G 3RHP2850E 3RHP2850F 3RHP2850G 3RHP6040E 3RHP6040F 3RHP6040G 3RHP6050E 3RHP6050F 3RHP6050G ol e Control Voltage OUTPUT SPECIFICATIONS (voltage) Description Operating Voltage (47-63Hz) [Vrms] Maximum Off-State Leakage Current per channel 280 VAC 600 VAC 24-280 0.05 mA @ 240 VAC 48-600 0.06 mA @ 480 VAC OUTPUT SPECIFICATIONS (current) Description 40A 50A Maximum Load Current per phase @ 40°C [Arms] (1) 40A Resistive Power terminals 1/4" Quick Connect and 10x32 binder head screws Wire Size 8-14 AWG 50A Resistive 1/4" Quick Connect and box lugs 6-14 AWG bs INPUT SPECIFICATIONS Description Coil Voltage [50/60 Hz] Min. Turn-On Voltage Min. Turn-Off Voltage Coil Power Consumption, inrush. Coil Power Consumption, sealed. SUFIX E SUFIX F SUFIX G 20-26 VAC 20 VAC 12 VAC 56 VA @ 24 VAC 6.6 VA @ 24 VAC 100-130 VAC 100 VAC 24 VAC 56 VA @ 120 VAC 6.6 VA @ 120 VAC 208-240 VAC 208 VAC 48 VAC 56 VA @ 220 VAC 6.6 VA @ 220 VAC GENERAL SPECIFICATIONS Description O Dielectric Strength, Input to Output Dielectric Strength, Input/Output to ground Contacts (2) Ambient Operating Temperature Range (3) Ambient Storage Temperature Range Max. Turn-On Time 50/60 Hz Max. Turn-Off Time 50/60Hz Maximum Number of Operations Lifetime Number of Operations @ Rated Current (4) Weight (typical) Screw Torque (input/Output) 40A Screw Torque (input/Output) 50A Parameters 4000 Vrms 2500 Vrms Three Normally Open -20 to 65 °C -40 to 100 °C 20 ms / 16.6 ms 40 ms / 32 ms 30 per Minute > 2 Million 1.19 lbs (540 g) 4.4-5 in lb (0.5-0.6 Nm) / 15-18 in lb (1.7-2.1 Nm) 4.4-5 in lb (0.5-0.6 Nm) / 20-25 in lb (2.2-2.9 Nm) GENERAL NOTES (1) (2) (3) (4) See Derating curves for additional operating conditions. The RHP includes a Solid State Relay, therefore electrical isolation is not provided. The RHP includes over temperature protection for the solid state relay. 40°C ambient temperature, 30 operations/min, maximum voltage control. ol e te MECHANICAL SPECIFICATIONS O bs THERMAL DERATE INFORMATION bs ol e te TYPICAL ELECTRICAL CONNECTIONS O AGENCY APPROVALS UL/cUL UL508, E116950 EN60950-1-2006 Rev.063011 O bs ol e te ACCESSORIES O te ol e bs O bs ol e te ANNEX - ENVIROMENTAL INFORMATION