MEANWELL RSP-2000-48

RSP-2000
2000W Single Output Power Supply
series
Features :
Universal AC input / Full range
Built-in 5V/0.3A, 12V/0.8A auxiliary power
Built-in active PFC function, PF>0.97
Protections: Short circuit / Overload / Over voltage / Over temperature
Forced air cooling by built-in DC fan with fan speed control
Output voltage can be trimmed between 40~115% of the rated output voltage
3
High Power density 21.4W/inch
1U low profile 41mm
Active current sharing up to 8000W(3+1)
Built-in remote ON-OFF control
Built-in remote sense function
DC OK signal, OTP alarm signal
3 years warranty
SPECIFICATION
MODEL
RSP-2000-12
RSP-2000-24
RSP-2000-48
DC VOLTAGE
12V
24V
48V
RATED CURRENT
100A
80A
42A
CURRENT RANGE
0 ~ 100A
0 ~ 80A
0 ~ 42A
RATED POWER
1200W
1920W
2016W
200mVp-p
300mVp-p
21 ~ 28V
1.0%
42 ~ 56V
1.0%
RIPPLE & NOISE (max.) Note.2 150mVp-p
OUTPUT
10.5 ~ 14V
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE Note.3 2.0%
LINE REGULATION
1.0%
0.5%
0.5%
LOAD REGULATION
1.0%
0.5%
0.5%
1500ms, 60ms/230VAC at full load
SETUP, RISE TIME
16ms/230VAC at 75% load
HOLD UP TIME (Typ.)
VOLTAGE RANGE
INPUT
Note.5 90 ~ 264VAC
10ms/230VAC at full load
127 ~ 370VDC
FREQUENCY RANGE
47 ~ 63Hz
POWER FACTOR (Typ.)
0.97/230VAC at full load
87%
7A/230VAC
AC CURRENT (Typ.)
Note.5 13A/115VAC
COLD START 50A
INRUSH CURRENT (Typ.)
90.5%
16A/115VAC
EFFICIENCY (Typ.)
LEAKAGE CURRENT
10A/230VAC
92%
16A/115VAC
10A/230VAC
<2mA / 240VAC
105 ~ 125% rated output power
OVERLOAD
PROTECTION OVER VOLTAGE
OVER TEMPERATURE
FUNCTION
29.5 ~ 35V
57.6 ~ 67.2V
Protection type : Shut down o/p voltage, re-power on to recover
80
5 (TSW1) detect on heatsink of power bridge
75
5
(TSW2) detect on heatsink of o/p diode
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
5V @ 0.3A, 12V @ 0.8A
REMOTE SENSE
DC OK SIGNAL
Compensate voltage drop on the load wiring up to 0.5V, refer to function manual
OUTPUT VOLTAGE TRIM
Adjustment of output voltage, possible between 40 ~ 115% of rated output, refer to function manual
WORKING TEMP.
-35 ~ +70
SAFETY STANDARDS
SAFETY & WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMC
(Note 4)
EMC EMISSION
EMC IMMUNITY
MTBF
DIMENSION
PACKING
NOTE
14.7 ~ 17.5V
AUXILIARY POWER
REMOTE ON/OFF CONTROL
WORKING HUMIDITY
ENVIRONMENT STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
OTHERS
Protection type : Constant current limiting, unit will shut down o/p voltage after 5 sec. re-power on to recover
By electrical signal or dry contact
Power ON:open
Power OFF:short, refer to function manual
The isolated TTL signal out, refer to function manual
(Refer to "Derating Curve")
20 ~ 90% RH non-condensing
-40 ~ +85
, 10 ~ 95% RH
0.03%/ (0 ~ 50 )
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
UL60950-1, TUV EN60950-1 approved
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
Compliance to EN55022 (CISPR22) Conduction Class B, Radiation Class A ; EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11, EN61000-6-2 (EN50082-2), heavy industry level, criteria A
46.3Khrs min. MIL-HDBK-217F (25 )
295*127*41mm (L*W*H)
1.95Kg; 6pcs/12.7Kg/1.15CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Derating may be needed under low input voltages. Please check the derating curve for more details.
6. Under parallel operation ripple of the output voltage may be higher than the SPEC at light load condition. It will go back to normal ripple level once the
output load is more than 5%.
File Name:RSP-2000-SPEC 2011-12-27
RSP-2000
2000W Single Output Power Supply
Mechanical Specification
Case No. 952D
series
Unit:mm
271
25.4
20.5
7.8
6
3-M4 L=6
295
21
34.5
18.5
41
59
-V
+V
Air flow
direction
2
1
CN502
21
43
65
3
2
1
10
7
CN504
90
127
CN501 SVR51
12
11
TB1
3-M4 L=4
7.8
20.5
25.4
3-M4 L=6
6
271
AC Input Terminal
Pin No. Assignment
Pin No.
1
2
3
Control Pi n No. Assignment (CN501) : HRS DF11-12DP-2DS or equivalent
Assignment
+S
-S
PV
GND
Pin No.
1
2
3
4
Assignment
AC/N
AC/L
FG
Pin No.
5
6
7
8
Assignment
DC-OK
T-ALARM
ON/OFF
GND-AUX
Pin No.
9
10
11
12
Assignment
GND-AUX
GND-AUX
+5V-AUX
+12V-AUX
Mating Housing
Terminal
HRS DF11-12DS
or equivalent
HRS DF11-**SC
or equivalent
Control Pin No. Assignment(CN502) : HRS DF11-6DP-2DSA or equivalent
Terminal
Assignment Mating Housing
DA
HRS DF11-6DS HRS DF11-**SC
DB
or equivalent or equivalent
GND
Pin No.
1,2
3,4
5,6
Block Diagram
PFC fosc : 110KHz
PWM fosc : 90KHz
+S
I/P
EMI
FILTER
ACTIVE
INRUSH
CURRENT
LIMITING
RECTIFIERS
&
PFC
ORING
FET
RECTIFIERS
&
FILTER
POWER
SWITCHING
+V
-V
-S
O.V.P.
PFC
CONTROL
DETECTION
CIRCUIT
ORING FET
CONTROL
DETECTION
CIRCUIT
PWM
CONTROL
MCU
MCU
PV
TRANSCEIVERS
DA/DB
DATA
ISOLATION
T-Alarm
DC-OK
O.T.P.
AUX
POWER
FAN
RECTIFIERS
&
FILTER
12V/0.8A
AUX POWER
5V/0.3A
ON/OFF
File Name:RSP-2000-SPEC 2011-12-27
RSP-2000
2000W Single Output Power Supply
series
Function Description of CN501
Pin No.
Function
1
+S
2
-S
Negative sensing. The -S signal should be connected to the negative terminal of the load. The -S and +S leads should be
twisted in pair to minimize noise pick-up effect. The maximum line drop compensation is 0.5V.
3
PV
Connection for output voltage trimming. The voltage can be trimmed within its defined range. (Note.1)
4
GND
5
DC-OK
6
Description
Positive sensing. The +S signal should be connected to the positive terminal of the load. The +S and -S leads should be
twisted in pair to minimize noise pick-up effect. The maximum line drop compensation is 0.5V.
This pin connect to the negative terminal(-V).
High : When the Vout
80% 6%. Low : When Vout
80% 6%. (Note.2)
High : When the internal temperature (TSW1 or TSW2 open) exceeds the limit of temperature alarm.
Low : When the internal temperature (TSW1 or TSW2 short) under the limit temperature. (Note.2)
T-ALARM
7
ON/OFF
8,9,10
GND-AUX
11
+5V-AUX
Auxiliary voltage output, 4.5~5.5V, referenced to GND-AUX (pin ). The maximum load current is 0.3A. This output has the
built-in "Oring diodes" and is not controlled by the remote ON/OFF control.
12
+12V-AUX
Auxiliary voltage output, 10.6~13.2V, referenced to GND-AUX (pin ). The maximum load current is 0.8A. This output has
the built-in "Oring diodes" and is not controlled by the remote ON/OFF control.
The unit can turn the output on and off by electrical signal or dry contact. (Note.2)
Auxiliary voltage output GND. The signal return is isolated from the output terminals (+V & -V).
Note1: Non-isolated signal, referenced to the output terminals (-V).
Note2: Isolated signal, referenced to GND-AUX.
Function Description of CN502
Pin No.
Function
1,2
DA
Description
Differential digital signal for parallel control.
3,4
DB
Differential digital signal for parallel control.
5,6
GND
These pins connect to the negative terminal (-V).
Function Description of CN504
Pin No.
Function
Description
1,2
Terminal
resistance
CN504 is the selector of terminal resistor that is designed for DA/DB signals and parallel control function.
Derating Curve
Static Characteristics
100
100
90
80
80
75
70
230VAC
Input only
LOAD (%)
60
LOAD (%)
50
40
20
12V
65
24V,48V
50
40
-35
-25
-10
0
15
30
50
60
70
90
(HORIZONTAL)
100
AMBIENT TEMPERATURE ( )
180
264
INPUT VOLTAGE (VAC) 60Hz
EFFICIENCY vs LOAD (48V Model)
DERATING LOAD(%) VS INPUT VOLTAGE
94
EFFICIENCY (%)
115
INPUT / VOLTAGE
115VAC
100VAC
90VAC
100%
95%
90%
80%
RSP-2000-24
100%
80%
75%
65%
RSP-2000-48
100%
80%
75%
65%
92
MODEL
90
RSP-2000-12
88
180VAC
86
84
82
80
10
20
30
40
50
60
70
80
90
100
LOAD
File Name:RSP-2000-SPEC 2011-12-27
RSP-2000
2000W Single Output Power Supply
series
Function Manual
1. Remote ON/OFF Control
The PSU can be turned ON/OFF together or separately by using the "Remote ON/OFF" function.
RSP-2000
ON/OFF
Between ON/OFF and +5V-AUX
7
SW
+5V-AUX
11
PSU Output
SW Open
ON
SW Short
OFF
2. Remote Sense
The remote sense compensates voltage drop on the load wiring up to 0.5V.
+V
+S 1
RSP-2000
-S
-V
+V
LOAD
2
-V
Sense lines should be twisted in pairs
3. Output Voltage Trimming
(1)Output voltage can be trimmed between 40~115% of its rated value by the following method.
(2)+S & +V, -S & -V also need to be connected on CN501.
1
+V
LOAD
-V
RSP-2000
-S
PV
GND
100
2
OUTPUT CURRENT (%)
+S
3
0~5V
4
Vout
87
60
40
20
OUTPUT VOLTAGE(%)
115
Non-Linear
20
100
40
60
80
100
V
115
OUTPUT VOLTAGE (%)
80
24V,48V
PV / VOLTAGE
12V
<0.4V
1V
2V
3V
4V
4.7V
RSP-2000-12
100%
60%
60%
80%
100%
115%
RSP-2000-24
100%
40%
60%
80%
100%
115%
RSP-2000-48
100%
40%
60%
80%
100%
115%
60
MODEL
40
30
0
0.4
1
2
3
4
4.7
5
V
EXTERNAL VOLTAGE (DC)
4. Front Panel Indicators & Corresponding Signal at Function Pins
* Signal
Function
LED
Description
DC-OK GREEN When output voltage 80% 5% of Vo rated.
0 ~ 0.5V
RED When output voltage 80% 5% of Vo rated.
DC-NG
4.5 ~ 5.5V
T-OK
GREEN When the internal temperature (TSW1 & TSW2 short) is within safe limit
0 ~ 0.5V
T-ALARM RED When the internal temperature (TSW1 or TSW2 open) exceeds the limit of temperature alarm 4.5 ~ 5.5V
PSU Output
ON
ON
ON
OFF
*Signal between function pin and "GND-AUX".
File Name:RSP-2000-SPEC 2011-12-27
RSP-2000
2000W Single Output Power Supply
series
5.Current Sharing with Remote Sensing
RSP-2000 has the built-in active current sharing function and can be connected in parallel to provide higher output power :
(1)Parallel operation is available by connecting the units shown as below.
(DA,DB and GND are connected mutually in parallel).
(2)Difference of output voltages among parallel units should be less than 2%.
(3)The total output current must not exceed the value determined by the following equation.
(output current at parallel operation)=(Rated current per unit) (Number of unit) 0.9
(4)In parallel operation 4 units is the maximum, please consult the manufacturer for applications of more connecting in parallel.
(5)The power supplies should be paralleled using short and large diameter wiring and then connected to the load.
(6) Under parallel operation, the minimum output load should be greater than 5% of total output load.
(7) Under parallel operation ripple of the output voltage may be higher than the SPEC at light load condition. It will go back to normal ripple level once the
output load is more than 5%.
(8) CN502/CN504 Function pin connection
PSU1
Parallel
PSU2
CN502
CN504
1 unit
X
V
2 unit
V
3 unit
4 unit
PSU3
CN502
CN504
V
V
V
V
V
V
V
V
V
PSU4
CN502
CN504
X
V
V
X
V
X
CN502
CN504
V
V
V is CN502/CN504 connected to plug pin, X is CN502/CN504 not connected to plug pin.
-V
+V
RSP-2000
RSP-2000
RSP-2000
RSP-2000
PSU1
PSU2
PSU3
PSU4
CN504
1
2
TB1
-V
+V
TB1
CN504
5
6
1
2
CN502
-V
+V
5
6
1
2
CN502
TB1
CN504
-V
+V
CN504
5
6
1
2
CN502
TB1
5
6
CN502
DB(pin3)
DA(pin1)
GND
(pin5)
-V
Sense lines should
be twisted in pairs
+V
LOAD
Fig 6.1
1
3
5
1
3
5
1
3
5
1
3
5
DA
DB
GND
DA
DB
GND
DA
DB
GND
DA
DB
GND
DA
DB
GND
DA
DB
GND
DA
DB
GND
DA
DB
GND
2
4
6
2
4
6
2
4
6
2
4
6
PSU1 CN502
PSU2 CN502
PSU3 CN502
PSU4 CN502
File Name:RSP-2000-SPEC 2011-12-27