MEANWELL RKP-6K1U-12

RKP-1U Rack System
2000~6000W Front End Power System
Features :
Universal AC input / Full range
Holds up to 3 power modules
Active current sharing up to 6000W(3 unit) in one 19”rack, 3 rack max.
can be operated in parallel (up to 9 units)
PMBus serial interface
IEC320-C20 or terminal block input
Front-end & rectifier applications
Stackable for system expansion
Low profile: 1U height, 19” rack mount
Hot swappable modules
Output voltage trimming function
3 years warranty
Description :
RCP-2000 rack power system is an advanced 19” rack-mounted power system containing up to 3 hot-swappable RCP-2000 rectifiers and
can deliver up to 6000W in the single rack. Up to 3 racks can be stacked to provide expanded total system capability up to 18,000W that
are especially suitable for the application of servers, information technology equipment, networking, telecommunications, and wide
range of industrial applications using distributed power architecture. Equipped with PMBus communication protocol, RCP-2000 rack
system can be controlled or monitored by external device such as monitoring unit (RCP-CMU-1) or PC.
SELECTION GUIDE
Rack: RKP-1U I
Whole System: RKP-6K1U I
C
C - 12
Output voltage
C: With RCP-CMU-1
-: Without RCP-CMU-1
C: With RCP-CMU-1
-: Without RCP-CMU-1
I: AC Inlet (IEC320-C20)
T: Terminal block
I: AC Inlet
T: Terminal
SPECIFICATION - Rack System
MODEL
OUTPUT
RKP-6K1U -12
RKP-6K1U -24
RKP-6K1U -48
MODULE
RCP-2000-12
RCP-2000-24
RCP-2000-48
RACK
RKP-1UI or RKP-1UT
OUTPUT VOLTAGE
12V
24V
48V
MAX. OUTPUT CURRENT
300A
240A
126A
5760W
6048W
MAX. OUTPUT POWER Note.6 3600W
VOLTAGE RANGE
INPUT
FUNCTION
Note.5 90 ~ 264VAC
FREQUENCY RANGE
7A/230VAC
16A/115VAC
11A/230VAC
16A/115VAC
11A/230VAC
LEAKAGE CURRENT
<3.5mA / 230VAC
AUXILIARY POWER
REMOTE ON/OFF CONTROL
5V @ 0.3A, 12V @ 0.8A
REMOTE SENSE
DC OK SIGNAL
Compensate voltage drop on the load wiring up to 0.5V. "Local Sense"should be connected in order to get the correct output voltage if the "Remote Sense"is not used
By electrical signal or dry contact
ON:short
OFF:open
The isolated TTL signal out, refer to function manual
AC FAIL SIGNAL
The isolated TTL signal out, refer to function manual
OUTPUT VOLTAGE TRIM
Adjustment of output voltage, possible between 90 ~ 110% of rated output
OVER TEMP WARNING
FAN FAIL SIGNAL
Logic " High" for over temperature warning, refer to function manual, isolated signal
The isolated TTL signal out, refer to function manual
WORKING HUMIDITY
ENVIRONMENT STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
SAFETY & WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMC
(Note 4)
EMC EMISSION
NOTE
47 ~ 63Hz
AC CURRENT (Typ.)FOR EACH UNIT 13A/115VAC
WORKING TEMP.
OTHERS
127 ~ 370VDC
-40 ~ +70
(Refer to "Derating Curve")
20 ~ 90% RH non-condensing
-40 ~ +85
, 10 ~ 95% RH
0.03%/ (0 ~ 50 )
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
UL60950-1, TUV EN60950-1 approved
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.7KVDC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
Compliance to EN55022 (CISPR22) Conduction Class B, Radiation Class A ; EN61000-3-2,-3
EMC IMMUNITY
Compliance to EN61000-4-2,3,4,5,6,8,11, EN61000-6-2 (EN50082-2), heavy industry level, criteria A
DIMENSION
Rack 483.6*350.8*44(L*W*H)
11.5Kg; 1pcs/11.5Kg/2.67CUFT
PACKING
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Derating may be needed under low input voltages. Please check the static characteristics for more details.
6. Output of all the RCP-2000 modules are connected in parallel in the rack.
7. Under parallel operation of more than one rack connecting together, ripple of the output voltage may be higher than the SPEC at light load condition.
It will go back to normal ripple level once the output load is more than 10%.
File Name:RKP-1U RACK SYSTEM-SPEC 2011-05-09
2000~6000W Front End Power System
RKP-1U Rack System
Mechanical Specification (Rack System)
Case No. 959A
Unit:mm
Fig1
C
-
B
25
1
13
ADDRESS
SWITCH
ADDRESS
SWITCH
ADDRESS
SWITCH
14
+
CN500
A
JK1
Fig2
RKP-1UT
FG
N
L
FG
8.2
10
L
FG
N
B
L
8.2
10
8
1
1
8
ADDRESS
SWITCH
ADDRESS
SWITCH
ADDRESS
SWITCH
C
N
10 8 8.2
-
+
A
CN500
JK1
RKP-1UI
Mounting Bracket
IEC320-C20
IEC320-C20
IEC320-C20
125
125
440
SVR1
SVR1
24
50
50
125
125
3-M5 L=6mm
3-M5 L=6mm
350.8
SVR1
22
22
Air flow
direction
Module B
Module A
DC OK
DC OK
466.1
DC OK
29.48
Module C
10.2
7.42
44
7.1 7
46
483.6
File Name:RKP-1U RACK SYSTEM-SPEC 2011-05-09
RKP-1U Rack System
2000~6000W Front End Power System
CN500 Pin No. Assignment
Connector Pin No. Assignment(CN500) : D-Type Right Angle 25 positions
Pin No.
1
2
3
4
5
Pin No.
Assignment
ON/OFF-A
AC-OK-A
DC-OK-A
PV-A
T-ALARM-A
Assignment
FAN FAIL-A
ON/OFF-B
AC-OK-B
DC-OK-B
PV-B
6
7
8
9
10
Pin No.
Assignment
T-ALARM-B
FAN FAIL-B
+5V-AUX
+12V-AUX
GND-AUX
11
12
13
14
15
Pin No.
16
17
18
19
20
Assignment
ON/OFF-C
AC-OK-C
DC-OK-C
PV-C
T-ALARM-C
Pin No.
21
22
23
24
25
Assignment
FAN FAIL-C
+S
-S
+V
-V
JK1 Pin No. Assignment
Connector Pin No. Assignment(CN ) : RJ45 8 positions
Pin No.
1
2
3
Pin No.
Assignment
DA
DB
-V
4
5
6
Assignment
CONTROL
NC
SDA
Pin No.
7
8
Assignment
SCL
GND-AUX
CN500 IN/OUT Connector pins function description
Pin No.
Function
1,7,16
ON/OFF
2,8,17
3,9,18
4,10,19
AC-OK
DC-OK
PV
5,11,20
T-ALARM
6,12,21
FAN FAIL
13
+5V-AUX
14
+12V-AUX Auxiliary voltage output, 10.8 ~ 13.2V, referenced to GND- AUX (pin 15). The maximum load current is 0.8A. This output has the
built-in "Oring diodes" and is not controlled by the remote ON/OFF control.
GND-AUX Auxiliary voltage output GND. The signal return is isolated from the output terminals (+V & -V).
Positive sensing. The +S signal should be connected to the positive terminal of the load. The +S and -S leads should be twisted
+S
in pair to minimize noise pick-up effect. The maximum line drop compensation is 0.5V.
15
22
23
-S
24
25
+V
-V
Description
Each unit can separately turn the output on and off by electrical signal or dry contact between ON/OFF A,B,C(pin 1,7,16) and
+5V-AUX(pin 15). Short: ON, Open:OFF. (Note.2)
Low : When the input voltage is 87Vrms. High : when the input voltage in 75Vrms. (Note.2)
High : When the Vout 80 5%. Low : When Vout 80 5%. (Note.2)
Connection for output voltage trimming. The voltage can be trimmed within its defined range. (Note.1)
High : When the internal temperature (TSW1 or TSW2 open) exceeds the limit of temperature alarm.
Low : When the internal temperature (TSW1 or TSW2 short) under the limit temperature. (Note.2)
High : When the internal fan fail. Low : When the internal fan is normal. (Note.2)
Auxiliary voltage output, 4.5 ~ 5.5V, referenced to GND- AUX (pin 15). The maximum load current is 0.3A. This output has the
built-in "Oring diodes" and is not controlled by the remote ON/OFF control.
Negative sensing. The -S signal should be connected to the negative terminal of the load. The -S and +S leads should be twisted
in pair to minimize noise pick-up effect. The maximum line drop compensation is 0.5V.
Positive output voltage. For local sense use only, can't be connected directly to the load.
Negative output voltage. For local sense use only, can't be connected directly to the load.
JK1 IN/OUT Connector pins function description
Pin No.
Function
1,2
DA,DB
Description
Differential digital signal for parallel control. (Note.1)
3
-V
4
CONTROL
5
NC
Not use.
6
SDA
Serial Data used in the PMBus interface. (Note.2)
7
SCL
Serial Clock used in the PMBus interface. (Note.2)
8
GND-AUX
Negative output voltage. For parallel control, can't be connected directly to the load.
Remote ON/OFF control pin used in the PMBus interface. (Note.2)
Auxiliary voltage output GND. The signal return is isolated from the output terminals (+V & -V).
Note.1: Non-isolated signal, referenced to the output terminals (-V).
Note.2: Isolated signal, referenced to GND-AUX.
File Name:RKP-1U RACK SYSTEM-SPEC 2011-05-09
RKP-1U Rack System
2000~6000W Front End Power System
Function Manual
1. Remote ON/OFF Control
The PSU can be turned ON/OFF together or separately by using the "Remote ON/OFF" function.
RKP-1U
1
7
16
ON/OFF A
ON/OFF B
ON/OFF C
ON/OFF A
ON/OFF B
ON/OFF C
RKP-1U
13
+5V-AUX
+5V-AUX
1
7
16
Between ON/OFF and +5V-AUX Output
13
SW Open
OFF
SW Short
ON
2. Voltage Drop Compensation
2.1 Remote Sense
The remote sense compensates voltage drop on the load wiring up to 0.5V.
+V
22
+S
RKP-1U
+V
LOAD
23
-S
-V
-V
Sense lines should be twisted in pairs
2.2 Local Sense
Notice : The +S,-S have to be connected to the +V,-V terminals locally in order to get the correct output voltage if the remote sensing is not used.
24
+V
22
+S
RKP-1U
25
-V
23
-S
3. Output Voltage TRIM
(1)Connecting an external DC source between PV(4,10,19) and -V(25) on CN500 that is shown in Fig. 3.1.
(2)Adjustment of output voltage is possible between 90~110%(Typ.) of the rated output which is shown in Fig. 3.2. Reducing output current is required when the
output voltage is trimmed up.
Vout
100
PV
0~5V
-V
25
OUTPUT CURRENT (%)
4,10,19
OUTPUT VOLTAGE(%)
110
100
90
80
70
90
80
70
60
60
Fig. 3.1 Add on 0~5V external voltage
0
0.5
1.5
3
4.5
5
V
V
70
EXTERNAL VOLTAGE(DC)
80
90
100
110
OUTPUT VOLTAGE (%)
Fig. 3.2 Output voltage trimming
4. Front Panel Indicators & Corresponding Signal at Function Pins
* Signal
Function
LED
Description
AC-OK GREEN When input voltage 87V
0 ~ 0.5V
AC-NG
4.5 ~ 5.5V
RED When input voltage 75V
DC-OK GREEN When output voltage 80% 5% of Vo rated.
0 ~ 0.5V
DC-NG
4.5 ~ 5.5V
RED When output voltage 80% 5% of Vo rated.
T-OK
0 ~ 0.5V
GREEN When the internal temperature (TSW1 & TSW2 short) is within safe limit
T-ALARM RED When the internal temperature (TSW1 or TSW2 open) exceeds the limit of temperature alarm 4.5 ~ 5.5V
PSU Output
ON
OFF
ON
ON
ON
OFF
*Signal between function pin and "GND-AUX".
File Name:RKP-1U RACK SYSTEM-SPEC 2011-05-09
RKP-1U Rack System
2000~6000W Front End Power System
5.PMBus communication interface
5.1 Interface specification
RCP-2000 support PMBus Rev.1.1 with maximum 100kHz bus speed.
5.2 Device Address (A0~A4)
MSB
LSB
1
0
A4 A3 A2 A1 A0
The device address can be defined by using DIP switch and shows below. The DIP switch down position is logic "1" and up position is logic "0".
12345
ON
DIP switch position
DIP switch position
Module
No.
1
2
3
4
5
Module
No.
1
2
3
4
5
0
ON
ON
ON
ON
ON
16
ON
ON
ON
ON
ON
1
OFF
ON
ON
ON
ON
17
OFF
ON
ON
ON
ON
2
ON
OFF
ON
ON
ON
18
ON
OFF
ON
ON
ON
3
OFF
OFF
ON
ON
ON
19
OFF
OFF
ON
ON
ON
4
ON
ON
OFF
ON
ON
20
ON
ON
OFF
ON
ON
5
OFF
ON
OFF
ON
ON
21
OFF
ON
OFF
ON
ON
6
ON
OFF
OFF
ON
ON
22
ON
OFF
OFF
ON
ON
7
OFF
OFF
OFF
ON
ON
23
OFF
OFF
OFF
ON
ON
8
ON
ON
ON
OFF
ON
24
ON
ON
ON
OFF
ON
9
OFF
ON
ON
OFF
ON
25
OFF
ON
ON
OFF
ON
10
ON
OFF
ON
OFF
ON
26
ON
OFF
ON
OFF
ON
11
OFF
OFF
ON
OFF
ON
27
OFF
OFF
ON
OFF
ON
12
ON
ON
OFF
OFF
ON
28
ON
ON
OFF
OFF
ON
13
OFF
ON
OFF
OFF
ON
29
OFF
ON
OFF
OFF
ON
14
ON
OFF
OFF
OFF
ON
30
ON
OFF
OFF
OFF
ON
15
OFF
OFF
OFF
OFF
ON
31
OFF
OFF
OFF
OFF
ON
5.3 Command Summary (ref. to PMBus Rev.1.1)
Command
Code
Command
Name
Transaction
Type
# of data
Bytes
Description
01h
OPERATION
R/W Byte
1
Remote ON/OFF control
02h
ON_OFF_CONFIG
Read Byte
1
ON/OFF function configuration
19h
CAPABILITY
Read Byte
1
Capabilities of a PMBus device
20h
VOUT_MODE
R Byte
1
Define data format for output voltage
(format: Linear, N= -9)
21h
VOUT_COMMAND
R Word
2
Output voltage setting value
(format: Linear, N= -9)
22h
VOUT_TRIM
R/W Word
2
Output voltage trimming value
(format: Linear, N= -9)
46h
IOUT_OC_FAULT_LIMIT
R/W Word
2
Output overcurrent setting value
47h
IOUT_OC_FAULT_RESPONSE
R Byte
1
Define protection and response when an
output overcurrent fault occurred
79h
STATUS_WORD
R Word
2
Summary status reporting
7Ah
STATUS_VOUT
R Byte
1
Output voltage status reporting
7Bh
STATUS_IOUT
R Byte
1
Output current status reporting
7Ch
STATUS_INPUT
R Byte
1
AC inpit voltage statusreporting
7Dh
STATUS_TEMPERATURE
R Byte
1
Temperature status reporting
File Name:RKP-1U RACK SYSTEM-SPEC 2011-05-09
2000~6000W Front End Power System
RKP-1U Rack System
Command
Code
Command
Name
80h
STATUS_MFR_SPECIFIC
R Byte
1
Manufacture specific status reporting
81h
STATUS_FANS_1_2
R Byte
1
Fan1 and 2 status reporting
88h
READ_VIN
R Word
2
AC input voltage reading value
(format: Linear, N=-1)
8Bh
READ_VOUT
R Word
2
Output voltage reading value
(format: Linear, N= -9)
8Ch
READ_IOUT
R Word
2
Output current reading value
(format: Linear, N= -3)
8Dh
READ_TEMPERATURE_1
R Word
2
Temperature 1 reading value
(format: Linear, N= -3)
90h
READ_FAN_SPEED_1
R Word
2
Fan speed 1 reading value
(format: Linear, N= 4)
91h
READ_FAN_SPEED_2
R Word
2
Fan speed 2 reading value
(format: Linear, N= 4)
98h
PMBUS_REVISION
R Byte
1
The compliant revision of the PMBus
(default: 11h for Rev. 1.1)
Transaction
Type
# of data
Bytes
Description
99h
MFR_ID
Block Read
12
Manufacturer's name
9Ah
MFR_MODEL
Block Read
12
Manufacturer's model name
9Bh
MFR_REVISION
Block Read
6
Firmware revision
9Ch
MFR_LOCATION
Block R/W
3
Manufacturer's factory location
9Dh
MFR_DATE
Block R/W
6
Manufacture date. (format: YYMMDD)
9Eh
MFR_SERIAL
Block R/W
12
Product serial number
File Name:RKP-1U RACK SYSTEM-SPEC 2011-05-09