FUJI EDSX10-70C

MICROJET RECORDER-E
DATA SHEET
PHE
This recorder can record up to 6 channels of thermocouples, resistance bulbs and DC voltage/current signals. The adoption of ink jet system makes it possible to record
measured data in analog trace and digital color printing (6
colors, max) on a 100mm wide chart paper.
FEATURES
1. Compact size
Depth: 175mm, mass; about 1.2kg (continuous type)
Depth: 197mm, mass; about 1.5kg (6-intermittent type)
Ideally suited for use with machines and equipments.
2. High-quality recording
• Continuous traces without pen offset are possible by
our unique ink jet system.
• Scales are printed on a chart paper for each channel,
eliminating the need for scale plate.
• 6 different scale on 6 intermittent recording universal
input type is available.
3. Easy setting of input signals
DC voltage input (5mV span, 50V max.), DC current
(4-20mA, 10-50mA), 12 kinds of thermocouples and resistance bulbs (Pt100) are field-settable for each channel.
4.Digital printing
In addition to analog recording of measured data, periodic data printing, measured value list, scale printing,
alarm printing, burnout printing, and parameter list are
also available.
5. Easy Operation
• A cartridge type recording device is used for easy
replacement.
• Allow to draw out the chart paper while recording.
SPECIFICATIONS
Input system
1, 2-continuous recording, 6-intermittent recording
Thermocouple:B, R, S, K, E, J, T, N, W, L,
U, PN
Resistance bulb: Pt100
DC voltage: 5 0 m V, 5 0 0 m V, 5 V, 5 0 V
range
DC current: 4 to 20mA DC, 10 to 50mA
DC (Shunt resistor (option)
need to be connected to
the terminal.)
Input signal setting and change:
Setting and change of input signal between thermocouple, resistance bulb
and DC voltage (50mV, 500mV, 5V, 50V
range) is possible for each channel by
the setting pin in the instrument and
keyboard operation.
Input points:
Input signal:
Measuring range (Recording range):
Recording range on each channel is settable within the raference range with
keyboard operation.
Measurement cycle:
1, 2-continuous: 0.2s/point
6-intermittent: 30s/all points
Burnout:
When thermocouple or resistance bulb
input is disconnected, the recording is
deflected to 100%.
Input filter:
Settable within the range of 0-255s by
1s. steps.
Initial set before delivery is 3 s.
Reference range
Input signal
°C
Thermocouple B
R
S
K
E
J
T
N
W
L
U
PN
Resistance bulb Pt 100
DC voltage
±50mV
±500mV
±5V
±50V
Scaling
400to1760
0to1760
0to1760
-200to1370
-200to 800
-200to1100
-200to 400
0to1300
0to1760
-200to 900
-200to 400
0to1300
°F
752to3200
32to3200
32to3200
-328to2498
-328to1472
-328to2012
-328to 752
32to2372
32to3200
-328to1652
-328to 752
32to2372
-200to 600
-328to 1112
-50.00 to 50.00mV
-500.0 to500.0mV
-5.000to 5.000V
-50.00 to 50.00V
Scaling is possible within the range of
-32767 to +32767 (decimal point may
be put as necessary)
Recording system
Writing system: Ink jet system, in 6 colors as max.
Chart width: 100mm
Chart length: Z fold 15.08m
Service life of ink (depends on operating conditions):
About 12 months for 1 continuous line
recording at 20mm/h of chart speed.
EDSX10-70c
Date
Apr. 1, 2011
PHE
1-continuous: Recording: purple
Printing: purple
2-continuous: Recording:
No. 1 channel, red No. 2 channel, blue
Printing: purple
6-intermittent recording:
No. 1 channel, orange
No. 2 channel, green
No. 3 channel, purple
No. 4 channel, red
No. 5 channel, black
No. 6 channel, blue
Printing: black
10, 20, 24, 30, 50, 120, 200, 300, 400,
1000, 1200, 1500 mm/h
Can be changed by key operation.
Initial set before delivery is 20mm/h
(Note) In continuous type, it records
data intermittently when the speed exceeds 400mm/h.
Recording cycle: Continuous recording:
Depend on chart speed
[Calculation formula]
400
Recording cycle (sec) =
chart speed (mm/h)
(not faster than 2 seconds.) Intermittent recording:
30 s/all points.
Industrial unit: Selectable on each channel in max. 7
characters by ASCII code.
Printing function:[Printing during analog recording]
[Note]Chart speed of continuous type
should be slower than 400mm/
h and that of intermittent type
should be slower than 50mm/h.
Channel No. printing: Beside of recording line Periodic printing: Channel number, measurement value, unit,
chart speed and year,
month, day, hour, minute.
[Note]Print period is automatically fixed
on chart speed.
Scale printing: This print out is effected
alternately with periodic
printing.
[Note]Print inter val is automatically
fixed on chart speed.
Alarm printing:Channel number, kind of
alarm and hour, minute.
Burnout printing:Channel number and
hour, minute.
[Printing independent of analog recording]
[Note]Printing is performed by key operation, while analog recording
is interrupted. After completion
of the printing, analog recording
starts again.
Recording color:
Chart speed:
2
Instantaneous value list:Channel number, measured value,
industrial unit, year,
m o n t h , d ay, h o u r,
minute.
Parameter list (set value list): Input signal, recording
range, measuring range,
scaling range, unit,
alarm, input filter, chart
speed, year, month, day,
hour, minute, etc.
Scale line printing:Optional scale line
by user.
Test pattern: All characters and color
patterns can be printed. [Other printing]
Recording start mark
Chart speed change mark
Indicating, key operation system
Indication:
LED (7 segments), 6 digits, green
Indication character:
7 segments, alphanumeral
Character height 10mm, width 5mm
Contents of indication:
Channel No.:1 digit (1 to 6)
Measured value:
5 digits (including sign for
value below 0)
Temperature:1 d i g i t b e l o w d e c i m a l
point
Voltage/current:
Scaling, -9999 is displayed
for -10000 and under.
Time:
Hour, Minute
Status indication:
Symbolic code as alarm,
burnout or carriage failure.
Measurement display cycle:
3s for channel selection,
1s for data update in the
same channel
Operation key: 3 keys and 1 reset key
Key lock: soft key lock is available by
key operation.
Power requirement
Line supply:
Specify when ordering
Rated voltage
100 to 120VAC or 200 to 240VAC
Usable voltage
85 to 132VAC or 180 to 264VAC
Frequency:
50/60Hz
Power consumption: 100 to 120VAC or 200 to 240VAC, without option, 13VA or less
100 to 120VAC or 200 to 240VAC, with
alarm, 15VA or less
Alarm
Type:
Setting:
Indication:
Printing:
Hysteresis:
Alarm output:
Absolute value alarm, high and low
Two levels for each channel (high: 2 levels, low: 2 levels, or each level at high/
low)
Alarm level is indicated for each channel at occurrence of alarm.
Channel No. alarm level and hour, minute.
Approx. 0.2% of measuring (recording)
range
See “Optional specifications”.
Physical data
Mounting:
Panel (may be inclined up to 30° backwards from the vertical)
= 90 to 60°
Two or more recorders can be mounted
side by side.
Panel thickness: 2 to 30mm
Material:
Case: mold Front door frame: mold
Finish color:
Case: black Front door frame: black
Protective structure:
Front door: IEC IP50
Case size:
Bezel 144 x 144mm
Depth 175mm (Continuous type)
195mm Intermittent type)
Cutout 137 x 137mm
External terminals:
Screw terminals (M4 screw)
Mass:
Approx. 1.2kg (continuous type)
Approx. 1.5kg (intermittent type)
External terminals: M4 screw
Performance and characteristics
Indication accuracy*1:
DC voltage, DC current : ±(0.3% of measuring range +1 digit)
Thermocouple, Resistance bulb:
Depend on the measuring range for
each input signal.
Refer to the table below.
input (0.3% of measuring range+1 digit)
signal
measuring range
(1% of measuring range+1 digit)
measuring range
B
1000°C or more
1832°F or more
600°C or more
1112°F or more
R
1000°C or more
1832°F or more
600°C or more
1112°F or more
S
1000°C or more
1832°F or more
600°C or more
1112°F or more
K
300°C or more
572°F or more
200°C or more
392°F or more
E
300°C or more
572°F or more
200°C or more
392°F or more
J
300°C or more
572°F or more
200°C or more
392°F or more
T
300°C or more
572°F or more
200°C or more
392°F or more
N
300°C or more
572°F or more
200°C or more
392°F or more
W
500°C or more
932°F or more
400°C or more
752°F or more
L
300°C or more
572°F or more
200°C or more
392°F or more
U
300°C or more
572°F or more
200°C or more
392°F or more
PN
300°C or more
572°F or more
200°C or more
392°F or more
Pt100 150°C or more
302°F or more
50°C or more
122°F or more
Thermocouple input : 0.1°C 0.1°F
Resistance bulb :0.1°C 0.1°F
DC voltage
:±50mV : 10µV
:±500mV : 100µV
:±5V
: 1mV
:±50V
: 10mV
DC current
:c o nve r t e d va l u e t o
DC voltage is guaranteed
Recording accuracy *1:
Indication accuracy ±(0.2% of measuring range)
Recording resolution:
0.1mm
Chart speed accuracy:
±0.1% (in case continuous feed of
more than 1m. Expansion and contraction of paper is not included)
Reference junction compensation accuracy:
K, E, J, T, N, L, U, PN : ±0.5°C
B, R, S, W
: ±1°C
90% response time:
Less than 2s (continuous type only)
Maximum input voltage:
Thermocouple, resistance bulb and DC
voltage (50mV, 500mV range):
±10V DC or less
DC 5V/50V range: ±100V DC or less
Input resistance:Thermocouple, 50mV voltage range
> 10MΩ
5V/50V range: > 1MΩ
500mV range: > 100kΩ
Isolation:
100MΩ (between each terminal and
earth at 500V DC)
Channel to channel:
500V AC, 1min
Power terminal to ground: 2000V AC,
1min
Input terminal to ground: 50 0V AC,
1min
Power terminal to input terminal: 1000V
AC, 1min
Alarm to alarm: 750V AC, 1min
(leak current: 5mA or less)
Common mode noise rejection:
120dB (50/60Hz)
Series mode noise rejection:
30dB (50/60Hz)
Clock accuracy: ±50ppm (2 minutes per month)
Memory protection: Non-volatile memory for parameters.
Lithium battery for clock.
[Note] *1 Measurement condition:
23±2°C, 65±10%RH, power voltage
100 to 120V, 200 to 240V, frequency
50/60Hz within 1%, warm-up time
30min or more, vertical mounting, and
free from the effects of vibration, noise,
etc.
Resolution*1:
[Note]1.For thermocouple input, in case of measuring
range includes -200°C to -100°C (-328°F to -148°F),
indication accuracy should be added +0.5%.
2.The indication accuracy of thermocouple does not
include reference junction compensation error.
3
PHE
Operating environment
Temperature limits: 0 to 50°C
Humidity limits: 20 to 80%RH
(temperature × humidity < 3200)
Mounting position:
Front inclination 0°, rear inclination 30°,
left/right inclination 0°
Signal source resistance:
Thermocouple input: 1kΩ or less
Resistance bulb input: Less than 10Ω
(line resistance of each wire of 3-wires
system should be balanced)
Voltage input: Less than 0.1% of input
resistance
Vibration:
10 to 60Hz, 0.2m/s2 or less
Shock:
None
Optional specifications
Alarm output (DO):
2, 4 or 6 points N.O contact relay (refer
to code symbols)
Contact capacity 250V AC/3A. 30V DC/3A (resistance load)
Alarm output unit is required.
4
External control input (DI):
1 point, no-volt age cont act input is
used for selection of chart speed in 2
steps.
Normally, operation is effected at main
chart speed.
Sub-speed is selected with cont act
ON, and main speed with contact OFF. Main/sub speed is set by key operation.
When sub-speed is set to 0mm/h, recording start/stop can be selected.
Alarm output /external control input unit
is required.
Other functions
Printing/recording adjustment:
Make adjustment when characters
bend and/or disturbance of record (round
trip difference) occur.
Adjustment of zero/span of analog trend record position:
The position of ink cartridge is adjusted
for correct recording on 0% point and
100% point on chart paper. This adjustment should be made after
replacement of ink cartridge or chart
paper.
Measured value shift:
Indication or recording value is shifted
by adding or subtracting calculation of
measured value.
Sub chart speed:This is for selecting chart speed with
external control input. It is selected
from the following.
0, 10, 20, 30, 50, 120, 200, 300, 400,
1000, 1200, 1500mm/h
Initial set before delivery: 20mm/h
0mm/h means stop recording.
Channel skip: This is used to stop the operation of
unused channel. Skipped channel stops
all operations including display and
alarm.
Setting recording status at power ON:
Re c o r d i n g c a n b e s t a r t e d a g a i n o r
disabled when power is ON or when
power is recovered from failure.
Real time clock: Setting year, month, day, hour, minute
CODE SYMBOLS
1 2 3 4 5 6 7 8
9 10 11 12 13
PHE
V V
0 0
2
Description
EV
Recording points <4th digit code>
1 continuous recording
2 continuous recording
6 intermittent recording
1
2
9
Power supply • Temperature Unit <7th digit code>
100 to 120VAC 50/60Hz
°C
200 to 240VAC 50/60Hz °C
100 to 120VAC 50/60Hz
°F
200 to 240VAC 50/60Hz °F
1
2
3
4
Alarm output/external control input (1 point) <11th digit code>
Without
2 points alarm output (1 continuous only)
4 points alarm output (2 continuous only)
6 points alarm output (6-intermittent only)
2 points alarm output/External control (1 continuous only)
4 points alarm output/External control (2 continuous only)
6 points alarm output/External control (6 intermittent only)
0
1
2
3
A
B
C
Input : Universal (Programmable)
Range: Field settable (Programmable)
Note) 1.
Initial set before delivery is ;
• Thermocouple K type 0 to 1200°C
2. Shunt resistor (10Ω ±0.1%) should be ordered separately for
current input.
Shunt Resister : Ordering code PHZT1101
3. When changing the kinds of input signal, some adjustments
may become necessary.
SCOPE OF DELIVERY
Recorder, panel mounting bracket, accessories
(ink cartridge 1 pc, chart paper 1 roll, input signal setting pin
for replacement 1pc, ink absorption cloth 1 sheet). instruction manual (1 copy)
Note: Ink cartridge is not mounted on the recorder at the
time of delivery.
Spare parts
Item
Ink cartridge
Chart paper
(0 to 50, 50 uniform division)
Part No.
Unit of quantity for sale
PHZH2002
(1, 2-continuous)
1 pc
PHZH1002
(6-intermittent)
1 pc
PEX00DL1 - 5000B
1 box (6 charts)
Other (optional items)
Item
Type
Specification
Shunt resistor
PHZT1101
For 10Ω±0.1%
5
PHE
OUTLINE DIAGRAM (Unit:mm)
1-continuous type
Mounting bracket
Alarm output /external control input unit(option)
2<
=T <
= 30
t
144
161
136.5
Panel
175
197
136.4
19
144
Power terminal
Input terminal
Panel cutout
When mounting one unit
When mounting multiple n unit
L
Connection diagram
Alarm output / external control input unit
6
+1.5
0
11
21 Alarm output 1
12
22 Alarm output 2
13
23 Not used
14
24 Not used
15
25 Not used
16
26 Not used
17
27 External control input
18
28 Not used
19
29 Not used
175MIN
137 +1.50
137
+1.5
0
137 +1.50
Power terminal
100 to 120VAC or
200 to 240VAC
50/60HZ
~
L
Input terminal
RTD
+
– TC
V
N
PE
11
12
13
No. of units L+1.50 (mm)
2
282
3
426
4
570
5
714
6
858
7
1002
8
1146
9
1290
10
1434
n
(144 x n) – 6
OUTLINE DIAGRAM (Unit:mm)
2-continuous type
175
197
136.4
Power terminal
Panel
144
161
136.5
<T <
Mounting bracket 2 =
= 30
t
Alarm output /external control input unit(option)
19
144
Input terminal
Panel cutout
When mounting one unit
When mounting multiple n unit
L
+1.5
0
Connection diagram
Alarm output /external control input unit
11
21 Alarm 1
12
22 Alarm 2
13
23 Alarm 3
14
24 Alarm 4
15
25 Not used
16
26 Not used
17
27 External control input
18
28 Not used
19
29 Not used
No. of units L +1.50 (mm)
2
282
3
426
4
570
5
714
6
858
7
1002
8
1146
9
1290
10
1434
n
(144 x n) – 6
175MIN
137 +1.50
137
+1.5
0
137 +1.50
Input terminal
Power terminal
100 to 120VAC or
200 to 240VAC
50/60HZ
~
L
RTD
+
–
+
– TC
V
N
PE
21 22 23
Input 2
11
12
13
Input 1
7
PHE
OUTLINE DIAGRAM (Unit:mm)
6-intermittent type
Panel
144
161
<T <
Mounting bracket 2 =
= 30
t
136.5
Alarm output /external control
input unit (option)
Input terminal
136.4
197
19
144
Power terminal
Panel cutout
When mounting one unit
When mounting multiple n unit
L
Connection diagram
Alarm output /external control input unit
11
21 Alarm output 1
12
22 Alarm output 2
+1.5
0
13
23 Alarm output 3
14
24 Alarm output 4
15
25 Alarm output 5
16
26 Alarm output 6
17
27 External control input
18
28 Not used
No. of units L+1.50 (mm)
2
282
3
426
4
570
5
714
6
858
7
1002
8
1146
9
1290
10
1434
n
(144 x n) – 6
175MIN
137 +1.50
137
+1.5
0
137 +1.50
Power terminal
Input terminal
100 to 120VAC or
200 to 240VAC
50/60HZ
RTD
–
~
L
+ TC
V
N
PE
13
12
11
23 22 21
33 32 31
43 42 41
53 52 51
63 62 61
73 72 71
Input 1
Input 2
Input 3
Input 4
Input 5
Input 6
Not used
19
29 Not used
CE mark
*The products conform to the requirements of the Electro magnetic compatibility Directive and Low voltage Directive.
Caution on Safety
*Before using this product, be sure to read its instruction manual in advance.
International Sales Div
Sales Group
Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome,
Shinagawa-ku, Tokyo 141-0032, Japan
http://www.fujielectric.com
Phone: 81-3-5435-7280, 7281 Fax: 81-3-5435-7425
http://www.fjielectric.com/products/instruments/
Information in this catalog is subject to change without notice.
Printed in Japan