FUJI EDS11-115G

FC SERIES SETTER (CONTINUOUS OUTPUT TYPE)
DATA SHEET
PNF3
The FC series setter is used for remote setting of a controller or variable constant setting of various types of computing elements.
This instrument uses a solid state indicator and a pushbutton operation system to provide reliable monitoring and
operating functions.
FEATURES
1. High reliability
This instrument is designed with few mechanical parts.
It is mainly composed of electronic parts such as a solid
state indicator which was formerly consisted of mechanical parts.
2. International standards
This instrument is compact in size, conforming to international standards IEC. It operates on 24V DC power to
deliver 1 to 5V DC signals as recommended by IEC standards.
100 and 200V AC power are also available for convenience of operation.
3. Front panel operation
Process values and set points can be read accurately
with digital indications on panel front. Various parameter
settings and setting operations are also possible from
the front panel of the instrument.
FUNCTIONAL DIAGRAM
PV
Linearize
Square-root
extraction
SV
Local mode
output (LS)
Remote request
(R-REQ)
Filter
Compensated
process
value signal
(KPV)
Process value
input (PV)
External set point
input (CAS or PI)
(1 to 5V DC,
pulse width,
or pulse number)
Remote
acknowledge
signal (R-ACK)
Limiter
H
Set point
output signal
(SV)
R
L
L
KPV
FAULT
FLT output
ALM
High alarm
output (H)
Low alarm
output (L)
EDS11-115g
Date
Aug. 15, 1996
PNF3
SPECIFICATIONS
1. Input signal
(1) Process value input signal:
1 input selectable from the following.
Voltage input signal
current input signal
I+
I0
I–
1 to 5V DC
Input resistance,
1MΩ or more
4 to 20mA DC
24V DC power supAllow. error
± 0.2%/FS
plied to transmitter
only when AC power
is used
Allow. error
± 0.2%/FS*
Note: * FS: Full scale
(2) Analog input signal: 1 point
External set point CAS
input signal
1 to 5V DC
Input resistance, 1MΩ or more
Allow. error ± 0.2%/FS
(3) Digital input signal: 1 point
Remote
acknowledge
signal
R-ACK
Contact input
(photo-coupler
insulation)
ON 0V, OFF 24V
( input current, approx.
11mA/24V DC)
Contents of indication:
Process value (industrial value), set point
(industrial value), high/low alarm, etc.
Indication contents are selectable by F/S ,
keys on front panel.
,
Setting method: By using F/S ,
,
,
, ST keys on
front panel.
(4) Setting functions
Fixed value setting method:
By using of
,
pushbuttons on front
panel.
Setting speed, approx. 40 sec/FS
Remote setting method:
By use of external set point signal
(voltage or pulse width input)
Tracking speed setting range; 0 to 900
sec/FS
(5) Operation mode changeover
By using of R/L pushbutton on front panel
R
R
(4) Pulse width or pulse number input signal: 1 set (either one)
Pulse width input
signal
Pulse number
input signal
PI+
PI–
Contact input
(photo-coupler
insulation)
ON 0V, OFF 24V
(input current, approx.
11mA/24 DC)
ON 0V, OFF 24V
(approx. 11mA/24V DC)
max. input frequency
500Hz
2. Output signal
(1) Analog output signal: 2 points
Compensated process
KPV
value signal
1 to 5V DC
Set point output signal MV
Output resistance, 1Ω
or less
Allow. error ± 0 2%/FS
(2) Digital output signal: 5 points
Fault output
FLT
Open-collector
LS
Remote request signal R-REQ output (photocoupler insulaHigh alarm output
H
tion)
Low alarm output
L
Local mode output
Rated output,
30V x 0.1A DC,
max.
3. Indication, setting, operating functions
(1) Bargraph indication
L changeover
Balanceless bumpless
Voltage signal*
Balance bumpless
Pulse width signal
Balanceless bumpless
Note: * Balanceless bumpless by setting tracking speed
(6) Alarm functions
High/low alarm settable in industrial values for process value
input signal.
4. Power failure processing functions
Power failure detection:
Setting output held at power failure
detection.
During power failure:
Data backed up by capacitor up to 5
minutes. Initial value of set point stored
in non-volatile memory (10 years expected at ambient temperature of 50°C
or less).
Power failure recovery:
Initial or continuous start mode can be
set within 5 minutes of power failure.
Recovery from power failure lasting
longer than 5 minutes is initial. **
Note: ** Operation mode set at initial can be registered
L: Local mode or R: Remote mode
5. Self-diagnosis functions
PV indicator
SV indicator
Indication method
LED (red)
LED (green)
No. of segments
101 + 2
101 + 2
Range
0 to 100%, linear
0 to 100%, linear
Resolution
1 %/FS
1%/FS
Scale length
100mm
100mm
Indicating mode
0 to 100% bargraph indication,
0 to 100% reverse bargraph indication,
dot indication, –50 to +50% deviation
indication
(2) Operation mode indication
Indicating method:
LED (green)
Green: L(local), R(remote)
(3) Numerical value indication, setting
Indication method:
LED (red), name in 3 digits + numerical
value in 5 digits (negative code included)
2
L changeover
Input signal abnormality:
FLT lamp lights, FLT output contact "ON"
Indication of abnormal contents:
Cause of abnormality indicated in numerical values on front panel.
6. Transmission functions
(1) Transmission items
Supervisory items:
PNF
Host
Process variable, set point, operation
mode, alarm information, fault information, various limiter values, constants, etc.
Setting operation items:
Host
PNF
Set point, operation mode, various limiter
values, constants, etc.
(2) Transmission setting inhibit:
Parameter setting enable/inhibit can be designated by
transmission from the host. Designation is done by keys
on the front panel key.
(3) Communication interface
(a) T-link: Private interface
Transmission speed: 500Kbps
No. of units connectable: 32 max.
Transmission distance: 1km max.
Transmission form: Multi-drop
Control method: I/O transmission and message
(b) RS-422A/485: Universal interface
Transmission speed: 2400, 4800, 9600 or 19200bps
configurable
No. of units connectable: 31 max.
Transmission distance: 1km max.
Transmission form: Multi-drop
Control method: Polling/selecting
7. Other functions
Data protective function by pass code
CODE SYMBOLS
1 2 3 4 5 6 7 8
PNF 3
B
9 10
Description
5 - 0
Process value input signal
1 to 5V DC
4 to 20mA DC with 24V DC power supply
A
B
Auxiliary analog input
None
B
Power supply
24V DC (20 to 30V DC)
100V AC (85 to 132V/47 to 63Hz AC)
200V AC (187 to 264V/47 to 63Hz AC)
1
2
3
Y
T
R
S
Transmission functions
None
T-link
RS-422A
RS-485
8. Operating conditions
Power supply:
Select from 3 types
24V DC (20 to 30V DC)
100V AC (85 to 132V/47 to 63Hz AC)
200V AC (187 to 264V/47 to 63Hz AC)
Power consumption:
Approx. 11W (DC)
Approx. 20VA (AC)
Dielectric strength:
1500V AC, 1 min.
Insulation resistance:
500V DC, 100MΩ or more
Ambient temperature:
0 to 50°C
Ambient humidity:
90% RH or less
Enclosure:
Steel case
Rating plate (Name plate):
100 (H) x 70 (W) mm, white acryl
Dimensions:
144 (H) x 72 (W) x 407 (D) mm, IEC
(DIN) standard
Mass {weight}: Approx. 2.9kg
Mounting method:
Flush indoor mounting; vertical mounting.
Mountable on tilted surface angle "α"
α=0° to 90°
Finish color:
Munsell N 1.5 for both front panel and
case
Scope of delivery: Setter and mounting bracket
3
PNF3
OUTLINE DIAGRAM
(Unit:mm)
Panel thickness 8mm or less
16
144
Terminals
Supporting
bracket
355
52
Mounting
bracket
200
72
Panel cutout
When mounting "n" units
+1
0
250min.
68
4
+0.7
0
138
138
+1
0
200min.
When mounting 1 unit
(72.2n – 4)
+1
0
No. of units
n 2
CONNECTION DIAGRAM
Compression Terminal
AI
(External set point)
— 01
CAS
I+
31 —
Io
32 —
— 03
I–
33 —
— 04
KPV
34 —
— 05
SV
35 —
— 02
Not use
36 —
AO
(Compensated PV signal)
AO
(Set point output signal)
Not use
SC
37 —
Al, AO Common bus
SC
38 —
— 06
AI, AO Common bus
Not use
— 07
SC
— 08
SC
— 09
39 —
— 10
40 —
— 11
41 —
— 12
42 —
— 13
DI
(Pulse input)
DO
(High-limit alarm output)
DO
(Low limit alarm output)
DO
(FLT output)
24VDC power for DI, DO
24VDC power for DI, DO
Instrument power
(24VDC)
PI+
— 15
PI–
RACK
45 —
— 16
H
RREQ
46 —
L
LS
47 —
—
–
—
–
—
–
—
Not use
43 —
— 14
— 17
Process value
input
44 —
18
FLT
19
PCD
VPD
20
PCD
VPD
21
PC*
VP*
G
AC AC
71
72
48 —
+
49 —
+
50 —
+
51 —
DI
(Remote acknowledge)
DO
(Remote request)
DO
(Local status)
Not use
24VDC power for DI, DO
Instrument power
(24V DC)
Note: * Symbols for AC instrument power are VPO, PCO.
Output:Approx. 24V DC (0.1A max.)
73
Ground
Instrument power (AC)
Instrument power (AC)
Connection for process value input terminals
1 to 5V DC
4 to 20mA DC
The 5th digit of
code symbols
B
4 to 20mA DC
with inner DC
power supply
of CC-S
The 5th digit of
code symbols
B
+
31
–
33
+
31
–
33
+
31
–
33
32
The 5th digit of
code symbols
A
+
32
–
+
–
32
PC
21
5
PNF3
COMMUNICATION CONNECTOR
1 SIG GND
6
2 SHLD(SD)
7
8 RXD +
9 RXD –
3 INH
4 TXD+(T1)
1 SIG GND
6
2 SHLD(SD)
Black
7
White
8 RXD +
9 RXD –
5 TXD–(T2)
Green
3 INH
4 TXD+(T1)
5 TXD–(T2)
Yellow
Note:Symbol in ( ):
T-link terminal symbol
Brown
Red
6
7
8 RXD +
9 RXD –
1 SIG GND
1 SIG GND
6
2 SHLD(SD)
7
3 INH
8 RXD +
4 TXD+(T1)
9 RXD –
5 TXD–(T2)
LINE
TERMINATION
RESISTOR
2 SHLD(SD)
Black
3 INH
White
4 TXD+(T1)
5 TXD–(T2)
Green
Yellow
Red
Brown
Termianl station
HOST
MASTER
CONTROLLER
First station
Host
Termination
Resistor
Transmission cable
PNF3
PNF3
PNF3
PNF3
The product conforms to the requirements of the
Electromagnetic compatibility Directive 89/336/EEC as
detailed within the technical construction file number
TN510402. The applicable standards used to demonstrate
compliance are :-
EN 55011 : 1991 CLASS A
Conducted and Radiated emissions
EN 50082-1 :-1992
Radiated immunity, ESD and FBT
Caution on Safety
*Before using this product, be sure to read its instruction manual in advance.
Head Office
6-17, Sanbancho, Chiyoda-ku, Tokyo 102-0075, Japan
http://www.fesys.co.jp/eng
Sales Div.
International Sales Dept.
No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan
Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187
http: //www.fic-net.jp/eng
Information in this catalog is subject to change without notice.
Printed in Japan