FUJI EDS9-22D

FC SERIES PT TYPE CALCULATOR
DATA SHEET
PTB
The FC series PT type calculator receives 4 analog inputs, provides four fundamental rules of arithmetic, square
root extraction, linearizer, etc., and convert into a signal of
1 to 5V DC or 4 to 20mA DC. In addition, transmission
function is avaiable.
Its structure is plug-in style.
SPECIFICATIONS
INPUT SPECIFICATION
Input signal:
4 points
Input type
Voltage
Current
Input signal
1 to 5V DC
4 to 20mA DC
Input resistance 1MΩ or over 250Ω
OUTPUT SPECIFICATION
Output signals:
2 points
Output type
Voltage
Current
Output signal
1 to 5V DC
4 to 20mA DC
Allowable load
resistance
15kΩ or over
600Ω or less
TRANSMISSION SPECIFICATION
1. Data transmission
Interface:
RS-485
Transmission system:
Start-stop synchronous system
Transmission speed:
2400, 4800, 9600, 19200bps
Connectable units:
31 units (Max.)
Code format: Data length……8 bits (binary)
Parity bit……even, odd, none
Stop bit……one or two bits
Transmission distance:
1 km (Max.)
2. Loader
Interface:
RS-232C equivalent
POWER SUPPLY
Power supply:
24V DC (20 to 30V DC)
24V AC, +13%, –10%, (47 to 63Hz)
100V AC (85 to 132V AC / 47 to 63Hz)
200V AC (187 to 264V AC / 47 to 63Hz)
as specified.
Power consumption:
Approx. 3W(at DC power)
Approx. 6VA (at AC power)
OPERATION CONDITION
Ambient temperature:
0 to 50°C
Ambient humidity:
Less than 90%RH (no condensation)
Outline dimension (HxWxD):
96 x 52 x130mm
Mass:
Appox. 300g
Housing:
Plastic housing (color: black)
Mounting method:
Panel mounting or DIN rail mounting
CHARACTERISCTICS
Accuracy:
Less than ± 0.1% of full span
Response time: Less than 0.3 sec.
Dielectric strengh:
1500V AC, 1 min.
(Input - Output - Transmission - Power Ground)
Insulation resistance:
500V DC, 100MΩ or over
(Input - Output - Transmission - Power Ground)
CODE SYMBOLS
1 2 3 4 5 6 7 8
P T B
W
9 10 11
Description
1 - Y
Input signal
1 to 5V DC
4 to 20mA DC
1
2
Output signals
1 to 5V DC/4 to 20mA DC
W
Calculating specification
Basic specification
Linearizer + root square
Deviation
Selector 1
Selector 2
Multiplication/Division
Flow rate compensation
Programmable
A
B
C
D
E
F
G
P
Power supply
24V DC/24V AC (50/60Hz)
100V AC (50/60Hz)
200V AC (50/60Hz)
1
2
3
Transmission function
With RS-485
R
Y
Loader interface
Without
EDS9-22d
Date
Mar. 25, 1999
PTB
FUNCTIONAL DIAGRAM
+
11
–
12
+
21
–
22
32
–
+
13
41
–
14
42
+ Output
– (1 to 5v DC )
43
+
+
23
44
–
Transmission
circuit
Input 1
Input 2
A/D
conversion
5
+
6
–
RS-485
31
Calculation
circuit
D/A
conversion
Input 3
Switch
panel
Power
supply
circuit
Input 4
–
24
+
Output
(4 to 20mA DC )
Power supply
Loader
interface
34
CALCULATING FUNCTIONS
There are 7 types of standard computation block.
1. Basic calculation (The 6th digit: A)
2. Linealizer + Root square calculation (The 6th digit: B)
Output terminal plate
Output terminal plate
V1
Ai 1
V2
Ai 2
a1 (V1 – b1) + c1
+
–
Ai 1
a2 (V2 – b2) + c2
+
–
Ai 2
a3 (V3 – b3) + c3
+
–
Ai 3
+
–
Ai 4
V1
a1 (X1 – b1)
+
–
a2 (V2 – b2)
+
–
a3 (X3 – b3)
+
–
a4 (X4 – b4)
+
–
x1
Lineariser
V2
Yout
Yout
V3
Ai 3
V4
Ai 4
a4 (V4 – b4) + c4
V3
x3
c3
V4
x4
c4
Constants
Initial
value
Constants
Initial
value
a1 ~ a4 : (– 200 =< a =
< 200%)
0%
a1 ~ a4 : (– 200 <
= a <= 200%)
0%
b1 ~ b4 : (– 200 =< b =
< 200%)
0%
0%
b1 ~ b4 : (– 200 < b < 200%)
= =
c3 ~ c4 : (
0 <= c <=200%)
0%
c1 ~ c4 : (– 200 <
= c <= 200%)
7%
3. Deviation calculation (The 6th digit: C)
4. Selector 1 (The 6th digit: D)
Output terminal plate
Output terminal plate
Ai 1
Ai 2
Ai 3
Ai 4
V1
V1
V2
a1 (V1– V2)
c1
Ai 1
–b1
+
–
Ai 2
–b2
+
–
c1
H
H/L
selector L
+
–
c2
H
H/L
selector L
+
–
V2
V3
V4
a1 (V1– b1)
a2 (V3– V4)
c2
Yout
V3
a3 (V3– b3) +c3
a2 (V2 – b2)
Yout
V3
+
–
Ai 3
+
–
Ai 4
a3 (V3 – b3)
c3
H
H/L
selector L
+
–
c4
H
H/L
selector L
+
–
V4
V4
a4 (V4– b4) +c4
a4 (V4 – b4)
Constants
Initial
value
Constants
Initial
value
a1 ~ a4 : (– 200 =
<a=
< 200%)
0%
a1 ~ a4 : (– 200 =< a =< 200%)
0%
b1 ~ b4 : (– 200 =
<a=
< 200%)
0%
b1 ~ b4 : (– 200 =< b =< 200%)
0%
c1 ~ c2 : (– 200 <
= b <= 200%)
100%
c1 ~ c4 : (– 200 =< c =
< 200%)
0%
c3 ~ c4 : (– 200 <
= c <= 200%)
0%
5. Selector 2 (The 6th digit: E)
6. Multiplication/Division calculation (The 6th digit: F)
Output terminal plate
V1
Ai 1
H/L
X2
H
V2 selector L
Ai 2
a1V1+b1
a2 (X2 – b2)
+
–
X2
H
H/L
V4 selector L
Ai 4
+
–
V2
X5/X3
X3
X4
+
–
X3 ·X2
Yout
a4V4+b4
Ai 4
+
–
a3 (V1 – V2)
– b3
c3
V4
+
–
a3V3+b3
V4
Yout
X1·X2
a2V2+b2
Ai 3
V1
X5
X2
V2
Ai 2
V3
V3
Ai 3
a1 (X1 – b1)
Output terminal plate
X1
V1
Ai 1
+
–
X4
a4 (V4 – b4)
H
H/L
selector L
c4
Constants
Initial
value
a1 ~ a4 : (– 200 =
<a=
< 200%)
0%
b1 ~ b4 : (– 200 < b < 200%)
= =
c3
: (– 200 < c < 200%)
= =
c4
: (– 200 <
= c <= 200%)
0%
+
–
c1
100%
Constants
Initial
value
a1 ~ a4 : (– 200 <
=a<
= 200%)
0%
b1 ~ b4 : (– 200 < b < 200%)
= =
c1
: (– 200 < c < 200%)
= =
0%
0%
0%
7. Flow rate compensation calculation (The 6th digit: G)
Ai 1
V1
X1 (V1 – b1)
Ai 2
Ai 3
Ai 4
V2
V3
V4
Lineariser
a3 (V3 – b3)
a4 (V4 – b4)
X1
Output terminal plate
X4
(X4/X2) – b2
X5
a2 (X5/X3)
X2
+
–
+
–
X3
Yout
c1
c2
+
–
+
–
Constants
a1 ~ a4 : (– 200 <= a <= 200%)
b1 ~ b2 : (– 200 <= b <= 200%)
Initial
value
0%
0%
c1
:(
0<
= c <= 100%)
7%
c2
: (– 200 <
=c<
= 200%)
0%
+
–
PTB
OUTLINE DIAGRAM (Unit: mm)
Terminal screw M2.5
(for transmission)
74
94
35
Main unit
Terminal screw M4
Terminal
2
48
100
52
Stopper
130
Panel mounting
DIN rail mounting
2-M4
DIN rail
40
52
EXTERNAL CONNECTION DIAGRAM
Voltage • Current input
INPUT1
INPUT3
+
11 12
13 14
INPUT2
INPUT4
+
21 22
+
23 24
+
5
Stopper
RANGE OF DELIVERY
Main unit and socket
ORDERING INFORMATION
1. Style or type
2. Calculating constants
+
RS-485
-
6
-
31 32
+
-
33 34
OUTPUT(mA)
41 42
+
-
43 44
+
-
OUTPUT(V)
POWER
Caution on Safety
*Before using this product, be sure to read its instruction manual in advance.
Head Office
Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome,
Shinagawa-ku, Tokyo 141-0032, Japan
http://www.fesys.co.jp/eng
Instrumentation Div.
International Sales Dept.
No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan
Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187
http://www.fic-net.jp/eng
Information in this catalog is subject to change without notice.
Printed in Japan