FC SERIES PT TYPE DISTRIBUTOR (48mm width) DATA SHEET PTL The FC series PT type distributor converts a current signal (4 to 20mA DC) from the transmitter into a voltage signal (1 to 5V DC ) then distributes the voltage signal to each receiver. In addition, the distributor is provided with built-in transmitter power supply. Its structure is plug-in style. SPECIFICATIONS INPUT SPECIFICATION Input signal: 1 point Input type Current Input signal 4 to 20mA DC Input resistance 250Ω OUTPUT SPECIFICATION Output signal: 2 points Output type Voltage Output signal 1 to 5 V DC Allowable load re- 500kΩ or over (reception, non-insulation) 15kΩ or over sistance (with output buffer) POWER SUPPLY Power supply: 24V DC (20 to 30V DC) 24V AC, +13%, –10%,(47 to 63Hz) 100V AC (85 to 132V AC / 47 to 63Hz) 200V AC (187 to 264V AC / 47 to 63Hz) as specified. Power consumption: Approx. 2W (at DC power) Approx. 6VA (at AC power) OPERATION CONDITION Ambient temperature: 0 to 50°C Ambient humidity: Less than 90%RH (no condensation) Outline dimension (HxWxD): 96 x 52 x130mm Mass: Appox. 300g Housing: Plastic housing (color: black) Mounting method: Panel mounting or DIN rail mounting CHARACTERISTICS Accuracy: Less than ± 0.1% of full span Response time: Less than 0.1 sec. (90% response) Dielectric strengh: 1500V AC, 1 min. (indicated below) Insolation resistance: 500V DC, 100MΩ or over (indicated below) Reception only: Input/Output - Ground Non-insulation type: Input/Output•Power - Ground Non-insulation with buffer: Input/Output•Power - Ground Power insulation with buffer: Input/Output - Power - Ground Power I/O insulation with buffer: Input - Output - Power - Ground Ambient temperature effect: Less than ± 0.15% of full span/10°C Power regulation effect: Less than ± 0.1% of full span CODE SYMBOLS 1 2 3 4 5 6 7 8 P L T 2 V Description 1 Input signal 4 to 20mA DC 2 Output signal 1 to 5V DC V A0 B1 C1 D1 E1 D2 E2 D3 E3 Output system Reception only Non-insulation type Non-insulation with buffer Power insulation with buffer Power I/O insulation with buffer Power insulation with buffer Power I/O insulation with buffer Power insulation with buffer Power I/O insulation with buffer Power supply None 24V DC 24V DC 24V DC/ 24V AC (50/ 60Hz) 24V DC/24V AC (50/ 60Hz) 100V AC (50/60Hz) 100V AC (50/60Hz) 200V AC (50/60Hz) 200 V AC (50/60Hz) EDS9-24a Date Feb. 20, 1996 PTL FUNCTIONAL DIAGRAM 1. Reception only type 11 31 Output 1 Transmitter (4 to 20mA DC) 250Ω 12 32 41 21 Output 2 42 22 34 2. Non-insulation type 11 Transmitter (4 to 20mA DC) Power restric circuit 31 Output 1 12 32 41 Output 2 21 42 22 250Ω 43 Power 44 34 3. Power insulation with buffer 11 Transmitter (4 to 20mA DC) Power restric circuit 31 Output 1 12 32 41 Output 2 21 42 22 Power circuit 43 Power 44 250Ω 34 4. Power input/output insulation with buffer Current limiting circuit 11 Transmitter (4 to 20mA DC) 31 Output 1 12 32 Signal insulation circuit 41 Output 2 21 42 22 43 Power circuit Power 44 250Ω 34 OUTLINE DIAGRAM (Unit: mm) Terminal screw M2.5 (for transmission) 35 74 Main unit 94 Terminal screw M4 Terminal 2 48 52 100 Stopper 130 Panel mounting DIN rail mounting 2-M4 DIN rail 40 52 Stopper PTL EXTERNAL CONNECTION DIAGRAM General Reception only type (non-insulation type, power insulation type, power I/O insulation type) + - + - 11 12 + - 13 14 11 12 + - 13 14 21 22 23 24 21 22 23 24 5 5 6 6 31 32 + - 33 34 OUTPUT 31 32 + - 33 34 OUTPUT 41 42 + - 43 44 + - 41 42 + - OUTPUT POWER OUTPUT 43 44 RANGE OF DELIVERY Main unit and socket Caution on Safety *Before using this product, be sure to read its instruction manual in advance. Head Office Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome, Shinagawa-ku, Tokyo 141-0032, Japan http://www.fesys.co.jp/eng Instrumentation Div. International Sales Dept. No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187 http://www.fic-net.jp/eng Information in this catalog is subject to change without notice. Printed in Japan