FC SERIES PT TYPE ISOLATER DATA SHEET PTF The FC series PT type isolator converts an input signal (1 to 5V DC or 4 to 20mA DC) into an isolated output signal. Its structure is plug-in style. SPECIFICATIONS INPUT SPECIFICATION Input signal: 1 point Input type Voltage Current Input signal 1 to 5V DC 4 to 20mA DC Input resistance 1MΩ or over 250Ω OUTPUT SPECIFICATION Output signal: 1 point Output type Voltage Current Output signal 1 to 5V DC 4 to 20mA DC Allowable load 15kΩ or over resistance 600Ω or less POWER SUPPLY 24V DC (20 to 30V DC) 24V AC, +13%, –10%, (47 to 63Hz) 100V AC (85 to 132V AC /47 to 63Hz) 200V AC (187 to 264V AC /47 to 63Hz) as specified. Power consumption: Approx. 2W (at DC power) Approx. 6VA (at AC power) Ambient temperature effect: Less than ± 0.1% of full span/10°C Power regulation effect: Less than ± 0.1% of full span Power supply: OPERATION CONDITION Ambient temperature: 0 to 50°C Ambient humidity: Less than 90%RH (no condensation) Outline dimension (HxWxD): 96 x 52 x 130mm Mass: Appox. 300g Housing: Plastic housing (color: black) Mounting method: Panel mounting or DIN rail mounting CODE SYMBOLS 1 2 3 4 5 6 7 8 P T F Y Description 1 Input signal 1 to 5V DC 4 to 20mA DC 1 2 Output signals 1 to 5V DC 4 to 20mA DC V A 1 2 3 Power supply 24V DC/24V AC (50/60Hz) 100V AC (50/60Hz) 200V AC (50/60Hz) CHARACTERISTICS Accuracy: Less than ± 0.1% of full span Response time: Less than 0.1 sec. (90% response) Dielectric strength: 1500V AC, 1 min. (Input - Output - Power- Ground) Insulation resistance: 500V DC, 100MΩ or over (Input - Output - Power) EDS9-23a Date Mar. 1, 1996 PTF 12 Input amplifier Signal isolation circuit Input amplifier AC/DC conversion 11 Input DC/AC conversion FUNCTIONAL DIAGRAM 31 Output 32 43 Power supply circuit Power supply 44 34 EXTERNAL CONNECTION DIAGRAM OUTLINE DIAGRAM (Unit: mm) Terminal screw M4 Terminal screw M2.5 (for transmission) Main unit Voltage • Current input 35 74 94 INPUT + 11 12 13 14 21 22 23 24 5 100 2 48 52 Terminal 6 Stopper 31 32 + - 130 Panel mounting 33 34 OUTPUT 41 42 DIN rail mounting 43 44 + POWER 2-M4 DIN rail RANGE OF DELIVERY Main unit and socket 40 52 Stopper Caution on Safety *Before using this product, be sure to read its instruction manual in advance. Head Office Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome, Shinagawa-ku, Tokyo 141-0032, Japan http://www.fesys.co.jp/eng Instrumentation Div. International Sales Dept. No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187 http://www.fic-net.jp/eng Information in this catalog is subject to change without notice. Printed in Japan