MEANWELL RCP-1000-12

RCP
1000 ~ 3000W Front End Power System
series
Features :
Universal AC input / Full range
Built-in 5V/0.3A auxiliary power
Built-in active PFC function, PF>0.96
Protections: Short circuit / Overload / Over voltage / Over temperature
Forced air cooling by built-in DC fan with fan speed control
Low profile:1U height
Active current sharing up to 3000W (3 units)in 19" rack, 3 racks max.
can be operated in parallel (up to 8 units) (Note.7)
Remote control for single unit
Built-in remote sense function
Output voltage trimming function
Hot-swap operation
Optional I2C serial data bus
AC OK & DC OK signal
Internal ORing diode
3 years warranty
SELECTION GUIDE
Single Unit: RCP-1000- 12 - C
2
C: With I C Interface
2
-: Without I C Interface
Output Voltage
I: AC Inlet(IEC320-C14)
T: Terminal Block
Rack: RCP-1U I
Whole System: RCP-3K1U I - 12 - C
2
C: With I C Interface
-: Without I 2 C Interface
Output Voltage
I: AC Inlet(IEC320-C14)
T: Terminal Block
SPECIFICATION - Single Unit
MODEL
RCP-1000-12
RCP-1000-24
RCP-1000-48
DC VOLTAGE
12V
24V
48V
RATED CURRENT
60A
40A
21A
CURRENT RANGE
0 ~ 60A
0 ~ 40A
0 ~ 21A
RATED POWER
720W
960W
1008W
200mVp-p
300mVp-p
23.2 ~ 24.8V
1.0%
46.3 ~ 49.7V
1.0%
RIPPLE & NOISE (max.) Note.2 150mVp-p
OUTPUT
11.6 ~ 12.4V
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE Note.3 1.0%
LINE REGULATION
0.5%
0.5%
0.5%
LOAD REGULATION
0.5%
0.5%
0.5%
1000ms, 60ms/230VAC at full load
SETUP, RISE TIME
16ms/230VAC at full load
HOLD UP TIME (Typ.)
VOLTAGE RANGE
INPUT
Note.5 90 ~ 264VAC
FREQUENCY RANGE
47 ~ 63Hz
EFFICIENCY (Typ.)
81%
8.5A/115VAC
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
127 ~ 370VDC
4.5A/230VAC
87%
10.5A/115VAC
5.5A/230VAC
89%
11A/115VAC
5.5A/230VAC
COLD START 50A
<1.1mA / 230VAC
105 ~ 125% rated output power
OVERLOAD
PROTECTION OVER VOLTAGE
OVER TEMPERATURE
Protection type : Constant current limiting, recovers automatically after fault condition is removed
13.2 ~ 16.2V
26.4 ~ 32.4V
52.8 ~ 64.8V
Protection type : Shut down o/p voltage, re-power on to recover
75
5 (TSW1) detect on heatsink of power transistor
85
5
(TSW2) detect on heatsink of power diode
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
File Name:RCP series-SPEC 2010-10-18
RCP
1000 ~ 3000W Front End Power System
MODEL
FUNCTION
RCP-1000-12
RCP-1000-24
RCP-1000-48
AUXILIARY POWER
REMOTE ON/OFF CONTROL
5V @ 0.3A
REMOTE SENSE
DC OK SIGNAL
Compensate voltage drop on the load wiring up to 0.5V
AC FAIL SIGNAL
The TTL signal out, refer to function manual
OUTPUT VOLTAGE TRIM
Adjustment of output voltage, possible between 90 ~ 110% of rated output
OVER TEMP WARNING
Logic " High" for over temperature warning, refer to function manual
WORKING TEMP.
-20 ~ +60
By electrical signal or dry contact
ON:short
series
OFF:open
The TTL signal out, refer to function manual
WORKING HUMIDITY
ENVIRONMENT STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
(Refer to output load derating curve)
20 ~ 90% RH non-condensing
-40 ~ +85
, 10 ~ 95% RH
0.02%/ (0 ~ 50 )
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
UL60950-1, TUV EN60950-1 approved
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.7KVDC
WITHSTAND VOLTAGE
SAFETY & ISOLATION RESISTANCE
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25
EMC
EMI CONDUCTION & RADIATION Compliance to EN55022 (CISPR22) Class B
/ 70% RH
(Note 4)
HARMONIC CURRENT
OTHERS
Compliance to EN61000-3-2,-3
EMS IMMUNITY
Compliance to EN61000-4-2,3,4,5,6,8,11, ENV50204, EN61000-6-2 (EN50082-2), heavy industry level, criteria A
MTBF
43.4Khrs min. MIL-HDBK-217F (25
295*127*41mm (L*W*H)
1.91Kg; 6pcs/12.5Kg/1.04CUFT
DIMENSION
PACKING
)
SPECIFICATION - Rack System
MODEL
OUTPUT
RCP-3K1U -12
RCP-3K1U -24
RCP-3K1U -48
MODULE
RCP-1000-12
RCP-1000-24
RCP-1000-48
RACK
RCP-1UI or RCP-1UT
OUTPUT VOLTAGE
12V
24V
48V
MAX. OUTPUT CURRENT
180A
120A
63A
2880W
3024W
MAX. OUTPUT POWER Note.6 2160W
VOLTAGE RANGE
INPUT
FUNCTION
Note.5 90 ~ 264VAC
FREQUENCY RANGE
127 ~ 370VDC
47 ~ 63Hz
AC CURRENT (Typ.)FOR EACH UNIT 8.5A/115VAC
4.5A/230VAC
10.5A/115VAC
5V @ 0.3A
REMOTE SENSE
DC OK SIGNAL
Compensate voltage drop on the load wiring up to 0.5V. "Local Sense"should be connected in order to get the correct output voltage if the "Remote Sense"is not used
The TTL signal out, refer to function manual
AC FAIL SIGNAL
The TTL signal out, refer to function manual
OUTPUT VOLTAGE TRIM
Adjustment of output voltage, possible between 90 ~ 110% of rated output
OVER TEMP WARNING
WORKING TEMP.
Logic " High" for over temperature warning, refer to function manual
-20 ~ +60 (Refer to output load derating curve)
WITHSTAND VOLTAGE
By electrical signal or dry contact
ON:short
OFF:open
20 ~ 90% RH non-condensing
-40 ~ +85
, 10 ~ 95% RH
0.02%/ (0 ~ 50 )
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
UL60950-1, TUV EN60950-1 approved
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.7KVDC
SAFETY & ISOLATION RESISTANCE
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25
EMC
EMI CONDUCTION & RADIATION Compliance to EN55022 (CISPR22) Class B
NOTE
5.5A/230VAC
AUXILIARY POWER
REMOTE ON/OFF CONTROL
SAFETY STANDARDS
OTHERS
11A/115VAC
<3.5mA / 230VAC
WORKING HUMIDITY
ENVIRONMENT STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
(Note 4)
5.5A/230VAC
LEAKAGE CURRENT
/ 70% RH
HARMONIC CURRENT
Compliance to EN61000-3-2,-3
EMS IMMUNITY
Compliance to EN61000-4-2,3,4,5,6,8,11, ENV50204, EN61000-6-2 (EN50082-2), heavy industry level, criteria A
DIMENSION
Rack 483.6*350.8*44(L*W*H)
11Kg; 1pcs/11Kg/2.67CUFT
PACKING
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.”
(as available on http://www.meanwell.com)
5. Derating may be needed under low input voltages. Please check the derating curve for more details.
6. Output of all the RCP-1000 modules are connected in parallel in the rack.
7. Under parallel operation of more than one rack connecting together, ripple of the output voltage may be higher than the SPEC at light load condition.
It will go back to normal ripple level once the output load is more than 10%.
File Name:RCP series-SPEC 2010-10-18
RCP
1000 ~ 3000W Front End Power System
Mechanical Specification (Single Unit)
Case No. 952A
series
Unit:mm
295
41
24
CN501
DC OK AC OK
46
127
SVR51
Air flow
direction
1
3
5 7 10 13 16 19
2
4
6 9 12 15 18 21 22
23
24
Input / Output Connector Pin No. Assignment(CN501) : Postronic P CIB24W9M400A1
Pin No.
1,2,4
3,5,6
7
8
9
Assignment
+V
-V
ON/OFF
+S
-S
Pin No.
10
11
12
13
14
Assignment
AC_OK
DC_OK
CS
V_TRIM
T_ALARM
Pin No.
15
16
17
18
19
Assignment
+5V_AUX
GND_AUX
SDA
SCL
A0
Pin No.
20
21
22
23
24
Assignment
A1
A2
FG
AC/ L
AC/ N
Mating Housing
Postronic
PCIB24W9F400A1
Block Diagram
PFC fosc : 110KHz
PWM fosc : 90KHz
+S
I/P
EMI
FILTER
ACTIVE
INRUSH
CURRENT
LIMITING
RECTIFIERS
&
PFC
POWER
SWITCHING
RECTIFIERS
&
FILTER
DETECTION
CIRCUIT
PWM
CONTROL
V_TRIM
2
O.V.P.
AUX
POWER
FAN
+V
-V
-S
CURRENT
SHARE
CURRENT
SHARE
O.L.P.
PFC
CONTROL
ORING
DIODE
I C FUNCTION
OPTIONAL
2
I C
RECTIFIERS
CONTROL
ON/OFF
ON/OFF
DETECTION
CIRCUIT
AC_OK
DC_OK
T_ALARM
RECTIFIERS
&
FILTER
AUX POWER
(5V/0.3A)
AUX GND
File Name:RCP series-SPEC 2010-10-18
RCP
1000 ~ 3000W Front End Power System
Mechanical Specification (Rack System)
Case No. 959A
series
Unit:mm
Fig1
ADDRESS
SWITCH
-
14
25
1
13
CN500
+
14
25
1
13
LC NC LB NB LA NA
RCP-1UT
10
8
ADDRESS
SWITCH
C
Mounting Bracket
B
A
-
RCP-1UI
CN500
+
14
25
1
13
24
50
3-M5 L=6mm
3-M5 L=6mm
22
22
Air flow
direction
Module B
DC OK AC OK
DC OK AC OK
Module A
31.8
Module C
10.6
466.2
DC OK AC OK
6.1
44
7.1
50
125
125
350.8
125
125
440
483.6
File Name:RCP series-SPEC 2010-10-18
RCP
1000 ~ 3000W Front End Power System
series
CN500 Pin No. Assignment
Connector Pin No. Assignment(CN500) : D-Type Right Angle 25 positions
Pin No.
1
2
3
4
5
Assignment
ON/OFF-A
AC-OK-A
DC-OK-A
V-TRIM-A
T-ALARM-A
Pin No.
Pin No.
Assignment
+5V-AUX
GND-AUX
ON/OFF-B
AC-OK-B
DC-OK-B
6
7
8
9
10
Assignment
V-TRIM-B
T-ALARM-B
NC
CS
ON/OFF-C
11
12
13
14
15
Pin No.
16
17
18
19
20
Pin No.
Assignment
AC-OK-C
DC-OK-C
V-TRIM-C
T-ALARM-C
+S
Assignment
-S
+V
SCL
SDA
-V
21
22
23
24
25
CN500 IN/OUT Connector pins function description
Pin No.
1,8,15
2,9,16
3,10,17
4,11,18
5,12,19
6
Function Description
ON/OFF Each unit can separately turn the output on and off by electrical or dry contact between ON/OFF A,B,C(pin 1,8,15) and -S(pin 21). Short: ON, Open:OFF.
AC-OK Low : When the input voltage is 82Vrms +/-4V. High : when the input voltage in 82Vrms +/-4V.
DC-OK High : When the Vout 80%+/-5%. Low : When Vout 80%+/-5%
V-TRIM Connection for output voltage trimming. The voltage can be trimmed within its defined range.
T-ALARM High : When the internal temperature is within safe limit. Low : 10 below the thermal shut down limit.
+5V-AUX Auxiliary voltage output, 4.3~5.3V, referenced to GND-AUX(pin 7). The maximum load current is 0.3A. This output has the built-in
"Oring diodes" and is not controlled by the remote ON/OFF control.
GND-AUX Auxiliary voltage output GND. The signal return is isolated from the output terminals (+V & -V).
Current sharing signal. When units are connected in parallel, the CS pins of the units should be connected to allow current balance
CS
between units.
7
14
20
+S
Positive sensing. The +S signal should be connected to the positive terminal of the load. The +S and -S leads should be twisted in pair to
minimize noise pick-up effect. The maximum line drop compensation is 0.5V.
21
-S
Negative sensing. The -S signal should be connected to the negative terminal of the load. The -S and +S leads should be twisted in pair to
minimize noise pick-up effect. The maximum line drop compensation is 0.5V.
22
23
24
25
+V
SCL
SDA
-V
Positive output voltage. For local sense use only, can't be connected directly to the load.
2
2
Serial clock used in the I C interface option. Refer to the I C interface description.
2
2
Serial data used in the I C interface option. Refer to the I C interface description.
Negative output voltage. For local sense use only, can't be connected directly to the load.
Static Characteristics
Derating Curve
Ta=25
100
100
90
80
80
70
LOAD (%)
LOAD (%)
60
40
20
-20
60
50
40
0
10
20
30
40
50
AMBIENT TEMPERATURE ( )
60
70
90
95
100
115
264
INPUT VOLTAGE (VAC) 60Hz
File Name:RCP series-SPEC 2010-10-18
RCP
1000 ~ 3000W Front End Power System
series
Function Manual
1. Remote ON/OFF Control
The PSU can be turned ON/OFF together or separately by using the "Remote ON/OFF" function.
RCP-1U
ON/OFF A
ON/OFF B
ON/OFF C
1
8
15
ON/OFF A
ON/OFF B
ON/OFF C
RCP-1U
-S 21
1
8
15
Between ON/OFF and -S Output
-S 21
SW Open
OFF
SW Short
ON
2. Voltage Drop Compensation
2.1 Remote Sense
The remote sense compensates voltage drop on the load wiring up to 0.5V.
+V
20
+S
RCP-1U
+V
LOAD
21
-S
-V
-V
Sense lines should be twisted in pairs
2.2 Local Sense
Notice : The +S,-S have to be connected to the +V,-V terminals locally in order to get the correct output voltage if the remote sensing is not used.
+V
+S
RCP-1U
-V
-S
22
20
25
21
3. Output Voltage Trimming
Output voltage can be trimmed between 90~110% of its rated value by the following method.
RCP-1U
+S
V-TRIM-A
V-TRIM-B
V-TRIM-C
-S
20
4
11
18
21
R1
R1
R1
R2
R2
R2
3.1 RCP-1000-12
Vout (%)
Vout (%)
100
110
98
108
96
106
94
104
92
102
90
100
180K
240K
350K
560K
1.2M
NC
R1 ( )
min. 0.1W
NC
300K
120K
62K
31K
13K
R2 ( )
min. 0.1W
File Name:RCP series-SPEC 2010-10-18
RCP
1000 ~ 3000W Front End Power System
3.2 RCP-1000-24
Vout (%)
series
Vout (%)
100
110
98
108
96
106
94
104
92
102
90
100
560K
750K
1M
1.6M
3.3M
NC
R1 ( )
min. 0.1W
NC
330K
130K
62K
30K
10K
R2 ( )
min. 0.1W
NC
345K
140K
70K
36K
15K
R2 ( )
min. 0.1W
3.3 RCP-1000-48
Vout (%)
Vout (%)
100
110
98
108
96
106
94
104
92
102
90
100
1.3M
1.7M
2.4M
3.6M
7.6M
NC
R1 ( )
min. 0.1W
4. Front Panel Indicators & Corresponding Signal at Function Pins
Function
AC-OK
AC-NG
DC-OK
DC-NG
T-OK
T-ALARM
LED
ON
OFF
ON
OFF
-------
* Signal
Description
0 ~ 0.5V
When input voltage 82V 4V
4.5 ~ 5.5V
When input voltage 82V 4V
0 ~ 0.5V
When output voltage 80% 5% of Vo rated.
4.5 ~ 5.5V
When output voltage 80% 5% of Vo rated.
0 ~ 0.5V
When the internal temperature (TSW1 & TSW2 short) is within safe limit
When the internal temperature (TSW1 or TSW2 open) exceeds the limit of temperature alarm 4.5 ~ 5.5V
PSU Output
ON
OFF
ON
ON
ON
OFF
*Signal between function pin and "-S".
2
5. I C Bus Interface Option
5.1 Addressing(A0,A1,A2)
2
The DIP switch down position is logic level "1" and the up position is level "0". Address are applicable when modules RCP-1000 I C function are used.
ON
1 2 3 4 5 6 7 8 9
OFF
Module A Module B Module C
Address dip switch setting
A2
A1
A0
Module
3
2
1
A
6
5
4
B
9
8
7
C
File Name:RCP series-SPEC 2010-10-18
RCP
1000 ~ 3000W Front End Power System
series
5.2 Digital Function (Read Only)
2
Digital function are provided by a PCF8574 8-bit I/O port device. When this device is read by the I C bus controller, a single 8-bit word provides the
following information.
BIT
GOOD STATE
FAIL STATE
0
AC Input Fail
FUNCTION
0
1
Input power fail
MEANING
1
Output Power Good / Fail
0
1
Output voltage is less than specification
2
Temperature Warning
0
1
Internal temperature is over 60
3
Over Temperature Protection
0
1
Temperature exceeds nominal operating limit. PSU turns off
4
Fan Fail Warning
0
1
Failure of an internal fan
5
Not Used
------
------
Not used
6
Not Used
------
------
Not used
7
Not Used
------
------
Not used
. PSU turns on
PCF8574 slave address
Bit
7
6
5
4
3
2
1
0
Value
0
1
0
0
A2
A1
A0
R/W
Read : 1
6. Analog Function (Read Only)
Write : 0
2
6.1 Analog function are provided by a single PCF8591 4-channel 8-bit A/D converter. When this device is read by the I C bus controller, it provides an 8-bit
word with the following information:
A/D Channel
FUNCTION
1
Output Voltage
2
Output Current
3
Internal Temperature
4
Not Used
PCF8591 slave address
Bit
7
6
5
4
3
2
1
0
Value
1
0
0
1
A2
A1
A0
R/W
1
0
PCF8591 control byte
Bit
7
6
5
4
3
2
Value
0
0
0
0
0
0
0
0
1
0 : Output Voltage
1 : Output Current
0 : Internal Temperature
6.2 A/D scaling
The voltage reading is made inside the power supply unit before the "Oring diode" and is typically 0.5V higher than the actual output voltage.
The following table for the scaling should be employed:
VALUE = BYTE VALUE x RESOLUTION
Output Voltage
Range
Scaling
12V
0~16V
0.0625V/Bit
5%
24V
0~33V
0.129V/Bit
+3%,-5%
48V
0~65V
0.254V/Bit
+2%,-5%
12V
0~80A
0.312A/Bit
10%
24V
0~55A
0.215A/Bit
10%
48V
0~30A
0.117A/Bit
10%
Tolerance
12V
0~100
0.391
/Bit
3
24V
0~100
0.391
/Bit
3
48V
0~100
0.391
/Bit
3
A/D Channel 1
Voltage
A/D Channel 2
Current
A/D Channel 3
Temperature
7.EEPROM Function (Read Only)
The EEPROM is a 2048 bit (256 byte) device which is preprogrammed at the factory with the following data :
EEPROM slave address
Address
Bytes
4
16
Manufacturer
Bit
7
6
5
4
3
2
1
0
20
20
Serial Number
Value
1
0
1
0
A2
A1
A0
R/W
40
16
Revision
56
16
Country of production
72
16
Model Name
88
16
Output Voltage
104
16
Date of production
254
2
Check Sum
Data
File Name:RCP series-SPEC 2010-10-18