EMERSON-NETWORKPOWER DS450DC-3-002

Embedded Power for
Business-Critical Continuity
DC Input
DS450DC-3/
DS550DC-3
450 - 550 Watts
Distributed Power System
Distributed Power Bulk Front-End
Total Output Power: 450 - 550 Watts
+12Vdc main Output
+3.3vdc Stand-by Output
DC Input 40 - 75 Vdc
Connector input shown
Electrical Specifications
Special Features
Input
Input ra­nge:
40-75 Vdc
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Frequency:
Inrush current:
DC input
1U X 2U Form Factor
10.3W / in3 (DS550)
8.4W / in3 (DS450)
+12vdc Output
+3.3vdc Stand-By
No Minimum Load Required
Hot Plug Operation
N + 1 Redundant
Internal OR’ing Fets
Active Current Sharing
Built-in Cooling Fans
(40mm x 28mm)
I2C Communication Interface Bus
EERPOM for FRU Data
Amber LED Status, Fan_Fail
Green LED Status, Power Good /
DC_OK Status (VIN_GOOD)
Internal Fan Speed Control
Fan Fail Tach Output Signal
One Year Warranty
Safety
•
•
•
•
•
UL/cUL 60950 (UL Recognized)
NEMKO+ CB Report EN60950
EN60950
CE Mark
China CCC
Efficiency:
21A maximum
EVT: 87% @ 72 Vdc; 87.4% @ 75 Vdc
Conducted EMI:
FCC Subpart J EN55022 Class A
Radiated EMI:
FCC Subpart J EN55022 Class A
Power factor:
N/A
Leakage current:
N/A No touch current required.
Hold up time:
1ms minimum
Output
Main DC voltage:
+12 V
Stand-By:
+3.3 vsb
Adjustment range:
Factory Set, no pot adjustments
Regulation:
+12 Vdc; +5%/-5%
+3.3 vsb; +5%/-5%
Over current:
See Table 1 next page
Over voltage:
+12 Vdc; 13.5 - 15 Vdc
+3.3 vsb; 3.76 - 4.30 Vdc
Under voltage:
+12 Vdc; 10.5 V - 11.0 V
+3.3 vsb; 2.77 - 3.00 Vdc
<3 seconds, EVT: 2 seconds
3 - 300 mS
Turn-on delay :
+12v Output Rise Time
Rev. 12.15.08
DS450DC/DS550DC
of 4
Embedded Power for
Business-Critical Continuity
Rev. 12.15.08
DS450DC/DS550DC
of 4
Logic Control
PS_ON/L
(Power supply enable)
The power supply output will be enabled when this signal is
pulled low (<0.8 V).
HIGH = Output V1 OFF
LOW = Output V1 ON
VIN_GOOD/H (Input OK)
Active High signal asserted when the input voltage rises above
the min input voltage specified.
This signal is internally pulled up through 4.7 K ohms to the
3.3 V housekeeping voltage.
POK/H (Output OK)
Active High signal asserted when the output is within regulation. This signal is internally pulled up through 1.0 K ohms to
the 3.3 V housekeeping voltage.
TACH_1
This open collector signal generates two pulses per each fan
revolution. This signal is eternally pulled up to the
housekeeping voltage.
PS_KILL
This signal will cause the output to shut down when drive high
(>24 V) or left floating. The PS_KILL will cause the output to
latch off and requires recycle of PS_ON or DC input to reset.
Digital Control
PMBus - I2C compliant
Environmental Specifications
Operating temperature:
+10° to 45°C (50% power derating at 70°C)
Storage temperature:
Altitude, operating:
-40°C to +70°C
10,000ft.
Electromagnetic
-EN61000-3-2, -3-3
susceptibility / Input transients: -EN61000-4-2, 4.3, 4-4, -4-5, 4-11 Level
-EN55024:1998
RoHS & lead-free compliant (no tantalum caps.)
Humidity:
20 to 90% RH, non-condensing
Shock and vibration specificatons complies with Astec Std. Specifications, Q3205
MTBF (observed)
500K Hrs at 80%, 40°C
Table 1
Ordering Information
Output
Nominal Output Set Point
Total
Minimum
Voltage Set Point Tolerance Regulation Current
Maximum
Current
Output Ripple
P/P
Over Current
Options
DS450DC-3
12.0vdc
3.3vsb
±0.2%
±1%
+5 / -3%
+5 / -4%
0A
0A
37.0A
3.0A
120mV
60mV
39.5 - 44.4%
4.9A Avg, 7A max
Standard
DS450DC-3-002
12.0vdc
3.3vsb
±0.2%
±1%
+5 / -3%
+5 / -4%
0A
0A
37.0A
3.0A
120mV
60mV
39.5 - 44.4%
4.9A Avg, 7A max
Reverse Air
DS550DC-3
12.0vdc
3.3vsb
±0.2%
±1%
+5 / -3%
+5 / -4%
0A
0A
45.0A
3.0A
120mV
60mV
48.0A - 54.0A
4.9A Avg, 7A max
Standard
DS550DC-3-003
12.0vdc
3.3vsb
±0.2%
±1%
+5 / -3%
+5 / -4%
0A
0A
45.0A
3.0A
120mV
60mV
48.0A - 54.0A
4.9A Avg, 7A max
Reverse Air
*Over current latches off if overcurrent lasts over 1 seconds, otherwise it is auto recovery.
*For 5vsb, consult marketing.
Embedded Power for
Business-Critical Continuity
Rev. 12.15.08
DS450DC/DS550DC
of 4
Mechanical Drawing
A
(2X)
REF RAMP TO FAN
1,6
40
38,4
254,7
337,6
305,6
10
± 0,8
276,3
254,7
(3X)
LABEL
3 ± 0,3
78
11
01
(1.8)
(0.7)
8
302,9
± 0,8
STANDARD AIR FLOW DIRECTION
-002 REVERSE AIR FLOW DIRECTION
07
5 ± 0,5
± 0,5
09
01
329,4
254,6
1.25 MIN
5,8
38,4
72,2
05
± 0,8
06
LATCHING SPRING DISTANCE (REF.)
3,8
± 0,8
39,8
± 0,8
04
74,1
± 0,6
01
A
08
24,7
± 0,5
41,5
A
326,7
78 ± 0,8
03
02
(3X)
( 80,1 )
254,6
01
01
12
Embedded Power for
Business-Critical Continuity
Rev. 12.15.08
DS450DC/DS550DC
of 4
Table 2
­Americas
DC Output Connector Pinout Assignment
5810 Van Allen Way
Carlsbad, CA 92008
USA
Telephone:+1 760 930 4600
Facsimile: +1 760 930 0698
Male connector as viewed from the rear of the supply:
D1
D2
D3
D4
D5
D6
C1
C2
C3
C4
C5
C6
B1
B2
B3
B4
B5
B6
A1
A2
A3
A4
A5
A6
PB1 PB2 PB3 PB4 PB5 PB6
P1 - Power Supply Side
1.FCI Power Blade 51721 series
51721-10002406AA
2.Molex Power Connector
SD-87667 series
87667-7002
Mating Connector (System Side)
1.FCI Power Blade
51741-10002406CC
Strait Pins
2.FCI Power Blade
51761-10002406AA
Right Angle
Europe (UK)
Pin
PB 1
PB 2
PB 3
PB 4
PB 5
PB 6
A1
A2
A3
A4
A5
A6
B1
B2
B3
B4
B5
B6
C1
C2
C3
C4
C5
C6
D1
D2
D3
D4
D5
D6
Signal Name
+12V RETURN
+12V RETURN
+12V RETURN
+12V
+12V
+12V
PS_KILL
+12V CURRENT SHARE
LOGIC RETURN
+3V3 STAND-BY
A0 (I2C Address BIT 0 Signal)
+3V3 STAND-BY
LOGIC RETURN
SPARE
LOGIC RETURN
+3V3 STAND-BY
SDA (I2C Data Signal)
PSON (Power Enable Signal)
LOGIC RETURN
TACH 1 (Fan Fail Signal)
LOGIC RETURN
+3V3 STAND-BY
SCL (I2C Clock Signal)
VIN_GOOD (AC Input Present)
-PS_PRESENT ( Power Supply Seated)
SPARE
LOGIC RETURN
+3V3 STAND-BY
S_INT (Alert)
POK (Output Power Ok)
Waterfront Business Park
Merry Hill, Dudley
West Midlands, DY5 1LX
United Kingdom
Telephone:+44 (0) 1384 842 211
Facsimile: +44 (0) 1384 843 355
Asia (HK)
14/F, Lu Plaza
2 Wing Yip Street
Kwun Tong, Kowloon
Hong Kong
Telephone:+852 2176 3333
Facsimile: +852 2176 3888
For global contact, visit:
www.PowerConversion.com
techsupport.embeddedpower
@emerson.com
While every precaution has been taken to ensure
accuracy and completeness in this literature, Emerson
Network Power assumes no responsibility, and disclaims
all liability for damages resulting from use of this
information or for any errors or omissions.
Emerson Network Power.
The global leader in enabling
business-critical continuity.
AC Power
Connectivity
DC Power
Embedded Computing
Embedded Power
Monitoring
Outside Plant
Power Switching & Controls
Precision Cooling
Racks & Integrated Cabinets
Services
Surge Protection
EmersonNetworkPower.com
Emerson Network Power and the Emerson
Network Power logo are trademarks and
service marks of Emerson Electric Co. ©2008 Emerson Electric Co.