LEM AHR500B420

AC/DC Current transducer AHR-B420
IPN = 500 .. 2000 A
The transducer for the electronic measurement of DC & distorted AC
waveform currents, with galvanic isolation between the primary circuit
(power) and the secondary circuit (measurement).
True r.m.s. 4-20 mA current output.
Electrical data
Primary nominal
DC & AC current
I PN (At rms)
Output currentt
2000
2500
2000
2500
3000
4-20
4-20
4-20
4-20
4-20
500
800
1000
1500
2000
RL
VC
IC
ISL
ÎP
Features
Primary AC current
max. peak value 1)
I P (A)
Type
• DC + distorted AC waveform currents
measurement
I OUT (mA DC)
Load resistance
Supply voltage
Current consumption
Output current limitation
Overload capability (Ampere Turns)
AHR
AHR
AHR
AHR
AHR
500 B420
800 B420
1000 B420
1500 B420
2000 B420
< 300
Ω
+ 20 .. 50 V DC
30 mA + IOUT
< 25
mA
30000
At
Performance data
X
ε
Accuracy @ IPN, TA = 25°C (excluding offset)
Linearity error (1% of IPN .. ± IPN)
Electrical offset current, TA = 25°C
Temperature coefficient of IOE ( 0 .. + 60 °C)
(- 40..+ 70 °C)
Temperature coefficient of G (% of reading)
Response time to 90% of IPN step
Frequency bandwidth (±1 dB)
L
IOE
TCIOE
TCG
tr
BW
< ± 1 % of IPN
< ± 1.0 % of IPN
4 mA <±1.0 % of IPN
± 3.2
µA/K
± 6.4
µA/K
± 0.15
%/K
< 150
ms
DC 20 .. 6000Hz
• True r.m.s. output
• Busbar or panel mounting
• Split core type
• Insulated plastic case recognized
according to UL94-V0.
Advantages
• High isolation between primary and
secondary circuits
• Eliminates insertion loss
• Easy installation.
Applications
• AC power supplies or Motors:
True r.m.s. current sensing - the most
accurate way to monitor power supply
or motor input power
• VFD Controlled Loads:
General data
TA
TS
m
IPxx
Ambient operating temperature
Ambient storage temperature
Mass
Protection degree
- 40 .. + 70
- 40 .. + 85
260
IP20
°C
°C
g
VFD output current monitoring to
indicate how the motor and the
attached load are operating
• SCRs or Switch-mode Rectifiers:
Accurate measurement of output
current
• Renewable Energy Installations or
Backup Batteries:
Note :
1)
The max. peak AC current is the highest peak level of the primary signal that is
taken into account for accurate true r.m.s. calculation. Yet the device is designed
for maximum continuous true r.m.s. value equal to I PN, whereas the output is limited
by the above specified output limitation.
Continuous condition minitoring
allowing automatic failure detection/
anticipation.
Page 1/3
061012/4
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
www.lem.com
Current Transducer AHR-B420
Isolation characteristics
Vb
Vd
dCp
dCl
CTI
Rated isolation voltage rms
600
V
with IEC 61010-1 according to the 61326 standards and following conditions:
- Double insulation
- Over voltage category CAT III
- Pollution degree PD2
- Heterogeneous field
Rms voltage for AC isolation test, 50Hz, 1min
5.2
kV
Creepage distance
11
mm
Clearance distance
11
mm
Comparative tracking index (Group I)
600
Output polarity with DC input
Output in mA
20
4
-Ipn
+Ipn
Safety
This transducer must be used in electric/electronic equipment with respect to
applicable standards and safety requirements in accordance with the
manufacturer’s operating instructions.
Installation and maintenance should be done with main power supply
disconnected.
The operator must have an accreditation to install this material.
Caution! Risk of electrical shock
When operating the transducer, certain parts of the module can carry hazardous
voltage (e.g. primary conductor).
Ignoring this warning can lead to injury and/or cause serious damage.
The user must take care of all protection guarantee against electrical shock.
This transducer is a built-in device, whose conducting parts must be inaccessible
after installation. A protective housing or additional shield could be used.
Page 2/3
061012/4
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
www.lem.com
Dimensions AHR-B420 (in mm. 1 mm = 0.0394 inch)
25
20
8.3 0
17 4
10 4
40
86
9.10
5 0.50
54.10
22. 28
3
8 .30
25 .60
5.5 0
15
35
15
37
20.34
55
110
15 0
Connections
Mechanical characteristics
• Wires up to 2 mm ∅
• Female connector provided (screw terminals)
• General tolerance
• Primary aperture
± 1 mm
104 x 40 mm
AHR-C420
• Busbar fastening
1 hole ∅ 5.5 mm &
2 slots 5.5 x 30 mm
Output Connector
1(Vcc) 2(Iout) 3(NC) 4(GND)
Panel mounting
Distance between holes axes
AHR
4 holes ∅ 3.2 mm
15 x 150 mm
Remarks
• The return busbar and primary conductor elbow must
be located at least at a distance of 2.5 x the window
length away from the transducer case.
• The temperature of the primary busbar can not exceed
90°C.
• Dynamic performances are the best with a primary
busbar completely filling the primary aperture.
• This is a standard model. For different versions
(supply voltages, different outputs, bidirectional
measurements...), please contact us.
24 VDC Power
(+)
(-)
(-)
(+)
Load
(Controller, meter etc)
+24VDC
OUT
Is
Ip
GND
Page 3/3
061012/4