ETC 420TWHL-AAXX-9

Isolating Terminal Blocks
420TW
The 420TW range of DIN-rail terminals provide input
isolation and signal conversion
■
Voltage, current and thermocouple inputs
■
RFI protection, input isolation
■
Replace standard DIN-rail terminals
■
Simple 2 wire connection
■
High noise immunity
■
Low cost solution
Options and ordering codes
420TW HL-A
A XX
–
9
PRICE
INFORMATION
AND ORDERING
Input
1-5 Volts
420TW HL-F
0-10 Volts
420TW HL-G
Thermocouple
420TW TC-J
▲
RTD
Wiring diagram
420TW RTD-J
4-20mA
0-10V
T/C
4-20mA
▲
Dimensions and connections
63mm
▲
The 420TW series of isolating terminal blocks can replace standard DIN-rail
terminals to provide input isolation and signal conversion.
The units are powered from the output side, making them ideal for PLC and data
acquisition applications.
Inputs available include thermocouple, RTD, current and voltage and the standard
output is 4-20mA.
For thermocouple inputs, internal rotary switches allow the user to select virtually
any type of thermocouple and the temperature range required.
A typical wiring arrangement is shown opposite.
The device is housed in an ultra-compact DIN-rail mounted enclosure only
18mm wide.
24V
▲
Description
▲
420TW HL-E
▲
1 2
58mm
0-5 Volts
▲
420TW HL-A
1.
2.
3.
4.
Output Ch +ve
Output Ch -ve
Input Ch +ve
Input Ch -ve
▲
4-20mA
▲
18mm
Input types
The 420TW device can accept J, K, T, R, S, E and N type thermocouples. The RTD
input accepts a PT100 2 wire sensor.
3 4
▲
Specifications
Parameter
Supply voltage
Input current
Full scale volt drop
Input impedance (volt in)
Input impedance (mA in)
Output linearity error
Temp coefficient
Load resistance error
Time constant (10-90%)
Operating ambient
Relative humidity
Isolation voltage
Surge voltage
Notes
Min
11V
0mA
Typ
24V
0-20mA
0.2V
1MΩ
10Ω
±0.1%
Max
32V
29mA
0.3V
100ppm/˚C
±5ppm/Ω
30ms
-15˚C
0%
1kV
Comments
Powered from output side
On input side (20mA input)
Voltage input
mA input
0<RL <600Ω
300ms for thermocouple input
70˚C
90%
2.5kV for 50µS
Transient of 10kV/µS
Absolute maximum ratings indicate sustained limits beyond which damage to the device may occur
Device is protected against reverse polarity connection
Accuracy figures based on 0-20mA input, 250Ω load resistance, and an ambient temperature of 20˚C