FC SERIES COMPACT CONTROLLER S (STEP OUTPUT TYPE) DATA SHEET PNC1 Compact controller S (fixed function type) is a compact single-loop controller using a microprocessor. It accepts uniform signals, and signals from a thermocouple and resistance bulbs as input, and includes sufficient control and computation functions which permit composition of a flexible system for PID control, square-root extraction, non-linear control, etc. FEATURES 1. PID auto turing function Optimum PID parameter can be obtained for processing. 2. High reliability LED's (red and green) are used for the bar graph indicator and for parameter indication (red). A non-volatile memory retains the control and computation parameters even if power should be interrupted. 3. All operations are performed from the front of the panel Operations such as parameter setting, auto/manual changeover are performed from the front of the panel. 4. Transmission function Incorporation of transmission function permits setting of concentrated monitoring data at the host system. FUNCTIONAL DIAGRAM Communication terminal Opening/resistance conversion Filter Linearize P I D Square-root extraction Internal input terminal External set point input (CAS) 4 to 20mA, thermocouple/ resistance bulb conversion A/D converter MV Process value input (PV) H R .A L M Pulse width conversion Non-linear SH R SL A.M Control output (pulse width) (PO) D/A converter Valve position input (W0) Bar graph indicator To other controllers Valve position output (voltage) (AO1) Compensated PV signal output (KPV) Set point transmit signal output (SV) Manual mode output (M) Local mode output (DO1) Remote request (R-REQ) M mode Pulse input (PI) L or SCC mode Manual mode command (SMV) External output terminal External input terminal Personal computer M mode R Fault output (FLT) PV tracking (DI1) High alarm output (H) Low alarm output (L) R mode Remote acknowledge signal (DI3) Fault FLT lamp H lamp Alarm L lamp : Option EDS11-101e Date Jan. 27, 1999 PNC1 (2) Analog output signal: 3 points SPECIFICATIONS 1. Control functions Compensated PV value signal KPV Set point transmission signal SV Value position (voltage) Proportional band (P); 1.0 to 3276.7% Integration time (I); 0.1 to 3276.7 sec Derivative time (D); 0.0 to 900.0 sec PID auto tuning function Additional function: Segmented line approximation; 15 segmented lines Square-root extraction; with low input cut function Filter; filter time constant 0.0 to 900.0 sec Non-linear control Output change rate limiter; 0.0 to 100.0% Alarm functions: 1 to 5V DC AO1 PID control: PV high/low limit alarm PV change rate alarm DV high/low limit alarm Control cycle: Select any 1 of 3 types at left Front panel LED (H, L) ON, digital output (H, L) "ON" 0.1 sec 2. Input signal (1) PV input signal: One point select from the following inputs. Voltage input signal 1 to 5V DC Input resistance, 1MΩ or more Allow. error, ± 0.2%/FS Current input signal 4 to 20mA DC 24V DC power is supplied to transmitter with AC power used. Allow. error, ± 0.2%/FS Thermocouple input I+ I0 I – Type J:0 to 600°C K:0 to 1200°C E:0 to 800°C R:0 to 1600°C 10mV DC span, or more Self-contained basic contact compensating function Allow. error ± 0.5%/FS 50°C span or more Allow. error ± 0.5%F/S JPt100/Pt100 –50 to 500°C Resistance bulb input (2) Analog input signal: 1 point External set point CAS 1 to 5V DC Input resistance, 1MΩ or more Allow. error ± 0.2%/FS (3) Digital input signal: 3 points SMV Contact input (photoDI1 coupler Remote acknouwledge signal DI3 insulation) Manual mode command PV tracking command ON/0V, OFF/24V (input current, approx. 11mA/24V DC) (4) Pulse width or pulse number input signal: any 1 set Pulse width input signal Pulse number input signal ON/0V, OFF/24V (input current, approx. 11mA/24V DC) Contact input PI+, (photo-coupler PI– insulation) ON/0V, OFF/24V (approx. 11mA/24V DC), max. input frequency 500Hz (5) Valve position input Voltage input signal W0 1 to 5V DC Input resistance, 1MΩ or more Allow. error, ± 0.5%/FS Resistance input signal W+ W0 W– 50 to 1000Ω width (Note 2) 3-wire system Potentiometer Allow. error, ± 0.5%/FS Output resistance, 1Ω or less Allow. error, ± 0.2%/FS (3) Digital output signal: 6 points Fault output FLT Manual mode output M High alarm output H Low alarm output L Local mode output DO1 Remote request signal DO2 Open-collector output (photocoupler insulation) Output rating, 30V x 0.1A DC, max. 4. Indication, setting and operating functions (1) Bar graph indication Indication system PV indicator SV indicator MV indicator Indication LED (red) LED (green) LED (red) Indication segment 101 + 2 101 + 2 51 + 2 Indication range 0 to 100% linear 0 to 100% linear 0 to 100%, linear Indication resolution 1 %/FS 1 %/FS 2%/FS Scale length 100mm 100mm 50mm Indication mode 0 to 100% bar graph indication, 0 to 100% reverse bar graph indication, dot indication, –50 to +50% deviation indication (2) Operation mode indication Indication method: LED (red and green) Red: M, SCC Green: A, R (3) Numerical indication, setting Indication method: LED (red), name in 3 digits + number in 5 digits (Negative sign included) Indication contents: Process variable (engineering unit), set point (engineering unit), alarm high/low values, PID parameters, etc. Indication contents are select by using F/S, , , keys Setting method: By using of F/S, , , , ST keys on front panel (4) SV setting function Fixed value setting method: By using , pushbuttons on front panel Setting speed, about 40 sec/FS Remote setting method: By external set point signal (voltage or pulse width input) (5) MV operating function Manual operating method: By using , buttons on front of the panel (6) Operation mode changeover By using R/A/M button on front panel R A changeover Balanceless bumpless Notes: (1) FS: Full scale (2) Basic value is 10 to 100 to 10Ω. Others should be specified. A R changeover Voltage signal Balance bumpless 3. Output signal A or R Pulse width input Balanceless bumpless (1) Control output signal: 1 set Pulse width PO+ Open-collector output PO (photo-coupler insulation) – 2 Output rating, 30V x 0.1A DC max. M changeover Balanceless bumpless 5. Power failure processing functions Power failure detection: Control stoppage at power failure detection During power failure: Operating parameters backed up by capacitor when power faulure occurs wthin 5 minutes Initial set point and manipulated output values, PID parameters, etc. are stored in nonvolatile memory (lasts for 10 years or longer at ambient temperature of 50°C or less). Power failure recovery time: Initial or continuous start set for power failure within 5 minutes. Recovery from power failure lasting longer than 5 minutes is done by initial. * Operation mode at initial set. M: Manual mode A: Auto mode R: Remote mode SCC: SCC mode 6. Self-diagnosis function Computation/control circuit abnormality: FLT indicator lights, FLT contact output turns "ON", and computation and control stop. Manipulated output can be controlled manually at FLT (soft manual). Input/output signal abnormality, manipulated output disconnection: FLT indicator lights, control stops and manipulated output is held. Computation processing and output processing other than for manipulated output continue. Fault contents indication: Cause of fault is indicated numerically on numerical indicator on front of the panel. 7. Transmission functions (1) Transmission items Supervisory items: From PNC to host Process variable, set point, manipulated output, deviation, operation mode, alarm information, PID parameters, various limiter values, constants, segmented line, analog input/output, digital input/output, etc. Setting operation items: From host to PNC Set point, manipulated output, operation mode, PID parameters, various limiter values, constants, segmented line, etc. (2) Transmission setting inhibit: Parameter setting enable/inhibit can be designated by transmission from the host. Designation is made by using F/S, , , , ST keys on the front of the panel. (3) Transmission interface: CC data line or RS422 interface select 1) CC data line: Connected with transmission controller (PMN) Interface: PMN and PNA; CC data line (PMN and host RS-232C) Transmission speed: 19.2 KBPS No. of units to be connected: 15 max. Transmission distance: 500m max. Transmission form: Multi-drop Code format: 12 bit binary 2) RS-422: Universal interface Transmission speed: 2400, 4800, 9600, 19200BPS, selectable No. of units connectable: 31 max. Code format: Stop bit .... 1 or 2 bit Parity bit ... Even, odd or none 8. Other functions Data protection function by use of pass code 9. Operating conditions Power supply: Select from the following 3 types 24V DC (20 to 30V) 100V AC (85 to 132V/47 to 63Hz AC) 200V AC (187 to 264V/47 to 63Hz AC) Power consumption: Approx. 12W (DC) Approx. 20VA (AC) Dielectric strength: 1500V AC, 1 min. Insulation resistance: 500V DC, 100MΩ or more Ambient temperature: 0 to 50°C Ambient humidity: 90% RH or less Enclosure: Steel case Enclosure class: Front IP65 (IEC 529) Name plate: 100 (H) x 70 (W), white acryl Dimensions: 144 (H) x 72 (W) x 391 (D) mm, IEC (DIN) standards Mass {weight}: Approx. 2.9kg Mounting method: Flush on indoor panel, vertical mounting is standard practice. Mounting on tilted surface possible (angle α) α=0° to 90° Finish color: Munsell N1.5 for the both of front and case. Range of delivery:Controller and mounting bracket Items prepared separately: Transmission cable (Type PNZ) 3 PNC1 CODE SYMBOLS 1 2 3 4 5 6 7 8 PNC 1 9 10 11 12 5 - 0 A Description Process variable input signal 1 to 5V DC 4 to 20mA DC J thermocouple 10mV DC span or more, with basic K thermocouple Junction compensatE thermocouple ing function R thermocouple Resistance bulb, JPt100, 3-wire system, 50°C span or more Resistance bulb, Pt100, 3-wire system, 50°C span or more A B C D E F G W Setting method A-M type R-A-M type A B Power supply 24V DC (20 to 30V DC) 100V AC (85 to 132V/47 to 63Hz AC) 200V AC (187 to 264V/47 to 63Hz AC) 1 2 3 Valve position input Voltage input (1 to 5V DC) Resistance input (50 to 1000Ω span) (Note 1) 1 2 Transmission function RS-422 CC data line (communication controller required) R C PID auto turing function Provided A Notes: (1) Standard resistance is 10 to 100 to 10Ω. Others should be specified. (2) Symbols of resistance bulbs are as follows. JPt100 ..... JIS C 1604-1981 Pt100 ....... IEC Pub751-1983 (JPt/Pt changeover is possible with front key.) OUTLINE DIAGRAM (Unit:mm) Terminal Panel thickness 8mm or less 16 144 Terminal cover Support bracket 140 36 Mounting bracket 200min. 72 355 Panel cutout 68 4 +0.7 0 138 +1 0 250min. When mounting "n" units 138 +1 0 200min. When mounting one unit (72.2n – 4) +1 0 No. of units n> =2 CONNECTION DIAGRAM Block terminals (M4 screws) AI (Process value input) DO (Manual mode) DO (Local mode) DO (Manual mode command) I+ (PV) I– (SC) 11 M 13 31 12 DO 1 14 SMV 15 AC I0 16 32 PI+ 33 PI– 34 FLT 35 AC PI (Pulse width input or pulse number input) DO (FLT output) Power supply (AC) AO (Compensated process value signal output) AO (Set point transmit signal) AO (Valve position output signal) W0 (Valve position input) AI, AO Common bus PO (Operation output) DO (High alarm output) DO (Low alarm output) Power supply (24V DC, AC power) DI, DO 24V power Ground – – KPV 51 71 CAS SV 52 72 AI1 AO 1 53 73 AI2 W0 54 74 W+ SC 55 75 W– PO+ 56 76 SC PO– 57 77 DO 2 H 58 78 DI 3 L 59 79 DI 2 PC* 60 80 DI 1 PCD 61 81 VP* G 62 82 VPD AI (External set point) Unused W+ (Valve position input) W– (Valve position input) AI, AO Common bus DO (Remote request) DI (Remote acknowledge) Unused DI PV tracking command + Power supply (24V DC, AC power) + DI, DO 24V power Note: * Symbols for AC power supply are VPO, PCO. Output is 24V DC (0.1A max.) approx. Process value input terminal connections 1 to 5V DC The 5th digit of code symbols: A 4 to 20mA DC The 5th digit of code symbols: B + Thermocouple The 5th digit of code symbols: C,D,E,F 11 31 + – 12 + 11 Resistance bulb The 5th digit of code symbols: G,W 31 – – 12 + 11 – 12 + + 11 – – 12 + 11 – 12 31 31 + 4 to 20mA DC power supply The 5th digit of code symbols: B – 31 PC 60 5 PNC1 Transmission connector 1 6 SIG GND (VST) 2 SHLD 7 8 RXD+ 9 RXD– 3 INH 4 TXD+ 1 6 SIG GND (VST) 2 SHLD Black 7 White 8 RXD+ 9 RXD– 5 TXD– 3 INH 4 TXD+ 5 TXD– Yellow Green Brown Red 6 7 8 RXD+ 9 RXD– 1 SIG GND (VST) 1 6 2 SHLD 7 3 INH 8 RXD+ 4 TXD+ 9 RXD– 5 TXD– Terminating resister SIG GND (VST) 2 SHLD Black 3 INH White 4 TXD+ 5 TXD– Green Yellow Red Brown End controller Host master controller 1st controller Host Termination resistor Transmission cable PNC1 PNC1 PNC1 PNC1 Caution on Safety *Before using this product, be sure to read its instruction manual in advance. Head Office 6-17, Sanbancho, Chiyoda-ku, Tokyo 102-0075, Japan http://www.fesys.co.jp/eng Sales Div. International Sales Dept. No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187 http: //www.fic-net.jp/eng Information in this catalog is subject to change without notice. Printed in Japan