FUJI EDSX5-92H

PRESSURE TRANSMITTER
FKG...5
DATA SHEET
The FCX – AIII pressure transmitter accurately measures
gauge pressure and transmits a proportional 4 to 20mA
signal.
The transmitter utilizes a unique micromachined capacitance
silicon sensor with state-of-the-art microprocessor technology to provide exceptional performance and functionality.
FEATURES
SPECIFICATIONS
Functional specifications
Service:
Output signal:
Power supply:
Liquid, gas, or vapour
4 to 20mA DC with digital signal superimposed on the 4 to 20mA signal.
Transmitter operates on 10.5V to 45V DC
at transmitter terminals.
10.5V to 32V DC for the units with optional
arrester.
[ L-Type ]
[ T-Type ]
Span, range and overrange limit:
Range limit
[kPa] {bar}
Span limit [kPa] {bar}
Type
F KG 01
FKG 02
FKG 03
FKG 04
FKG 05
Min.
Max.
1.3
{0.013}
5
{0.05}
30
{0.3}
100
{1}
500
{5}
130
{1.3}
500
{5}
3000
{30}
10000
{100}
50000
{500}
Lower limit Upper limit
−100
{−1}
−100
{−1}
−100
{−1}
−100
{−1}
−100
{−1}
130
{1.3}
500
{5}
3000
{30}
10000
{100}
50000
{500}
Overrange
limit
[MPa] {bar}
1
{10}
1.5
{15}
9
{90}
15
{150}
75
{750}
Remark: To minimize environmental influence, span should be greater
than 1/40 of the max. span in most applications.
– Lower range limit (vacuum limit) ;
Silicone fill sensor: See Fig. 1
Fluorinated fill sensor: 66kPa abs (500mmHg abs) at
below 60°C
– Conversion factors to different units;
1 MPa=103 kPa=10bar=10.19716kgf/cm2= 145.0377psi
1kPa=10mbar=101.9716mmH2O =4.01463inH2O
Load limitations: see figure below
[Ω]
2000
Load resistance
1. High accuracy up to ±0.04%
0.065% accuracy as standard, 0.04% accuracy as option.
Fuji’s micro-capacitance silicon sensor assures this accuracy for all elevated or suppressed calibration ranges
without additional adjustment.
2. Minimum environmental influence
The “Advance Floating Cell” design which protects the
pressure sensor against changes in temperature, and
overpressure substantially reduces total measurement
error in actual field applications.
3. Fuji/HART® bilingual communications protocol
FCX–AIII series transmitter offers bilingual communications to speak both Fuji proprietary protocol and HART®.
Any HART® compatible devices can communicate with
FCX–AIII.
4. Application flexibility
Various options that render the FCX–AIII suitable for almost any process applications include:
– Full range of hazardous area approvals
– Built-in RFI filter and lightning arrester
– 5-digit LCD meter with engineering unit
– Stainless steel electronics housing
5. Burnout current flexibility (Under Scale: 3.2 to 4.0mA,
Over Scale: 20.0 to 22.5mA)
Burnout signal level is adjustable using Model FXW
Hand Held Communicator (HHC) to comply with NAMUR
NE43.
6. Dry calibration without reference pressure
Thanks to the best combination of unique construction
of mechanical parts (Sensor unit) and high performance
electronics circuit (Electronics unit), reliability of dry
calibration without reference pressure is at equal level as
wet calibration.
1500
1474Ω
R=
E-10.5
(Imax+0.9)x10-3
1000
577Ω
Operating
area
500
24V
250
0
10
16.35
10.5V
Power voltage (DC)
45V
50
E[ V ]
Note: For communication with HHC(1) (Model: FXW), min. of 250 
required.
EDSX5-92h
Date
Aug. 10, 2011
FKG...5
Hazardous locations: (Under an application) SEE TABLE2
Zero/span adjustment:
Zero and span are adjustable from the
HHC(1). Zero and span are also adjustable
externally from the adjustment screw.
Damping:
Adjustable from HHC or local configurator
unit with LCD display.
The time constant is adjustable between
0.06 to 32 seconds.
Zero elevation/suppression:
Zero can be elevated or suppressed
within the specified range limit of each
sensor model.
Normal/reverse action:
Selectable from HHC(1).
Indication:
Analog indicator or 5-digit LCD meter, as
specified.
Burnout direction: Selectable from HHC(1)
If self-diagnostic detect transmitter failure,
the analog signal will be driven to either
“Output Hold”, “Output Overscale”or
“Output Underscale” modes.
“Output Hold”:
Output signal is hold as the value just
before failure happens.
“Output Overscale”:
Adjustable within the range 20.0mA to
22.5mA from HHC(1)
“Output Underscale”:
Adjustable within the range 3.2mA to
4.0mA from HHC
3.2
4
20
22.5 [mA]
Over scale
Burnout
Normal operating range
Under scale
Probable under range
Burnout
Probable over range
Output limits conforming to NAMUR NE43 by order.
Loop-check output:
Transmitter can be configured to provide
constant signal 3.2mA through 22.5mA
by HHC.
Temperature limit:
Ambient: −40 to +85°C
(−20 to +80°C for LCD indicator)
(−40 to +60°C for arrester option)
(−10 to +60°C for fluorinated oil fill
transmitter)
For explosionproof units (flameproof
or intrinsic safety), ambient temperature must be within the limits specified by each standard.
Process: −40 to +100°C for silicone fill
sensor
−20 to +80°C for fluorinated oil fill
sensor
Storage: −40 to +90°C
Humidity limit:
0 to 100% RH
Communication: With HHC(1) (Model FXW, consult Data
Sheet No. EDS8-47), following items can
be remotely displayed or configured.
Note: HHC’s version must be higher than
7.0 (or FXW
1– 4), for FCX AIII.
(Note)
2
(1) HHC: Hand Held Communicator
Local configurator with LCD display (option):
Local confi gurator with 3 push button
and LCD display can support following
items.
Items
By communication By local configurator
with FXW
(with 3 push button)
Display
Set
Display
Set
Tag No.
v
v
v
v
Model No.
v
v
v
v
Serial No. & Software Version
v
—
v
—
Engineering unit
v
v
v
v
Range limit
v
—
v
—
Measuring range
v
v
v
v
Damping
v
v
v
v
Output mode
v
—
v
—
Burnout direction
v
v
v
v
Calibration
v
v
v
v
Output adjust
—
v
—
v
Data
v
—
v
—
Self diagnoses
v
—
v
—
Printer (In case of FXW with
printer option)
v
—
—
—
External switch lock
v
v
v
v
Transmitter display
v
v
v
v
Linearize
v
v
—
—
Rerange
v
v
v
v
Saturate current
v
v
v
v
Write protect
v
v
v
v
History
– Calibration history
– Ambient temperature history
v
v
v
—
v
v
v
—
EMC Conformity: EN61326-1: 2006
Performance specifications
Reference conditions, silicone oil fill, 316SS isolating diaphragms, 4
to 20mA analog output in linear mode.
Accuracy rating: (including linearity, hysteresis, and repeatability)
Max span below 10000kPa model:
For spans greater than 1/10 of URL:
±0.065% of span or
±0.04% of span (21th digit: H)
For spans below 1/10 of URL:
0.1  URL
± 0.015+0.05
% of span
Span
Max span 50000kPa model:
For spans greater than 1/10 of URL: ±0.1% of span
For spans below 1/10 of URL:
0.1  URL
± 0.05+0.05
% of span
Span
Stability:
±0.1% of upper range limit (URL) for 10
years.
Temperature effect:
Effects per 28°C change between the
limits of −40°C and +85°C
URL
Zero shift: ±(0.075+0.0125 span )%
URL
Total effect: ±(0.095+0.0125
)%
span
Overrange effect: Zero shift; 0.2% of URL for any overrange to maximum limit
Supply voltage effect:
Less than 0.005% of calibrated span per
1V
Update rate:
60 msec
Step response: Time constant: 0.08s (at 23°C)
Dead time: approximately 0.12s
(without electrical damping)
(
)
(
)
Physical specifications
Electrical connections:
G1/2, 1/2-14 NPT, Pg13.5, or M20 × 1.5
conduit, as specified.
Process connections:
1/4-18 NPT or Rc1/4 on 54mm centers, as
specified.
Meet DIN 19213
Process-wetted parts material:
l
e
t
e
symbols)
a i r e t aM
d o c
Process
i g i d h tcover
7(
d oC n i
V
316 stainless
steel(*1)
316 stainless
steel(*1)
316 stainless
steel(*1)
W
J
H
M
T
Diaphragm
Wetted
sensor body
316L stainless 316 stainless
steel
steel
316 stainless
Hastelloy-C
steel
316L stainless 316 stainless
steel
steel
+Au coating
Hastelloy-C
316 stainless Hastelloy-C
lining
steel(*1)
Monel lining
Monel
316 stainless
steel(*1)
Tantalum
Tantalum
316 stainless
lining
steel(*1)
Vent/drain
316 stainless
steel
316 stainless
steel
316 stainless
steel
316 stainless
steel
316 stainless
steel
316 stainless
steel
Note: *(1) ASTM CF8M
Remark: Availability of above material design depends on
ranges. Refer to “Code symbols”.
Non-wetted parts material:
Electronics housing: Low copper die-cast
aluminum alloy finished with polyester
coating (standard), or 316 stainless
steel (SCS14 per JIS G5121), as specified.
Bolts and nuts: Cr-Mo alloy (standard),
304 or 316 stainless steel (630 stainless steel for 50MPa unit).
Fill fluid: Silicone oil (standard) or fluorinated oil
Mounting bracket: 304 or 316 stainless
steel
Environmental protection:
IEC IP67 and NEMA 6/6P
Mounting:
On 60.5mm (JIS 50A) pipe using mounting bracket, direct wall mounting, or direct process mounting.
Mass {weight}:
Transmitter approximately 2.9 to 3.4kg
without options.
Add; 0.5kg for mounting bracket
4.5kg for stainless steel housing
option
Optional features
Indicator:
A plug-in analog indicator (2.5% accuracy)
An optional 5-digit LCD meter with engineering unit is also available.
Local configurator with LCD display:
An optional 5 digits LCD meter with 3
push buttons can support items as using
communication with FXW.
Arrester:
A built-in arrester protects the electronics
from lightning surges.
Lightning surge immunity:
4kV (1.2 × 50µs)
Oxygen service: Special cleaning procedures are followed
throughout the process to maintain all
process wetted parts oil-free.
The fill fluid is fluorinated oil.
Chlorine service: The fill fluid is fluorinated oil.
Degreasing:
Process-wetted parts are cleaned, but the
fill fluid is standard silicone oil. Not for use
on oxygen or chlorine measurement.
NACE specification:
Metallic materials for all pressure boundary parts comply with NACE MR-01-75.
ASTM B7M or L7M bolts and 2HM nuts
(Class II) are available.
Vacuum service: Special silicone oil and filling procedure
are applied.
See Fig.1.
Optional tag plate:
An extra stainless steel tag with customer tag data is wired to the transmitter.
Coating of cell: Cell’s surface is finished with epoxy/polyurethane double coating. Specify if environment is extermely corrosive.
Silicone oil (Code:Y,G,N)
Silicone oil (Code:R)
[kPa abs]
{mbar abs}
101
{1010}
Operating pressure
Mounting position effect:
Zero shift, less than 0.1kPa {1m bar} for a
10° tilt in any plane.
No effect on span. This error can be corrected by adjusting Zero.
Dielectric strength:
500V AC, 50/60Hz 1 min., between circuit and earth.
Insulation resistance:
More than 100M at 500V DC.
Internal resistance for external field indicator:
12 or less
Operating
area
20
{200}
4
{40}
2.7
{27}
None-operating
area
−40 −15
60 85 120
Process temperature [°C ]
Fig. 1 Relation between process temperature and
operating pressure
3
FKG...5
CODE SYMBOLS
1 2 3 4 5 6 7 8
Digit
4
6, 7
<Connections>
Oval flange
Process
screw
connection
7/16-20UNF
Rc1/4
1/4-18NPT
7/16-20UNF
1/4-18NPT
M10 (or M12)(*1)
1/4-18NPT
M10 (or M12)(*1)
1/4-18NPT
7/16-20UNF
7/16-20UNF
Rc1/4
1/4-18NPT
7/16-20UNF
1/4-18NPT
M10 (or M12)(*1)
1/4-18NPT
M10 (or M12)(*1)
1/4-18NPT
7/16-20UNF
<Span and materials>
Span limit
Process cover
[kPa]{bar}(*2)
1.3…130
316 stainless steel
{0.013…1.3}
316 stainless steel
316 stainless steel
5…500
{0.05…5}
30…3000
{0.3…30}
100…10000
{1…100}
500…50000
{5…500}
9
316 stainless steel
316 stainless steel
316 stainless steel
316 stainless steel
316 stainless steel
316 stainless steel
316 stainless steel
316 stainless steel
316 stainless steel
316 stainless steel
316 stainless steel
316 stainless steel
316 stainless steel
316 stainless steel
316 stainless steel
316 stainless steel
316 stainless steel
316 stainless steel
316 stainless steel
316 stainless steel
316 stainless steel
316 stainless steel
SCS14
316 stainless steel
Conduit
connection
G1/2
1/2-14NPT
Pg13.5
M20×1.5
Pg13.5
G1/2
1/2-14NPT
Pg13.5
M20×1.5
Pg13.5
F KG
9 10 11 12 13
5
0
Case type
T type
T type
T type
T type
T type
L type
L type
L type
L type
L type
Note 1
Note 1
Note 1
Note 1
5
6
7
8
9
S
T
V
W
X
Note 2
Diaphragm
Wetted cell body
316L stainless steel
Hast. C
316L stainless steel
+Au coating
Hast. C
Monel
Tantalum
316L stainless steel
Hast. C
316L stainless steel
+Au coating
Hast. C
Monel
Tantalum
316L stainless steel
Hast. C
316L stainless steel
+Au coating
Hast. C
Monel
Tantalum
316L stainless steel
Hast. C
316L stainless steel
+Au coating
Hast. C
Monel
Tantalum
316L stainless steel
Hast. C
316L stainless steel
+Au coating
316 stainless steel
SUS316
316 stainless steel
1V
1W
1J
Hast. C lining
Monel lining
Tantalum lining
316 stainless steel
SUS316
316 stainless steel
1H
1M
1T
2V
2W
2J
Hast. C lining
Monel lining
Tantalum lining
316 stainless steel
SUS316
316 stainless steel
2H
2M
2T
3V
3W
3J
Hast. C lining
Monel lining
Tantalum lining
316 stainless steel
SUS316
316 stainless steel
3H
3M
3T
4V
4W
4J
Hast. C lining
Monel lining
Tantalum lining
316 stainless steel
SUS316
316 stainless steel
4H
4M
4T
5V
5W
5J
<Indicator and arrester>
Indicator
None
Analog, 0 to 100% linear scale
Analog, custom scale
None
Analog, 0 to 100% linear scale
Analog, custom scale
Digital, 0 to 100% linear scale
Digital, custom scale
Digital, 0 to 100% linear scale
Digital, custom scale
Digital, 0 to 100% linear scale
(Local configurator unit with LCD display)
Digital, custom scale
(Local configurator unit with LCD display)
Digital, 0 to 100% linear scale
(Local configurator unit with LCD display)
Digital, custom scale
(Local configurator unit with LCD display)
Note 1 : (*1)
Note 2 : (*2)
4
Note
Description
Arrester
None
None
None
Yes
Yes
Yes
None
None
Yes
Yes
A
B
D
E
F
H
L
P
Q
S
1
None
2
None
4
Yes
5
Yes
For 50MPa {500bar} units, M12 is provided rather than M10.
100: 1 turn down is possible, but should be used at the span greater than
1/40 of the maximum span for better performance.
14 15
21
Digit No.
of code
1 2 3 4 5 6 7 8
Digit
10
11
12
13
14
15
21
Description
<Approvals for hazardous locations>
None (for ordinary locations)
TIIS, Flameproof (Cable gland seal) (*6)
TIIS, Intrinsic safety
FM, Flameproof (or explosionproof) (*9)
FM, Intrinsic safety and nonincentive
FM Combined of flameproof and intrinsic safety (*9)
ATEX Flameproof (*8)
ATEX Intrinsic safety
ATEX Type n
ATEX Combined of flameproof and intrinsic safety (*8)
IECEx Scheme, Flameproof (*8)
IECEx Scheme, Intrinsic safety
CSA, Flameproof (or explosionproof) (*9)
CSA, Intrinsic safety and nonincentive
NEPSI, Flameproof (or exprosionproof)
NEPSI, Intrinsic safety
NEPSI, Combined of flameproof and intrinsic safety
<Vent/ drain and mounting bracket>
Vent/drain
Mounting bracket
Process connection
Standard
None
Standard
Standard
Yes, SUS304
Standard
Standard
Yes, SUS316
Standard
Side
None
Standard
Side
Yes, SUS304
Standard
Side
Yes, SUS316
Standard
<Options>
Extra SS tag plate
Stainless steel elec. housing
Coating of cell
None
None
None
Yes
None
None
(*3)
None
None
Yes
Yes
None
Yes
None
Yes
Yes
(*5)
Yes
Yes
Yes
<Special applications and fill fluid>
Treatment
Fill fluid
Standard
Silicone oil
Standard
Fluorinated oil
Degreasing
Silicone oil
Oxygen service
Fluorinated oil (7th digit code "V", "W", "J" only)
Chlorine service
Fluorinated oil (7th digit code "H", "T")
NACE specification
Silicone oil (Not available for 6th digit code "5", 7th
digit code "T", 15th digit code "A", "B")
Vacuum service
Silicone oil for vacuum use
<Sensor O-ring / Gasket>
Teflon (gasket)
Vent Drain plug type
<Bolt/nut> (*10)
Cr-Mo alloy hexagon socket head cap screw/carbon steel nut Standard
Standard
Cr-Mo alloy hexagon bolt/nut
Standard
NACE bolt/nut (ASTM A193 B7M/A194 2HM)
NACE bolt/nut (ASTM A320 L7M/A194 2HM)
(*11) Standard
Standard
304 stainless steel bolt/304 stainless steel nut
Standard
630 stainless steel bolt/304 stainless steel nut (*12)
Standard
316 stainless steel bolt/316 stainless steel nut (*11)
<Other options> (*4)
High accuracy type (*11)
Instruction manual attached
Opposite Vent/Drain Plug Position
Instruction manual attached
Instruction manual unattached
Opposite Vent/Drain Plug Position
Instruction manual unattached
Note3: (*3) Customer tag number can be engraved on standartd stainless steel
name plate. If extra tag plate is required, select "Yes".
Note4: (*4) If other option is not necessary, 21st digit code is blank.
In case of 21st digit code is blank, instruction manual attached.
Note5: (*5) Not available for 10th digit code "C".
Note6: (*6) Available for 4th digit code "S".
Note
F KG
Note 6
Note 9
Note 9
Note 8
Note 8
Note 8
Note 9
0
9 10 11 12 13
14 15
21
5
Digit No.
of code
A
C
G
D
H
V
X
K
P
M
R
T
E
J
F
S
U
A
C
K
D
F
L
Note 3
Note 5
Note 5
Y
B
M
N
P
Q
Y
W
G
A
D
N
R
B
Note 10
Note 11
Note 11
Note 11
Note 12
Note 11
Note4
Note 11
Note8:
Note9:
Note10:
Note11:
Note12:
A
B
C
D
E
F
U
H
C
L
P
(*8) Available for 4th digit code "6", "8", "T", "W".
(*9) Available for 4th digit code "6", "T".
(*10) In case of tropical use, select stainless bolts and nuts.
(*11) Not available for 6th digit code "5".
(*12) Available for 6th digit code "5".
ACCESSORIES
ORDERING INFORMATION
Oval flanges:
When ordering this instrument, specify.
1. CODE SYMBOLS
2. Measuring range
3. Output orientation (burnout direction) when abnormality
is occured in the transmitter.
Hold/Overscale/Overscale
Unless otherwise specified, output hold function is supplied.
4. Indication method (indicated value and unit) in case of the
actual scale (code D,H,P,S on 9th digit).
5. Tag No.(up to 14 alphanumerical characters), if required.
(Model FFP, refer to Data Sheet No.
EDS6-128)
Converts process connection to 1/2-14
NPT or to Rc1/2; in carbon steel or in 316
stainless steel.
Hand-held communicator:
(Model FXW, refer to Data Sheet No.
EDS8-47)
5
FKG...5
OUTLINE DIAGRAM (Unit:mm)
<AMP. case: L type>
VENT/DRAIN PLUG
(WHEN THE VENT/DRAIN PLUG
ATTACHED ON THE UPPER SIDE
OF THE DETECTOR) NOTE2)
MTG. PIPE JIS 50A (2B)
IN CASE OF 4TH DIGIT CODE "S,V,W,X"
VENT/DRAIN PLUG
57
φ81
120
103
φ81
103
70
38
U-BOLT M8
41
41
ZERO ADJ. SCREW
8
"A" PRESS. CONN.
10
IN CASE OF 4TH DIGIT CODE "T"
"B" CONDUIT CONN.
37
4 HOLES 9 DIA.
172
(21)
(175)
(11)
WITH ANALOG IND.
NOTE3)
126
43
41
WITH DIGITAL IND.
EARTH TERMINAL
DETAIL "A"
(PRESS. CONN.)
OVAL FLANGE SCREW
SEE TABLE1
2.5
φ18.5
SIDE VENT(OPTION)
41.3
198
φ15
F
8
H
E
L.P
10
D
SEE TABLE1
4th digit of the
code symbols
S
H.P
4-M8×12
SEE TABLE1
Conduit conn.
D
G 1/2
E
Press. conn.
F
18
Oval frange screw
27
H
2
Rc1/4
7/16-20UNF
SCREW DEPTH15
T
1/2-14NPT
16
4
1/4-18NPT
7/16-20UNF
SCREW DEPTH15
V
Pg13.5
10.5
4.5
1/4-18NPT
M10
SCREW DEPTH15
W
M20×1.5
16
4
1/4-18NPT
M10
SCREW DEPTH15
X
Pg13.5
10.5
4.5
1/4-18NPT
7/16-20UNF
SCREW DEPTH15
70
104
TABLE 1
OPTION PARTS FOR FLAMEPROOF OF TIIS (JAPAN)
10th digit code C (Cable gland type)
NOTE1)
G1/2
DETAIL C
φ33.5
φ13
<SS TAG PLATE>
19
106
17
CONNECTION DIAGRAM
"C" CONDUIT CONN.
G1/2
−/CK− CK+
CABLE GLAND
75
+
20
6
NOTE1) IN CASE OF 10TH CODE“C”
, φ11 CABLE IS SUITBLE.
NOTE2) THE PRESSURE CONNECTOR IS LOCATED ON THE DOWN SIDE
SURFACE OF THE DETECTOR, WHEN THE VENT/DRAIN PLUG IS
ATTACHED ON THE UPPER SIDE OF THE DETECTOR
(WHEN THE 21ST DIGIT OF THE CODE SYMBOLS : C,P).
NOTE3) WHEN THE 7TH DIGIT OF THE CODE SYMBOLS "H,M,T"
(201)NOTE3)
DETAIL "B"
(CONDUIT CONN.)
<AMP. case: T type>
VENT/DRAIN PLUG
(WHEN THE VENT/DRAIN PLUG
ATTACHED ON THE UPPER SIDE
OF THE DETECTOR) NOTE2)
WITH ANALOG IND.
WITH DIGITAL IND.
φ81
100
70
U-BOLT M8
ZERO ADJ. SCREW
(21)
(11)
110
41
EARTH TERMINAL
8
IN CASE OF 4TH DIGIT CODE "5,7,8,9"
"A" PRESS. CONN.
10
MTG. PIPE JIS 50A (2B)
IN CASE OF 4TH DIGIT CODE "6"
"B" CONDUIT CONN.
38
VENT/DRAIN PLUG
57
37
4 HOLES 9 DIA.
168
(171)
17
127
20
NOTE3)
DETAIL "A"
(PRESS. CONN.)
2.5
φ18.5
H
OVAL FLANGE SCREW
SEE TABLE1
φ15
E
10
SEE TABLE1
SEE TABLE1
4th digit of the
code symbols
5
Conduit conn.
Press. conn.
D
E
F
H
G 1/2
18
2
Rc1/4
H.P
L.P
D
226
F
41.3
8
SIDE VENT(OPTION)
(229) NOTE3)
DETAIL "B"
(CONDUIT CONN.)
4-M8×12
Oval frange screw
7/16-20UNF
SCREW DEPTH15
6
1/2-14NPT
16
4
1/4-18NPT
7/16-20UNF
SCREW DEPTH15
7
Pg13.5
10.5
4.5
1/4-18NPT
M10
SCREW DEPTH15
8
M20×1.5
16
4
1/4-18NPT
M10
SCREW DEPTH15
9
Pg13.5
10.5
4.5
1/4-18NPT
7/16-20UNF
SCREW DEPTH15
27
70
104
TABLE 1
CONNECTION DIAGRAM
−/CK− CK+
75
+
<SS TAG PLATE>
20
NOTE2) THE PRESSURE CONNECTOR IS LOCATED ON THE DOWN SIDE
SURFACE OF THE DETECTOR, WHEN THE VENT/DRAIN PLUG IS
ATTACHED ON THE UPPER SIDE OF THE DETECTOR
(WHEN THE 21ST DIGIT OF THE CODE SYMBOLS : C,P).
NOTE3) WHEN THE 7TH DIGIT OF THE CODE SYMBOLS "H,M,T"
7
FKG...5
TABLE 2
Authorities
ATEX
Authorities
Intrinsic safety
Ex II 1 G
Ex ia IIC T5 Tamb = –40°C to +50°C
Ex ia IIC T4 Tamb = –40°C to +70°C
Entity Parameters:
Ui=28V, Ii=94.3mA, Pi=0.66W,
Ci=26nF (Without Arrester), Li=0.6mH (Without analog indicator),
Ci=36nF (With Arrester), Li=0.7mH (With analog indicator)
Factory
Mutual
13th digit
Y,G,N,R
Y,G,N,R
Y,G,N,R
Y,G,N,R
W,A,D
Factory
Mutual
Class I
Div.1 Groups B, C, D
T6 Type 4X
Class II III
Div.1 Groups E, F, G
T6 Type 4X
Tamb max = +60°C
CSA
Class I
Div.1 Groups C, D
Class II
Div.1 Groups E, F, G
Class III
Div.1
Tamb
−40°C to +85°C
−20°C to +80°C
−20°C to +60°C
−40°C to +60°C
−10°C to +60°C
Entity Parameters:
Vmax=28V, Imax=94.3mA, Pi=0.66W,
Ci=35.98nF, Li=0.694mH
CSA
Ex II 2 GD
Ex d IIC T6 IP66/67 T85°C
Tamb = −40°C to +65°C
Ex d IIC T5 IP66/67 T100°C
Tamb = −40°C to +85°C
Class I II III
Div.1 Groups A, B, C, D, E, F, G
T4 Entity Type 4X
Model code
9th digit
A,B,D
L,P,1,2
Q,S,4,5
E,F,H
−
Class I
Div.1 Groups A, B, C, D
Class II
Div.1 Groups E, F, G
Class III
Div.1
Temp Code T5
Tamb max = +50°C
Temp Code T4
Tamb max = +70°C
Entity Parameters:
Vmax=28V, Imax=94.3mA, Ci=25nF (Without Arrester),
Ci=36nF (With Arrester),Li=0.6mH (Without analog meter),
Li=0.7mH (With analog meter)
TIIS
Ex ia IIC T4
Tamb max = +60°C
Entity Parameters:
Ui=28V, Ii=94.3mA, Pi=0.66W,
Ci=38.4nF, Li=0.694mH
IECEx
Scheme
Ex ia IIC T4
Tamb = –40°C to +70°C
Ex ia IIC T5
Tamb = –40°C to +50°C
Entity Parameters:
Ui=28V, Ii=94.3mA, Pi=0.66W,
Ci=26nF (Without Arrester), Li=0.6mH (Without analog indicator),
Ci=36nF (With Arrester), Li=0.7mH (With analog indicator)
NEPSI
Ex ia IIC T4
Ex d IIB+H2 T6 / Ex ia IIC T4
Model code
9th digit
A,B,D
L,P,1,2
Q,S,4,5
E,F,H
−
13th digit
Y,G,N,R
Y,G,N,R
Y,G,N,R
Y,G,N,R
W,A,D
Note) “Seal Not Required” enclosure is allowed.
TIIS
Ex do IIB+H2 T4
Tamb max = +60°C
Maximum process temp. = +120°C
IECEx
Scheme
Ex d IIC T5 IP66/67
Tamb = −40°C to +85°C
Ex d IIC T6 IP66/67
Tamb = −40°C to +65°C
NEPSI
Ex d IIB+H2 T6
Tamb = −40°C to +60°C
Type n
Nonincendive
Authorities
ATEX
Ex II 3 GD
EEx nL IIC T5 Tamb = −40°C to +50°C
EEx nL IIC T4 Tamb = −40°C to +70°C
Specific Parameters:
Model without arrester:
Ui=42.4V, Ii=113mA, Pi=1W,
Ci=25.18nF, Li=0.694mH
Model with arrester:
Ui=32V, Ii=113mA, Pi=1W,
Ci=35.98nF, Li=0.694mH
EEx nAL IIC T5 Tamb = −40°C to +50°C
EEx nAL IIC T4 Tamb = −40°C to +70°C
Specific Parameters:
Model without arrester:
Umax=42.4V, Imax=113mA, Pmax=1W
Model with arrester:
Umax=32V, Imax=113mA, Pmax=1W
Factory
Mutual
(pending)
Class I II III
Div.2 Groups A, B, C, D, F, G
T4 Entity Type 4X
Model code
9th digit
A,B,D
L,P,1,2
Q,S,4,5
E,F,H
−
Tamb
−40°C to +85°C
−20°C to +80°C
−20°C to +60°C
−40°C to +60°C
−10°C to +60°C
Flameproof
ATEX
CSA
Entity Parameters:
Ui=42.4V, Ii=113mA, Pi=1W,
Ci=35.98nF, Li=0.694mH
Caution on Safety
13th digit
Y,G,N,R
Y,G,N,R
Y,G,N,R
Y,G,N,R
W,A,D
Tamb
−40°C to +85°C
−20°C to +80°C
−20°C to +60°C
−40°C to +60°C
−10°C to +60°C
Class I
Div.2 Groups A, B, C, D
Class II
Div.2 Groups E, F, G
Class III
Div.2
Temp Code T5
Tamb max = +50°C
Temp Code T4
Tamb max = +70°C
Entity Parameters:
Vmax=28V, Ci=25.18nF (Without Arrester),
Ci=35.98nF (With Arrester), Li=0.694mH
*Before using this product, be sure to read its instruction manual in advance.
International Sales Div
Sales Group
Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome,
Shinagawa-ku, Tokyo 141-0032, Japan
http://www.fujielectric.com
Phone: 81-3-5435-7280, 7281 Fax: 81-3-5435-7425
http://www.fjielectric.com/products/instruments/
Information in this catalog is subject to change without notice.
Printed in Japan