PRESSURE TRANSMITTER FKG...5 DATA SHEET The FCX – AIII pressure transmitter accurately measures gauge pressure and transmits a proportional 4 to 20mA signal. The transmitter utilizes a unique micromachined capacitance silicon sensor with state-of-the-art microprocessor technology to provide exceptional performance and functionality. FEATURES SPECIFICATIONS Functional specifications Service: Output signal: Power supply: Liquid, gas, or vapour 4 to 20mA DC with digital signal superimposed on the 4 to 20mA signal. Transmitter operates on 10.5V to 45V DC at transmitter terminals. 10.5V to 32V DC for the units with optional arrester. [ L-Type ] [ T-Type ] Span, range and overrange limit: Range limit [kPa] {bar} Span limit [kPa] {bar} Type F KG 01 FKG 02 FKG 03 FKG 04 FKG 05 Min. Max. 1.3 {0.013} 5 {0.05} 30 {0.3} 100 {1} 500 {5} 130 {1.3} 500 {5} 3000 {30} 10000 {100} 50000 {500} Lower limit Upper limit −100 {−1} −100 {−1} −100 {−1} −100 {−1} −100 {−1} 130 {1.3} 500 {5} 3000 {30} 10000 {100} 50000 {500} Overrange limit [MPa] {bar} 1 {10} 1.5 {15} 9 {90} 15 {150} 75 {750} Remark: To minimize environmental influence, span should be greater than 1/40 of the max. span in most applications. – Lower range limit (vacuum limit) ; Silicone fill sensor: See Fig. 1 Fluorinated fill sensor: 66kPa abs (500mmHg abs) at below 60°C – Conversion factors to different units; 1 MPa=103 kPa=10bar=10.19716kgf/cm2= 145.0377psi 1kPa=10mbar=101.9716mmH2O =4.01463inH2O Load limitations: see figure below [Ω] 2000 Load resistance 1. High accuracy up to ±0.04% 0.065% accuracy as standard, 0.04% accuracy as option. Fuji’s micro-capacitance silicon sensor assures this accuracy for all elevated or suppressed calibration ranges without additional adjustment. 2. Minimum environmental influence The “Advance Floating Cell” design which protects the pressure sensor against changes in temperature, and overpressure substantially reduces total measurement error in actual field applications. 3. Fuji/HART® bilingual communications protocol FCX–AIII series transmitter offers bilingual communications to speak both Fuji proprietary protocol and HART®. Any HART® compatible devices can communicate with FCX–AIII. 4. Application flexibility Various options that render the FCX–AIII suitable for almost any process applications include: – Full range of hazardous area approvals – Built-in RFI filter and lightning arrester – 5-digit LCD meter with engineering unit – Stainless steel electronics housing 5. Burnout current flexibility (Under Scale: 3.2 to 4.0mA, Over Scale: 20.0 to 22.5mA) Burnout signal level is adjustable using Model FXW Hand Held Communicator (HHC) to comply with NAMUR NE43. 6. Dry calibration without reference pressure Thanks to the best combination of unique construction of mechanical parts (Sensor unit) and high performance electronics circuit (Electronics unit), reliability of dry calibration without reference pressure is at equal level as wet calibration. 1500 1474Ω R= E-10.5 (Imax+0.9)x10-3 1000 577Ω Operating area 500 24V 250 0 10 16.35 10.5V Power voltage (DC) 45V 50 E[ V ] Note: For communication with HHC(1) (Model: FXW), min. of 250 required. EDSX5-92h Date Aug. 10, 2011 FKG...5 Hazardous locations: (Under an application) SEE TABLE2 Zero/span adjustment: Zero and span are adjustable from the HHC(1). Zero and span are also adjustable externally from the adjustment screw. Damping: Adjustable from HHC or local configurator unit with LCD display. The time constant is adjustable between 0.06 to 32 seconds. Zero elevation/suppression: Zero can be elevated or suppressed within the specified range limit of each sensor model. Normal/reverse action: Selectable from HHC(1). Indication: Analog indicator or 5-digit LCD meter, as specified. Burnout direction: Selectable from HHC(1) If self-diagnostic detect transmitter failure, the analog signal will be driven to either “Output Hold”, “Output Overscale”or “Output Underscale” modes. “Output Hold”: Output signal is hold as the value just before failure happens. “Output Overscale”: Adjustable within the range 20.0mA to 22.5mA from HHC(1) “Output Underscale”: Adjustable within the range 3.2mA to 4.0mA from HHC 3.2 4 20 22.5 [mA] Over scale Burnout Normal operating range Under scale Probable under range Burnout Probable over range Output limits conforming to NAMUR NE43 by order. Loop-check output: Transmitter can be configured to provide constant signal 3.2mA through 22.5mA by HHC. Temperature limit: Ambient: −40 to +85°C (−20 to +80°C for LCD indicator) (−40 to +60°C for arrester option) (−10 to +60°C for fluorinated oil fill transmitter) For explosionproof units (flameproof or intrinsic safety), ambient temperature must be within the limits specified by each standard. Process: −40 to +100°C for silicone fill sensor −20 to +80°C for fluorinated oil fill sensor Storage: −40 to +90°C Humidity limit: 0 to 100% RH Communication: With HHC(1) (Model FXW, consult Data Sheet No. EDS8-47), following items can be remotely displayed or configured. Note: HHC’s version must be higher than 7.0 (or FXW 1– 4), for FCX AIII. (Note) 2 (1) HHC: Hand Held Communicator Local configurator with LCD display (option): Local confi gurator with 3 push button and LCD display can support following items. Items By communication By local configurator with FXW (with 3 push button) Display Set Display Set Tag No. v v v v Model No. v v v v Serial No. & Software Version v — v — Engineering unit v v v v Range limit v — v — Measuring range v v v v Damping v v v v Output mode v — v — Burnout direction v v v v Calibration v v v v Output adjust — v — v Data v — v — Self diagnoses v — v — Printer (In case of FXW with printer option) v — — — External switch lock v v v v Transmitter display v v v v Linearize v v — — Rerange v v v v Saturate current v v v v Write protect v v v v History – Calibration history – Ambient temperature history v v v — v v v — EMC Conformity: EN61326-1: 2006 Performance specifications Reference conditions, silicone oil fill, 316SS isolating diaphragms, 4 to 20mA analog output in linear mode. Accuracy rating: (including linearity, hysteresis, and repeatability) Max span below 10000kPa model: For spans greater than 1/10 of URL: ±0.065% of span or ±0.04% of span (21th digit: H) For spans below 1/10 of URL: 0.1 URL ± 0.015+0.05 % of span Span Max span 50000kPa model: For spans greater than 1/10 of URL: ±0.1% of span For spans below 1/10 of URL: 0.1 URL ± 0.05+0.05 % of span Span Stability: ±0.1% of upper range limit (URL) for 10 years. Temperature effect: Effects per 28°C change between the limits of −40°C and +85°C URL Zero shift: ±(0.075+0.0125 span )% URL Total effect: ±(0.095+0.0125 )% span Overrange effect: Zero shift; 0.2% of URL for any overrange to maximum limit Supply voltage effect: Less than 0.005% of calibrated span per 1V Update rate: 60 msec Step response: Time constant: 0.08s (at 23°C) Dead time: approximately 0.12s (without electrical damping) ( ) ( ) Physical specifications Electrical connections: G1/2, 1/2-14 NPT, Pg13.5, or M20 × 1.5 conduit, as specified. Process connections: 1/4-18 NPT or Rc1/4 on 54mm centers, as specified. Meet DIN 19213 Process-wetted parts material: l e t e symbols) a i r e t aM d o c Process i g i d h tcover 7( d oC n i V 316 stainless steel(*1) 316 stainless steel(*1) 316 stainless steel(*1) W J H M T Diaphragm Wetted sensor body 316L stainless 316 stainless steel steel 316 stainless Hastelloy-C steel 316L stainless 316 stainless steel steel +Au coating Hastelloy-C 316 stainless Hastelloy-C lining steel(*1) Monel lining Monel 316 stainless steel(*1) Tantalum Tantalum 316 stainless lining steel(*1) Vent/drain 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel Note: *(1) ASTM CF8M Remark: Availability of above material design depends on ranges. Refer to “Code symbols”. Non-wetted parts material: Electronics housing: Low copper die-cast aluminum alloy finished with polyester coating (standard), or 316 stainless steel (SCS14 per JIS G5121), as specified. Bolts and nuts: Cr-Mo alloy (standard), 304 or 316 stainless steel (630 stainless steel for 50MPa unit). Fill fluid: Silicone oil (standard) or fluorinated oil Mounting bracket: 304 or 316 stainless steel Environmental protection: IEC IP67 and NEMA 6/6P Mounting: On 60.5mm (JIS 50A) pipe using mounting bracket, direct wall mounting, or direct process mounting. Mass {weight}: Transmitter approximately 2.9 to 3.4kg without options. Add; 0.5kg for mounting bracket 4.5kg for stainless steel housing option Optional features Indicator: A plug-in analog indicator (2.5% accuracy) An optional 5-digit LCD meter with engineering unit is also available. Local configurator with LCD display: An optional 5 digits LCD meter with 3 push buttons can support items as using communication with FXW. Arrester: A built-in arrester protects the electronics from lightning surges. Lightning surge immunity: 4kV (1.2 × 50µs) Oxygen service: Special cleaning procedures are followed throughout the process to maintain all process wetted parts oil-free. The fill fluid is fluorinated oil. Chlorine service: The fill fluid is fluorinated oil. Degreasing: Process-wetted parts are cleaned, but the fill fluid is standard silicone oil. Not for use on oxygen or chlorine measurement. NACE specification: Metallic materials for all pressure boundary parts comply with NACE MR-01-75. ASTM B7M or L7M bolts and 2HM nuts (Class II) are available. Vacuum service: Special silicone oil and filling procedure are applied. See Fig.1. Optional tag plate: An extra stainless steel tag with customer tag data is wired to the transmitter. Coating of cell: Cell’s surface is finished with epoxy/polyurethane double coating. Specify if environment is extermely corrosive. Silicone oil (Code:Y,G,N) Silicone oil (Code:R) [kPa abs] {mbar abs} 101 {1010} Operating pressure Mounting position effect: Zero shift, less than 0.1kPa {1m bar} for a 10° tilt in any plane. No effect on span. This error can be corrected by adjusting Zero. Dielectric strength: 500V AC, 50/60Hz 1 min., between circuit and earth. Insulation resistance: More than 100M at 500V DC. Internal resistance for external field indicator: 12 or less Operating area 20 {200} 4 {40} 2.7 {27} None-operating area −40 −15 60 85 120 Process temperature [°C ] Fig. 1 Relation between process temperature and operating pressure 3 FKG...5 CODE SYMBOLS 1 2 3 4 5 6 7 8 Digit 4 6, 7 <Connections> Oval flange Process screw connection 7/16-20UNF Rc1/4 1/4-18NPT 7/16-20UNF 1/4-18NPT M10 (or M12)(*1) 1/4-18NPT M10 (or M12)(*1) 1/4-18NPT 7/16-20UNF 7/16-20UNF Rc1/4 1/4-18NPT 7/16-20UNF 1/4-18NPT M10 (or M12)(*1) 1/4-18NPT M10 (or M12)(*1) 1/4-18NPT 7/16-20UNF <Span and materials> Span limit Process cover [kPa]{bar}(*2) 1.3…130 316 stainless steel {0.013…1.3} 316 stainless steel 316 stainless steel 5…500 {0.05…5} 30…3000 {0.3…30} 100…10000 {1…100} 500…50000 {5…500} 9 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel SCS14 316 stainless steel Conduit connection G1/2 1/2-14NPT Pg13.5 M20×1.5 Pg13.5 G1/2 1/2-14NPT Pg13.5 M20×1.5 Pg13.5 F KG 9 10 11 12 13 5 0 Case type T type T type T type T type T type L type L type L type L type L type Note 1 Note 1 Note 1 Note 1 5 6 7 8 9 S T V W X Note 2 Diaphragm Wetted cell body 316L stainless steel Hast. C 316L stainless steel +Au coating Hast. C Monel Tantalum 316L stainless steel Hast. C 316L stainless steel +Au coating Hast. C Monel Tantalum 316L stainless steel Hast. C 316L stainless steel +Au coating Hast. C Monel Tantalum 316L stainless steel Hast. C 316L stainless steel +Au coating Hast. C Monel Tantalum 316L stainless steel Hast. C 316L stainless steel +Au coating 316 stainless steel SUS316 316 stainless steel 1V 1W 1J Hast. C lining Monel lining Tantalum lining 316 stainless steel SUS316 316 stainless steel 1H 1M 1T 2V 2W 2J Hast. C lining Monel lining Tantalum lining 316 stainless steel SUS316 316 stainless steel 2H 2M 2T 3V 3W 3J Hast. C lining Monel lining Tantalum lining 316 stainless steel SUS316 316 stainless steel 3H 3M 3T 4V 4W 4J Hast. C lining Monel lining Tantalum lining 316 stainless steel SUS316 316 stainless steel 4H 4M 4T 5V 5W 5J <Indicator and arrester> Indicator None Analog, 0 to 100% linear scale Analog, custom scale None Analog, 0 to 100% linear scale Analog, custom scale Digital, 0 to 100% linear scale Digital, custom scale Digital, 0 to 100% linear scale Digital, custom scale Digital, 0 to 100% linear scale (Local configurator unit with LCD display) Digital, custom scale (Local configurator unit with LCD display) Digital, 0 to 100% linear scale (Local configurator unit with LCD display) Digital, custom scale (Local configurator unit with LCD display) Note 1 : (*1) Note 2 : (*2) 4 Note Description Arrester None None None Yes Yes Yes None None Yes Yes A B D E F H L P Q S 1 None 2 None 4 Yes 5 Yes For 50MPa {500bar} units, M12 is provided rather than M10. 100: 1 turn down is possible, but should be used at the span greater than 1/40 of the maximum span for better performance. 14 15 21 Digit No. of code 1 2 3 4 5 6 7 8 Digit 10 11 12 13 14 15 21 Description <Approvals for hazardous locations> None (for ordinary locations) TIIS, Flameproof (Cable gland seal) (*6) TIIS, Intrinsic safety FM, Flameproof (or explosionproof) (*9) FM, Intrinsic safety and nonincentive FM Combined of flameproof and intrinsic safety (*9) ATEX Flameproof (*8) ATEX Intrinsic safety ATEX Type n ATEX Combined of flameproof and intrinsic safety (*8) IECEx Scheme, Flameproof (*8) IECEx Scheme, Intrinsic safety CSA, Flameproof (or explosionproof) (*9) CSA, Intrinsic safety and nonincentive NEPSI, Flameproof (or exprosionproof) NEPSI, Intrinsic safety NEPSI, Combined of flameproof and intrinsic safety <Vent/ drain and mounting bracket> Vent/drain Mounting bracket Process connection Standard None Standard Standard Yes, SUS304 Standard Standard Yes, SUS316 Standard Side None Standard Side Yes, SUS304 Standard Side Yes, SUS316 Standard <Options> Extra SS tag plate Stainless steel elec. housing Coating of cell None None None Yes None None (*3) None None Yes Yes None Yes None Yes Yes (*5) Yes Yes Yes <Special applications and fill fluid> Treatment Fill fluid Standard Silicone oil Standard Fluorinated oil Degreasing Silicone oil Oxygen service Fluorinated oil (7th digit code "V", "W", "J" only) Chlorine service Fluorinated oil (7th digit code "H", "T") NACE specification Silicone oil (Not available for 6th digit code "5", 7th digit code "T", 15th digit code "A", "B") Vacuum service Silicone oil for vacuum use <Sensor O-ring / Gasket> Teflon (gasket) Vent Drain plug type <Bolt/nut> (*10) Cr-Mo alloy hexagon socket head cap screw/carbon steel nut Standard Standard Cr-Mo alloy hexagon bolt/nut Standard NACE bolt/nut (ASTM A193 B7M/A194 2HM) NACE bolt/nut (ASTM A320 L7M/A194 2HM) (*11) Standard Standard 304 stainless steel bolt/304 stainless steel nut Standard 630 stainless steel bolt/304 stainless steel nut (*12) Standard 316 stainless steel bolt/316 stainless steel nut (*11) <Other options> (*4) High accuracy type (*11) Instruction manual attached Opposite Vent/Drain Plug Position Instruction manual attached Instruction manual unattached Opposite Vent/Drain Plug Position Instruction manual unattached Note3: (*3) Customer tag number can be engraved on standartd stainless steel name plate. If extra tag plate is required, select "Yes". Note4: (*4) If other option is not necessary, 21st digit code is blank. In case of 21st digit code is blank, instruction manual attached. Note5: (*5) Not available for 10th digit code "C". Note6: (*6) Available for 4th digit code "S". Note F KG Note 6 Note 9 Note 9 Note 8 Note 8 Note 8 Note 9 0 9 10 11 12 13 14 15 21 5 Digit No. of code A C G D H V X K P M R T E J F S U A C K D F L Note 3 Note 5 Note 5 Y B M N P Q Y W G A D N R B Note 10 Note 11 Note 11 Note 11 Note 12 Note 11 Note4 Note 11 Note8: Note9: Note10: Note11: Note12: A B C D E F U H C L P (*8) Available for 4th digit code "6", "8", "T", "W". (*9) Available for 4th digit code "6", "T". (*10) In case of tropical use, select stainless bolts and nuts. (*11) Not available for 6th digit code "5". (*12) Available for 6th digit code "5". ACCESSORIES ORDERING INFORMATION Oval flanges: When ordering this instrument, specify. 1. CODE SYMBOLS 2. Measuring range 3. Output orientation (burnout direction) when abnormality is occured in the transmitter. Hold/Overscale/Overscale Unless otherwise specified, output hold function is supplied. 4. Indication method (indicated value and unit) in case of the actual scale (code D,H,P,S on 9th digit). 5. Tag No.(up to 14 alphanumerical characters), if required. (Model FFP, refer to Data Sheet No. EDS6-128) Converts process connection to 1/2-14 NPT or to Rc1/2; in carbon steel or in 316 stainless steel. Hand-held communicator: (Model FXW, refer to Data Sheet No. EDS8-47) 5 FKG...5 OUTLINE DIAGRAM (Unit:mm) <AMP. case: L type> VENT/DRAIN PLUG (WHEN THE VENT/DRAIN PLUG ATTACHED ON THE UPPER SIDE OF THE DETECTOR) NOTE2) MTG. PIPE JIS 50A (2B) IN CASE OF 4TH DIGIT CODE "S,V,W,X" VENT/DRAIN PLUG 57 φ81 120 103 φ81 103 70 38 U-BOLT M8 41 41 ZERO ADJ. SCREW 8 "A" PRESS. CONN. 10 IN CASE OF 4TH DIGIT CODE "T" "B" CONDUIT CONN. 37 4 HOLES 9 DIA. 172 (21) (175) (11) WITH ANALOG IND. NOTE3) 126 43 41 WITH DIGITAL IND. EARTH TERMINAL DETAIL "A" (PRESS. CONN.) OVAL FLANGE SCREW SEE TABLE1 2.5 φ18.5 SIDE VENT(OPTION) 41.3 198 φ15 F 8 H E L.P 10 D SEE TABLE1 4th digit of the code symbols S H.P 4-M8×12 SEE TABLE1 Conduit conn. D G 1/2 E Press. conn. F 18 Oval frange screw 27 H 2 Rc1/4 7/16-20UNF SCREW DEPTH15 T 1/2-14NPT 16 4 1/4-18NPT 7/16-20UNF SCREW DEPTH15 V Pg13.5 10.5 4.5 1/4-18NPT M10 SCREW DEPTH15 W M20×1.5 16 4 1/4-18NPT M10 SCREW DEPTH15 X Pg13.5 10.5 4.5 1/4-18NPT 7/16-20UNF SCREW DEPTH15 70 104 TABLE 1 OPTION PARTS FOR FLAMEPROOF OF TIIS (JAPAN) 10th digit code C (Cable gland type) NOTE1) G1/2 DETAIL C φ33.5 φ13 <SS TAG PLATE> 19 106 17 CONNECTION DIAGRAM "C" CONDUIT CONN. G1/2 −/CK− CK+ CABLE GLAND 75 + 20 6 NOTE1) IN CASE OF 10TH CODE“C” , φ11 CABLE IS SUITBLE. NOTE2) THE PRESSURE CONNECTOR IS LOCATED ON THE DOWN SIDE SURFACE OF THE DETECTOR, WHEN THE VENT/DRAIN PLUG IS ATTACHED ON THE UPPER SIDE OF THE DETECTOR (WHEN THE 21ST DIGIT OF THE CODE SYMBOLS : C,P). NOTE3) WHEN THE 7TH DIGIT OF THE CODE SYMBOLS "H,M,T" (201)NOTE3) DETAIL "B" (CONDUIT CONN.) <AMP. case: T type> VENT/DRAIN PLUG (WHEN THE VENT/DRAIN PLUG ATTACHED ON THE UPPER SIDE OF THE DETECTOR) NOTE2) WITH ANALOG IND. WITH DIGITAL IND. φ81 100 70 U-BOLT M8 ZERO ADJ. SCREW (21) (11) 110 41 EARTH TERMINAL 8 IN CASE OF 4TH DIGIT CODE "5,7,8,9" "A" PRESS. CONN. 10 MTG. PIPE JIS 50A (2B) IN CASE OF 4TH DIGIT CODE "6" "B" CONDUIT CONN. 38 VENT/DRAIN PLUG 57 37 4 HOLES 9 DIA. 168 (171) 17 127 20 NOTE3) DETAIL "A" (PRESS. CONN.) 2.5 φ18.5 H OVAL FLANGE SCREW SEE TABLE1 φ15 E 10 SEE TABLE1 SEE TABLE1 4th digit of the code symbols 5 Conduit conn. Press. conn. D E F H G 1/2 18 2 Rc1/4 H.P L.P D 226 F 41.3 8 SIDE VENT(OPTION) (229) NOTE3) DETAIL "B" (CONDUIT CONN.) 4-M8×12 Oval frange screw 7/16-20UNF SCREW DEPTH15 6 1/2-14NPT 16 4 1/4-18NPT 7/16-20UNF SCREW DEPTH15 7 Pg13.5 10.5 4.5 1/4-18NPT M10 SCREW DEPTH15 8 M20×1.5 16 4 1/4-18NPT M10 SCREW DEPTH15 9 Pg13.5 10.5 4.5 1/4-18NPT 7/16-20UNF SCREW DEPTH15 27 70 104 TABLE 1 CONNECTION DIAGRAM −/CK− CK+ 75 + <SS TAG PLATE> 20 NOTE2) THE PRESSURE CONNECTOR IS LOCATED ON THE DOWN SIDE SURFACE OF THE DETECTOR, WHEN THE VENT/DRAIN PLUG IS ATTACHED ON THE UPPER SIDE OF THE DETECTOR (WHEN THE 21ST DIGIT OF THE CODE SYMBOLS : C,P). NOTE3) WHEN THE 7TH DIGIT OF THE CODE SYMBOLS "H,M,T" 7 FKG...5 TABLE 2 Authorities ATEX Authorities Intrinsic safety Ex II 1 G Ex ia IIC T5 Tamb = –40°C to +50°C Ex ia IIC T4 Tamb = –40°C to +70°C Entity Parameters: Ui=28V, Ii=94.3mA, Pi=0.66W, Ci=26nF (Without Arrester), Li=0.6mH (Without analog indicator), Ci=36nF (With Arrester), Li=0.7mH (With analog indicator) Factory Mutual 13th digit Y,G,N,R Y,G,N,R Y,G,N,R Y,G,N,R W,A,D Factory Mutual Class I Div.1 Groups B, C, D T6 Type 4X Class II III Div.1 Groups E, F, G T6 Type 4X Tamb max = +60°C CSA Class I Div.1 Groups C, D Class II Div.1 Groups E, F, G Class III Div.1 Tamb −40°C to +85°C −20°C to +80°C −20°C to +60°C −40°C to +60°C −10°C to +60°C Entity Parameters: Vmax=28V, Imax=94.3mA, Pi=0.66W, Ci=35.98nF, Li=0.694mH CSA Ex II 2 GD Ex d IIC T6 IP66/67 T85°C Tamb = −40°C to +65°C Ex d IIC T5 IP66/67 T100°C Tamb = −40°C to +85°C Class I II III Div.1 Groups A, B, C, D, E, F, G T4 Entity Type 4X Model code 9th digit A,B,D L,P,1,2 Q,S,4,5 E,F,H − Class I Div.1 Groups A, B, C, D Class II Div.1 Groups E, F, G Class III Div.1 Temp Code T5 Tamb max = +50°C Temp Code T4 Tamb max = +70°C Entity Parameters: Vmax=28V, Imax=94.3mA, Ci=25nF (Without Arrester), Ci=36nF (With Arrester),Li=0.6mH (Without analog meter), Li=0.7mH (With analog meter) TIIS Ex ia IIC T4 Tamb max = +60°C Entity Parameters: Ui=28V, Ii=94.3mA, Pi=0.66W, Ci=38.4nF, Li=0.694mH IECEx Scheme Ex ia IIC T4 Tamb = –40°C to +70°C Ex ia IIC T5 Tamb = –40°C to +50°C Entity Parameters: Ui=28V, Ii=94.3mA, Pi=0.66W, Ci=26nF (Without Arrester), Li=0.6mH (Without analog indicator), Ci=36nF (With Arrester), Li=0.7mH (With analog indicator) NEPSI Ex ia IIC T4 Ex d IIB+H2 T6 / Ex ia IIC T4 Model code 9th digit A,B,D L,P,1,2 Q,S,4,5 E,F,H − 13th digit Y,G,N,R Y,G,N,R Y,G,N,R Y,G,N,R W,A,D Note) “Seal Not Required” enclosure is allowed. TIIS Ex do IIB+H2 T4 Tamb max = +60°C Maximum process temp. = +120°C IECEx Scheme Ex d IIC T5 IP66/67 Tamb = −40°C to +85°C Ex d IIC T6 IP66/67 Tamb = −40°C to +65°C NEPSI Ex d IIB+H2 T6 Tamb = −40°C to +60°C Type n Nonincendive Authorities ATEX Ex II 3 GD EEx nL IIC T5 Tamb = −40°C to +50°C EEx nL IIC T4 Tamb = −40°C to +70°C Specific Parameters: Model without arrester: Ui=42.4V, Ii=113mA, Pi=1W, Ci=25.18nF, Li=0.694mH Model with arrester: Ui=32V, Ii=113mA, Pi=1W, Ci=35.98nF, Li=0.694mH EEx nAL IIC T5 Tamb = −40°C to +50°C EEx nAL IIC T4 Tamb = −40°C to +70°C Specific Parameters: Model without arrester: Umax=42.4V, Imax=113mA, Pmax=1W Model with arrester: Umax=32V, Imax=113mA, Pmax=1W Factory Mutual (pending) Class I II III Div.2 Groups A, B, C, D, F, G T4 Entity Type 4X Model code 9th digit A,B,D L,P,1,2 Q,S,4,5 E,F,H − Tamb −40°C to +85°C −20°C to +80°C −20°C to +60°C −40°C to +60°C −10°C to +60°C Flameproof ATEX CSA Entity Parameters: Ui=42.4V, Ii=113mA, Pi=1W, Ci=35.98nF, Li=0.694mH Caution on Safety 13th digit Y,G,N,R Y,G,N,R Y,G,N,R Y,G,N,R W,A,D Tamb −40°C to +85°C −20°C to +80°C −20°C to +60°C −40°C to +60°C −10°C to +60°C Class I Div.2 Groups A, B, C, D Class II Div.2 Groups E, F, G Class III Div.2 Temp Code T5 Tamb max = +50°C Temp Code T4 Tamb max = +70°C Entity Parameters: Vmax=28V, Ci=25.18nF (Without Arrester), Ci=35.98nF (With Arrester), Li=0.694mH *Before using this product, be sure to read its instruction manual in advance. International Sales Div Sales Group Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome, Shinagawa-ku, Tokyo 141-0032, Japan http://www.fujielectric.com Phone: 81-3-5435-7280, 7281 Fax: 81-3-5435-7425 http://www.fjielectric.com/products/instruments/ Information in this catalog is subject to change without notice. Printed in Japan