LEM HAL600-S

Current Transducer HAL 50..600-S
IPN = 50 A
For the electronic measurement of DC, AC and pulsed currents,
with a galvanic isolation between the primary (high power) circuit
and the secondary (electronic) circuit.
Electrical data
Primary nominal
r.m.s. current
IPN (A)
Primary current
measuring range
IP (A)
50
100
200
300
400
500
600
ÎP
VOUT
RL
VC
IC
Vb
Vd
Ris
± 150
± 300
± 600
± 900
± 1000
± 1000
± 1000
Type
Features
HAL
HAL
HAL
HAL
HAL
HAL
HAL
50-S
100-S
200-S
300-S
400-S
500-S
600-S
Overload capacity (Ampere Turns)
Analogue output voltage @ ± IPN
Load resistance
TA = 0 .. + 70°C
TA = - 25 .. + 85°C
Supply voltage (± 5 %)
Current consumption (max)
Rms rated voltage1)
Rms voltage for AC isolation test, 50 Hz, 1 mn
Isolation resistance @ 500 VDC
· Open loop transducer using Hall
Effect
· Panel mounting - Horizontal or
Vertical
· Insulated plastic case to UL 94-V0.
30000
±4
>1
>3
± 15
25
500
3
> 500
A
V
kW
kW
V
mA
V
kV
MW
Accuracy - Dynamic performance data
Accuracy 2) @ IPN, TA = 25°C, @ ± 15 V
Linearity 2)
X
e
L
VOE
VOM
VOT
TCeG
tr
di/dt
f
Electrical offset voltage @ IP = 0, TA = 25°C
Residual offset voltage @ IP = 0
after an overload of 3 x IPN
Thermal drift of offset voltage TA = - 25 .. + 85°C
Thermal drift of gain TA = - 25 .. + 85°C
Response time @ 90 % of IP
di/dt accurately followed
Frequency bandwidth (- 3 dB) 3)
±1
± 0.5
Max
± 10
± 10
±2
± 0.05
<3
> 50
DC .. 50
%
%
mV
mV
mV/°K
%/°K
µs
A/µs
kHz
Advantages
· Very good linearity
· Very good accuracy
· Low temperature drift
· Wide frequency bandwidth
· Very low insertion losses
· High immunity to external
interference
· Current overload capability
· Low power consumption
· Wide dynamic range, 50 to 600 A in
one package.
Applications
· AC variable speed drives and servo
motor drives
· Static converters for DC motor drives
· Battery supplied applications
· Uninterruptable Power Supplies
(UPS)
· Switched Mode Power Supplies
General data
TA
TS
m
Ambient operating temperature
Ambient storage temperature
Mass
Standards Safety
EMC
Deviation in output when tested to EN 61000-4-6
Deviation in output when tested to EN 61000-4-4
Notes :
1)
(SMPS)
- 25 .. + 85
°C
- 25 .. + 85
°C
75
g
EN50178 (1994)
EN50082-2 (1992)
EN50081-1 (1992)
< 10
% of IPN
< 10
% of IPN
Overvoltage Category III, Pollution Degree 2
Excludes the electrical offset
3)
Refer to derating curves in the technical file to avoid excessive core
heating at high frequency
· Power supplies for welding
applications.
001107/1
2)
LEM Components
www.lem.com
Dimensions HAL 50..600-S (in mm)
Bottom view
Left view
Secondary terminals
Terminal
Terminal
Terminal
Terminal
1
2
3
4
: supply voltage + 15 V
: supply voltage - 15 V
: output
: 0V
Front view
Mechanical characteristics
· General tolerance
· Primary through-hole
· Connection of secondary
Remarks
± 0.5 mm
20 mm x 15 mm
Molex 5045-04-A
· VOUT is positive when IP flows in the direction of the arrow.
· Temperature of the primary conductor should not exceed
90°C.
· This is a standard model. For different versions (supply
voltages, secondary connections, unidirectional measurements, operating temperatures, etc.) please contact us.
LEM have a policy of continual product improvement and the company reserves the right to revise the above specification without prior notice.