LEM HNC-050P_06

Current Transducer HNC-050P 50A-50mA
IPN = 50 A
For the electronic measurement of currents: DC, AC, pulsed, mixed,
with a galvanic isolation between the primary circuit (high power) and
the secondary circuit (electronic circuit).
45361
Electrical data
IPN
IPM
VC
IC
Vd
R IS
IOUT
RL
Primary nominal current rms
Primary current, measuring range
Supply voltage (± 5 %)
Current consumption
Rms voltage for AC isolation test, 50Hz, 1min
Isolation resistance @ 500 VDC
Output current @ ± IPN, R L = 80 Ω, TA = 25°C
Load resistance
50
± 75
± 15
A
A
V
15mA+(IPN/1000)mA
2.5
> 500
50
80
kV
MΩ
mA
Ω
ε
Accuracy @ IPN, TA = 25°C (excluding offset)
Linearity error 1) (0 .. ± IPN)
Electrical offset current @ TA = 25°C, IP = 0
Hysteresis offset current @ IP = 0;
after an excursion of 1 x IPN
Temperature coefficient of IOE @ TA = - 5 .. + 70 °C
Temperature coefficient of IOUT (% of reading)
@ TA = -5..+70°C
Response time to 90% of IPN step
L
IOE
IOH
TCIOE
TCIOUT
tr
• Hall effect measuring principle
• Galvanic isolation between primary
and secondary circuit
• Low power consumption
• Insulated plastic case recognized
according to UL 94-V0
Advantages
Accuracy-Dynamic performance data
X
Features
<±1
< ± 0.5
< ± 0.2
%
% of IPN
mA
• Easy installation.
• Small size and space saving
• Only one design for wide current
ratings range
< ± 0.15
mA
< ± 0.005 mA/K
< ± 0.04
<1
%/K
µs
General data
• High immunity to external
interference
Applications
• DC motor drives
• Switched Mode Power Supplies
(SMPS)
TA
TS
m
Ambient operating temperature
Ambient storage temperature
Mass
- 10 .. + 80
- 15 .. + 85
20
°C
°C
g
• AC variable speed drives
• Uninterruptible Power Supplies
(UPS)
• Battery supplied applications
• Power supplies for welding
applications
Application domain
• Industrial
Note :
1)
Linearity data exclude the electrical offset.
Page 1/2
061025/1
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
www.lem.com
Dimensions HNC-050P 50A-50mA (in mm. 1 mm = 0.0394 inch)
Current direction
Mechanical characteristics
• General tolerance
Safety
± 1 mm
This transducer must be used in electric/electronic equipment
with respect to applicable standards and safety requirements
in accordance with the following manufacturer's operating
instructions.
Caution, risk of electrical shock
When operating the transducer, certain parts of the module can
carry hazardous voltage (eg. primary busbar, power supply).
Ignoring this warning can lead to injury and/or cause serious
damage.
This transducer is a built-in device, whose conducting parts
must be inaccessible after installation.
A protective housing or additional shield could be used.
Main supply must be able to be disconnected.
Page 2/2
061025/1
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
www.lem.com