COOPER LPJ

Bussmann®
LOW-PEAK®
LPJ_SPI
Dual-Element, Time-Delay Fuses
Class J – 600 Volt
70 to 600A
Dimensional Data
4.63"
(– 0.03)
3.63"
2.63"
.75"
1.13" (– 0.03)
1" .28"
.43"
70A to 100A
.13"
5.75"
(– 0.03)
4.38"
3.0"
110A to
200A
.43"
Catalog Symbol: LPJ-_SPI
Dual-Element, Time-Delay – 10 seconds (minimum) at 500%
rated current
Current-Limiting
Ampere Rating: 70 to 600A
Voltage Rating:
ac: 600V (or less)
dc: 300V (or less)
Interrupting Rating:
ac: 300,000A RMS Sym.
dc: 100,000A
Agency Information:
UL Listed – Special Purpose†, Guide JFHR, File E56412
CSA Certified, Class J per CSA C22.2 No. 248.8,
Class 1422-02, File 53787
1.13"
.28"
1.63" (– 0.03)
1.38"
.19"
225A to 400A
450A to 600A
†Meets all performance requirements of UL Standard 248-8 for Class J fuses.
Catalog Symbol and Ampere Ratings
LPJ-70SPI
LPJ-125SPI
LPJ-250SPI
LPJ-500SPI
LPJ-80SPI
LPJ-150SPI
LPJ-300SPI
LPJ-600SPI
LPJ-90SPI
LPJ-175SPI
LPJ-350SPI
—
LPJ-100SPI
LPJ-200SPI
LPJ-400SPI
—
LPJ-110SPI
LPJ-225SPI
LPJ-450SPI
—
Carton Quantity and Weight
Weight*
Ampere
Ratings
Carton
Qty.
Lbs.
Kg.
70–100
5
1.69
0.767
110–200
5
4.21
1.910
225–400
1
1.67
0.758
450–600
1
2.80
1.270
*Weight per carton.
Recommended fuseblocks for
Class J 600V fuses
See Data Sheet: 1114
For non-indicating version, the LPJ_SP
is available. See Data Sheet: 1007.
8-26-04
SB04295
General Information:
• Permanent replacement fuse indication.
• True dual-element fuses with a minimum 10 second timedelay at 500% overload.
• Long time-delay minimizes needless fuse openings due to
temporary overloads and transient surges.
• Can often be sized for back-up protection against motor
burnout from overload or single-phasing if other overload
protective devices fail.
• High interrupting rating to safely interrupt overcurrents up
to 300,000A.
• High degree of current-limitation due to the fast speed-ofresponse to short-circuits.
• Faster response to damaging short-circuit currents than
mechanical overcurrent protective devices.
• Reduces let-through thermal and magnetic forces in order
to protect low withstand rated components.
• Proper sizing provides “no damage” Type “2” coordinated
protection for NEMA and IEC motor control in accordance
with IEC Standard 947-4-1.
• Dual-element fuses have lower resistance than ordinary
fuses, hence they run cooler.
• Lower watts loss reduces power consumption.
• Unique dimensions assure that another class of fuse with a
lesser voltage rating, interrupting rating or current-Iimiting
ability cannot be substituted.
• Space-saving package for equipment down sizing.
CE logo denotes compliance with European Union Low Voltage Directive
(50-1000Vac, 75-1500Vdc). Refer to Data Sheet: 8002 or contact
Bussmann Application Engineering at 636-527-1270 for more information.
Form No. LPJ 70-600
Page 1 of 3
Data Sheet: 1063
Bussmann®
LOW-PEAK®
LPJ_SPI
Dual-Element, Time-Delay Fuses
Class J – 600 Volt
70-600A
600A
400A
200A
250A
125A
80A
100A
Time-Current Characteristic Curves–Average Melt
AMPERE
RATING
300
200
100
TIME IN SECONDS
10
1
.1
10,000
100
1,000
.01
CURRENT IN AMPERES
8-26-04
SB04295
Form No. LPJ 70-600
Page 2 of 3
Data Sheet: 1063
Bussmann®
LOW-PEAK®
Dual-Element, Time-Delay Fuses
Class J – 600 Volt
LPJ_SPI
70-600A
Current-Limitation Curves
The only controlled copy of this Data Sheet is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is
intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
8-26-04
SB04295
Form No. LPJ 70-600
Page 3 of 3
Data Sheet: 1063