AC-DC 30 Watts xppower.com PDM30 Series • CEC2008 & EISA2007 Compliant ≥9 V • Worldwide Medical Approvals • 4000 VAC Isolation • Class II Construction • Single Outputs from 5 V to 24 V • High Efficiency • Operation to +60 °C Specification Input Input Voltage Input Frequency Input Current Inrush Current Input Protection General • • • • • 90-264 VAC 47-63 Hz 0.6 A rms max 50 A max at 264 VAC Fitted with a T2 A/250 VAC fuse in live line Output Efficiency Isolation Switching Frequency Power Density MTBF • • • • • 82% typical 4000 VAC Input to Output 70 kHz typical 3 W/Inch3 500 kHrs to MIL-STD-217F Environmental Output Voltage Initial Set Accuracy Minimum Load Start Up Delay Start Up Rise Time Hold Up Time Line Regulation Load Regulation Transient Response • • • • • • • • • Ripple & Noise Overvoltage Protection Overload Protection Short Circuit Protection Temperature Coefficient • • • • • See table ±2% set at 60% load No mimimum load required 3 s max 2 ms 16 ms minimum at 115 VAC ±1% See tables 5% max deviation recovering to within 1% within 500 µs for 50% load change 1% max, 20 MHz BW see note 2 See tables 120-150% Trip & restart (hiccup mode), auto-recovery ±0.05%/°C Operating Temperature • 0 °C to +60 °C, derate from 100% load at +40 °C to 60% load at +60 °C for 5, 9 & 12 V models. Derate from 100% load at +50 °C to 80% load at +60 °C for 15, 18 & 24 V models Cooling • Convection-cooled Operating Humidity • 15-95% non-condensing Storage Temperature • -20 °C to +85 °C Operating Altitude • 3000 m Vibration • 5-500 Hz at 3 g for 10 mins on each axis Shock • 30 g with 18 ms half sine wave, 3 times on each axis EMC & Safety Emissions Harmonic Currents Voltage Flicker ESD Immunity Radiated Immunity EFT/Burst Surge Conducted Immunity Dips & Interruptions Safety Approvals • • • • • • • • • EN55011 Level B conducted & radiated EN61000-3-2 EN61000-3-3 EN61000-4-2 Level 3, Perf Criteria A EN61000-4-3 Level 2, Perf Criteria A EN61000-4-4, Level 3, Perf Criteria A EN61000-4-5 Level 3, Perf Criteria A EN61000-4-6 Level 3, Perf Criteria A EN61000-4-11, 70% UT for 500 ms, 40% UT for 100 ms, <5% UT for 5000 ms Perf criteria A, B, B • UL60601-1, EN60601-1, IEC60601-1, CE Mark Output Voltage 5V 9V 12 V 15 V 18 V 24 V Output Current 4.00 A 3.00 A 2.50 A 2.00 A 1.65 A 1.25 A OVP Range 6.45-7.14 10.5-11.6 14.3-15.8 17.1-18.9 20.9-23.1 25.7-28.4 Regulation Efficiency V V V V V V Line(3) ±1% ±1% ±1% ±1% ±1% ±1% 74% 81% 82% 83% 83% 83% Model Number PDM30US05 PDM30US09 PDM30US12 PDM30US15 PDM30US18 PDM30US24 Load(4) ±6% ±4% ±3% ±3% ±2% ±2% Notes 1. 2. 3. 4. Initial set accuracy is set at 60% full load. Add a 0.1 µF ceramic capacitor and a 10 µF electrolytic capacitor to output for ripple and noise measuring at 20 MHz bandwidth. Line regulation is measured from 100 VAC to 240 VAC with full load. Load regulation is measured from 20% to 100% full load (60% ±40% full load). Mechanical Details 48.00 ±0.80 (1220.0 ±20.0) 2.28 (58.00) 5.2 (132.00) LED 0.47 (12.00) 1.2 (30.5) IEC320-C8 Output connector is right angle jack 0.22 x 0.10 x 0.47 (5.5 x 2.5 x 12.0), center postive. Weight: 210 g (0.46 lbs). All dimensions in inches (mm). Derating Curves 15 V, 18 V & 24 V Models 100 100 80 80 Output Power (%) Output Power (%) 5 V, 9 V & 12 V Models 60 40 20 0 10 20 30 40 50 Ambient Temperature (°C) 60 60 40 20 0 10 20 30 40 50 60 Ambient Temperature (°C) 17-Nov-08 AC-DC PDM30 Models and Ratings