Velociti® Series ADPF and ADPRF Analog Addressable Low-Flow Duct Sensor Description The Gamewell-FCI Velociti® Series, low-flow photoelectronic air duct smoke sensors are capable of sensing smoke in air velocities from 100 to 4,000 feet per minute (0.5 to 20.32 m/sec.). ADPF sensors feature low-flow technology that enables duct smoke detection throughout a broad range of airflow environments. Many difficult to solve HVAC applications occur in low airflow duct applications where reliable smoke detection is critical. ADPF low-flow technology can detect smoke at air speed velocities of 100 feet per minute or greater, while continuing the same reliable performance to 4,000 feet per minute. The ADPF sensor samples air currents passing through a duct and gives dependable performance for shutdown of fans, blowers, and air conditioning systems, preventing the spread of toxic smoke and fire gases through the protected area. The Velociti® Series use a communication protocol that substantially increases the speed of communication between the sensors and certain Gamewell-FCI analog addressable fire alarm controls. These devices operate in a grouped fashion. If one of the devices in the group has a status change, the panel’s microprocessor stops the group poll and concentrates on the single device. The net effect is a response speed up to five times greater than earlier designs. These intelligent sensors communicate and are continuously monitored through the signaling line circuit. Sensor sensitivity changes caused by dirt, temperature, or humidity are reported to the panel, allowing compensation algorithms to maintain the sensor’s set sensitivity. An advance indication at the panel specifies the sensor address, allowing for selected maintenance to be performed as needed. ADPF ADPRF Features • Air velocity rating from 100 to 4,000 feet per minute (0.5 to 20.32 m/sec.) • Patented telescopic sampling tube • Easily accessible code switches • Outside mounting tabs • Easy and quick mounting to round or rectangular ducts from 1'-12' (0.3-3.7 meters) wide • Easy to clean • UL recognized field-replaceable power and sensor boards • Transparent cover for convenient visual inspection. Bi-color LEDs flash green whenever the sensor is addressed, and light steady red on alarm *Note: Only the red LED is operative in panels that do not operate in Velociti mode. An ISO 9000-2000 Company SIGNALING FM ® ® Velociti and E3 Series are registered trademarks of Honeywell International Inc. S1913 MEA Approved 3023594 219-02-E Vol.VI 03240-0694:238 APPROVED GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use. www.gamewell-fci.com 9020-0622 Rev. C page 1 of 2 ©2008 by Honeywell International Inc. All rights reserved. Description (continued) Model ADPFRF (with Relay) Remote alarm annunciation can be accomplished by using the RA400Z remote annunciator or the RTS451or RTS451KEY remote test station. Both these devices allow testing of the sensor from a remote location. Current Requirements (using no accessories) Power Supply Voltage: 20-30 VDC 30 VAC, 120 VAC, 22/240 VAC, 50-60 Hz 50-60 Hz 50-60 Hz Max. Standby Current: 26 mA 65 mA RMS 44 mA RMS 25 mA RMS Max. Alarm Current: 87 mA 182 mA RMS 52 mA RMS 30 mA RMS Alarm Response Time: 3 to 10 sec. 3 to 10 sec. 3 to 10 sec. 3 to 10 sec. ADPF low-flow duct sensors are designed for simplified installation and easy maintenance. The modular construction allows for easy cleaning and uncomplicated field replacement of the UL recognized power and sensor boards. Auxiliary Relay Contact Ratings The ADPF (non-relay) has outputs for a remote LED display and remote test switch. It incorporates zener diodes to conserve power for communications to other devices. The ADPF is a 2-wire device that requires signaling line circuit power only. The ADPRF (with relay) has powered outputs for remote LED indication with a remote test switch and audible sounder. Two form “C” auxiliary contacts can be configured as a relay version or jumpered to mimic the non-relay version. It has a patented cover tamper trouble signal. The ADPRF is a 4-wire device that requires both signaling line circuit power and either 24VAC/DC or 120/240VAC for proper operation. Specifications Operating Temperature Operating Humidity Range: Storage Temperature Range: Duct Air Velocity: Shipping Weight: Dimensions Length: Width: Depth: 32° to 131° F (0° to 55° C) 10 to 93% relative humidity (non–condensing) -22° to 158° F (-30° to +70° C) 100-4000 ft./min. (0.5—20.32 m/s) ADPF: 3.35 lbs. (1.5 kg) ADPFRF:3.90 lbs. (1.8 kg) 14 3/4” (37 cm) 5 1/2” (14 cm) 2 3/4” (7 cm) Ordering Information Part Number Description ADPF ADPRF ST-1.5 ST-3 ST-5 ST-10 A5060 A5067 Model ADPF (Non-relay) Voltage Range: Standby Current: Alarm auxiliary contacts* (DPDT): 10 A @ 30 VDC 10 A @ 277 VAC (0.75 power factor) 240 VA @ 249 VAC (0.4 power factor) 1/8 HP @ 120 VAC 1/4 HP @ 240 VAC Supervisory contact (SPST): 2.0 A @ 30 VDC (resistive) Minimum switching current for auxiliary contact must be 100 mA DC minimum @ 5 VDC. Accessory Current Loads at 24 VDC Device Standby Alarm PA400 0 mA 15 mA Max. RA400Z 0 mA 12 mA Max. RTS451/ 0 mA 10 mA Max. RTS451KEY 15 to 32 VDC 300 µA @ 24 VDC (one communication every 5 seconds with LED flash enabled) Analog addressable low-flow photoelectronic non-relay duct smoke sensor Analog addressable low-flow photoelectronic with relay duct smoke sensor Sampling tube duct widths 1’-2’ Sampling tube duct widths 2’-4’ Sampling tube duct widths 4’-8’ Sampling tube duct widths 8’-12’ Replacement power board for ADPF-RF (w/relay) Replacement power board for ADPF (w/o relay) Accessories Description RTS451 RTS451KEY RA400Z F36-09-11 M02-04-00 P48-21-00 P48-61-00 S08-39-01 GAMEWELL-FCI Remote test station Remote test station w/key Remote LED Replacement filters Test magnet End cap of metal sampling tube End cap for plastic sampling tube Replacement photo insect screen 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 9020-0622 Rev. C page 2 of 2 www.gamewell-fci.com