LEM APR400

AC Current transducer APR-B420L
IPN = 10 .. 400 A
Split core transducer for the electronic measurement distorted AC
waveforms current, with galvanic isolation between the primary (High
power) and the secondary circuits (Electronic circuit). Switch selectable
ranges and True RMS 4-20mA current output.
Preliminary
Electrical data
Primary Nominal Current
IPN (A.t.RMS)
10,25,50
50,75,100
100,150,200
200,300,400
RL
VC
Vd
Features
Analogue Output Signal
IOUT (mA)
4-20
4-20
4-20
4-20
Load resistance
Supply voltage (loop powered)
R.m.s. voltage for AC isolation test, 50/60Hz, 1 mn
Limitation of output current
Type
• VFD and SCR waveforms current
measurement
APR 50 B420L
APR 100 B420L
APR 200 B420L
APR 400 B420L
< 350
+24
5
< 25
Ω
V DC
kV
mA
• True RMS output
• Split core type
• Loop powered 4-20mA current output
• DIN mounting & Panel mounting
• Eliminates insertion loss
• Switch selectable ranges
Advantages
• Large aperture for cable up to Ø18mm
• High isolation between primary and
secondary circuits
• Easy to mount
Accuracy-Dynamic performance data
X
ε
L
IOE
IOT
TC ε G
tr
f
Accuracy @ IPN, TA = 25°C (without offset)
Linearity (0 .. ± IPN)
Electrical offset current, TA = 25°C
Thermal drift of IOE
Thermal drift of the gain (% of reading)
Response time @ 90% of IP
Frequency bandwidth (-3 dB)
< ±1
% of IPN
< ±0.5 % of IPN
4
mA
±1
µA/K
±0.1
%/K
< 1000
ms
10 .. 6000
Hz
Applications
• VFD Controlled Loads:
VFD output indicates how the motor
and attached load are operating.
• SCR Controlled Loads:
Acurate measurement of phase angle
fired or burst fired (time proportioned)
SCRs. Current measurement gives
faster response than temperature
General data
TA
TS
m
Ambient operating temperature
Ambient storage temperature
Mass
Protection type
Reliable isolation according to EN50178, EN61010
Creepage distance
EMC in accordance with EN50082-2
Plastic according to UL94V0, CTI 1
-20 .. +60
°C
-20 .. +85
°C
90
g
IP20
300
V AC
> 5.5
mm
measurement.
• Switching Power Supplies and
Electronic Ballasts:
True RMS sensing is the most
accurate way to measure power
supply or ballast input power.
Notes : Installation and maintenance should be done with power supply disconnected.
030708/0
LEM Components
www.lem.com
Dimensions AP(R)-B420L
(unit : mm, 1mm = 0.0394 inch)
Mechanical characteristics
• General tolerance
• Primary aperture
±1 mm
∅ 18.5 mm
• Panel mounting
• Distance between holes
2 holes ∅ 4.0 mm
40.0 mm
For panel mounting, replace M4 screws by new one (not supplied) with appropriate length to panel´s thickness.
Connections
• Wires up to 2 mm ∅
Load
24 VDC P ower
4-20mA
Load Resistance vs. Supply Voltage
(C o n troller,
(+)
(+)
(-)
A P /A P R
25
20
15
10
5
0
O u tp u t
C o n n e c to r
0
100
200
300
400
Load Resistance
3 n o n e 2 (-) 1 (+)
F ront
30
Supply Voltage
(-)
M e te r, e tc ,)
R a n g e S w itc h
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.