Selector Guide
GFCI Circuit Breaker Selector Guide
PB-SERIES
PC-SERIES
PD-SERIES
1-3 poles, 3rd pole switched neutral
1-poles (1 Circuit Breaker + 1 GFCI Sensor
Module), 120V
2-pole (2 Circuit Breakers + 1 GFCI Sensor
Module), 120/240V or 120V with Neutral Break.
2-pole (2 Circuit Breakers + 1 GFCI Sensor
Module), 240VAC
3-pole 120/240V with Neutral Break (Sensor
module has 2 pole width)
1-3 poles, with switched or
unswitched neutral options
Handle, Rocker, Flat Rocker actuators
Handle, Rocker, Flat Rocker, Push-to-reset
Handle, with handle guard option
30mA & 6mA
30mA & 6mA
7-100 milliamps
LEAKAGE CURRENT
TRIP LEVEL
For 30mA leakage trip:
≤ 22.2mA, shall not trip
30mA, shall trip within .10 seconds,
complying with UL-1053
& ABYC E11. For 6mA leakage
trip: ≤25ms, complying with UL-943.
For 30mA leakage trip:
≤ 22.2mA, shall not trip
30mA, shall trip within .10 seconds,
complying with UL-1053
& ABYC E11. For 6mA leakage
trip: ≤25ms, complying with UL-943.
300 ms Max. @ 100%, 40ms
Max. @ 500% of must trip leakage current
LEAKAGE CURRENT
TRIP TIME
0.10 - 30 amps @ 120/240VAC
0.10 - 50 amps @ 120/240VAC - 240VAC
120VAC, Single Phase
120/208VAC, Single Phase
120/240VAC, Single Phase
208/240VAC, Three Phase
480Y/277VAC, Three Phase
5,000 amps
5,000 amps
5,000A @ 120/208 VAC;
120/240VAC, Single phase
2,000A @ 208/240, Three phase
2,000A @ 480Y/277VAC,
Three phase
Series Trip
Series Trip
Series Trip
.250 Quick Connect Tabs
8-32, 10-32, M4,M5 screw with upturned lugs
8-32, 10-32, M4,M5 screw, Bus Type
10-32 Threaded Stud
Front Connected Box Lug
w/ pressure plate
TERMINAL
OPTIONS
Front Panel
Front Panel
Front Mounted or Din Rail
Mounted
MOUNTING METHOD
-35° C to +65° C
-35° C to +65° C
-10°C to 60°C
UL489, CSA, UL1077, UL1500
UL943, UL1053, UL1500
UL Recognized, CSA, TUV
NUMBER OF POLES
ACTUATOR STYLE
MAXIMUM CURRENT &
VOLTAGE RATINGS
MAXIMUM
INTERRUPTING
CAPACITY
AVAILABLE
CIRCUITS
OPERATING
TEMPERATURE
AGENCY
APPROVALS
GFCI-SG_01_2014
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231